Calcs- Shelm Meadows- Plan 1431 BainbridgeLGI Homes - WA 12951 Bel Red Rd Bellevue, Washington 98005 Shelm Meadows PLAN 1431- BAINBRIDGE INDEX TO STRUCTURAL CALCULATIONS Design Criteria SHEET 1 Vertical Analysis SHEETS 2-14 Lateral Analysis SHEETS L1-L18 OWNERSHIP OF DOCUMENTS: CALCULATIONS, DRAWINGS AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE, AND SHALL REMAIN THE PROPERTY OF THE ENGINEER. THEY ARE NOT TO BE USED ON OTHER PROJECTS OR EXTENSIONS OF THIS PROJECT EXCEPT BY AGREEMENT IN WRITING WITH THE APPROPRIATE COMPENSATION TO FELTEN GROUP, INC. WA-FE25-001104 130734 18325 N. ALLIED WAY, SUITE #200 * PHOENIX, AZ 85054 * PHONE: 602.867.2500 * FAX: 602.867.2503 02/12/25 2018 SHINGLE OR MEMBRANE PSF PSF 12.00 7.00 27.00 (MAX) GOVERNING CODE AND LATERAL LOAD CRITERIA: 3 SEC GUST (MPH): BUILDING CODE: MUNICIPALITY: Thurston County, WA 85/110 ROOF LOADS: ROOF FRAMING DEAD LOAD PSF 10.00NON-CONCURRENT ATTIC LL WITHOUT STORAGE (PSF) = LESS THAN 4:12 SLOPE ROOF LL (PSF) = 4:12 SLOPE AND GREATER TOTAL ROOF LL (PSF) = 16.00 20.00 15.00 ROOF FRAMING LIVE LOAD TOTAL ROOF DL (PSF) = DECK FRAMING LIVE LOAD TOTAL DECK LL (PSF) = 60.00 TOTAL FLOOR DL (PSF) = 10.00 WITH PARTITION WALLS (PSF) = +5.00 SEISMIC DESIGN CATEGORY: EXPOSURE AT MWFRS: EXPOSURE AT C & C: D2 C C TOTAL WALL DL (PSF) = INTERIOR WALL DEAD LOAD WITH TILE (PSF) = +5.00 EXTERIOR WALL DEAD LOAD WALL DEAD LOADS: FLOOR FRAMING LIVE LOAD TOTAL FLOOR LL (PSF) = 40.00 IBC/IRC TOTAL WALL DL (PSF) = TOTAL WALL DL W/ STONE VENEER (PSF) = SNOW LOAD TOTAL SNOW LOAD (PSF) = 20.00 FLOOR LOADS: FLOOR FRAMING DEAD LOAD PSF "Where quality engineering leads to lower costs." 2021 CLIENT: PROJECT: FELTENdROUP ARCHITECTURE I ENGINEERING I FORENSICS ROOF FRAMING PLAN DATE: SHEET OF BY: CLIENT: PROJECT: FELTENGROUP ARCHITECTURE I ENGINEERING I FORENSICS ROOF FRAMING PLAN DATE: SHEET OF BY: CLIENT: PROJECT: FELTENdROUP ARCHITECTURE I ENGINEERING I FORENSICS DATE: SHEET OF FLOOR FRAMING PLAN BY: SHEET 5 OF BY CLIENT:LGI HOMES PROJECT:PLAN 1431- VERTICAL LA Multi-Span Girder Key Girder Loading Point Loads Uniform Loads Id Load Type P (lb)x (ft)wstart (plf)wstop (plf)Total Length (ft) Span 3 (ft) Left Right xstart (ft)xstop (ft) Span 1 (ft) Span 2 (ft)Cantilever Data Truss Type Span 4 (ft)Girder Ply Requirements Based on Crushing Post Height Post Height Support Material Type Support Material Type Support Material Type Support Material Type Support Material Type Load Combo Max/Min Reaction R4 (lb) Load Combo Max/Min Reaction R5 (lb) Load Combo Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Max/Min Reaction R1 (lb) Load Combo Max/Min Reaction R2 (lb) Load Combo Max/Min Reaction R3 (lb) Post Height Post Height Posts / Hanger Posts / Hanger Posts / Hanger Posts / Hanger Fo u n d a t i o n S u p p o r t D e s i g n Support Condition Support Condition Support Condition Support Condition Support Condition Gi r d e r S u p p o r t De s i g n Post Height Posts / Hanger Support Location Support Location Support Location Support Location Support Location Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in) Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf) Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in) Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in) Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb) Girder Diagram Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf) Support Size Support Size Support Size Support Size Support Size Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 6 OF BY D 60 60 0.000 14.000 S 100 100 0.000 14.000 0.6W -40 -40 0.000 14.000 1120 1120 -31 -31 D 15 15 0.000 40.000 S 25 25 0.000 40.000 0.6W -10 -10 0.000 40.000 D 15 15 0.000 14.000 S 25 25 0.000 14.000 0.6W -10 -10 0.000 14.000 D 60 60 14.000 40.000 S 100 100 14.000 40.000 0.6W -40 -40 14.000 40.000 519 4190 1611 -14 -115 -44 PROJECT:PLAN 1431- VERTICAL LA G1 CLIENT:LGI HOMES 14.000 Cantilever Data Truss Type Total Length (ft) No 2x Roof 14.000No Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider) 0.6D + 0.6W 0.6D + 0.6W 5.5 5.5 Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional 9.083 9.083 Edge Edge (0) 2x6 POSTS (0) 2x6 POSTS 12 12 2500 2500 18 18 410 410 NO FTG REQ'D NO FTG REQ'D 20.000 G2 No 2x Roof 40.000No 20.000 Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n D + S D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING 0.6D + 0.6W 0.6D + 0.6W 0.6D + 0.6W 5.5 5.5 5.5 9.083 9.083 9.083 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider) Edge Edge Edge (0) 2x6 POSTS (1) 2x6 POSTS (0) 2x6 POSTS Conventional Conventional Conventional 12 12 12 2500 2500 2500 18 18 18 530 1090 530 NO FTG REQ'D NO FTG REQ'D NO FTG REQ'DFo u n d a t i o n S u p p o r t D e s i g n 14' 120 120 20'20' 60 60 150 150 Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 7 OF BY Left Support Right Support Rleft (#)Rright (#) Vd Mmax fb F'b CD fv F'v CL Δactual Δmax CF/CV Cfu Cr Use: 446 446 210 0.000 4.250 385 474 5.5 5.5 929 1459 8.000 8.000 1.15 55 173 9.083 9.083 N/A 2500 N/A 2500 0.995 0.111 0.170 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)12 18 12 18 1.500 1.000 (1) 2x6 KS (1) 2x6 KS 290 0 290 0 1.00 Use:(1) 2x6 (1) 2x6 656 656 210 0.000 6.250 560 1025 5.5 5.5 814 1256 8.000 8.000 1.15 51 173 9.083 9.083 N/A 2500 N/A 2500 0.988 0.133 0.250 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)12 18 12 18 1.300 1.000 (1) 2x6 KS (1) 2x6 KS 290 0 290 0 1.00 Use:(1) 2x6 (1) 2x6 1381 1381 850 0.000 3.250 992 1122 5.5 5.5 890 1263 8.000 8.000 1.15 90 173 9.083 9.083 N/A 2500 N/A 2500 0.994 0.039 0.130 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)12 18 12 18 1.300 1.000 (1) 2x6 KS (1) 2x6 KS 930 0 930 0 1.00 Use:(1) 2x6 (1) 2x6 480 480 160 0.000 6.000 357 720 5.5 5.5 173 1227 9.000 9.000 1.15 17 207 N/A 2500 N/A 2500 0.988 0.013 0.240 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)12 18 12 18 1.200 1.000 200 0 200 0 1.00 Use:(1) 2x6 (1) 2x6 1706 1706 210 0.000 16.250 1496 6932 5.5 5.5 1109 2031 9.000 9.000 1.15 60 305 N/A 2500 N/A 2500 0.736 0.407 0.650 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)12 9 12 9 1.000 1.000 290 0 290 0 1.00 Use:(1) 2x6 (1) 2x6 731 731 90 0.000 16.250 647 2971 5.5 5.5 563 877 9.000 9.000 1.15 29 173 N/A 2500 N/A 2500 0.897 0.305 0.650 Hem-Fir Stud (2" & wider)Hem-Fir Stud (2" & wider)12 9 12 9 1.000 1.000 200 0 200 0 1.00 Use:(1) 2x6 (1) 2x6 PROJECT:PLAN 1431- VERTICAL LA Beam / Header Design and Loading CLIENT:LGI HOMES Point Loads Uniform Loads Results Left Support Right Support Id Span (ft) P (#)x (ft)w (plf) Unbraced Length(ft) King Stud Height (ft)Slab Thickness (in)Bearing Pressure (psf) Trimmer and King Stud Material Standard Width (in)Standard Depth (in) start (ft)stop (ft) Bearing Length (in) / Hanger Support Condition Trimmer or Post Height (ft)Location Of Support H1 4.250 Conventional Conventional Edge Edge Material Type Member Size King Studs Uniform Load (plf)Point Load (#) Dual Spec Material Type Dual Spec Member Size Trimmers/ Hangers Size (in) H2 6.250 Conventional Conventional Edge Edge 4.250 Hem-Fir #2 Common (2) 2x4 Select Material NO FTG REQ'D NO FTG REQ'D H3 3.250 Conventional Conventional Edge Edge 6.250 Hem-Fir #2 Common (2) 2x6 Select Material NO FTG REQ'D NO FTG REQ'D H4 6.000 Conventional Conventional Edge Edge 3.250 Hem-Fir #2 Common (2) 2x6 Select Material NO FTG REQ'D NO FTG REQ'D H5 16.250 Conventional Conventional Edge Edge 6.000 Doug-Fir #2 (2" & wider)4x10 Select Material NO FTG REQ'D NO FTG REQ'D H6 16.250 Conventional Conventional Edge Edge 16.250 24F-1.8E (24F-V4)3 1/8 x 12 Select Material NO FTG REQ'D NO FTG REQ'D 16.250 Hem-Fir #2 Common (2) 2x12 Select Material NO FTG REQ'D NO FTG REQ'D Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 8 OF BY Lub,top (ft)TL (L/x) Lub,bot (ft)LL (L/x) Cr Ci CM CT Dmax (in) CLtop Dcant (in) CLbot Left dn (in)Dmax (in) CF/Cvtop Right dn (in)Dcant (in) CF/Cvbot Cfu CLIENT:LGI HOMES PROJECT:PLAN 1431- VERTICAL LA Single Multi-Span Header / Beam Key F'v (psi) F'b+ (psi) fb- (psi)F'b- (psi) Total Length, L (ft) Allowable StressPoint Loads Uniform Loads Id Load Type P (lb)x (ft)wstart (plf)wstop (plf)xstart (ft) Header/Beam Loading Unbraced Lengths Deflection Data Results Load Combo Actual Stress Span 1 (ft) NDS Factors Cantilever Data M+max (lb-ft)M+fb+ (psi) Left DTL Limit M-max (lb-ft)M- xstop (ft) DL Creep Factor Vmax (lb)V fv (psi) Span 2 (ft) Right DLL Limit Deflections DTL Span 3 (ft) Scarf Cut Data DTL DLL DLL Span 4 (ft)Material Type Member Size Span 5 (ft) Span 6 (ft) Span 7 (ft) Span 8 (ft) Span 9 (ft) He a d e r / B e a m S u p p o r t De s i g n Max/Min Reaction R1 (lb) Load Combo Max/Min Reaction R2 (lb) Load Combo Max/Min Reaction R3 (lb) Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height Support Material Type Trimmer or Post Height Trimmer or Post Height King Stud Height King Stud Height King Stud Height King Stud Height King Stud Height Load Combo Max/Min Reaction R4 (lb) Load Combo Max/Min Reaction R5 (lb) Load Combo Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Support Material Type Support Material Type Support Material Type Support Material Type Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Support Condition Support Location Support Location Support Location Support Location Support Location King Studs King Studs King Studs King Studs King Studs Support Condition Support Condition Support Condition Support Condition Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in) Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf) Point Load at Support (lb) Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf) Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in) Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in) He a d e r / B e a m S u p p o r t De s i g n Max/Min Reaction R6 (lb) Load Combo Max/Min Reaction R7 (lb) Load Combo Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb) Fo u n d a t i o n S u p p o r t D e s i g n Max/Min Reaction R8 (lb) Load Combo Max/Min Reaction R9 (lb) Load Combo Max/Min Reaction R10 (lb) Load Combo Support Size Support Size Support Size Support Size Support Size Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height King Stud Height King Stud Height King Stud Height King Stud Height King Stud Height Support Material Type Support Material Type Support Material Type Support Material Type Support Material Type Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger King Studs King Studs King Studs King Studs King Studs Support Location Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in) Fo u n d a t i o n S u p p o r t D e s i g n Support Condition Support Condition Support Condition Support Condition Support Condition Support Location Support Location Support Location Support Location Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf) Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in) Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in) Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb) Beam/Header Diagram Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf) Support Size Support Size Support Size Support Size Support Size Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 9 OF BY D 24 24 0.000 49.957 1.000 240 L 64 64 0.000 49.957 360 Factors Yes 1.150 No MC<=19% T<=100 -0.136 0.990 0.000 0.803 No -0.096 1.100 No 0.000 1.100 1.000 410 1040 503 734 705 120 305 148 215 207 841 291 247 86 PROJECT:PLAN 1431- VERTICAL LA CLIENT:LGI HOMES -1042 D + L J1 1.000 525 D + L 57 150 49.957 8.000 Hem-Fir #2 (2" & wider)2x10 Select Material 584 864 7.250 No Deflections D + L 7.250 11.125 Cantilever Data 929 D + L 521 1064 No 8.166 8.166 He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data L D + L D + L D + L D + L D + L D D D D D 5.125 3.125 3.125 3.125 3.125 To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below 3.125 5.125 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below To Framing Below Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below To Framing Below To Framing Below To Framing Below 11.125'7.25'7.25'8'8.166'8.166' 88 88 Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 10 OF BY D 155 155 0.000 25.108 1.000 240 L 413 413 0.000 25.108 360 Factors No 1.000 No MC<=19% T<=100 -0.040 0.999 0.003 0.997 No -0.029 1.300 No 0.002 1.300 1.000 2695 3461 3155 3758 755 970 884 1053 1303 365 PROJECT:PLAN 1431- VERTICAL LA CLIENT:LGI HOMES 120 -2026 D + L C1 1.000 1637 D + L 97 180 25.108L 5.777 Doug-Fir #2 (2" & wider)4x8 Select Material 793 1167 5.777 No 180 Deflections D + L 5.777 2.000 Cantilever Data 1482 D + L 580 1169 Yes 5.777 He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data D + L L D + L D + L D + L D + L D D D D 3.5 3.5 3.5 3.5 4 4 4 4 Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider) 4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS Isolated Footing Isolated Footing Isolated Footing Isolated Footing 2500 2500 2500 2500 0 0 0 0 15" DIA. x 8" DEEP NO REBAR 16" DIA. x 8" DEEP NO REBAR 16" DIA. x 8" DEEP NO REBAR 17" DIA. x 8" DEEP NO REBAR 3.5 He a d e r / B e a m S u p p o r t De s i g n D + L D Fo u n d a t i o n S u p p o r t D e s i g n 4 Doug-Fir #2 (2" & wider) 4x4 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Isolated Footing 2500 0 10" DIA. x 8" DEEP NO REBAR 2'5.777'5.777'5.777'5.777' 567 567 Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 11 OF BY D 155 155 0.000 25.108 1.000 240 L 413 413 0.000 25.108 360 Factors No 1.000 No MC<=19% T<=100 -0.040 0.999 0.003 0.997 No -0.029 1.300 No 0.002 1.300 1.000 1303 3758 3155 3461 2695 365 1053 884 970 755 PROJECT:PLAN 1431- VERTICAL LA CLIENT:LGI HOMES 120 -2026 D + L C1 1.000 1637 D + L 97 180 25.108L 5.777 Doug-Fir #2 (2" & wider)4x8 Select Material 793 1167 5.777 Yes 180 Deflections D + L 5.777 5.777 Cantilever Data 1482 D + L 580 1169 No 2.000 He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data D + L L D + L D + L D + L D + L D + L D D D D D 3.5 3.5 3.5 3.5 3.5 4 4 4 4 4 Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider) 4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS Isolated Footing Isolated Footing Isolated Footing Isolated Footing Isolated Footing 2500 2500 2500 2500 2500 0 0 0 0 0 10" DIA. x 8" DEEP NO REBAR 17" DIA. x 8" DEEP NO REBAR 16" DIA. x 8" DEEP NO REBAR 16" DIA. x 8" DEEP NO REBAR 15" DIA. x 8" DEEP NO REBAR He a d e r / B e a m S u p p o r t De s i g n Fo u n d a t i o n S u p p o r t D e s i g n Fo u n d a t i o n S u p p o r t D e s i g n 5.777'5.777'5.777'5.777'2' 567 567 Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 12 OF BY D 145 145 0.000 19.165 1.000 240 L 388 388 0.000 19.165 360 Factors No 1.000 No MC<=19% T<=100 -0.010 0.999 -0.008 0.997 No -0.007 1.300 No -0.006 1.300 1.000 2421 2738 2738 2421 676 765 765 676 PROJECT:PLAN 1431- VERTICAL LA CLIENT:LGI HOMES 120 -1160 D + L C2 1.000 1077 D + L 64 180 19.165L 5.055 Doug-Fir #2 (2" & wider)4x8 Select Material 454 1166 5.055 Yes 180 Deflections D + L 5.055 2.000 Cantilever Data 601 D + L 235 1169 Yes 2.000 He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data D + L L D + L D + L D + L D + L D D D D 3.5 3.5 3.5 3.5 4 4 4 4 Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider) 4x4 POSTS 4x4 POSTS 4x4 POSTS 4x4 POSTS Isolated Footing Isolated Footing Isolated Footing Isolated Footing 2500 2500 2500 2500 0 0 0 0 14" DIA. x 8" DEEP NO REBAR 15" DIA. x 8" DEEP NO REBAR 15" DIA. x 8" DEEP NO REBAR 14" DIA. x 8" DEEP NO REBAR He a d e r / B e a m S u p p o r t De s i g n Fo u n d a t i o n S u p p o r t D e s i g n Fo u n d a t i o n S u p p o r t D e s i g n 2'5.055'5.055'5.055'2' 533 533 Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 13 OF BY D 173 173 0.000 12.666 1.000 240 L 463 463 0.000 12.666 360 Factors No 1.000 No MC<=19% T<=100 -0.004 0.999 -0.018 0.997 No -0.003 1.300 No -0.013 1.300 1.000 2765 2582 2765 770 719 770 PROJECT:PLAN 1431- VERTICAL LA CLIENT:LGI HOMES 120 -1281 D + L C3 1.000 1281 D + L 76 180 12.666L 2.000 Doug-Fir #2 (2" & wider)4x8 Select Material 501 1166 4.333 Yes 180 Deflections D + L 4.333 2.000 Cantilever Data 438 D + L 172 1169 Yes He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data D + L L D + L D + L D + L D D D 3.5 3.5 3.5 4 4 4 Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider)Doug-Fir #2 (2" & wider) 4x4 POSTS 4x4 POSTS 4x4 POSTS Isolated Footing Isolated Footing Isolated Footing 2500 2500 2500 0 0 0 15" DIA. x 8" DEEP NO REBAR 14" DIA. x 8" DEEP NO REBAR 15" DIA. x 8" DEEP NO REBAR He a d e r / B e a m S u p p o r t De s i g n Fo u n d a t i o n S u p p o r t D e s i g n Fo u n d a t i o n S u p p o r t D e s i g n 2'4.333'4.333'2' 636 636 Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm SHEET 14 OF BY S1 1 3.00 180 YES 1.50 0.7 NO ROOF TYPE:15.00 9.08 40.00 10.00 TARGET WALL 1.00 25.00 21.00 9.05 16.13 9.08 SPECIES TITLE 10.10 10.00 SCANT CFB b (IN) 5.00 FB (PSI)CFC d (IN) 8.71 FC (PSI)CR A (IN2) 5.50 0.00 EMIN (PSI)c Sx (IN3) Ex (PSI)Ix (IN4) CD 0.90 172.78 " o.c. 1.00 186.52 " o.c. 1.25 215.76 " o.c. 1.15 83.41 " o.c. 1.25 215.76 " o.c. 1.25 215.76 " o.c. 1.15 97.93 " o.c. 1.25 215.76 " o.c. 1.60 87.60 " o.c. 1.60 109.80 " o.c. 1.60 103.68 " o.c. 1.60 68.40 " o.c. 1.60 103.68 " o.c. 1.60 125.16 " o.c. 1.60 77.28 " o.c. 1.60 125.16 " o.c. 1.60 64.49 " o.c.GOVERNS 1.00 " o.c. 24 " o.c. C&CWIND DEFLECTION, L/GYP OR WOOD COMP. SOLE PLATE THICKNESS (IN)PRE-FAB TRUSSES C&CWIND FACTOR = GYP AND WOOD COMP. CLIENT:LGI HOMES PROJECT:PLAN 1431- VERTICAL LA WALL NUMBER:STUD LOCATION:(1 = ROOF, 2 = FIRST FLOOR BELOW ROOF, 3 = SECOND FLOOR BELOW ROOF) ROOF SPAN (FT)ROOF LOADS (PSF)SUPPORTING WALL SIMPLE D HEIGHT (FT) TOP PLATE THICKNESS (IN)WALL HAS CONTINUOUS SHEATHING ON ONE SIDE YES ROOF ASSEMBLY TYPE SIMPLE 0.6*WUPLIFT MAIN SPAN LR WEIGHT (PSF) OVERHANG S TOTAL TRIB.R TARGET WALL STUD MATERIAL 0.6*C&C (PSF)HEIGHT (FT)Hem-Fir Stud (2" & wider)2x6 HEM-FIR STUD GRADE STUDS 0.6*W (PSF)WEIGHT (PSF)NO 1.00 1.50 0.7*E (PSF)PARTIAL LOADING (WIND)675 1.00 5.50 STOP (FT)800 1.15 8.250 WALL WIDTH (IN)START (FT)440000 0.80 7.563 D + R D + 0.75L + 0.75LR D + 0.75L + 0.75S D + 0.75L + 0.75R D + 0.6W D + 0.7E 1200000 20.797 ASCE7 LOAD COMBINATIONS C & C LOADING BENDING (NDS Section 3.3) Le = 9.08ft - (3.00in + 1.50in)(1ft/12in) = 8.71ft M = 305.84#-ft F'b = Fb(Cd)(Cr)(Cfb) = 675(1.60)(1.15)(1.00) = 1242.00psi fb = (12in/1ft)(305.84#-ft)/7.56in^3 = 485.30psi DEFLECTION (NDS Section 3.5.1) DELTA = 0.09in BENDING AND DEFLECTION CAPACITY CHECK 485.30psi/1242.00psi = 0.391 < 1.000 O.K. 0.09in < 0.58in O.K. THEREFORE, USE 2x6 HEM-FIR STUD GRADE STUDS AT 24in O.C. D D + L D + LR D + S 0.6C&C1 D + L (NON-CONCURRENT) DESIRED SPACING FOR CALCULATIONS: 1 Per Table IBC 1604.3 footnote f, for ASD the wind load for deflection shall be taken as 0.42 times the C&C loading. The 0.42 factor is a conversion from Ultimate loads to service loads (0.6W) and then further multiplied by 0.7 to adjust for the 10 year mean return interval. Therefore, 0.6 * 0.7 = 0.42 D + 0.75(0.6W) + 0.75L + 0.75LR D + 0.75(0.6W) + 0.75L + 0.75S D + 0.75(0.6W) + 0.75L + 0.75R D + 0.75(0.7E) + 0.75L + 0.75LR D + 0.75(0.7E) + 0.75L + 0.75S D + 0.75(0.7E) + 0.75L + 0.75R Printed by Larissa.anaya on 02/12/2025 at 09:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- Vertical Book - SQL1.xlsm CLIENT: FELTENGROUP ARCHITECTURE I ENGINEERING I FORENSICS DATE: SHEET OF BRACED/SHEAR WALL PLAN BY: CLIENT:SHEET L2 OF PROJECT:BY 110 mph C (Section 26.7) II (Table 1.5-1) 0.85 (Table 26.6-1) 1.00 (Section 26.8.2) 100 (Section 26.9)Ke = 1.00 (Table 26.9-1) 0.6 (Section 2.4.1) Truss Heel Height:0.333 ft Plate Height:9.083 ft Length (Dimension Perpendicular to Truss Span):50.000 ft Width (Dimension Parallel to Truss Span):40.000 ft Roof Pitch:5.00 in/12 in Roof Angle:22.620 deg Mean Roof Height:13.583 ft Ridge Height:17.749 ft Design Edge Strip (a):4.000 ft Design End Zone (2a):8.000 ft Velocity Pressure Coefficient (Kz):0.850 (Table 26.10-1) 0.6*qz (Velocity Pressure):13.38 psf (Equation 26.10-1) 0.6*Pcc,wall (Maximum Wall Pressure):16.13 psf (Equation 30.3-1) 0.6*Pend zone stud (End Zone Stud Design Pressure):12.73 psf Load Case A 0.6*Pint zone stud (Int. Zone Stud Design Pressure):9.60 psf Load Case A 0.6*Pp (Parapet Pressure 1.5WW and -1.0LW):20.07 psf Windward and -13.38 psf Leeward Design Method:Low-Rise Building (Section 28.3.1) Basic Wind Speed (3 sec gust): Exposure: LGI HOMES PLAN 1431- WIND LA Elevation Label: Design Code:ASCE 7-16 Risk Category: Wind Directionality (Kd): Topographic Factor (Kzt): Ground Elevation Factor (ft) (Ke): ASD Load Combination Factor for W: ONE STORY DIAPHRAGM WIND LOADS FOR ASD LOAD COMBINATIONS Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L3 OF PROJECT:BY p = 0.6 * qz * [GCpf - GCpi](Equation 28.3-1) GCpf interpolated from Figure 28.3-1 GCpi 0.18 enclosed buildings Table 26.13-1 (GCpi acts either inward or outward at any one time) GCpf GCpi Zone 1:0.54 -0.18 Zone 2:-0.45 0.18 Zone 3:-0.47 0.18 Zone 4:-0.41 -0.18 Zone 1E:0.77 -0.18 Zone 2E:-0.72 0.18 Zone 3E:-0.65 0.18 Zone 4E:-0.60 -0.18 GCpf GCpi Zone 1:-0.45 -0.18 Zone 2:-0.69 0.18 Zone 3:-0.37 0.18 Zone 4:-0.45 -0.18 Zone 5:0.40 -0.18 Zone 6:-0.29 -0.18 Zone 1E:-0.48 -0.18 Zone 2E:-1.07 0.18 Zone 3E:-0.53 0.18 Zone 4E:-0.48 -0.18 Zone 5E:0.61 -0.18 Zone 6E:-0.43 -0.18 Note: Plus and minus signs signify pressures acting toward and away from the surfaces, respectively. LGI HOMES PLAN 1431- WIND LA Gable End Loading Load Case A Load Case B 7.20 -2.41 9.60 Hip End Loading Load Case A Load Case B Load Case A Pressures -6.08 2.41 -8.49 -6.25 2.41 -8.66 0.6*qz*GCpf (psf)0.6*qz*GCpi (psf)Pressure (psf) -9.62 2.41 -12.03 -8.67 2.41 -11.08 -5.54 -2.41 -3.13 10.32 -2.41 12.73 -6.02 -2.41 -3.61 -9.23 2.41 -11.64 -8.00 -2.41 -5.59 Load Case B Pressures 0.6*qz*GCpf (psf)0.6*qz*GCpi (psf)Pressure (psf) 5.35 -2.41 7.76 -3.88 -2.41 -1.47 -4.95 2.41 -7.36 -6.02 -2.41 -3.61 -7.09 2.41 -9.50 -6.42 -2.41 -4.01 -6.42 -2.41 -4.01 -14.32 2.41 -16.72 8.16 -2.41 10.57 -5.75 -2.41 -3.34 Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L4 OF PROJECT:BY Case A 6.64 psf 6.63 psf Case B 10.05 psf 5.29 psf GCpf GCpf 6.35 psf 4.59 psf GCpf GCpf 7.70 psf 5.94 psf GCpi GCpi 2.41 psf 2.41 psf 13.63 psf 10.93 psf 0.00 psf 9.05 psf 10.08 psf 3323 #3954 # 3472 # Case A 6.64 psf 6.63 psf Case B 8.25 psf 7.09 psf GCpf GCpf GCpf GCpf 7.70 psf 5.94 psf 5.49 psf 3.97 psf GCpi GCpi 2.41 psf 2.41 psf 13.63 psf 9.47 psf 0.00 psf 0.00 psf 9.05 psf 10.08 psf 3323 #1846 # LGI HOMES PLAN 1431- WIND LA Load Cases A & B total pressures are determined by using a weighted average of end zone total plus interior zone total. This number is then compared to the code required 16psf minimum for the horizontal direction. Roof uplift for the left and right sides of the roof are determined using a weighted Total Horizontal Pressure at Wall =Total Horizontal Pressure at Wall = average of end zone plus interior zone and then the total roof uplift is the average of the left and right sides. GCpi assumed to act inward for wall design, outward for roof uplift design. ONE STORY DIAPHRAGM GABLE END WIND LOADS FOR ASD LOAD COMBINATIONS Load Case A Load Case B GCpf Windward GCpf Leeward ∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case A ∴Use 10.93 psf Wall Horizontal Pressure at Case B ∴Use 10.10 psf at Wall for Windward Only Case (0.6*W)∴Use 8.76 psf at Wall for Windward Only Case (0.6*W) Total Horizontal Pressure at Roof = Total Uplift Pressure at Roof =Total Uplift Pressure at Roof = Total Base Shear Due to Wind Loads =Total Base Shear Due to Wind Loads = Total Base Shear Due to 0.6*16psf at Wall and 0.6*8psf at Roof =4340 #Total Base Shear Due to 0.6*16psf = Total Horizontal Pressure at Wall =Total Horizontal Pressure at Wall = Total Horizontal Pressure at Roof =Total Horizontal Pressure at Roof = Total Uplift Pressure at Roof =Total Uplift Pressure at Roof = ONE STORY DIAPHRAGM HIP END WIND LOADS FOR ASD LOAD COMBINATIONS Load Case A Load Case B GCpf Windward GCpf Leeward GCpf Windward GCpf Leeward ∴Use 10.10 psf at Wall for Windward Only Case (0.6*W)∴Use 7.90 psf at Wall for Windward Only Case (0.6*W) 2672 # ∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case A ∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case B Total Base Shear Due to Wind Loads =Total Base Shear Due to Wind Loads = Total Base Shear Due to 0.6*16psf at Wall and 0.6*8psf at Roof =3540 #Total Base Shear Due to 0.6*16psf at Wall and 0.6*8psf at Roof = Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L5 OF BY WALL ROOF PARAPET TRIB. WALL HEEL TRIB. RIDGE PARAPET SHEAR DISTANCE PRESSURE PRESSURE PRESSURE HEIGHT HEIGHT TO HEEL HEIGHT UNIFORM START STOP #FT PSF PSF PSF FT FT FT FT PLF FT FT 10.93 10.93 4.542 0.333 4.167 1ST FLOOR 1ST FLOOR 1ST FLOOR 1ST FLOOR PROJECT:PLAN 1431- WIND LA LINE CALLOUT % CANT.WIND DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES SHEAR (#) CHORD (#) WINDWARD INFORMATION LEEWARD INFORMATION NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # 1977 1977 439 0 0 99 0.000 B 0.00% 45.000 0 40.000 A 40.000 1977 19770 1977 0 STORY CALC DESCRIPTION ALL ELEVATIONS 0 0 0 0 0 0 0 0 0.00%0 0 0 0 STORY CALC DESCRIPTION 0 0 0 0 0 0 0 0 0.00%0 0 0 0 STORY CALC DESCRIPTION 0 0 0 0 0 0 0 0 0.00%0 STORY CALC DESCRIPTION 0 0 0 Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L6 OF BY WALL ROOF PARAPET TRIB. WALL HEEL TRIB. RIDGE PARAPET SHEAR DISTANCE PRESSURE PRESSURE PRESSURE HEIGHT HEIGHT TO HEEL HEIGHT UNIFORM START STOP #FT PSF PSF PSF FT FT FT FT PLF FT FT 9.60 4.80 4.542 0.333 8.333 9.60 4.80 4.542 0.333 2.917 1ST FLOOR 1ST FLOOR 9.60 4.80 4.542 0.333 8.333 9.60 4.80 4.542 0.333 4.167 9.60 4.80 4.542 0.333 2.917 9.60 4.80 4.542 0.333 1.458 1ST FLOOR 1ST FLOOR PROJECT:PLAN 1431- WIND LA LINE CALLOUT % CANT.WIND DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES SHEAR (#) CHORD (#) WINDWARD INFORMATION LEEWARD INFORMATION NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # 2163 2163 674 61 45.000 50.000 0 87 0.000 2 0.00% 40.000 0 45.000 1 50.000 2163 20460 2046 0 STORY CALC DESCRIPTION ELEVATION A 0 0 0 0 0 0 0 0 0.00%0 0 0 0 STORY CALC DESCRIPTION 1 50.000 87 0.000 25.000 2033 2033 595 67 25.000 38.000 43.000 50.000 1686 2033 61 38.000 43.000 2 0.00% 40.000 54 0 1686 0 STORY CALC DESCRIPTION ELEVATION B 0 0 0 0 0 0 0 0 0.00%0 STORY CALC DESCRIPTION 0 0 0 Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L7 OF BY WIND DESIGN: WALL BRACING ANALYSES 110 13.58 1 1 C 8.33 9 2 NO YES NO NO 0.00 0.00 40.00 0.00 1.20 0.90 0.95 1.00 1.00 1.00 1.00 1.00 1.00 6.50 0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP WSP L (ft)20.00 8.00 16.00 ADJ. H (ft) LCONT. (ft)20.00 8.00 16.00 44.00 110 13.58 1 1 C 8.33 9 2 NO YES NO NO 0.00 0.00 40.00 0.00 1.200 0.900 0.950 1.000 1.000 1.000 1.000 1.000 1.000 6.500 0.000 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP L (ft)45.00 ADJ. H (ft) LCONT. (ft)45.00 45.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 CLIENT:LGI HOMES PROJECT:PLAN 1431- WIND LA BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL A 6.67 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 44.00>=6.67 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL B 6.67 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 45.00>=6.67 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOORBASEMENT Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L8 OF BY WIND DESIGN: WALL BRACING ANALYSES 110 13.58 1 1 C 8.33 9 2 NO YES NO NO 0.00 0.00 24.50 0.00 1.20 0.90 0.95 1.00 1.00 1.00 1.00 1.00 1.00 4.18 0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP L (ft)19.50 6.63 ADJ. H (ft) LCONT. (ft)19.50 6.63 26.13 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 CLIENT:LGI HOMES PROJECT:PLAN 1431- WIND LA BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL 1 4.28 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 26.13>=4.28 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOORBASEMENT Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L9 OF BY LATERAL LOAD ANALYSIS: FORCE TRANSFER AROUND OPENINGS (FTAO) SDPWS 4.3.5.2 V ==544 # 740 # 2.00 15.00 9.05 740 # 1.083 →→ ←← 5.000 →→ ←← 3.000 →→→ ←←← 4.000 6.000 4.000 D =0.076 in WOOD 353 Left Uplift from Above (#) Right Uplift from Above (#) 0 0 Type of Shear (Wall/Value (plf)) 3 Left Restraint (#) Right Restraint (#)Left Pier (ft) =Window (ft) =Right Pier (ft) = 0 0 250 250 189 118 0 0.000 0.000 0 118 189 Left Holdown Strap Force (#) Max. Shear Panel Force (plf) Right Holdown Strap Force (#)Bottom Pier (ft) = Concrete Concrete Name / Value (#) / D Name / Value (#) / D Stem Stem 353 353 353 353 Position Position Left Sill Strap Force (#) Right Sill Strap Force (#) Window (ft) = Location Location 10 Material Material Wall Weight (psf) 353 353 353 353 Left Holdown Right Holdown NO STRAP Top Pier (ft) = 353 24 353 Left Strap (Name/Value (#)) Right Strap (Name/Value (#))Left Header Strap Force (#) Stud Spacing (inches o.c.) Right Header Strap Force (#)NO STRAP ATRIB. (ft) =Roof DL (psf) =WUPLIFT (psf) =← VALLOW = → VALLOW = CLIENT:LGI HOMES PROJECT:PLAN 1431- WIND LA 2 FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L10 OF BY LATERAL LOAD ANALYSIS: APA PORTAL FRAME PER TT-100H V ==1502 # 2930 # 1.000 9.000 10.000 D =0.510 in CLIENT:LGI HOMES PROJECT:PLAN 1431- WIND LA 2 2 VALLOW = Specific Gravity SG Reduction 0.430 0.93 Beam Height (ft) = Number of Piers Door Height (ft) = Pier Height (ft) = Left Pier (ft) 2.000 APA PORTAL FRAME PER TT-100H FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/11/2025 at 13:03 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L11 OF PROJECT:BY SEISMIC LOAD CALCULATIONS PER ASCE 7-16 *USING BASIC LOAD COMBINATIONS PER SECTION 2.4* ALL LOAD COMBINATIONS USE: 0.7*E E = Eh + Ev (EQN 12.4-1 and EQN 12.4-3) Eh = ρQE (EQN 12.4-3) ρ = 1.30 (SECTION 12.3.4.2.a) QE = V (SECTION 12.4.2.1) Ev = 0.2SDSD (EV = 0 IF SDS <= 0.125)(EQN 12.4-4a) II (TABLE 1.5-1) D (PER PROJECT SOILS REPORT OR TABLE 20.3-1)DEFAULT 13.583 (MEAN ROOF HEIGHT OF STRUCTURE) 1.288 (MAPPED MCE SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS) 0.465 (MAPPED MCE SPECTRAL RESPONSE ACCELERATION AT A PERIOD OF 1 s) Fa =1.200 (TABLE 11.4-1) Fv =1.835 (TABLE 11.4-2) SMS = FaSs =1.546 (EQN 11.4-1) SM1 = FvS1 =0.853 (EQN 11.4-2) SDS = 2/3SMS =1.030 (EQN 11.4-3) SD1 = 2/3SM1 =0.569 (EQN 11.4-4) 1.000 (TABLE 1.5-2) 0.552 (SECTION 11.4.6) SDC BASED ON SDS =D (TABLE 11.6-1)**EXCEPTION IN SECTION 11.6 CAN BE CHECKED S1<0.75 AND Ta<0.8Ts SDC BASED ON SD1 =N/A (TABLE 11.6-2) DESIGN SDC =D (SECTION 11.6) R FRONT/BACK =6.500 R SIDE/SIDE =6.500 (TABLE 12.2-1 (A.15)) 0.020 (TABLE 12.8-2) x =0.750 (TABLE 12.8-2) 0.142 (EQN 12.8-7) TL =6.000 (TABLE 22-14) V = CSW (EQN 12.8-1) CS = SEISMIC RESPONSE COEFFICIENT (SECTION 12.8.1.1) W = EFFECTIVE SEISMIC WEIGHT (SECTION 12.7.2) FRONT/BACK SIDE/SIDE CS =SDS/(R/IE) =0.159 CS =SDS/(R/IE) =0.159 GOVERNS Csmax = SD1/(T(R/IE)) =0.618 GOVERNS Csmax = SD1/(T(R/IE)) =0.618 Csmax = SD1TL/(T2(R/IE)) =26.223 Csmax = SD1TL/(T2(R/IE)) =26.223 GOVERNS Csmin = 0.044*SDS*IE>=0.01 0.045 GOVERNS Csmin = 0.044*SDS*IE>=0.01 0.045 Csmin = 0.5S1/(R/IE) =0.036 Csmin = 0.5S1/(R/IE) =0.036 EQN 12.8-2 GOVERNS AND QE = V = 0.159 *W EQN 12.8-2 GOVERNS AND QE = V = 0.159 *W SDS SDS EV =0.206 *D 0.7*EV =0.144 *D EV =0.206 *D 0.7*EV =0.144 *D LGI HOMES PLAN 1431- SEISMIC LA Elevation Label: Ct= RISK CATEGORY = SITE CLASS = hn (ft) = Ss = S1 = IE= Ts= **USE TABLE 11.6-1 ALONE IF RIGID DIAPHRAGM AND T<Ts OR WHEN USING BRACING TABLES FOR IRC DESIGN Ta = Cthn x = }0.618 }0.618 }0.045 }0.045 > 0.125, THEREFORE > 0.125, THEREFORE Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L12 OF PROJECT: Mass Calculations Area (ft2) Load (psf) Weight (lb) Total Length (ft) Load (psf) Weight (lb) Total Length (ft) Load (psf) Weight (lb) Roof 9.083 2054 15 30810 192 10 8720 216.137 7 6871 46401 0 0 0 0 0 0 0 0 30810 8720 6871 46401 Base Shear ASD Eh (lb) Eh * 0.7 (lb)Level wx (lb) hx (ft) wxhx (lb-ft) wxhx k ∑wihi k (%) Fx (lb) Fx Ax (psf) 9562 6694 Roof 46401 9.1 421458 1.000 6694 3.26 0 0.0 0 0.000 0 0.00 0 0.0 0 0.000 0 0.00 46401 421458 6694 Base Shear ASD Eh (lb) Eh * 0.7 (lb)Level wx (lb) hx (ft) wxhx (lb-ft) wxhx k ∑wihi k (%) Fx (lb) Fx Ax (psf) 9562 6694 Roof 46401 9.1 421458 1.000 6694 3.26 0 0.0 0 0.000 0 0.00 0 0.0 0 0.000 0 0.00 46401 421458 6694 LGI HOMES PLAN 1431- SEISMIC Total Mass Level Plate Height (ft) Floor Depth (ft) Diaphragm Exterior Walls Interior Walls Total Weight (lb) ρ 1.30 Redundancy Front/Back Vertical Distribution of Seismic Forces (12.8.3) [Ta <= 0.5s k=1] ρ 1.30 Redundancy Side/Side Vertical Distribution of Seismic Forces (12.8.3) [Ta <= 0.5s k=1] Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L13 OF BY SHEAR DISTANCE UNIFORM START STOP #FT PLF FT FT 1ST FLOOR 1ST FLOOR 1ST FLOOR 1ST FLOOR PROJECT:PLAN 1431- SEISMIC LA LINE CALLOUT % CANT.SEISMIC DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # SEISMIC LOAD SEISMIC DEPTH PARALLEL TO DIRECTION PSF TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # A 40.000 3.26 50.000 3.26 45.000 14.000 3121 3121 670 147 14.000 40.000 FT SHEAR (#) CHORD (#) 3121 0 163 0.000 0 STORY CALC DESCRIPTION 0 29730B 0.00% 45.000 2973 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L14 OF BY SHEAR DISTANCE UNIFORM START STOP #FT PLF FT FT 1ST FLOOR 1ST FLOOR 1ST FLOOR 1ST FLOOR PROJECT:PLAN 1431- SEISMIC LA LINE CALLOUT % CANT.SEISMIC DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # SEISMIC LOAD SEISMIC DEPTH PARALLEL TO DIRECTION PSF TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # 1 50.000 3.26 40.000 3.26 14.000 45.000 3238 3238 1005 46 45.000 50.000 FT SHEAR (#) CHORD (#) 3238 0 130 0.000 0 STORY CALC DESCRIPTION 0 285602 0.00% 40.000 2856 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L15 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==3121 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 20.00 9.00 2x6 1.4E+06 1440 1.000 72 232 21.00 10.00 15.00 0.14 24645 81000 2 3 24 8.00 9.00 2x6 1.4E+06 552 1.000 69 232 21.00 10.00 15.00 0.14 6838 12960 3 3 24 16.00 9.00 2x6 1.4E+06 1136 1.000 71 232 21.00 10.00 15.00 0.14 17702 51840 4 5 6 3128 1 0 0 2 0 0 3 0 0 4 5 6 V ==2973 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 45.00 9.00 2x6 1.4E+06 3015 1.000 67 232 21.00 10.00 15.00 0.14 86289 410063 2 3 4 5 6 3015 1 0 0 2 3 4 5 6 LA A VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1431- SEISMIC 0.061 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC B TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = 0.056 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM WOOD/ CONC LEFT END RIGHT END CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L16 OF BY LATERAL LOAD ANALYSIS: PERFORATED SHEAR WALLS (PSW) SDPWS 4.3.2.3 V ==3238 # 2.00 10.00 15.00 0.14 29407 96664 1 19.500 0 0 2 6.500 3 3.000 4 SDPWS Equation (4.3-6) C0 = Awall / (3SA0+SAfhs) 5 SDPWS Equation (4.3-5) VALLOW = vMAXC0Sbi 6 7 8 9 0.787 3 221 4869 >=3238 OK ∑Afhs =263.407 ∑AO =∑bi =27.982 V ==# 1 2 3 4 SDPWS Equation (4.3-6) C0 = Awall / (3SA0+SAfhs) 5 SDPWS Equation (4.3-5) VALLOW = vMAXC0Sbi 6 7 8 9 0 ∑Afhs =∑AO =∑bi = ∑MOT = Vh ∑MR = [DLATRIB.+WWALLh][LTOT]2/2 Wall Length, LTOT (ft)Wall Height, h (ft)Stud Spacing (in)TDESIGN = [∑MOT-(0.6-0.7*0.2*SDS)∑MR]/[CO∑bi]-(0.6-0.7*0.2*SDS)WINT.WALL+T2nd FLOOR {EQN 4.3-8} CLIENT:LGI HOMES PROJECT:PLAN 1431- SEISMIC LA 1 ATRIB. (ft) WWALL (psf) DL (psf) 0.7*0.2* SDS ∑MOT (#-ft) ∑MR (#-ft)LOCATION POSITION 40.000 9.083 24 LEFT END RIGHT END Full Height Wall Segment, Li (ft) Openings Adjusted Segment, bi (ft) WOOD/ CONC TDESIGN (#)HOLDOWN STEM CONCRETE WINT.WALL (#)STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)LOCATION POSITION TDESIGN (#)HOLDOWN Height (ft)Width (ft)Area, AO (ft2) T2nd FLOOR (#) 5.000 5.000 25.000 19.500 6.833 6.000 40.998 6.500 WOOD/ CONC 1.982 V (#) DESIGN CHECK PERFORATED SHEAR WALL RESULTS CO WALL TYPE vMAX (plf) VALLOW (#) ∑MOT = Vh ∑MR = [DLATRIB.+WWALLh][LTOT]2/2 Wall Length, LTOT (ft)Wall Height, h (ft)Stud Spacing (in)TDESIGN = [∑MOT-(0.6-0.7*0.2*SDS)∑MR]/[CO∑bi]-(0.6-0.7*0.2*SDS)WINT.WALL+T2nd FLOOR {EQN 4.3-8} 65.998 ATRIB. (ft) WWALL (psf) DL (psf) 0.7*0.2* SDS ∑MOT (#-ft) ∑MR (#-ft)LOCATION POSITION 24 LEFT END RIGHT END Full Height Wall Segment, Li (ft) Openings Adjusted Segment, bi (ft) WOOD/ CONC TDESIGN (#)HOLDOWN STEM CONCRETE WINT.WALL (#)STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)LOCATION POSITION TDESIGN (#)HOLDOWN Height (ft)Width (ft)Area, AO (ft2) T2nd FLOOR (#) WOOD/ CONC PERFORATED SHEAR WALL RESULTS CO WALL TYPE vMAX (plf) VALLOW (#) V (#) DESIGN CHECK FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L17 OF BY LATERAL LOAD ANALYSIS: FORCE TRANSFER AROUND OPENINGS (FTAO) SDPWS 4.3.5.2 V ==764 # 875 # 2.00 15.00 0.14 875 # 1.083 →→ ←← 5.000 →→ ←← 3.000 →→→ ←←← 4.000 6.000 4.000 D =#######in CLIENT:LGI HOMES PROJECT:PLAN 1431- SEISMIC LA 2 → VALLOW = Left Header Strap Force (#) Stud Spacing (inches o.c.) Right Header Strap Force (#)CS20 ATRIB. (ft) =Roof DL (psf) =0.7*0.2*SDS =← VALLOW = CS20 Top Pier (ft) = 417 24 417 Left Strap (Name/Value (#)) Right Strap (Name/Value (#)) Material Material Wall Weight (psf) 1030 1030 417 417 Left Holdown Right Holdown Window (ft) = Location Location 10 Stem Stem 417 417 417 417 Position Position Left Sill Strap Force (#) Right Sill Strap Force (#) Left Holdown Strap Force (#) Max. Shear Panel Force (plf) Right Holdown Strap Force (#)Bottom Pier (ft) = Concrete Concrete Name / Value (#) / D Name / Value (#) / D Left Restraint (#) Right Restraint (#)Left Pier (ft) =Window (ft) =Right Pier (ft) = 0 0 250 250 251 139 0 0.000 0.000 0 139 251 WOOD 252 Left Uplift from Above (#) Right Uplift from Above (#) 0 0 Type of Shear (Wall/Value (plf)) 3 FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L18 OF BY LATERAL LOAD ANALYSIS: APA PORTAL FRAME PER TT-100H V ==2092 # 2093 # 1.000 9.000 10.000 D =0.510 in CLIENT:LGI HOMES PROJECT:PLAN 1431- SEISMIC LA 2 2 VALLOW = Specific Gravity SG Reduction 0.430 0.93 Beam Height (ft) = Number of Piers Door Height (ft) = Pier Height (ft) = Left Pier (ft) 2.000 APA PORTAL FRAME PER TT-100H FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/11/2025 at 13:05 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\40 Wide Series\Plan1431\00-Engineering\PLAN 1431- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm