Calcs- Shelm Meadows- Plan 2006 Sales OfficeLGI Homes - WA
12951 Bel Red Rd
Bellevue, Washington 98005
Shelm Meadows
PLAN 2006 SALES OFFICE
INDEX TO STRUCTURAL CALCULATIONS
Design Criteria SHEET 1
Vertical Analysis SHEETS 2-12
Lateral Analysis SHEETS L1-L16
OWNERSHIP OF DOCUMENTS: CALCULATIONS, DRAWINGS AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE, AND SHALL REMAIN
THE PROPERTY OF THE ENGINEER. THEY ARE NOT TO BE USED ON OTHER PROJECTS OR EXTENSIONS OF THIS PROJECT EXCEPT BY
AGREEMENT IN WRITING WITH THE APPROPRIATE COMPENSATION TO FELTEN GROUP, INC.
WA-FE25-001106
130736
18325 N. ALLIED WAY, SUITE #200 * PHOENIX, AZ 85054 * PHONE: 602.867.2500 * FAX: 602.867.2503
02/07/25
2018
SHINGLE OR MEMBRANE
PSF PSF
12.00 7.00
27.00 (MAX)
GOVERNING CODE AND LATERAL LOAD CRITERIA:
3 SEC GUST (MPH):
BUILDING CODE:
MUNICIPALITY: Thurston County, WA
85/110
ROOF LOADS:
ROOF FRAMING DEAD LOAD PSF
10.00NON-CONCURRENT ATTIC LL WITHOUT STORAGE (PSF) =
LESS THAN 4:12 SLOPE ROOF LL (PSF) =
4:12 SLOPE AND GREATER TOTAL ROOF LL (PSF) = 16.00
20.00
15.00
ROOF FRAMING LIVE LOAD
TOTAL ROOF DL (PSF) =
DECK FRAMING LIVE LOAD
TOTAL DECK LL (PSF) = 60.00
TOTAL FLOOR DL (PSF) = 10.00
WITH PARTITION WALLS (PSF) = +5.00
SEISMIC DESIGN CATEGORY:
EXPOSURE AT MWFRS:
EXPOSURE AT C & C:
D2
C
C
TOTAL WALL DL (PSF) =
INTERIOR WALL DEAD LOAD
WITH TILE (PSF) = +5.00
EXTERIOR WALL DEAD LOAD
WALL DEAD LOADS:
FLOOR FRAMING LIVE LOAD
TOTAL FLOOR LL (PSF) = 40.00
IBC/IRC
TOTAL WALL DL (PSF) =
TOTAL WALL DL W/ STONE VENEER (PSF) =
SNOW LOAD
TOTAL SNOW LOAD (PSF) = 20.00
FLOOR LOADS:
FLOOR FRAMING DEAD LOAD PSF
"Where quality engineering leads to lower costs."
2021
CLIENT:
FELTENdROUP
ARCHITECTURE I ENGINEERING I FORENSICS
ROOF FRAMING PLAN
DATE: SHEET OF
BY:
CLIENT:
FELTENdROUP
ARCHITECTURE I ENGINEERING I FORENSICS
FLOOR FRAMING PLAN
DATE: SHEET OF
BY:
SHEET 4 OF
BY
Left Support Right Support
Rleft (#)Rright (#)
Vd Mmax
fb F'b
CD fv F'v
CL Δactual Δmax
CF/CV
Cr Use:
163 163
100 0.000 3.250 133 132 5.5 3.5
259 1460 8.000 8.000
1.15 19 173 9.083 10.000 N/A 2500 N/A 2500
0.996 0.018 0.130 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)12 18 12 18
1.500 (1) 2x6 KS (1) 2x4 KS 200 0 200 0
1.00 Use:(1) 2x6 (1) 2x4
313 313
100 0.000 6.250 267 488 5.5 5.5
387 1256 8.000 8.000
1.15 24 173 9.083 9.083 N/A 2500 N/A 2500
0.988 0.063 0.250 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)12 18 12 18
1.300 (1) 2x6 KS (1) 2x6 KS 200 0 200 0
1.00 Use:(1) 2x6 (1) 2x6
813 813
100 0.000 16.250 719 3301 5.5 5.5
626 877 8.000 8.000
1.15 32 173 N/A 2500 N/A 2500
0.897 0.339 0.650 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)12 18 12 18
1.000 200 0 200 0
1.00 Use:(1) 2x6 (1) 2x6
1463 1463
900 0.000 3.250 1050 1188 5.5 5.5
943 1263 8.000 8.000
1.15 95 173 9.083 12.083 N/A 2500 N/A 2500
0.994 0.042 0.130 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)12 18 12 18
1.300 (1) 2x6 KS (1) 2x6 KS 1000 0 1000 0
1.00 Use:(1) 2x6 (1) 2x6
1913 1913
900 0.000 4.250 1369 2032 5.5 5.5
928 1161 8.000 8.000
1.15 94 173 9.083 9.083 N/A 2500 N/A 2500
0.990 0.053 0.170 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)12 18 12 18
1.200 (1) 2x6 KS (1) 2x6 KS 1000 0 1000 0
1.00 Use:(1) 2x6 (1) 2x6
1260 1260
480 0.000 5.250 970 1654 Hanger 3.5
755 1158 9.000
1.15 67 173 N/A N/A N/A 2500
0.987 0.066 0.210 Doug-Fir #2 (2" to 4" wide)N/A N/A 12 18
1.200 N/A N/A 200 0
1.00 Use:4x4
5.250
Hem-Fir #2 Common Sizes 2-2x8
Select Material To Hanger NO FTG REQ'D
H6 5.250 To Hanger Conventional
N/A Edge
4.250
Hem-Fir #2 Common Sizes 2-2x8
Select Material NO FTG REQ'D NO FTG REQ'D
H5 4.250 Conventional Conventional
Edge Edge
3.250
Hem-Fir #2 Common Sizes 2-2x6
Select Material NO FTG REQ'D NO FTG REQ'D
H4 3.250 Conventional Conventional
Edge Edge
16.250
Hem-Fir #2 Common Sizes 2-2x12
Select Material NO FTG REQ'D NO FTG REQ'D
H3 16.250 Conventional Conventional
Edge Edge
6.250
Hem-Fir #2 Common Sizes 2-2x6
Select Material NO FTG REQ'D NO FTG REQ'D
H2 6.250 Conventional Conventional
Edge Edge
3.250
Hem-Fir #2 Common Sizes 2-2x4
Select Material NO FTG REQ'D NO FTG REQ'D
H1 3.250 Conventional Conventional
Edge Edge
Material Type Member Size King Studs Uniform Load (plf)Point Load (#)
Dual Spec Material Type Dual Spec Member Size Trimmers/ Hangers Size (in)
Point Loads Uniform Loads Results Left Support Right Support
Id Span (ft)
P (#)x (ft)w (plf)
Unbraced
Length(ft)
King Stud Height (ft)Slab Thickness (in)Bearing Pressure (psf)
Trimmer and King Stud Material Standard Width (in)Standard Depth (in)
start (ft)stop (ft)
Bearing Length (in) / Hanger Support Condition
Trimmer or Post Height (ft)Location Of Support
PROJECT:Sales Office JEM
Beam / Header Design and Loading
CLIENT:
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 5 OF
BY
Left Support Right Support
Rleft (#)Rright (#)
Vd Mmax
fb F'b
CD fv F'v
CL Δactual Δmax
CF/CV
Cr Use:
1648 1648
1014 0.000 3.250 1183 1339 5.5 5.5
1062 1263 8.000 8.000
1.15 108 173 9.083 9.083 N/A 2500 N/A 2500
0.994 0.047 0.130 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)12 18 12 18
1.300 (1) 2x6 KS (1) 2x6 KS 1100 0 1100 0
1.00 Use:(1) 2x6 (1) 2x6
Select Support Select Support
Use:
Select Support Select Support
Use:
Select Support Select Support
Use:
Select Support Select Support
Use:
Select Support Select Support
Use:
PROJECT:Sales Office JEM
Beam / Header Design and Loading
CLIENT:
Point Loads Uniform Loads Results Left Support Right Support
Id Span (ft)
P (#)x (ft)w (plf)
Unbraced
Length(ft)
King Stud Height (ft)Slab Thickness (in)Bearing Pressure (psf)
Trimmer and King Stud Material Standard Width (in)Standard Depth (in)
start (ft)stop (ft)
Bearing Length (in) / Hanger Support Condition
Trimmer or Post Height (ft)Location Of Support
H7 3.250 Conventional Conventional
Edge Edge
Material Type Member Size King Studs Uniform Load (plf)Point Load (#)
Dual Spec Material Type Dual Spec Member Size Trimmers/ Hangers Size (in)
3.250
Hem-Fir #2 Common Sizes 2-2x6
Select Material NO FTG REQ'D NO FTG REQ'D
Select Material
Select Material
Select Material
Select Material
Select Material
Select Material
Select Material
Select Material
Select Material
Select Material
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 6 OF
BY
Lub,top (ft)TL (L/x)
Lub,bot (ft)LL (L/x)
Cr
Ci
CM
CT Dmax (in)
CLtop Dcant (in)
CLbot Left dn (in)Dmax (in)
CF/Cvtop Right dn (in)Dcant (in)
CF/Cvbot
Support Size Support Size Support Size Support Size Support Size
Beam/Header Diagram
Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)
Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in)
Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)
Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)
Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)
Support Material Type Support Material Type
Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger
Support Condition
Support Location Support Location Support Location Support Location Support Location
King Studs King Studs King Studs King Studs King Studs
Support Condition Support Condition Support Condition Support Condition
Trimmer or Post Height Trimmer or Post Height
King Stud Height King Stud Height King Stud Height King Stud Height King Stud Height
Load Combo
Max/Min
Reaction
R4 (lb)
Load Combo
Max/Min
Reaction
R5 (lb)
Load Combo
Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
Max/Min
Reaction
R1 (lb)
Load Combo
Max/Min
Reaction
R2 (lb)
Load Combo
Max/Min
Reaction
R3 (lb)
Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height
Support Material Type Support Material Type Support Material Type
Member Size
Dual Spec Material Type Dual Spec Member Size
Span 2
(ft)
Right DLL Limit Deflections
DTL
Span 3
(ft)
Scarf Cut Data DTL
DLL
Span 1
(ft)
NDS
Factors
Cantilever Data M+max
(lb-ft)M+fb+ (psi)F'b+ (psi)
Left DTL Limit
xstop (ft)
DL Creep
Factor
Vmax
(lb)V fv (psi)F'v (psi)
M-max
(lb-ft)M-fb- (psi)F'b- (psi)
Total Length, L (ft)DLL
Span 4
(ft)
Material Type
Id
Load
Type P (lb)x (ft)wstart (plf)wstop (plf)xstart (ft)
Header/Beam Loading Unbraced
Lengths
CLIENT:
PROJECT:Sales Office JEM
Multi-Span Header / Beam Key
Allowable
StressPoint Loads Uniform Loads Deflection Data Results Load Combo Actual
Stress
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 7 OF
BY
D 24 24 0.000 10.500 1.000 240
L 64 64 0.000 10.500 360
Factors
Yes
1.150
No
MC<=19%
T<=100 -0.193
0.991 0.000
1.000 No -0.136
1.000 No 0.000
1.000
476 476
140 140
240
360
Factors
No
No
MC<=19%
T<=100
No
No
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
Scarf Cut Data
No Deflections
No
Cantilever Data
1.000
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Hem-Fir #2 (2" to 4" wide)2x10
Select Material
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L D + L
D D
D + L
1248 D + L 700
No Deflections
10.500
Scarf Cut Data
L 10.500
J1 1.000 406 D + L 44 150
1065
No
0 D 0 968
Cantilever Data
PROJECT:Sales Office JEM
CLIENT:
10.5'
88 88
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 8 OF
BY
Lub,top (ft)TL (L/x)
Lub,bot (ft)LL (L/x)
Cr
Ci
CM
CT Dmax (in)
CLtop Dcant (in)
CLbot Left dn (in)Dmax (in)
CF/Cvtop Right dn (in)Dcant (in)
CF/Cvbot
Support Size Support Size Support Size Support Size Support Size
Beam/Header Diagram
Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)
Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in)
Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)
Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)
Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)
Support Material Type Support Material Type
Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger
Support Condition
Support Location Support Location Support Location Support Location Support Location
King Studs King Studs King Studs King Studs King Studs
Support Condition Support Condition Support Condition Support Condition
Trimmer or Post Height Trimmer or Post Height
King Stud Height King Stud Height King Stud Height King Stud Height King Stud Height
Load Combo
Max/Min
Reaction
R9 (lb)
Load Combo
Max/Min
Reaction
R10 (lb)
Load Combo
Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
Max/Min
Reaction
R6 (lb)
Load Combo
Max/Min
Reaction
R7 (lb)
Load Combo
Max/Min
Reaction
R8 (lb)
Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height
Support Material Type Support Material Type Support Material Type
Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)
Support Size Support Size Support Size Support Size Support Size
Support Width (in)Support Width (in)
Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)
Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)
Support Location
Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Support Condition Support Condition Support Condition Support Condition Support Condition
Support Location Support Location Support Location Support Location
Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)
Support Width (in)Support Width (in)Support Width (in)
Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger
King Studs King Studs King Studs King Studs King Studs
Support Material Type Support Material Type Support Material Type Support Material Type Support Material Type
Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger
Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height
Span 5
(ft)
Span 6
(ft)
Span 7
(ft)
Span 8
(ft)
Max/Min
Reaction
R3 (lb)
Load Combo
Max/Min
Reaction
R4 (lb)
Load Combo
Max/Min
Reaction
R5 (lb)
Load Combo
Span 9
(ft)
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
Max/Min
Reaction
R1 (lb)
Load Combo
Max/Min
Reaction
R2 (lb)
Load Combo
Bearing Length (in)/Hanger Bearing Length (in)/Hanger
King Stud Height King Stud Height King Stud Height King Stud Height King Stud Height
Span 3
(ft)
Scarf Cut Data DTL
DLL
DLL
Span 4
(ft)Material Type Member Size
Total Length, L (ft)
Allowable
StressPoint Loads Uniform Loads
Id
Load
Type P (lb)x (ft)wstart (plf)wstop (plf)xstart (ft)
Header/Beam Loading Unbraced
Lengths Deflection Data Results Load Combo Actual
Stress
Span 1
(ft)
NDS
Factors
Cantilever Data M+max
(lb-ft)M+fb+ (psi)
Left
CLIENT:
PROJECT:Sales Office JEM
Single Multi-Span Header / Beam Key
F'v (psi)
F'b+ (psi)
fb- (psi)F'b- (psi)
DTL Limit M-max
(lb-ft)M-
xstop (ft)
DL Creep
Factor
Vmax
(lb)V fv (psi)
Span 2
(ft)
Right DLL Limit Deflections
DTL
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 9 OF
BY
D 164 164 0.000 6.000 2.000 240
L 438 438 0.000 6.000 360
D 188 188 6.000 62.000 Factors
L 500 500 6.000 62.000 No
1.000
No
MC<=19%
T<=100 -0.067
0.997 0.029
0.995 No -0.048
1.000 No 0.021
1.000
3248 5509 5127 5237
911 1545 1438 1469
5192 5263 5024 5910 2055
1456 1476 1409 1657 576
20" DIA. x 9" DEEP NO
REBAR
20" DIA. x 9" DEEP NO
REBAR
20" DIA. x 9" DEEP NO
REBAR
21" DIA. x 9" DEEP NO
REBAR
13" DIA. x 8" DEEP NO
REBAR
0 0 0 0 0
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Isolated Footing Isolated Footing Isolated Footing Isolated Footing Isolated Footing
2500 2500 2500 2500 2500
Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)
4x4 POSTS 4x4 POSTS 4x4 POSTS 4x6 POSTS 4x4 POSTS
D D
3.5 3.5 3.5 3.5 3.5
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L D + L D + L D + L D + L
D D D
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
8 8 8 8 8
16" DIA. x 8" DEEP NO
REBAR
21" DIA. x 9" DEEP NO
REBAR
20" DIA. x 9" DEEP NO
REBAR
20" DIA. x 9" DEEP NO
REBAR
0 0 0 0
2500 2500 2500 2500
4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS
Isolated Footing Isolated Footing Isolated Footing Isolated Footing
Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)
3.5 3.5 3.5 3.5
8 8 8 8
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L D + L D + L D + L
D D D D
7.500
7.500
7.500
7.500
7.500
Scarf Cut Data D + L
L 62.000L
7.500 Doug-Fir #2 (2" to 4" wide)4x10
Select Material
993 1075
7.500 No 180 Deflections
D + L
7.500
2.000
Cantilever Data 3039 D + L 731 1077
Yes 120
-4130 D + L
C1 1.000 2588 D + L 120 180
PROJECT:Sales Office JEM
CLIENT:
2'7.5'7.5'7.5'7.5'7.5'7.5'7.5'7.5'
602 602 688 688
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 10 OF
BY
D 188 188 0.000 32.500 2.000 240
L 500 500 0.000 32.500 360
Factors
No
1.000
No
MC<=19%
T<=100 -0.039
0.997 0.000
0.996 No -0.028
1.000 No 0.000
1.000
3586 5324 4765 5324
1006 1493 1336 1493
3586
1006
17" DIA. x 8" DEEP NO
REBAR
0
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Isolated Footing
2500
Doug-Fir #2 (2" to 4" wide)
4x4 POSTS
3.5
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L
D
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
8
17" DIA. x 8" DEEP NO
REBAR
20" DIA. x 9" DEEP NO
REBAR
19" DIA. x 8" DEEP NO
REBAR
20" DIA. x 9" DEEP NO
REBAR
0 0 0 0
2500 2500 2500 2500
4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS
Isolated Footing Isolated Footing Isolated Footing Isolated Footing
Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)
3.5 3.5 3.5 3.5
8 8 8 8
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L D + L D + L D + L
D D D D
7.125
2.000
Scarf Cut Data D
L 32.500
7.125 Doug-Fir #2 (2" to 4" wide)4x10
Select Material
813 1075
7.125 Yes 180 Deflections
D + L
7.125
2.000
Cantilever Data 2080 D + L 500 1077
Yes 120
-3382 D + L
C2 1.000 2199 D + L 102 180
PROJECT:Sales Office JEM
CLIENT:
2'7.125'7.125'7.125'7.125'2'
688 688
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 11 OF
BY
D 110 110 0.000 6.000 2.000 240
L 294 294 0.000 6.000 360
D 188 188 6.000 38.500 Factors
L 500 500 6.000 38.500 No
1.000
No
MC<=19%
T<=100 -0.032
0.997 0.000
0.996 No -0.023
1.000 No 0.000
1.000
2134 4760 4822 4734
607 1337 1352 1328
5083 3515
1425 986
20" DIA. x 9" DEEP NO
REBAR
17" DIA. x 8" DEEP NO
REBAR
0 0
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
Isolated Footing Isolated Footing
2500 2500
Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)
4x4 POSTS 4x4 POSTS
3.5 3.5
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L D + L
D D
Fo
u
n
d
a
t
i
o
n
S
u
p
p
o
r
t
D
e
s
i
g
n
8 8
13" DIA. x 8" DEEP NO
REBAR
19" DIA. x 8" DEEP NO
REBAR
19" DIA. x 8" DEEP NO
REBAR
19" DIA. x 8" DEEP NO
REBAR
0 0 0 0
2500 2500 2500 2500
4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS
Isolated Footing Isolated Footing Isolated Footing Isolated Footing
Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)
3.5 3.5 3.5 3.5
8 8 8 8
He
a
d
e
r
/
B
e
a
m
S
u
p
p
o
r
t
De
s
i
g
n
D + L D + L D + L D + L
D D D D
6.917
6.833
2.000
Scarf Cut Data D
L 38.500
6.917 Doug-Fir #2 (2" to 4" wide)4x10
Select Material
742 1076
6.917 Yes 180 Deflections
D + L
6.917
2.000
Cantilever Data 1863 D + L 448 1077
Yes 120
-3085 D + L
C3 1.000 2051 D + L 95 180
PROJECT:Sales Office JEM
CLIENT:
2'6.9167'6.9167'6.9167'6.9167'6.833'2'
404 404 688 688
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
SHEET 12 OF
BY
S1 1
3.00 180 NO
1.50 0.7 NO
ROOF
TYPE:15.00 12.08
40.00 10.00 TARGET
WALL
1.00 25.00
21.00
8.97
16.13 12.08 SPECIES TITLE
10.02 10.00 SCANT CFB b (IN)
5.00 FB (PSI)CFC d (IN)
11.71 FC (PSI)CR A (IN2)
5.50 0.00 EMIN (PSI)c Sx (IN3)
Ex (PSI)
CD
0.90 118.62 " o.c.
1.00 122.87 " o.c.
1.25 130.31 " o.c.
1.15 53.27 " o.c.
1.25 130.31 " o.c.
1.25 130.31 " o.c.
1.15 62.36 " o.c.
1.25 130.31 " o.c.
1.60 46.92 " o.c.
1.60 57.36 " o.c.
1.60 54.96 " o.c.
1.60 36.12 " o.c.
1.60 54.96 " o.c.
1.60 65.16 " o.c.
1.60 40.68 " o.c.
1.60 65.16 " o.c.
1.60 35.68 " o.c.GOVERNS
1.00 " o.c.
24 " o.c.
1 Per Table IBC 1604.3 footnote f, for ASD the wind load for deflection shall be taken as 0.42 times the C&C loading. The 0.42 factor is a conversion from Ultimate loads to service loads (0.6W) and then further
multiplied by 0.7 to adjust for the 10 year mean return interval. Therefore, 0.6 * 0.7 = 0.42
D + 0.75(0.6W) + 0.75L + 0.75LR
D + 0.75(0.6W) + 0.75L + 0.75S
D + 0.75(0.6W) + 0.75L + 0.75R
D + 0.75(0.7E) + 0.75L + 0.75LR
D + 0.75(0.7E) + 0.75L + 0.75S
D + 0.75(0.7E) + 0.75L + 0.75R
D + R
D + 0.75L + 0.75LR
D + 0.75L + 0.75S
D + 0.75L + 0.75R
D + 0.6W
D + 0.7E
1200000 20.797
ASCE7 LOAD COMBINATIONS
C & C LOADING
BENDING (NDS Section 3.3)
Le = 12.08ft - (3.00in + 1.50in)(1ft/12in) = 11.71ft
M = 552.76#-ft
F'b = Fb(Cd)(Cr)(Cfb) = 675(1.60)(1.15)(1.00) = 1242.00psi
fb = (12in/1ft)(552.76#-ft)/7.56in^3 = 877.11psi
DEFLECTION (NDS Section 3.5.1)
DELTA = 0.38in
BENDING AND DEFLECTION CAPACITY CHECK
877.11psi/1242.00psi = 0.706 < 1.000 O.K.
0.38in < 0.78in O.K.
THEREFORE, USE 2x6 HEM-FIR STUD GRADE STUDS AT 24in O.C.
D
D + L
D + LR
D + S
0.6C&C1
D + L (NON-CONCURRENT)
DESIRED SPACING FOR CALCULATIONS:
STOP (FT)800 1.15 8.250
WALL WIDTH (IN)START (FT)440000 0.80 7.563
0.6*W (PSF)WEIGHT (PSF)NO 1.00 1.50
0.7*E (PSF)PARTIAL LOADING (WIND)675 1.00 5.50
TARGET WALL STUD MATERIAL
0.6*C&C (PSF)HEIGHT (FT)Hem-Fir Stud (2" to 4" wide)2x6 HEM-FIR STUD GRADE STUDS
SIMPLE 0.6*WUPLIFT
MAIN SPAN LR WEIGHT (PSF)
OVERHANG S
TOTAL TRIB.R
ROOF SPAN (FT)ROOF LOADS (PSF)SUPPORTING WALL
SIMPLE D HEIGHT (FT)
TOP PLATE THICKNESS (IN)WALL HAS CONTINUOUS
SHEATHING ON ONE SIDE NO ROOF ASSEMBLY TYPE C&CWIND DEFLECTION, L/GYP COMP.
SOLE PLATE THICKNESS (IN)PRE-FAB TRUSSES C&CWIND FACTOR = GYP + WOOD COMP.
CLIENT:
PROJECT:Sales Office JEM
WALL NUMBER:STUD LOCATION:(1 = ROOF, 2 = FIRST FLOOR BELOW ROOF, 3 = SECOND FLOOR BELOW ROOF)
Printed by larissa.anaya on 02/06/2025 at 13:05
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\Vertical Book1.xlsm
CLIENT:
FELTENdROUP
ARCHITECTURE I ENGINEERING I FORENSICS
DATE: SHEET OF
BRACED/SHEAR WALL PLAN
BY:
CLIENT:SHEET L2 OF
PROJECT:BY
110 mph
C (Section 26.7)
II (Table 1.5-1)
0.85 (Table 26.6-1)
1.00 (Section 26.8.2)
100 (Section 26.9)Ke = 1.00 (Table 26.9-1)
0.6 (Section 2.4.1)
Truss Heel Height:0.333 ft
Plate Height:9.083 ft
Length (Dimension Perpendicular to Truss Span):60.000 ft
Width (Dimension Parallel to Truss Span):40.000 ft
Roof Pitch:5.00 in/12 in
Roof Angle:22.620 deg
Mean Roof Height:13.583 ft
Ridge Height:17.749 ft
Design Edge Strip (a):4.000 ft
Design End Zone (2a):8.000 ft
Velocity Pressure Coefficient (Kz):0.850 (Table 26.10-1)
0.6*qz (Velocity Pressure):13.38 psf (Equation 26.10-1)
0.6*Pcc,wall (Maximum Wall Pressure):16.13 psf (Equation 30.3-1)
0.6*Pend zone stud (End Zone Stud Design Pressure):12.73 psf Load Case A
0.6*Pint zone stud (Int. Zone Stud Design Pressure):9.60 psf Load Case A
0.6*Pp (Parapet Pressure 1.5WW and -1.0LW):20.07 psf Windward and -13.38 psf Leeward
Risk Category:
Wind Directionality (Kd):
Topographic Factor (Kzt):
Ground Elevation Factor (ft) (Ke):
ASD Load Combination Factor for W:
ONE STORY DIAPHRAGM WIND LOADS FOR ASD LOAD COMBINATIONS
Design Method:Low-Rise Building (Section 28.3.1)
Basic Wind Speed (3 sec gust):
Exposure:
Sales Office JEM
Elevation Label:
Design Code:ASCE 7-16
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
CLIENT:SHEET L3 OF
PROJECT:BY
p = 0.6 * qz * [GCpf - GCpi](Equation 28.3-1)
GCpf interpolated from Figure 28.3-1
GCpi 0.18 enclosed buildings Table 26.13-1
(GCpi acts either inward or outward at any one time)
GCpf GCpi
Zone 1:0.54 -0.18
Zone 2:-0.45 0.18
Zone 3:-0.47 0.18
Zone 4:-0.41 -0.18
Zone 1E:0.77 -0.18
Zone 2E:-0.72 0.18
Zone 3E:-0.65 0.18
Zone 4E:-0.60 -0.18
GCpf GCpi
Zone 1:-0.45 -0.18
Zone 2:-0.69 0.18
Zone 3:-0.37 0.18
Zone 4:-0.45 -0.18
Zone 5:0.40 -0.18
Zone 6:-0.29 -0.18
Zone 1E:-0.48 -0.18
Zone 2E:-1.07 0.18
Zone 3E:-0.53 0.18
Zone 4E:-0.48 -0.18
Zone 5E:0.61 -0.18
Zone 6E:-0.43 -0.18
Note: Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
8.16 -2.41 10.57
-5.75 -2.41 -3.34
-7.09 2.41 -9.50
-6.42 -2.41 -4.01
-6.42 -2.41 -4.01
-14.32 2.41 -16.72
5.35 -2.41 7.76
-3.88 -2.41 -1.47
-4.95 2.41 -7.36
-6.02 -2.41 -3.61
-6.02 -2.41 -3.61
-9.23 2.41 -11.64
-8.00 -2.41 -5.59
Load Case B Pressures
0.6*qz*GCpf (psf)0.6*qz*GCpi (psf)Pressure (psf)
-9.62 2.41 -12.03
-8.67 2.41 -11.08
-5.54 -2.41 -3.13
10.32 -2.41 12.73
-6.08 2.41 -8.49
-6.25 2.41 -8.66
0.6*qz*GCpf (psf)0.6*qz*GCpi (psf)Pressure (psf)
7.20 -2.41 9.60
Hip End Loading
Load Case A Load Case B
Load Case A Pressures
Sales Office JEM
Gable End Loading
Load Case A Load Case B
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
CLIENT:SHEET L4 OF
PROJECT:BY
Case A 6.55 psf 6.57 psf
Case B 9.91 psf 5.24 psf
GCpf GCpf
6.35 psf 4.59 psf
GCpf GCpf
7.61 psf 5.87 psf
GCpi GCpi
2.41 psf 2.41 psf
13.48 psf 10.93 psf
0.00 psf
8.97 psf 9.98 psf
3943 #3954 #
3472 #
Case A 6.55 psf 6.57 psf Case B 8.05 psf 7.09 psf
GCpf GCpf GCpf GCpf
7.61 psf 5.87 psf 5.49 psf 3.97 psf
GCpi GCpi
2.41 psf 2.41 psf
13.48 psf 9.47 psf
0.00 psf 0.00 psf
8.97 psf 9.98 psf
3943 #1846 #
∴Use 10.02 psf at Wall for Windward Only Case (0.6*W)∴Use 7.90 psf at Wall for Windward Only Case (0.6*W)
2672 #
∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case A ∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case B
Total Base Shear Due to Wind Loads =Total Base Shear Due to Wind Loads =
Total Base Shear Due to 0.6*16psf at Wall
and 0.6*8psf at Roof =4408 #Total Base Shear Due to 0.6*16psf at Wall
and 0.6*8psf at Roof =
Total Horizontal Pressure at Wall =Total Horizontal Pressure at Wall =
Total Horizontal Pressure at Roof =Total Horizontal Pressure at Roof =
Total Uplift Pressure at Roof =Total Uplift Pressure at Roof =
ONE STORY DIAPHRAGM HIP END WIND LOADS FOR ASD LOAD COMBINATIONS
Load Case A Load Case B
GCpf Windward GCpf Leeward GCpf Windward GCpf Leeward
∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case A ∴Use 10.93 psf Wall Horizontal Pressure at Case B
∴Use 10.02 psf at Wall for Windward Only Case (0.6*W)∴Use 8.76 psf at Wall for Windward Only Case (0.6*W)
Total Horizontal Pressure at Roof =
Total Uplift Pressure at Roof =Total Uplift Pressure at Roof =
Total Base Shear Due to Wind Loads =Total Base Shear Due to Wind Loads =
Total Base Shear Due to 0.6*16psf at Wall
and 0.6*8psf at Roof =5208 #Total Base Shear Due to 0.6*16psf =
Total Horizontal Pressure at Wall =Total Horizontal Pressure at Wall =
average of end zone plus interior zone and then the total roof uplift is the average of the left and right
sides. GCpi assumed to act inward for wall design, outward for roof uplift design.
ONE STORY DIAPHRAGM GABLE END WIND LOADS FOR ASD LOAD COMBINATIONS
Load Case A Load Case B
GCpf Windward GCpf Leeward
Sales Office JEM
Load Cases A & B total pressures are determined by using a weighted average of end zone total
plus interior zone total. This number is then compared to the code required 16psf minimum for the
horizontal direction. Roof uplift for the left and right sides of the roof are determined using a weighted
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
SHEET L5 OF
BY
WALL ROOF PARAPET TRIB. WALL HEEL TRIB. RIDGE PARAPET
SHEAR DISTANCE PRESSURE PRESSURE PRESSURE HEIGHT HEIGHT TO HEEL HEIGHT UNIFORM START STOP
#FT PSF PSF PSF FT FT FT FT PLF FT FT
10.93 10.93 4.542 0.333 4.167
1ST FLOOR
1ST FLOOR
9.60 4.80 4.542 0.333 8.333
1ST FLOOR
9.60 4.80 4.542 0.333 8.333
1714 0.000
9.60 4.80 4.542 0.333 4.375
1ST FLOOR
3
0.00%
40.000
0
STORY CALC DESCRIPTION
0
1021 0
2812 173
68 20.500 25.500
1021
0
STORY CALC DESCRIPTION
2 25.500
87 0.000 20.500
2812
2812
2*
0.00%
40.000
0
0
1714 0
1714 423
0
1714
0
STORY CALC DESCRIPTION
1 39.500
87 0.000 39.500
1714
1714
0.00%0
0
0 0
0 0
0
0
0
STORY CALC DESCRIPTION
0
0
0
B
0.00%
60.000
0
40.000
A 40.000
1977
0
1977 0
1977
1977 330
0
0
99 0.000
1977
SHEAR
(#)
CHORD
(#)
WINDWARD INFORMATION
LEEWARD INFORMATION
NEXT
LINE
FROM
NEXT
CHORD
DIST.
FT
SOURCE LINE NEXT
LINE
#
TARGET
LINE
TO
TARGET
LINE
SPACING
FT
POINT SHEAR FROM
OTHER LINES
UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET
LINE
#
PROJECT:Sales Office JEM
LINE
CALLOUT % CANT.WIND DESIGN SHEAR DIAPHRAGM
CLIENT:
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
SHEET L6 OF
BY
LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1
V ==1977 #
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.6WUPLIFT
(psf)
∑MOT
(#-ft)
∑MR
(#-ft)
1 3 24 21.00 10.00 2x6 1.4E+06 1008 1.000 48 324 20.00 10.00 15.00 9.98 54097 88200
2 3 24 19.00 9.08 2x6 1.4E+06 1007 1.000 53 324 20.00 10.00 15.00 9.98 45179 70545
3
4
5
6
2015
1 56 56
2 150 150
3
4
5
6
V ==#
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.6WUPLIFT
(psf)
∑MOT
(#-ft)
∑MR
(#-ft)
1
2
3
4
5
6
1
2
3
4
5
6
TDESIGN
(#)HOLDOWNT2nd FLOOR
(#)CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
LOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
LEFT END RIGHT END
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
VTOTAL (#) =
TDESIGN
(#)HOLDOWNLOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
0.045
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
LEFT END RIGHT END
JEM
A
VTOTAL (#) =
CLIENT:
PROJECT:Sales Office
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
3rd FLOOR
3rd FLOOR
BASEMENT
BASEMENT
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
SHEET L7 OF
BY
WIND DESIGN: WALL BRACING ANALYSES
110 13.58 1 1 C 13.58 9 2 NO YES NO NO 0.00 0.00 40.00
1.20 1.21 0.95 1.00 1.00 1.00 1.00 1.00 1.00 6.50 0.00
WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14
METHOD WSP WSP WSP WSP WSP
L (ft)10.83 8.17 4.08 6.42 21.50
ADJ. H (ft)
LCONT. (ft)10.83 8.17 4.08 6.42 21.50 51.00
WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14
METHOD
L (ft)
ADJ. H (ft)
LCONT. (ft)0.00
WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14
METHOD
L (ft)
ADJ. H (ft)
LCONT. (ft)0.00
EAVE TO
RIDGE H
(ft)
STORY
HEIGHT
(ft)
NUMBER
OF LINES
PARAPET
HEEL H
(ft)
PARAPET
H (ft)
LINE
SPACING
1 (ft)
LINE
SPACING
2 (ft)
REQUIRED LENGTH
(ft)
LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft)
NOT PERMITTEDTOTAL
(ft)
BRACED WALL INPUTS AND FACTORS
WIND
SPEED
(mph)
MEAN
ROOF H
(ft)
NUMBER
OF
STORIES
STORY
LOCATION EXPOSURE
MIN. 800#
HOLD-
DOWN
GB ON
INSIDE
FACE
GB
4"O.C.
PANEL
PLYWOOD
BLOCKING
OMITTED
LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft)
NOT PERMITTEDTOTAL
(ft)
PLYWOOD
BLOCKING
OMITTED
PARAPET
HEEL H
(ft)
PARAPET
H (ft)
LINE
SPACING
1 (ft)
LINE
SPACING
2 (ft)
REQUIRED LENGTH
(ft)
EAVE TO
RIDGE H
(ft)
STORY
HEIGHT
(ft)
NUMBER
OF LINES
BRACED WALL INPUTS AND FACTORS
WIND
SPEED
(mph)
MEAN
ROOF H
(ft)
NUMBER
OF
STORIES
STORY
LOCATION EXPOSURE
MIN. 800#
HOLD-
DOWN
GB ON
INSIDE
FACE
GB
4"O.C.
PANEL
PARAPET
HEEL H
(ft)
PARAPET
H (ft)
LINE
SPACING
1 (ft)
LINE
SPACING
2 (ft)
REQUIRED LENGTH
(ft)
9.00
LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft)
51.00>=9.00 O.K.TOTAL
(ft)
BRACED WALL INPUTS AND FACTORS
WIND
SPEED
(mph)
MEAN
ROOF H
(ft)
NUMBER
OF
STORIES
STORY
LOCATION EXPOSURE
MIN. 800#
HOLD-
DOWN
GB ON
INSIDE
FACE
GB
4"O.C.
PANEL
B
PLYWOOD
BLOCKING
OMITTED
CLIENT:
PROJECT:Sales Office JEM
EAVE TO
RIDGE H
(ft)
STORY
HEIGHT
(ft)
NUMBER
OF LINES
METHOD CS-WSP (INCLUDES CS-G & CS-PF)
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED)
METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED)
3rd FLOOR
3rd FLOOR
BASEMENT
BASEMENT
METHOD CS-WSP (INCLUDES CS-G & CS-PF)
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED)
3rd FLOORBASEMENT
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
SHEET L8 OF
BY
WIND DESIGN: WALL BRACING ANALYSES
110 13.58 1 1 C 13.58 9 3 NO YES NO NO 0.00 0.00 39.50 0.00
1.20 1.21 0.95 1.30 1.00 1.00 1.00 1.00 1.00 6.43 0.00
WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14
METHOD WSP WSP
L (ft)6.33 13.00
ADJ. H (ft)
LCONT. (ft)6.33 13.00 19.33
WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14
METHOD
L (ft)
ADJ. H (ft)
LCONT. (ft)0.00
WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14
METHOD
L (ft)
ADJ. H (ft)
LCONT. (ft)0.00
EAVE TO
RIDGE H
(ft)
STORY
HEIGHT
(ft)
NUMBER
OF LINES
PARAPET
HEEL H
(ft)
PARAPET
H (ft)
LINE
SPACING
1 (ft)
LINE
SPACING
2 (ft)
REQUIRED LENGTH
(ft)
LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft)
NOT PERMITTEDTOTAL
(ft)
BRACED WALL INPUTS AND FACTORS
WIND
SPEED
(mph)
MEAN
ROOF H
(ft)
NUMBER
OF
STORIES
STORY
LOCATION EXPOSURE
MIN. 800#
HOLD-
DOWN
GB ON
INSIDE
FACE
GB
4"O.C.
PANEL
PLYWOOD
BLOCKING
OMITTED
LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft)
NOT PERMITTEDTOTAL
(ft)
PLYWOOD
BLOCKING
OMITTED
PARAPET
HEEL H
(ft)
PARAPET
H (ft)
LINE
SPACING
1 (ft)
LINE
SPACING
2 (ft)
REQUIRED LENGTH
(ft)
EAVE TO
RIDGE H
(ft)
STORY
HEIGHT
(ft)
NUMBER
OF LINES
BRACED WALL INPUTS AND FACTORS
WIND
SPEED
(mph)
MEAN
ROOF H
(ft)
NUMBER
OF
STORIES
STORY
LOCATION EXPOSURE
MIN. 800#
HOLD-
DOWN
GB ON
INSIDE
FACE
GB
4"O.C.
PANEL
PARAPET
HEEL H
(ft)
PARAPET
H (ft)
LINE
SPACING
1 (ft)
LINE
SPACING
2 (ft)
REQUIRED LENGTH
(ft)
11.57
LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft)
19.33>=11.57 O.K.TOTAL
(ft)
BRACED WALL INPUTS AND FACTORS
WIND
SPEED
(mph)
MEAN
ROOF H
(ft)
NUMBER
OF
STORIES
STORY
LOCATION EXPOSURE
MIN. 800#
HOLD-
DOWN
GB ON
INSIDE
FACE
GB
4"O.C.
PANEL
1
PLYWOOD
BLOCKING
OMITTED
CLIENT:
PROJECT:Sales Office JEM
EAVE TO
RIDGE H
(ft)
STORY
HEIGHT
(ft)
NUMBER
OF LINES
METHOD CS-WSP (INCLUDES CS-G & CS-PF)
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED)
METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED)
3rd FLOOR
3rd FLOOR
BASEMENT
BASEMENT
METHOD CS-WSP (INCLUDES CS-G & CS-PF)
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED)
3rd FLOORBASEMENT
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
SHEET L9 OF
BY
LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1
V ==2812 #
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.6WUPLIFT
(psf)
∑MOT
(#-ft)
∑MR
(#-ft)
1 3 24 19.00 12.00 2x6 1.4E+06 2812 1.000 148 324 2.00 10.00 15.00 8.97 36981 27075
2
3
4
5
6
2812
1 CONC EXT CORNER 6 CRKD 1091 D CONC EXT CORNER 6 CRKD 1091 D
2
3
4
5
6
V ==#
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.6WUPLIFT
(psf)
∑MOT
(#-ft)
∑MR
(#-ft)
1
2
3
4
5
6
1
2
3
4
5
6
TDESIGN
(#)HOLDOWNT2nd FLOOR
(#)CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
LOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
LEFT END RIGHT END
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
VTOTAL (#) =
TDESIGN
(#)HOLDOWNLOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
0.199
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
LEFT END RIGHT END
JEM
2
VTOTAL (#) =
CLIENT:
PROJECT:Sales Office
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
3rd FLOOR
3rd FLOOR
BASEMENT
BASEMENT
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
SHEET L10 OF
BY
LATERAL LOAD ANALYSIS: APA PORTAL FRAME PER TT-100H
V ==1021 #
2930 #
1.000
9.000
10.000
D =0.510 in
2.000
APA PORTAL FRAME PER TT-100H
Number of Piers
Door Height (ft) =
Pier Height (ft) =
Left Pier (ft)
2
0.430 0.93 Beam Height (ft) =
CLIENT:
PROJECT:Sales Office JEM
3
VALLOW =
Specific Gravity SG Reduction
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT
Printed by larissa.anaya on 02/06/2025 at 12:16
\\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Sales Office\00 - Engineering\ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm
CLIENT:SHEET L11 OF
PROJECT:BY
SEISMIC LOAD CALCULATIONS PER ASCE 7-16
*USING BASIC LOAD COMBINATIONS PER SECTION 2.4*
ALL LOAD COMBINATIONS USE: 0.7*E
E = Eh + Ev (EQN 12.4-1 and EQN 12.4-3)
Eh = ρQE (EQN 12.4-3)
ρ = 1.30 (SECTION 12.3.4.2.a)
QE = V (SECTION 12.4.2.1)
Ev = 0.2SDSD (EV = 0 IF SDS <= 0.125)(EQN 12.4-4a)
II (TABLE 1.5-1)
D (PER PROJECT SOILS REPORT OR TABLE 20.3-1)DEFAULT
13.583 (MEAN ROOF HEIGHT OF STRUCTURE)
1.288 (MAPPED MCE SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS)
0.465 (MAPPED MCE SPECTRAL RESPONSE ACCELERATION AT A PERIOD OF 1 s)
Fa =1.200 (TABLE 11.4-1)
Fv =1.835 (TABLE 11.4-2)
SMS = FaSs =1.546 (EQN 11.4-1)
SM1 = FvS1 =0.853 (EQN 11.4-2)
SDS = 2/3SMS =1.030 (EQN 11.4-3)
SD1 = 2/3SM1 =0.569 (EQN 11.4-4)
1.000 (TABLE 1.5-2)
0.552 (SECTION 11.4.6)
SDC BASED ON SDS =D (TABLE 11.6-1)**EXCEPTION IN SECTION 11.6 CAN BE CHECKED S1<0.75 AND Ta<0.8Ts
SDC BASED ON SD1 =N/A (TABLE 11.6-2)
DESIGN SDC =D (SECTION 11.6)
R FRONT/BACK =6.500 R SIDE/SIDE =6.500 (TABLE 12.2-1 (A.15))
0.020 (TABLE 12.8-2)
x =0.750 (TABLE 12.8-2)
0.142 (EQN 12.8-7)
TL =6.000 (TABLE 22-14)
V = CSW (EQN 12.8-1)
CS = SEISMIC RESPONSE COEFFICIENT (SECTION 12.8.1.1)
W = EFFECTIVE SEISMIC WEIGHT (SECTION 12.7.2)
FRONT/BACK SIDE/SIDE
CS =SDS/(R/IE) =0.159 CS =SDS/(R/IE) =0.159
GOVERNS Csmax = SD1/(T(R/IE)) =0.618 GOVERNS Csmax = SD1/(T(R/IE)) =0.618
Csmax = SD1TL/(T2(R/IE)) =26.223 Csmax = SD1TL/(T2(R/IE)) =26.223
GOVERNS Csmin = 0.044*SDS*IE>=0.01 0.045 GOVERNS Csmin = 0.044*SDS*IE>=0.01 0.045
Csmin = 0.5S1/(R/IE) =0.036 Csmin = 0.5S1/(R/IE) =0.036
EQN 12.8-2 GOVERNS AND QE = V = 0.159 *W EQN 12.8-2 GOVERNS AND QE = V = 0.159 *W
SDS SDS
EV =0.206 *D 0.7*EV =0.144 *D EV =0.206 *D 0.7*EV =0.144 *D
Sales Office JEM
Elevation Label:
RISK CATEGORY =
SITE CLASS =
hn (ft) =
Ss =
S1 =
IE=
Ts=
**USE TABLE 11.6-1 ALONE IF RIGID DIAPHRAGM AND T<Ts OR WHEN
USING BRACING TABLES FOR IRC DESIGN
Ct=
Ta = Cthn
x =
}0.618 }0.618
}0.045 }0.045
> 0.125, THEREFORE > 0.125, THEREFORE
Printed by larissa.anaya on 02/07/2025 at 12:22
\\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\Sales Office\00 - Engineering\ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm
CLIENT:SHEET L12 OF
PROJECT:
Mass Calculations
Area
(ft2)
Load
(psf)
Weight
(lb)
Total
Length
(ft)
Load
(psf)
Weight
(lb)
Total
Length
(ft)
Load
(psf)
Weight
(lb)
Roof 9.1 2505 15 37575 214 10 9737 223.828 7 7129 54441
0 0 0 0
0 0 0 0
37575 9737 7129 54441
Base
Shear ASD
Eh
(lb)
Eh * 0.7
(lb)Level wx
(lb)
hx
(ft)
wxhx
(lb-ft)
wxhx
k
∑wihi
k
(%)
Fx
(lb)
Fx
Ax
(psf)
11219 7853 Roof 54441 9.1 495412 1.000 7853 3.14
0 0.0 0 0.000 0 0.00
0 0.0 0 0.000 0 0.00
54441 495412 7853
Base
Shear ASD
Eh
(lb)
Eh * 0.7
(lb)Level wx
(lb)
hx
(ft)
wxhx
(lb-ft)
wxhx
k
∑wihi
k
(%)
Fx
(lb)
Fx
Ax
(psf)
11219 7853 Roof 54441 9.1 495412 1.000 7853 3.14
0 0.0 0 0.000 0 0.00
0 0.0 0 0.000 0 0.00
54441 495412 7853
Sales Office
Total Mass
Total
Weight
(lb)
Redundancy Front/Back Vertical Distribution of Seismic Forces (12.8.3)
[Ta <= 0.5s k=1]
ρ
1.30
Level
Plate
Height
(ft)
Floor
Depth
(ft)
Diaphragm Exterior Walls
Redundancy Side/Side Vertical Distribution of Seismic Forces (12.8.3)
[Ta <= 0.5s k=1]
ρ
1.30
Interior Walls
Printed by larissa.anaya on 02/07/2025 at 12:22
\\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\Sales Office\00 - Engineering\ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm
SHEET L13 OF
BY
SHEAR DISTANCE UNIFORM START STOP
#FT PLF FT FT
1ST FLOOR
1ST FLOOR
1ST FLOOR
2477 0.000
1ST FLOOR
PROJECT:Sales Office JEM
LINE
CALLOUT % CANT.SEISMIC DESIGN SHEAR DIAPHRAGM
CLIENT:
NEXT
LINE
FROM
NEXT
CHORD
DIST.
FT
SOURCE LINE NEXT
LINE
#
SEISMIC LOAD SEISMIC DEPTH PARALLEL TO DIRECTION
PSF
TARGET
LINE
TO
TARGET
LINE
SPACING
FT
POINT SHEAR FROM
OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE
TARGET
LINE
#
A 40.000
3.14 60.000
3.14 65.000
19.000
3849
4005 656
204 19.000 40.000
FT
SHEAR
(#)
CHORD
(#)
3849 0
188 0.000
0
STORY CALC DESCRIPTION
0
40050B
0.00%
60.000
4005
0
0 0
0
0
0 0
0
0
STORY CALC DESCRIPTION
00
0.00%
0
2477
2477 611
0
0
0
125 0.000 39.500
0
1 39.500
3.14 40.000
2477
STORY CALC DESCRIPTION
247702*
0.00%
40.000
2477
4046
4046 246
66 20.500 25.500
0
2 25.500
3.14 40.000
3.14 21.000
4046 0
STORY CALC DESCRIPTION
133003
0.00%
40.000
1330
125 0.000 20.500
0
Printed by larissa.anaya on 02/07/2025 at 12:22
\\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\Sales Office\00 - Engineering\ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm
SHEET L14 OF
BY
LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1
V ==3849 #
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.7*
0.2*SDS
∑MOT
(#-ft)
∑MR
(#-ft)
1 3 24 21.00 10.00 2x6 1.4E+06 1932 1.000 92 232 20.00 10.00 15.00 0.14 19956 88200
2 3 24 19.00 9.08 2x6 1.4E+06 1919 1.000 101 232 20.00 10.00 15.00 0.14 17951 70545
3
4
5
6
3851
1 0 0
2 0 0
3
4
5
6
V ==4005 #
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.7*
0.2*SDS
∑MOT
(#-ft)
∑MR
(#-ft)
1 3 24 10.83 9.08 2x6 1.4E+06 1061 1.000 98 232 20.00 10.00 15.00 0.14 9806 22920
2 3 24 8.17 9.08 2x6 1.4E+06 784 1.000 96 232 20.00 10.00 15.00 0.14 7217 13034
3 3 24 21.50 9.08 2x6 1.4E+06 2172 1.000 101 232 20.00 10.00 15.00 0.14 20395 90331
4
5
6
4017
1 0 0
2 0 0
3 0 0
4
5
6
JEM
A
VTOTAL (#) =
CLIENT:
PROJECT:Sales Office
0.087
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
LEFT END RIGHT END
WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
B
TDESIGN
(#)HOLDOWNLOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)CONCRETE
VTOTAL (#) =
0.086
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
LEFT END RIGHT END
T2nd FLOOR
(#)CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
LOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
TDESIGN
(#)HOLDOWN
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
3rd FLOOR
3rd FLOOR
BASEMENT
BASEMENT
Printed by larissa.anaya on 02/07/2025 at 12:22
\\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\Sales Office\00 - Engineering\ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm
SHEET L15 OF
BY
LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1
V ==2477 #
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.7*
0.2*SDS
∑MOT
(#-ft)
∑MR
(#-ft)
1 3 24 18.00 9.08 2x6 1.4E+06 1692 1.000 94 232 2.00 10.00 15.00 0.14 15415 19574
2 3 24 6.33 9.08 2x6 1.4E+06 557 1.000 88 232 2.00 10.00 15.00 0.14 5065 2423
3 3 24 3.00 9.08 2x6 1.4E+06 240 0.872 80 202 2.00 10.00 15.00 0.14 2181 544
4
5
6
2489
1 800 0 800 0
2 800 90 800 90
3 800 138 800 138
4
5
6
V ==4046 #
WALL
n
Wall
Type
Studs
(in o.c.)
2
SIDED
Ln
(ft)
hn
(ft)
Wall
Width
Chord
En (psi)
D
(in)
Vdesign
(#)CWSP
vdesign
(plf)
vallow
(plf)
ATRIB.
(ft)
WWALL
(psf)
DL
(psf)
0.7*
0.2*SDS
∑MOT
(#-ft)
∑MR
(#-ft)
1 3 24 19.00 12.00 2x6 1.4E+06 4047 1.000 213 232 2.00 10.00 15.00 0.14 48616 27075
2
3
4
5
6
4047
1 CONC EXT CORNER 6 CRKD 800 1224 D CONC EXT CORNER 6 CRKD 800 1224 D
2
3
4
5
6
JEM
1
VTOTAL (#) =
CLIENT:
PROJECT:Sales Office
0.080
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
LEFT END RIGHT END
WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
2
TDESIGN
(#)HOLDOWNLOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)CONCRETE
VTOTAL (#) =
0.293
WALL
n
WOOD/
CONC
LOCATION
OR NAME POSITION STEM
LEFT END RIGHT END
T2nd FLOOR
(#)CONCRETE WINT.WALL
(#)
T2nd FLOOR
(#)
TDESIGN
(#)HOLDOWN WOOD/
CONC
LOCATION
OR NAME POSITION STEM CONCRETE WINT.WALL
(#)
TDESIGN
(#)HOLDOWN
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR
3rd FLOOR
3rd FLOOR
BASEMENT
BASEMENT
Printed by larissa.anaya on 02/07/2025 at 12:22
\\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\Sales Office\00 - Engineering\ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm
SHEET L16 OF
BY
LATERAL LOAD ANALYSIS: APA PORTAL FRAME PER TT-100H
V ==1330 #
2093 #
1.000
9.000
10.000
D =0.510 in
CLIENT:
PROJECT:Sales Office JEM
3
VALLOW =
Specific Gravity SG Reduction
2.000
APA PORTAL FRAME PER TT-100H
Number of Piers
Door Height (ft) =
Pier Height (ft) =
Left Pier (ft)
2
0.430 0.93 Beam Height (ft) =
FRONT-BACK SIDE-SIDE
1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT
Printed by larissa.anaya on 02/07/2025 at 12:22
\\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\Sales Office\00 - Engineering\ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm