Calcs- Shelm Meadows- Plan 1623 CypressLGI Homes - WA 12951 Bel Red Rd Bellevue, Washington 98005 Shelm Meadows PLAN 1623 CYPRESS INDEX TO STRUCTURAL CALCULATIONS Design Criteria SHEET 1 Vertical Analysis SHEETS 2-33 Lateral Analysis SHEETS L1-L27 OWNERSHIP OF DOCUMENTS: CALCULATIONS, DRAWINGS AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE, AND SHALL REMAIN THE PROPERTY OF THE ENGINEER. THEY ARE NOT TO BE USED ON OTHER PROJECTS OR EXTENSIONS OF THIS PROJECT EXCEPT BY AGREEMENT IN WRITING WITH THE APPROPRIATE COMPENSATION TO FELTEN GROUP, INC. WA-FE25-001100 130730 18325 N. ALLIED WAY, SUITE #200 * PHOENIX, AZ 85054 * PHONE: 602.867.2500 * FAX: 602.867.2503 02/07/25 2018 SHINGLE OR MEMBRANE PSF PSF 12.00 7.00 27.00 (MAX) GOVERNING CODE AND LATERAL LOAD CRITERIA: 3 SEC GUST (MPH): BUILDING CODE: MUNICIPALITY: Thurston County, WA 85/110 ROOF LOADS: ROOF FRAMING DEAD LOAD PSF 10.00NON-CONCURRENT ATTIC LL WITHOUT STORAGE (PSF) = LESS THAN 4:12 SLOPE ROOF LL (PSF) = 4:12 SLOPE AND GREATER TOTAL ROOF LL (PSF) = 16.00 20.00 15.00 ROOF FRAMING LIVE LOAD TOTAL ROOF DL (PSF) = DECK FRAMING LIVE LOAD TOTAL DECK LL (PSF) = 60.00 TOTAL FLOOR DL (PSF) = 10.00 WITH PARTITION WALLS (PSF) = +5.00 SEISMIC DESIGN CATEGORY: EXPOSURE AT MWFRS: EXPOSURE AT C & C: D2 C C TOTAL WALL DL (PSF) = INTERIOR WALL DEAD LOAD WITH TILE (PSF) = +5.00 EXTERIOR WALL DEAD LOAD WALL DEAD LOADS: FLOOR FRAMING LIVE LOAD TOTAL FLOOR LL (PSF) = 40.00 IBC/IRC TOTAL WALL DL (PSF) = TOTAL WALL DL W/ STONE VENEER (PSF) = SNOW LOAD TOTAL SNOW LOAD (PSF) = 20.00 FLOOR LOADS: FLOOR FRAMING DEAD LOAD PSF "Where quality engineering leads to lower costs." 2021 CLIENT: PROJECT: FELTENGROUP ARCHITECTURE I ENGINEERING I FORENSICS I ROOF FRAMING DATE: SHEET OF BY: CLIENT: PROJECT: I FELTENdROUP ARCHITECTURE I ENGINEERING I FORENSICS DATE: SHEET OF ®�I 11R - 11 0"M-W01111 11�1111 III _ 11 �. � !V! II 11�1 ICI ® II '�I''�'11■IMCA Ell 8 ROOF FRAMING IN BY: FELTENdROUP ARCHITECTURE I ENGINEERING I FORENSICS CLIENT: PROJECT: 1 1 II `L r I iF m i r �m 4 ��r � I FLOOR FRAMING PLAN 0 DATE: SHEET OF BY: 0 UPPER FLOOR/ LOWER ROOF FRAMING PLAN STAIR FRAMING PLAN CLIENT: FELTENdROUP ARCHITECTURE I ENGINEERING I FORENSICS DATE: SHEET OF PROJECT: BY: CLIENT: FELTENdROUP ARCHITECTURE I ENGINEERING I FORENSICS DATE: SHEET OF PROJECT: BY: SHEET 7 OF BY D 60 60 0.000 16.250 S 100 100 0.000 16.250 1300 1300 488 488 D 15 15 0.000 6.000 S 25 25 0.000 6.000 D 45 45 0.000 3.000 S 75 75 0.000 3.000 D 488 4.000 122 122 5.000 6.000 S 813 4.000 203 203 5.000 6.000 850 1375 319 515 PROJECT:PLAN 1623- VERTICAL jem G1 CLIENT:LGI HOMES 16.250 Cantilever Data Truss Type Total Length (ft) No 2x Roof 16.250No Gi r d e r S u p p o r t De s i g n D + S D + S D D Hanger Hanger Fo u n d a t i o n S u p p o r t D e s i g n To Hanger To Hanger To Hanger To Hanger 6.000 G2 No 2x Roof 6.000No Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING D D 5.5 Hanger 9.083 Hem-Fir Stud (2" to 4" wide) (0) 2x6 POSTS To Framing Below To Hanger To Framing Below To HangerFo u n d a t i o n S u p p o r t D e s i g n 16.25' 160 160 6' 1300 160 160 40 40 365365 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 8 OF BY D 15 15 0.000 26.500 S 25 25 0.000 26.500 D 45 45 0.000 9.250 S 75 75 0.000 9.250 D 515 10.250 15 15 11.250 26.500 S 859 10.250 25 25 11.250 26.500 2465 1690 924 634 D 15 15 0.000 8.000 S 25 25 0.000 8.000 D 488 2.000 45 45 0.000 1.000 S 813 2.000 75 75 0.000 1.000 D 634 4.000 199 199 5.000 8.000 S 1056 4.000 331 331 5.000 8.000 2391 2629 896 986 PROJECT:PLAN 1623- VERTICAL jem G3 CLIENT:LGI HOMES 26.500 Cantilever Data Truss Type Total Length (ft) No 2x Roof 26.500No Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING Hem-Fir Stud (2" to 4" wide) D D 5.5 Hanger Fo u n d a t i o n S u p p o r t D e s i g n Conventional To Hanger 9.083 Edge (1) 2x6 POSTS 14 2500 18 711 NO FTG REQ'D To Hanger 8.000 G4 No 2x Roof 8.000No Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING D D 5.5 Hanger 9.083 Hem-Fir Stud (2" to 4" wide) (1) 2x6 POSTS To Framing Below To Hanger To Framing Below To HangerFo u n d a t i o n S u p p o r t D e s i g n 26.5' 1375 160 160 40 40 80 80 8' 1300 1690 160160 40 40 570 570 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 9 OF BY D 38 38 0.000 8.000 S 63 63 0.000 8.000 400 400 150 150 D 15 15 0.000 30.000 S 25 25 0.000 30.000 D 986 26.500 15 15 0.000 25.500 S 1643 26.500 25 25 0.000 25.500 D 150 27.000 15 15 28.000 30.000 S 250 27.000 25 25 28.000 30.000 1536 3793 576 1423 PROJECT:PLAN 1623- VERTICAL jem G5 CLIENT:LGI HOMES 8.000 Cantilever Data Truss Type Total Length (ft) No 2x Roof 8.000No Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING Hem-Fir Stud (2" to 4" wide) D D 5.5 Hanger Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below To Hanger 9.083 (0) 2x6 POSTS To Framing Below To Hanger 30.000 G6 No 2x Roof 30.000No Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING D D 5.5 5.5 9.083 18.66 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) Edge Edge (0) 2x6 POSTS (3) 2x6 POSTS Conventional Conventional 2500 2500 711 755 NO FTG REQ'D NO FTG REQ'DFo u n d a t i o n S u p p o r t D e s i g n 18 18 14 14 8' 100 100 30' 2629400 80 80 40 40 80 80 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 10 OF BY Left Support Right Support Rleft (#)Rright (#) Vd Mmax fb F'b CD fv F'v CL Δactual Δmax CF/CV Cr Use: 213 213 100 0.000 4.250 183 226 5.5 5.5 442 1459 8.000 8.000 1.15 26 173 9.083 9.083 N/A N/A N/A N/A 0.995 0.053 0.170 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)N/A N/A N/A N/A 1.500 (1) 2x6 KS (1) 2x6 KS N/A N/A N/A N/A 1.00 Use:(1) 2x6 (1) 2x6 263 263 100 0.000 5.250 217 345 5.5 5.5 273 1259 8.000 8.000 1.15 20 173 9.083 9.083 N/A N/A N/A N/A 0.990 0.032 0.210 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)N/A N/A N/A N/A 1.300 (1) 2x6 KS (1) 2x6 KS N/A N/A N/A N/A 1.00 Use:(1) 2x6 (1) 2x6 1073 1073 660 0.000 3.250 770 871 5.5 5.5 691 1263 8.000 8.000 1.15 70 173 9.083 9.083 N/A N/A N/A N/A 0.994 0.031 0.130 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)N/A N/A N/A N/A 1.300 (1) 2x6 KS (1) 2x6 KS N/A N/A N/A N/A 1.00 Use:(1) 2x6 (1) 2x6 743 743 660 0.000 2.250 550 418 5.5 5.5 818 1462 8.000 8.000 1.15 79 173 9.083 9.083 N/A N/A N/A N/A 0.997 0.027 0.090 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)N/A N/A N/A N/A 1.500 (1) 2x6 KS (1) 2x6 KS N/A N/A N/A N/A 1.00 Use:(1) 2x6 (1) 2x6 113 113 100 0.000 2.250 83 63 5.5 5.5 124 1462 17.660 17.660 1.15 12 173 18.666 18.666 N/A N/A N/A N/A 0.997 0.004 0.090 Hem-Fir #2 (2" to 4" wide)Hem-Fir #2 (2" to 4" wide)N/A N/A N/A N/A 1.500 (1) 2x6 KS (1) 2x6 KS N/A N/A N/A N/A 1.00 Use:(1) 2x6 (1) 2x6 377 127 400 0.250 110 1.250 2.200 77 94 5.5 5.5 75 1266 17.000 17.000 1.15 7 173 18.500 18.500 N/A N/A N/A N/A 0.996 0.001 0.088 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide)N/A N/A N/A N/A 1.300 (2) 2x6 KS (2) 2x6 KS N/A N/A N/A N/A 1.00 Use:(1) 2x6 (1) 2x6 PROJECT:PLAN 1623- VERTICAL jem Beam / Header Design and Loading CLIENT:LGI HOMES Point Loads Uniform Loads Results Left Support Right Support Id Span (ft) P (#)x (ft)w (plf) Unbraced Length(ft) King Stud Height (ft)Slab Thickness (in)Bearing Pressure (psf) Trimmer and King Stud Material Standard Width (in)Standard Depth (in) start (ft)stop (ft) Bearing Length (in) / Hanger Support Condition Trimmer or Post Height (ft)Location Of Support H1 4.250 To Framing Below To Framing Below N/A N/A Material Type Member Size King Studs Uniform Load (plf)Point Load (#) Dual Spec Material Type Dual Spec Member Size Trimmers/ Hangers Size (in) H2 5.250 To Framing Below To Framing Below N/A N/A 4.250 Hem-Fir #2 Common Sizes 2-2x4 Hem-Fir #2 (2" to 4" wide)2x4 To Framing Below To Framing Below H3 3.250 To Framing Below To Framing Below N/A N/A 5.250 Hem-Fir #2 Common Sizes 2-2x6 Hem-Fir #2 (2" to 4" wide)2x6 To Framing Below To Framing Below H4 2.250 To Framing Below To Framing Below N/A N/A 3.250 Hem-Fir #2 Common Sizes 2-2x6 Hem-Fir #2 (2" to 4" wide)2x8 To Framing Below To Framing Below H5 2.250 To Framing Below To Framing Below N/A N/A 2.250 Hem-Fir #2 Common Sizes 2-2x4 Hem-Fir #2 (2" to 4" wide)2x6 To Framing Below To Framing Below H6 2.200 To Framing Below To Framing Below N/A N/A 2.250 Hem-Fir #2 Common Sizes 2-2x4 Hem-Fir #2 (2" to 4" wide)2x4 To Framing Below To Framing Below 2.200 Hem-Fir #2 Common Sizes 2-2x6 Select Material To Framing Below To Framing Below Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 11 OF BY CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL jem Multi-Span Girder Key Girder Loading Point Loads Uniform Loads Id Load Type P (lb)x (ft)wstart (plf)wstop (plf)Total Length (ft) Span 3 (ft) Left Right xstart (ft)xstop (ft) Span 1 (ft) Span 2 (ft)Cantilever Data Truss Type Span 4 (ft)Girder Ply Requirements Based on Crushing Post Height Post Height Support Material Type Support Material Type Support Material Type Support Material Type Support Material Type Load Combo Max/Min Reaction R4 (lb) Load Combo Max/Min Reaction R5 (lb) Load Combo Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Max/Min Reaction R1 (lb) Load Combo Max/Min Reaction R2 (lb) Load Combo Max/Min Reaction R3 (lb) Post Height Post Height Posts / Hanger Posts / Hanger Posts / Hanger Posts / Hanger Fo u n d a t i o n S u p p o r t D e s i g n Support Condition Support Condition Support Condition Support Condition Support Condition Gi r d e r S u p p o r t De s i g n Post Height Posts / Hanger Support Location Support Location Support Location Support Location Support Location Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in) Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf) Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in) Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in)Support Depth (in) Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb) Girder Diagram Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf) Support Size Support Size Support Size Support Size Support Size Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 12 OF BY D 45 45 0.000 11.500 S 75 75 0.000 11.500 690 690 259 259 PROJECT:PLAN 1623- VERTICAL jem G7 CLIENT:LGI HOMES 11.500 Cantilever Data Truss Type Total Length (ft) No 2x Roof 11.500No Gi r d e r S u p p o r t De s i g n D + S D + S USE PREFABRICATED GIRDER TRUSS WITH MINIMUM (1) PLY AT BEARING Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) D D 5.5 5.5 Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional 9.083 9.083 Edge Edge (0) 2x6 POSTS (0) 2x6 POSTS 14 14 2500 2500 18 18 360 360 NO FTG REQ'D NO FTG REQ'D No 2x RoofNo Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n Fo u n d a t i o n S u p p o r t D e s i g n 11.5' 120 120 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 13 OF BY D 30 30 0.000 15.000 L 80 80 0.000 15.000 D 43 43 15.000 18.500 L 113 113 15.000 18.500 1033 1163 282 317 D 139 139 0.000 3.750 L 370 370 0.000 3.750 D 15 15 0.000 8.000 S 25 25 0.000 8.000 D 110 110 0.000 8.000 S 50 50 0.000 8.000 D 113 113 3.750 8.000 L 300 300 3.750 8.000 2426 2235 1025 973 PROJECT:PLAN 1623- VERTICAL jem FG1 CLIENT:LGI HOMES 18.500 Cantilever Data Truss Type Total Length (ft) No 4x Floor 18.500No Gi r d e r S u p p o r t De s i g n D + L D + L USE PREFABRICATED 4x2 FLOOR GIRDER TRUSS D D 3.125 3.125 Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below To Framing Below 8.000 REF No 4x Floor 8.000No Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n D + L D + L USE PREFABRICATED 4x2 FLOOR GIRDER TRUSS D D 3.125 5.5 9.083 Hem-Fir Stud (2" to 4" wide) Edge To Framing Below (1) 2x6 POSTS To Framing Below Conventional 2500 200 To Framing Below NO FTG REQ'DFo u n d a t i o n S u p p o r t D e s i g n 18 800 14 18.5' 110 110 156 156 8' 709 709 612 612 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 14 OF BY Lub,top (ft)TL (L/x) Lub,bot (ft)LL (L/x) Cr Ci CM CT Dmax (in) CLtop Dcant (in) CLbot Left dn (in)Dmax (in) CF/Cvtop Right dn (in)Dcant (in) CF/Cvbot CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL jem Multi-Span Header / Beam Key Allowable StressPoint Loads Uniform Loads Deflection Data Results Load Combo Actual Stress Id Load Type P (lb)x (ft)wstart (plf)wstop (plf)xstart (ft) Header/Beam Loading Unbraced Lengths Span 1 (ft) NDS Factors Cantilever Data M+max (lb-ft)M+fb+ (psi)F'b+ (psi) Left DTL Limit xstop (ft) DL Creep Factor Vmax (lb)V fv (psi)F'v (psi) M-max (lb-ft)M-fb- (psi)F'b- (psi) Total Length, L (ft)DLL Span 4 (ft) Material Type Member Size Dual Spec Material Type Dual Spec Member Size Span 2 (ft) Right DLL Limit Deflections DTL Span 3 (ft) Scarf Cut Data DTL DLL He a d e r / B e a m S u p p o r t De s i g n Max/Min Reaction R1 (lb) Load Combo Max/Min Reaction R2 (lb) Load Combo Max/Min Reaction R3 (lb) Trimmer or Post Height Trimmer or Post Height Trimmer or Post Height Support Material Type Support Material Type Support Material Type Trimmer or Post Height Trimmer or Post Height King Stud Height King Stud Height King Stud Height King Stud Height King Stud Height Load Combo Max/Min Reaction R4 (lb) Load Combo Max/Min Reaction R5 (lb) Load Combo Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Bearing Length (in)/Hanger Support Material Type Support Material Type Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Trimmers / Hanger Support Condition Support Location Support Location Support Location Support Location Support Location King Studs King Studs King Studs King Studs King Studs Support Condition Support Condition Support Condition Support Condition Support Depth (in)Support Depth (in)Support Depth (in) Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in)Slab Thickness (in) Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf)Bearing Pressure (psf) Support Size Support Size Support Size Support Size Support Size Beam/Header Diagram Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb)Point Load at Support (lb) Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf)Uniform Load at Support (plf) Fo u n d a t i o n S u p p o r t D e s i g n Support Width (in)Support Width (in)Support Width (in)Support Width (in)Support Width (in) Support Depth (in)Support Depth (in) Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 15 OF BY D 119 119 0.000 3.250 240 L 317 317 0.000 3.250 360 D 135 135 0.000 3.250 Factors S 50 50 0.000 3.250 No 1.000 No MC<=19% T<=100 -0.027 0.996 0.000 1.000 No -0.015 1.000 No 0.000 1.000 933 933 418 418 D 119 119 0.000 6.250 240 L 317 317 0.000 6.250 360 D 135 135 0.000 6.250 Factors S 50 50 0.000 6.250 No 1.000 No MC<=19% T<=100 -0.077 0.985 0.000 1.000 No -0.042 1.000 No 0.000 1.000 1801 1801 810 810 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES B1 1.000 670 D + L 61 150 1100 No 0 D 0 994 Cantilever Data 758 D + L 601 No Deflections 3.250 Scarf Cut Data L 3.250 D + L 5.5 5.5 Hem-Fir #2 Common Sizes 2-2x6 Hem-Fir #2 (2" to 4" wide)2x8 8 8 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D 9.083 9.083 (1) 2x6 KS (1) 2x6 KS Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (1) 2x6 TRIMMERS (1) 2x6 TRIMMERS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 845 845 NOT REQ'D NOT REQ'D B2 6.250 Cantilever Data 2813 D + L 789 1.000 1368 D + L 74 150 921 No Deflections No 0 D 0 842 Scarf Cut Data L 6.250 D + L 5.5 5.5 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Hem-Fir #2 Common Sizes 2-2x10 Doug-Fir #2 (2" to 4" wide)4x8 8 8 9.083 9.083 (1) 2x6 KS (1) 2x6 KS Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (1) 2x6 TRIMMERS (1) 2x6 TRIMMERS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 845 845 NOT REQ'D NOT REQ'D 3.25' 620 620 6.25' 620 620 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 16 OF BY D 119 119 0.000 5.250 240 L 317 317 0.000 5.250 360 D 135 135 0.000 5.250 Factors S 50 50 0.000 5.250 No 1.000 No MC<=19% T<=100 -0.079 0.991 0.000 1.000 No -0.044 1.000 No 0.000 1.000 1510 1510 677 677 D 314 314 0.000 2.917 240 L 800 800 0.000 2.917 360 Factors No 1.000 No MC<=19% T<=100 -0.034 0.996 0.000 1.000 No -0.024 1.000 No 0.000 1.000 1629 1629 462 462 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES B3 1.000 1162 D + L 80 150 1011 No 0 D 0 918 Cantilever Data 1981 D + L 905 No Deflections 5.250 Scarf Cut Data L 5.250 D + L 5.5 5.5 Hem-Fir #2 Common Sizes 2-2x8 Select Material 8 8 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D 9.083 9.083 (1) 2x6 KS (1) 2x6 KS Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (1) 2x6 TRIMMERS (1) 2x6 TRIMMERS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 845 845 NOT REQ'D NOT REQ'D B4 2.917 Cantilever Data 1188 D + L 943 1.000 1117 D + L 102 150 1101 No Deflections No 0 D 0 994 Scarf Cut Data L 2.917 D + L 5.5 5.5 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Hem-Fir #2 Common Sizes 2-2x6 Hem-Fir #2 (2" to 4" wide)2x10 8 8 9.083 9.083 (1) 2x6 KS (1) 2x6 KS Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (1) 2x6 TRIMMERS (1) 2x6 TRIMMERS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 1225 1225 NOT REQ'D NOT REQ'D 5.25' 620 620 2.9167' 1114 1114 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 17 OF BY D 119 119 0.000 4.250 240 L 317 317 0.000 4.250 360 D 317 0.250 139 139 1.250 4.250 Factors L 846 0.250 370 370 1.250 4.250 No 1.000 No MC<=19% T<=100 -0.055 0.993 0.000 1.000 No -0.040 1.000 No 0.000 1.000 2569 1992 707 550 D 128 128 0.000 18.750 2.000 240 L 340 340 0.000 18.750 360 D 59 59 0.000 8.583 Factors L 53 53 0.000 8.583 No S 21 21 0.000 8.583 1.000 D 23 23 8.583 18.750 No S 38 38 8.583 18.750 MC<=19% D 110 110 8.583 18.750 T<=100 -0.652 S 50 50 8.583 18.750 1.000 0.000 1.000 No -0.389 0.989 No 0.000 1.000 5649 5742 2111 2450 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES B5 1.000 1639 D + L 113 150 1012 No 0 D 0 918 Cantilever Data 2090 D + L 954 No Deflections 4.250 Scarf Cut Data L 4.250 D + L 3.5 5.5 Hem-Fir #2 Common Sizes 2-2x8 Hem-Fir #2 (2" to 4" wide) 8 8 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (2) 2x4 POSTS (1) 2x6 POSTS Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below Conventional Edge 2500 14 18 800 To Framing Below NOT REQ'D B6 18.750 Cantilever Data 26721 D + L 1668 1.000 4972 D + L 97 265 2374 No Deflections No 0 D 0 1665 Scarf Cut Data L 18.750 D + L 5.5 5.5 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Glu-Lam (24F-1.8E)5 1/8 x 15 GLB Select Material 9 10 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (2) 2x6 POSTS (2) 2x6 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 2235 200 200 NOT REQ'D NOT REQ'D 4.25' 1163 435435 944 944 18.75' 601 601 688 688 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 18 OF BY D 126 126 0.000 7.167 240 L 27 27 0.000 7.167 360 S 54 54 0.000 7.167 Factors D 53 53 7.167 16.250 No S 38 38 7.167 16.250 1.000 No MC<=19% T<=100 -0.319 0.955 0.000 1.000 No -0.105 1.000 No 0.000 1.000 1316 941 904 607 D 1025 0.500 15 15 0.000 2.500 240 L 1401 0.500 40 40 0.000 2.500 360 D 226 226 0.000 2.500 Factors S 300 0.500 202 202 0.000 2.500 No D 26 26 0.000 2.500 1.000 S 44 44 0.000 2.500 No MC<=19% T<=100 -0.005 0.995 0.000 1.000 No -0.002 1.000 No 0.000 1.000 2449 1068 1160 545 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES B7 1.000 1136 D + 0.75(L + S)43 207 1087 No 0 D 0 891 Cantilever Data 4500 D + S 731 No Deflections 16.250 Scarf Cut Data S 16.250 D + S 5.5 5.5 Doug-Fir #2 (2" to 4" wide)4x12 Select Material 8 8 He a d e r / B e a m S u p p o r t De s i g n D + 0.75(L + S)D + S D D 10.04 10.04 (2) 2x6 KS (2) 2x6 KS Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (1) 2x6 TRIMMERS (1) 2x6 TRIMMERS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 500 500 NOT REQ'D NOT REQ'D B8 2.500 Cantilever Data 1126 D + L 316 1.000 1408 D + L 76 150 930 No Deflections No 0 D 0 842 Scarf Cut Data 0.75(L + S)2.500 D + 0.75(L + S) 3.5 3.5 He a d e r / B e a m S u p p o r t De s i g n D + 0.75(L + S)D + 0.75(L + S) D D Hem-Fir #2 Common Sizes 2-2x10 Doug-Fir #2 (2" to 4" wide)4x8 8 8 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (2) 2x4 POSTS (1) 2x4 POSTS Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below To Framing Below To Framing Below To Framing Below 16.25' 207 207 90 90 2.5' 2726 553 553 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 19 OF BY D 111 111 0.000 4.250 240 S 169 169 0.000 4.250 360 Factors No 1.000 No MC<=19% T<=100 -0.017 0.991 0.000 1.000 No -0.010 1.000 No 0.000 1.000 604 604 244 244 D 77 77 0.000 4.000 240 L 205 205 0.000 4.000 360 Factors No 1.000 No MC<=19% T<=100 -0.030 0.995 0.000 1.000 No -0.022 1.000 No 0.000 1.000 570 570 160 160 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES B9 1.000 432 D + S 30 173 1163 No 0 D 0 918 Cantilever Data 641 D + S 293 No Deflections 4.250 Scarf Cut Data S 4.250 D + S 3.5 5.5 Hem-Fir #2 Common Sizes 2-2x8 Select Material 8 8 He a d e r / B e a m S u p p o r t De s i g n D + S D + S D D Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (1) 2x4 POSTS (1) 2x6 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 200 500 NOT REQ'D NOT REQ'D B10 4.000 Cantilever Data 570 D + L 452 1.000 439 D + L 40 150 1100 No Deflections No 0 D 0 994 Scarf Cut Data L 4.000 D + L Select Support Select Support He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Hem-Fir #2 Common Sizes 2-2x6 Select Material Fo u n d a t i o n S u p p o r t D e s i g n 4' 282 282 4.25' 280 280 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 20 OF BY D 90 90 0.000 8.000 240 S 150 150 0.000 8.000 360 Factors No 1.000 No MC<=19% T<=100 -0.182 0.983 0.000 1.000 No -0.112 1.000 No 0.000 1.000 976 976 376 376 D 128 128 0.000 18.750 2.000 240 L 340 340 0.000 18.750 360 D 59 59 0.000 8.500 Factors L 53 53 0.000 8.500 No S 21 21 0.000 8.500 1.000 D 23 23 8.500 18.750 No S 38 38 8.500 18.750 MC<=19% D 140 140 8.500 18.750 T<=100 -0.670 S 100 100 8.500 18.750 1.000 0.000 1.000 No -0.389 0.989 No 0.000 1.000 5734 5966 2198 2676 200 365 NOT REQ'D NOT REQ'D 18 18 2235 Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 Hem-Fir Stud (2" to 4" wide)Hem-Fir Stud (2" to 4" wide) (2) 2x6 POSTS (2) 2x6 POSTS 9 5.5 5.5 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Glu-Lam (24F-1.8E)5 1/8 x 15 GLB Select Material 9 Scarf Cut Data L 18.750 D + L 265 2374 No Deflections No 0 D 0 1665 B12 18.750 Cantilever Data 27510 D + L 1718 1.000 5160 D + L 101 200 NOT REQ'D 9" DIA. x 8" DEEP NO REBAR 18 Fo u n d a t i o n S u p p o r t D e s i g n Conventional Isolated Footing Edge 2500 2500 14 Hem-Fir Stud (2" to 4" wide)Doug-Fir #2 (2" to 4" wide) (1) 2x6 POSTS 4x4 POSTS Hem-Fir #2 Common Sizes 2-2x8 Select Material 9 9 He a d e r / B e a m S u p p o r t De s i g n D + S D + S D D D + S 5.5 3.5 1952 D + S 891 No Deflections 8.000 Scarf Cut Data S 8.000 B11 1.000 829 D + S 57 173 1153 No 0 D 0 918 Cantilever Data PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES 8' 240 240 18.75' 601 601 768 768 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 21 OF BY D 45 45 0.000 4.000 240 S 75 75 0.000 4.000 360 Factors No 1.000 No MC<=19% T<=100 -0.006 0.992 0.000 1.000 No -0.003 1.000 No 0.000 1.000 248 248 98 98 D 98 0.000 45 45 0.000 11.500 240 S 150 0.000 75 75 0.000 11.500 360 D 98 11.500 Factors S 150 11.500 No 1.000 No MC<=19% T<=100 -0.394 0.973 0.000 1.000 No -0.238 1.000 No 0.000 1.000 961 961 380 380 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES B13 1.000 173 D + S 12 173 1163 No 0 D 0 918 Cantilever Data 248 D + S 113 No Deflections 4.000 Scarf Cut Data S 4.000 D + S Hanger 5.5 Hem-Fir #2 Common Sizes 2-2x8 Select Material 9 He a d e r / B e a m S u p p o r t De s i g n D + S D + S D D Hem-Fir Stud (2" to 4" wide) (1) 2x6 POSTS Fo u n d a t i o n S u p p o r t D e s i g n To Hanger Conventional Edge 2500 14 18 360 To Hanger NOT REQ'D B14 11.500 Cantilever Data 2051 D + S 936 1.000 641 D + S 44 173 1141 No Deflections No 0 D 0 918 Scarf Cut Data S 11.500 D + S 3.5 3.5 He a d e r / B e a m S u p p o r t De s i g n D + S D + S D D Hem-Fir #2 Common Sizes 2-2x8 Select Material 9 9 Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide) 4x4 POSTS 4x4 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Conventional Conventional Edge Edge 2500 2500 14 14 18 18 120 120 NOT REQ'D NOT REQ'D 4' 120 120 11.5' 248248 120 120 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 22 OF BY D 139 139 0.000 3.750 1.000 240 L 370 370 0.000 3.750 360 D 15 15 0.000 8.000 Factors S 25 25 0.000 8.000 No D 110 110 0.000 8.000 1.000 S 50 50 0.000 8.000 No D 113 113 3.750 8.000 MC<=19% L 300 300 3.750 8.000 T<=100 -0.034 0.996 0.000 1.000 No -0.019 1.000 No 0.000 1.000 2467 2274 1066 1012 240 360 Factors No No MC<=19% T<=100 No No Fo u n d a t i o n S u p p o r t D e s i g n He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data No Deflections No Cantilever Data 1.000 200 To Framing Below NOT REQ'D 18 800 2500 14 Fo u n d a t i o n S u p p o r t D e s i g n To Framing Below Conventional Edge To Framing Below Hem-Fir Stud (2" to 4" wide) (1) 2x6 POSTS 9 3.125 5.5 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Glu-Lam (24F-1.8E)3 1/8 x 15 GLB Select Material Scarf Cut Data L 8.000 D + L No Deflections 2390 No 0 D 0 1665 8.000 Cantilever Data 4725 D + L 484 B15 1.000 1671 D + L 53 265 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES 8' 709 709 612 612 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 23 OF BY D 24 24 0.000 30.000 1.000 240 L 64 64 0.000 30.000 10.000 360 Factors Yes 1.150 No MC<=19% T<=100 -0.084 0.991 0.000 0.902 No -0.059 1.000 No 0.000 1.000 362 996 996 362 106 292 292 106 D 12 12 0.000 11.167 1.000 240 L 32 32 0.000 11.167 360 D 183 183 0.000 3.500 Factors S 50 50 0.000 3.500 No 1.000 No MC<=19% T<=100 -0.012 0.989 0.000 0.947 No -0.011 1.000 No 0.000 1.000 378 734 134 298 472 31 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES J1 1.000 471 D + L 51 150 1065 No -906 D + L 508 970 Cantilever Data 725 D + L 407 10.000 No Deflections 10.000 10.000 Scarf Cut Data L 30.000 D + L D Hem-Fir #2 (2" to 4" wide)2x10 Select Material He a d e r / B e a m S u p p o r t De s i g n D + L D + L D + L D + L D D D Fo u n d a t i o n S u p p o r t D e s i g n J2 3.500 Cantilever Data 289 D + S 162 1.000 317 D + L 34 150 1064 7.667 No Deflections No -345 D + L 194 886 Scarf Cut Data L 11.167 D + L Select Support Select Support Select Support He a d e r / B e a m S u p p o r t De s i g n D + S D + 0.75(L + S)D + L D D D + S Hem-Fir #2 (2" to 4" wide)2x10 Select Material Fo u n d a t i o n S u p p o r t D e s i g n 10'10'10' 88 88 3.5'7.667' 277 277 44 44 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 24 OF BY D 20 20 0.000 11.500 1.000 240 L 53 53 0.000 11.500 360 Factors Yes 1.150 No MC<=19% T<=100 -0.231 0.991 0.000 1.000 No -0.162 1.000 No 0.000 1.000 435 435 130 130 D 38 38 0.000 11.500 1.000 240 L 100 100 0.000 11.500 360 D 160 3.667 176 176 3.667 7.333 Factors L 410 3.667 300 300 3.667 7.333 Yes 1.150 No MC<=19% T<=100 -0.028 0.991 0.000 0.969 No -0.019 1.000 No 0.000 1.000 463 3152 317 136 1041 95 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES J3 1.000 376 D + L 41 150 1065 No 0 D 0 968 Cantilever Data 1250 D + L 701 No Deflections 11.500 Scarf Cut Data L 11.500 D + L Hem-Fir #2 (2" to 4" wide)2x10 Select Material He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Fo u n d a t i o n S u p p o r t D e s i g n J4 5.500 Cantilever Data 761 D + L 427 1.000 1284 D + L 139 150 1065 6.000 No Deflections No -1427 D + L 801 1042 Scarf Cut Data L 11.500 D + L Select Support 3.5 Select Support He a d e r / B e a m S u p p o r t De s i g n D + L D + L D + L D D D Hem-Fir #2 (2" to 4" wide)2x10 Select Material 4 Doug-Fir #2 (2" to 4" wide) 4x4 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Isolated Footing 2500 16" DIA. x 8" DEEP NO REBAR 11.5' 73 73 5.5'6' 570 138 138 613 613 138 138 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 25 OF BY D 38 38 0.000 11.500 1.000 240 L 100 100 0.000 11.500 6.000 360 D 707 7.167 182 182 0.000 7.167 Factors L 1862 7.167 317 317 0.000 7.167 No 1.150 No MC<=19% T<=100 -0.024 0.999 0.000 0.997 No -0.018 1.000 No 0.000 1.000 1197 5885 739 445 1884 209 240 360 Factors No No MC<=19% T<=100 No No PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES J5 1.000 3027 D + L 109 150 1074 No -3166 D + L 592 1073 Cantilever Data 1833 D + L 343 6.000 No Deflections 5.500 Scarf Cut Data L 11.500 D + L 3.5 Hem-Fir #2 (2" to 4" wide)3-2x10 Select Material 8 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D + L D D D Doug-Fir #2 (2" to 4" wide) 4x6 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Isolated Footing 2500 21" DIA. x 9" DEEP NO REBAR Cantilever Data 1.000 No Deflections No Scarf Cut Data He a d e r / B e a m S u p p o r t De s i g n Fo u n d a t i o n S u p p o r t D e s i g n 5.5'6' 2569 636 636 138 138 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 26 OF BY D 13 13 0.000 7.750 1.000 240 L 80 80 0.000 7.750 360 S 33 33 0.000 7.750 Factors Yes 1.150 Yes MC>19% T<=100 -0.131 0.993 0.000 1.000 No -0.111 1.000 No 0.000 1.000 387 387 58 58 D 7 7 0.000 7.750 1.000 240 L 40 40 0.000 7.750 360 S 17 17 0.000 7.750 Factors Yes D 90 90 2.125 5.625 1.150 L 240 240 2.125 5.625 Yes MC>19% T<=100 -0.118 0.999 0.000 1.000 No -0.086 1.000 No 0.000 1.000 783 783 208 208 To Hanger To HangerFo u n d a t i o n S u p p o r t D e s i g n To Hanger To Hanger Hanger Hanger He a d e r / B e a m S u p p o r t De s i g n D + L D + L D D Hem-Fir #2 (2" to 4" wide)3-2x8 Select Material Scarf Cut Data L 7.750 D + L 146 797 No Deflections No 0 D 0 718 J8 7.750 Cantilever Data 2131 D + L 649 1.000 751 D + L 35 To Hanger To Framing BelowFo u n d a t i o n S u p p o r t D e s i g n To Hanger To Framing Below To Framing Below Hem-Fir #2 (2" to 4" wide)2x8 Select Material He a d e r / B e a m S u p p o r t De s i g n D + 0.75(L + S)D + 0.75(L + S) D D D + 0.75(L + S) Hanger 3.125 713 D + L 652 No Deflections 7.750 Scarf Cut Data 0.75(L + S)7.750 J7 1.000 311 D + L 43 146 792 No 0 D 0 718 Cantilever Data PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES 7.75' 63 63 393 393 63 63 7.75' 126 126 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 27 OF BY D 188 188 0.000 14.000 240 L 500 500 0.000 14.000 360 Factors No 1.000 No MC<=19% T<=100 -0.011 0.997 -0.012 0.997 No -0.008 1.000 No -0.009 1.000 3103 3502 3103 865 977 865 D 108 108 0.000 6.833 2.000 240 L 288 288 0.000 6.833 360 D 1160 2.000 267 267 4.500 6.833 Factors L 1171 2.000 40 40 4.500 6.833 No S 548 2.000 246 246 4.500 6.833 1.000 D 545 4.500 No L 330 4.500 MC<=19% S 368 4.500 T<=100 -0.054 D 160 6.833 0.998 0.051 L 410 6.833 0.997 No -0.028 1.000 No 0.025 1.000 4865 2532 2121 1142 PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES C1 1.000 1387 D + L 82 180 1166 Yes 120 -1473 D + L 577 1166 Cantilever Data 737 D + L 288 5.000 Yes 180 Deflections 2.000 5.000 Scarf Cut Data D + L L 14.000L D + L D 3.5 3.5 3.5 2.000 Doug-Fir #2 (2" to 4" wide)4x8 Select Material 4 4 4 He a d e r / B e a m S u p p o r t De s i g n D + L D + L D + L D D Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide) 4x4 POSTS 4x4 POSTS 4x4 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Isolated Footing Isolated Footing Isolated Footing 2500 2500 2500 16" DIA. x 8" DEEP NO REBAR 17" DIA. x 8" DEEP NO REBAR 16" DIA. x 8" DEEP NO REBAR C2 2.000 Cantilever Data 2271 D + L 889 1.000 1593 D + 0.75(L + S)94 207 1168 4.833 No 180 Deflections Yes 120 -803 D + L 314 1167 Scarf Cut Data D + 0.75(L + S) 0.75(L + S)6.8330.75(L + S) D + 0.75(L + S) 3.5 3.5 He a d e r / B e a m S u p p o r t De s i g n D + L D + 0.75(L + S) D D Doug-Fir #2 (2" to 4" wide)4x8 Select Material 4 4 Doug-Fir #2 (2" to 4" wide)Doug-Fir #2 (2" to 4" wide) 4x4 POSTS 4x4 POSTS Fo u n d a t i o n S u p p o r t D e s i g n Isolated Footing Isolated Footing 2500 2500 19" DIA. x 8" DEEP NO REBAR 14" DIA. x 8" DEEP NO REBAR 2'5'5'2' 688 688 2'4.833' 2879 1243 570 395 395 948 948 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 28 OF BY D 129 0.000 39 39 0.000 10.000 1.330 240 L 103 0.000 236 236 0.000 10.000 360 S 98 98 0.000 10.000 Factors No D 376 0.000 1.000 S 600 0.000 Yes MC>19% T<=100 -0.101 0.998 0.000 1.000 No -0.085 1.000 No 0.000 1.000 2521 1489 742 237 240 360 Factors No No MC<=19% T<=100 No No Fo u n d a t i o n S u p p o r t D e s i g n He a d e r / B e a m S u p p o r t De s i g n Scarf Cut Data No Deflections No Cantilever Data 1.000 14" SQ. x 8" DEEP w/ (2) #4 EA. WAY 11" SQ. x 8" DEEP w/ (2) #4 EA. WAYFo u n d a t i o n S u p p o r t D e s i g n Isolated Footing Isolated Footing 2500 2500 Doug-Fir #2 (5"x5" & larger)Doug-Fir #2 (5"x5" & larger) 4x6 POSTS 4x6 POSTS Doug-Fir #2 (2" to 4" wide)4x12 Select Material 20 20 He a d e r / B e a m S u p p o r t De s i g n D + 0.75(L + S)D + 0.75(L + S) D D D + 0.75(L + S) 5.5 5.5 3542 D + L 576 No Deflections 10.000 Scarf Cut Data 0.75(L + S)10.000 C3 1.000 1157 D + L 44 175 672 No 0 D 0 606 Cantilever Data PROJECT:PLAN 1623- VERTICAL jem CLIENT:LGI HOMES 10' 1208 374 374 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 29 OF BY D 110 1.000 15 15 0.000 1.000 S 50 1.000 25 25 0.000 1.000 D 15 15 1.000 3.000 L 40 40 1.000 3.000 156 115 96 59 PROJECT:PLAN 1623- VERTICAL jem REF1 CLIENT:LGI HOMES 3.000 Cantilever Data Truss Type Total Length (ft) No 2x Roof 3.000No Gi r d e r S u p p o r t De s i g n D + 0.75(L + S)D + 0.75(L + S) D D Fo u n d a t i o n S u p p o r t D e s i g n No 2x RoofNo Cantilever Data Truss Type Total Length (ft) Gi r d e r S u p p o r t De s i g n Fo u n d a t i o n S u p p o r t D e s i g n 3' 160 4040 55 55 Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 30 OF BY Total Conn A35 Total ASCE LOAD COMBINATIONS CD Load (plf)Cap (plf)Cap (plf)Cap (plf) D 26 D 0.90 26 77 0 77 L D + L 1.00 26 86 0 86 Lr D + Lr 1.25 26 108 0 108 S 44 D + S 1.15 70 99 0 99 R D + R 1.25 26 108 0 108 0.6W D + 0.75L + 0.75Lr 1.25 26 108 0 108 E D + 0.75L + 0.75S 1.15 59 99 0 99 D + 0.75L + 0.75R 1.25 26 108 0 108 2x6 D + 0.6W 1.60 26 138 0 138 SPF/HF D + 0.7E 1.60 26 138 0 138 2 D + 0.75(0.6W) + 0.75L + 0.75Lr 1.60 26 138 0 138 .131 x 3"D + 0.75(0.6W) + 0.75L + 0.75S 1.60 59 138 0 138 Normal D + 0.75(0.6W) + 0.75L + 0.75R 1.60 26 138 0 138 1 D + 0.75(0.7E) + 0.75L + 0.75Lr 1.60 26 138 0 138 24 in.D + 0.75(0.7E) + 0.75L + 0.75S 1.60 59 138 0 138 D + 0.75(0.7E) + 0.75L + 0.75R 1.60 26 138 0 138 in. Total Conn A35 Total ASCE LOAD COMBINATIONS CD Load (plf)Cap (plf)Cap (plf)Cap (plf) D 39 D 0.90 39 248 0 248 L 236 D + L 1.00 276 276 0 276 Lr D + Lr 1.25 39 345 0 345 S 98 D + S 1.15 138 317 0 317 R D + R 1.25 39 345 0 345 0.6W D + 0.75L + 0.75Lr 1.25 217 345 0 345 E D + 0.75L + 0.75S 1.15 290 317 0 317 D + 0.75L + 0.75R 1.25 217 345 0 345 2x8 D + 0.6W 1.60 39 441 0 441 SPF/HF D + 0.7E 1.60 39 441 0 441 2 D + 0.75(0.6W) + 0.75L + 0.75Lr 1.60 217 441 0 441 1/4" x 4 1/2" SDS D + 0.75(0.6W) + 0.75L + 0.75S 1.60 290 441 0 441 Normal D + 0.75(0.6W) + 0.75L + 0.75R 1.60 217 441 0 441 1 D + 0.75(0.7E) + 0.75L + 0.75Lr 1.60 217 441 0 441 16 in.D + 0.75(0.7E) + 0.75L + 0.75S 1.60 290 441 0 441 D + 0.75(0.7E) + 0.75L + 0.75R 1.60 217 441 0 441 in. jem L1 Load Type w (plf) Conn Placement: Ledger Size: Ledger Material: No. of Connectors: Type of Connector: CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL Conn Placement: No. of cols/Conn Spacing of Connector: No. of A35: Spacing of A35: L2 Load Type w (plf) Ledger Size: Ledger Material: No. of Connectors: Type of Connector: No. of cols/Conn Spacing of Connector: No. of A35: Spacing of A35: Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 31 OF BY S1 2 3.00 180 NO 1.50 0.7 NO ROOF TYPE:15.00 8.08 30.00 10.00 1.00 25.00 16.00 6.89 FLOOR TYPE:10.04 15.83 40.00 10.00 TARGET WALL 7.92 17.51 10.04 SPECIES TITLE 11.08 10.00 SCANT CFB b (IN) 5.00 FB (PSI)CFC d (IN) 9.67 FC (PSI)CR A (IN2) 5.50 0.00 EMIN (PSI)c Sx (IN3) Ex (PSI) CD 0.90 147.53 " o.c. 1.00 84.25 " o.c. 1.25 172.55 " o.c. 1.15 80.25 " o.c. 1.25 172.55 " o.c. 1.25 105.21 " o.c. 1.15 68.10 " o.c. 1.25 105.21 " o.c. 1.60 58.80 " o.c. 1.60 83.04 " o.c. 1.60 54.24 " o.c. 1.60 42.48 " o.c.GOVERNS 1.60 54.24 " o.c. 1.60 68.40 " o.c. 1.60 51.12 " o.c. 1.60 68.40 " o.c. 1.60 48.24 " o.c. 1.00 " o.c. 24 " o.c. C&CWIND DEFLECTION, L/GYP COMP. SOLE PLATE THICKNESS (IN)PRE-FAB TRUSSES C&CWIND FACTOR = GYP + WOOD COMP. CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL jem WALL NUMBER:STUD LOCATION:(1 = ROOF, 2 = FIRST FLOOR BELOW ROOF, 3 = SECOND FLOOR BELOW ROOF) ROOF SPAN (FT)ROOF LOADS (PSF)SUPPORTING WALL SIMPLE D HEIGHT (FT) TOP PLATE THICKNESS (IN)WALL HAS CONTINUOUS SHEATHING ON ONE SIDE NO ROOF ASSEMBLY TYPE SIMPLE 0.6*WUPLIFT MAIN SPAN LR WEIGHT (PSF) OVERHANG S TOTAL TRIB.R FLOOR SPAN (FT)FLOOR LOADS (PSF)SUPPORTING WALL SIMPLE D HEIGHT (FT) SIMPLE MAIN SPAN L WEIGHT (PSF) TOTAL TRIB. TARGET WALL STUD MATERIAL 0.6*C&C (PSF)HEIGHT (FT)Hem-Fir Stud (2" to 4" wide)2x6 HEM-FIR STUD GRADE STUDS 0.6*W (PSF)WEIGHT (PSF)NO 1.00 1.50 0.7*E (PSF)PARTIAL LOADING (WIND)675 1.00 5.50 1200000 20.797 ASCE7 LOAD COMBINATIONS AXIAL (NDS Section 3.7) Emin = 440000 Le/d = 21.09 <= 50 c = 0.80 Fce = 0.822Emin'/(Le/d)^2 = 0.822(440000psi)/21.09^2 = 813.36psi F*c = Fc(Cd)(Cfc) = 800(1.60)(1.00) = 1280.00psi Fce/F*c = 813.36psi/1280.00psi = 0.64 A1 = (1 + Fce/F*c)/2c = 1.64/1.60 = 1.02 A2 = (Fce/F*c)/c = 0.64/0.80 = 0.79 Cp = A1-[A1^2-A2]^0.5 = 1.02-[1.04-0.79]^0.5 = 0.52 F'c = F*c(Cp) = 1280.00psi(0.52) = 667.72psi P = 825.85plf*2.00ft = 1651.69# fc = P/A = 1651.69#/8.25in^2 = 200.20psi BENDING (NDS Section 3.3) Le = 10.04ft - (3.00in + 1.50in)(1ft/12in) = 9.67ft M = 194.06#-ft F'b = Fb(Cd)(Cr)(Cfb) = 675(1.60)(1.15)(1.00) = 1242.00psi fb = (12in/1ft)(194.06#-ft)/7.56in^3 = 307.94psi INTERACTION EQUATION (NDS Section 3.9.2) (200.20psi/667.72psi)^2 + (1/(1-(200.20psi/813.36psi)))(307.94psi/1242.00psi) = 0.42 = 0.419 < 1.000 O.K. THEREFORE, USE 2x6 HEM-FIR STUD GRADE STUDS AT 24in O.C. D D + L D + LR D + S 0.6C&C D + L (NON-CONCURRENT) DESIRED SPACING FOR CALCULATIONS: STOP (FT)800 1.15 8.250 WALL WIDTH (IN)START (FT)440000 0.80 7.563 D + 0.75(0.6W) + 0.75L + 0.75LR D + 0.75(0.6W) + 0.75L + 0.75S D + 0.75(0.6W) + 0.75L + 0.75R D + 0.75(0.7E) + 0.75L + 0.75LR D + 0.75(0.7E) + 0.75L + 0.75S D + 0.75(0.7E) + 0.75L + 0.75R D + R D + 0.75L + 0.75LR D + 0.75L + 0.75S D + 0.75L + 0.75R D + 0.6W D + 0.7E Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 32 OF BY S2 2 3.00 180 NO 1.50 0.7 NO ROOF TYPE: FLOOR TYPE:15.00 9.08 15.83 40.00 7.00 TARGET WALL 7.92 9.08 SPECIES TITLE 7.00 SCANT CFB b (IN) 5.00 FB (PSI)CFC d (IN) 8.71 FC (PSI)CR A (IN2) 3.50 0.00 EMIN (PSI)c Sx (IN3) Ex (PSI) CD 0.90 152.44 " o.c. 1.00 50.14 " o.c. 1.25 161.03 " o.c. 1.15 159.19 " o.c. 1.25 161.03 " o.c. 1.25 62.47 " o.c. 1.15 61.76 " o.c. 1.25 62.47 " o.c. 1.60 165.42 " o.c. 1.60 55.44 " o.c. 1.60 64.18 " o.c. 1.60 64.18 " o.c. 1.60 64.18 " o.c. 1.60 36.60 " o.c.GOVERNS 1.60 36.60 " o.c.GOVERNS 1.60 36.60 " o.c.GOVERNS 1.60 1200.00 " o.c. 1.00 " o.c. 16 " o.c. C&CWIND DEFLECTION, L/GYP COMP. SOLE PLATE THICKNESS (IN)PRE-FAB TRUSSES C&CWIND FACTOR = GYP + WOOD COMP. CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL jem WALL NUMBER:STUD LOCATION:(1 = ROOF, 2 = FIRST FLOOR BELOW ROOF, 3 = SECOND FLOOR BELOW ROOF) ROOF SPAN (FT)ROOF LOADS (PSF)SUPPORTING WALL D HEIGHT (FT) TOP PLATE THICKNESS (IN)WALL HAS CONTINUOUS SHEATHING ON ONE SIDE NO ROOF ASSEMBLY TYPE 0.6*WUPLIFT LR WEIGHT (PSF) S TOTAL TRIB.R FLOOR SPAN (FT)FLOOR LOADS (PSF)SUPPORTING WALL SIMPLE D HEIGHT (FT) SIMPLE MAIN SPAN L WEIGHT (PSF) TOTAL TRIB. TARGET WALL STUD MATERIAL 0.6*C&C (PSF)HEIGHT (FT)Hem-Fir Stud (2" to 4" wide)2x4 HEM-FIR STUD GRADE STUDS 0.6*W (PSF)WEIGHT (PSF)NO 1.10 1.50 0.7*E (PSF)PARTIAL LOADING (WIND)675 1.05 3.50 1200000 5.359 ASCE7 LOAD COMBINATIONS AXIAL (NDS Section 3.7) Emin = 440000 Le/d = 29.86 <= 50 c = 0.80 Fce = 0.822Emin'/(Le/d)^2 = 0.822(440000psi)/29.86^2 = 405.75psi F*c = Fc(Cd)(Cfc) = 800(1.60)(1.05) = 1344.00psi Fce/F*c = 405.75psi/1344.00psi = 0.30 A1 = (1 + Fce/F*c)/2c = 1.30/1.60 = 0.81 A2 = (Fce/F*c)/c = 0.30/0.80 = 0.38 Cp = A1-[A1^2-A2]^0.5 = 0.81-[0.66-0.38]^0.5 = 0.28 F'c = F*c(Cp) = 1344.00psi(0.28) = 376.46psi P = 388.03plf*1.33ft = 517.38# fc = P/A = 517.38#/5.25in^2 = 98.55psi BENDING (NDS Section 3.3) Le = 9.08ft - (3.00in + 1.50in)(1ft/12in) = 8.71ft M = 47.39#-ft F'b = Fb(Cd)(Cr)(Cfb) = 675(1.60)(1.15)(1.10) = 1366.20psi fb = (12in/1ft)(47.39#-ft)/3.06in^3 = 185.70psi INTERACTION EQUATION (NDS Section 3.9.2) (98.55psi/376.46psi)^2 + (1/(1-(98.55psi/405.75psi)))(185.70psi/1366.20psi) = 0.25 = 0.248 < 1.000 O.K. THEREFORE, USE 2x4 HEM-FIR STUD GRADE STUDS AT 16in O.C. D D + L D + LR D + S 0.6C&C D + L (NON-CONCURRENT) DESIRED SPACING FOR CALCULATIONS: STOP (FT)800 1.15 5.250 WALL WIDTH (IN)START (FT)440000 0.80 3.063 D + 0.75(0.6W) + 0.75L + 0.75LR D + 0.75(0.6W) + 0.75L + 0.75S D + 0.75(0.6W) + 0.75L + 0.75R D + 0.75(0.7E) + 0.75L + 0.75LR D + 0.75(0.7E) + 0.75L + 0.75S D + 0.75(0.7E) + 0.75L + 0.75R D + R D + 0.75L + 0.75LR D + 0.75L + 0.75S D + 0.75L + 0.75R D + 0.6W D + 0.7E Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 33 OF BY S3 1 3.00 180 NO 1.50 0.7 YES ROOF TYPE:15.00 18.67 30.00 10.00 TARGET WALL 1.00 25.00 16.00 6.89 15.87 18.67 SPECIES TITLE 11.08 10.00 SCANT CFB b (IN) 5.00 FB (PSI)CFC d (IN) 18.29 FC (PSI)CR A (IN2) 5.50 0.00 EMIN (PSI)c Sx (IN3) Ex (PSI) CD 0.90 85.41 " o.c. 1.00 85.93 " o.c. 1.25 86.83 " o.c. 1.15 39.33 " o.c. 1.25 86.83 " o.c. 1.25 86.83 " o.c. 1.15 45.54 " o.c. 1.25 86.83 " o.c. 1.60 26.64 " o.c. 1.60 36.60 " o.c. 1.60 31.44 " o.c. 1.60 22.20 " o.c.GOVERNS 1.60 31.44 " o.c. 1.60 41.28 " o.c. 1.60 27.00 " o.c. 1.60 41.28 " o.c. 1.60 24.33 " o.c. 1.00 " o.c. 16 " o.c. C&CWIND DEFLECTION, L/GYP COMP. SOLE PLATE THICKNESS (IN)PRE-FAB TRUSSES C&CWIND FACTOR = GYP + WOOD COMP. CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL jem WALL NUMBER:STUD LOCATION:(1 = ROOF, 2 = FIRST FLOOR BELOW ROOF, 3 = SECOND FLOOR BELOW ROOF) ROOF SPAN (FT)ROOF LOADS (PSF)SUPPORTING WALL SIMPLE D HEIGHT (FT) TOP PLATE THICKNESS (IN)WALL HAS CONTINUOUS SHEATHING ON ONE SIDE YES ROOF ASSEMBLY TYPE SIMPLE 0.6*WUPLIFT MAIN SPAN LR WEIGHT (PSF) OVERHANG S TOTAL TRIB.R TARGET WALL STUD MATERIAL 0.6*C&C (PSF)HEIGHT (FT)Hem-Fir #2 (2" to 4" wide)2x6 HEM-FIR #2 GRADE STUDS 0.6*W (PSF)WEIGHT (PSF)NO 1.30 1.50 0.7*E (PSF)PARTIAL LOADING (WIND)850 1.10 5.50 1300000 20.797 ASCE7 LOAD COMBINATIONS AXIAL (NDS Section 3.7) Emin = 470000 Le/d = 36.58 <= 50 c = 0.80 Fce = 0.822Emin'/(Le/d)^2 = 0.822(470000psi)/36.58^2 = 288.69psi F*c = Fc(Cd)(Cfc) = 1300(1.60)(1.10) = 2288.00psi Fce/F*c = 288.69psi/2288.00psi = 0.13 A1 = (1 + Fce/F*c)/2c = 1.13/1.60 = 0.70 A2 = (Fce/F*c)/c = 0.13/0.80 = 0.16 Cp = A1-[A1^2-A2]^0.5 = 0.70-[0.50-0.16]^0.5 = 0.12 F'c = F*c(Cp) = 2288.00psi(0.12) = 280.83psi P = 550.65plf*1.33ft = 734.20# fc = P/A = 734.20#/8.25in^2 = 88.99psi BENDING (NDS Section 3.3) Le = 18.67ft - (3.00in + 1.50in)(1ft/12in) = 18.29ft M = 463.37#-ft F'b = Fb(Cd)(Cr)(Cfb) = 850(1.60)(1.15)(1.30) = 2033.20psi fb = (12in/1ft)(463.37#-ft)/7.56in^3 = 735.26psi INTERACTION EQUATION (NDS Section 3.9.2) (88.99psi/280.83psi)^2 + (1/(1-(88.99psi/288.69psi)))(735.26psi/2033.20psi) = 0.62 = 0.623 < 1.000 O.K. THEREFORE, USE 2x6 HEM-FIR #2 GRADE STUDS AT 16in O.C. D D + L D + LR D + S 0.6C&C D + L (NON-CONCURRENT) DESIRED SPACING FOR CALCULATIONS: STOP (FT)1300 1.15 8.250 WALL WIDTH (IN)START (FT)470000 0.80 7.563 D + 0.75(0.6W) + 0.75L + 0.75LR D + 0.75(0.6W) + 0.75L + 0.75S D + 0.75(0.6W) + 0.75L + 0.75R D + 0.75(0.7E) + 0.75L + 0.75LR D + 0.75(0.7E) + 0.75L + 0.75S D + 0.75(0.7E) + 0.75L + 0.75R D + R D + 0.75L + 0.75LR D + 0.75L + 0.75S D + 0.75L + 0.75R D + 0.6W D + 0.7E Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm SHEET 34 OF BY S4 2 3.00 180 NO 1.50 0.7 NO ROOF TYPE: FLOOR TYPE:15.00 9.08 17.25 40.00 10.00 14.75 TARGET WALL 20.10 17.51 9.08 SPECIES TITLE 11.08 10.00 SCANT CFB b (IN) 5.00 FB (PSI)CFC d (IN) 8.71 FC (PSI)CR A (IN2) 5.50 0.00 EMIN (PSI)c Sx (IN3) Ex (PSI) CD 0.90 170.74 " o.c. 1.00 55.11 " o.c. 1.25 207.27 " o.c. 1.15 198.40 " o.c. 1.25 207.27 " o.c. 1.25 75.70 " o.c. 1.15 72.46 " o.c. 1.25 75.70 " o.c. 1.60 66.24 " o.c. 1.60 104.28 " o.c. 1.60 46.92 " o.c.GOVERNS 1.60 46.92 " o.c.GOVERNS 1.60 46.92 " o.c.GOVERNS 1.60 59.04 " o.c. 1.60 59.04 " o.c. 1.60 59.04 " o.c. 1.60 59.42 " o.c. 1.00 " o.c. 24 " o.c. C&CWIND DEFLECTION, L/GYP COMP. SOLE PLATE THICKNESS (IN)PRE-FAB TRUSSES C&CWIND FACTOR = GYP + WOOD COMP. CLIENT:LGI HOMES PROJECT:PLAN 1623- VERTICAL jem WALL NUMBER:STUD LOCATION:(1 = ROOF, 2 = FIRST FLOOR BELOW ROOF, 3 = SECOND FLOOR BELOW ROOF) ROOF SPAN (FT)ROOF LOADS (PSF)SUPPORTING WALL D HEIGHT (FT) TOP PLATE THICKNESS (IN)WALL HAS CONTINUOUS SHEATHING ON ONE SIDE NO ROOF ASSEMBLY TYPE 0.6*WUPLIFT LR WEIGHT (PSF) S TOTAL TRIB.R FLOOR SPAN (FT)FLOOR LOADS (PSF)SUPPORTING WALL CONTINUOUS D HEIGHT (FT) CONTINUOUS LONG SPAN L WEIGHT (PSF) SHORT SPAN TOTAL TRIB. TARGET WALL STUD MATERIAL 0.6*C&C (PSF)HEIGHT (FT)Hem-Fir Stud (2" to 4" wide)2x6 HEM-FIR STUD GRADE STUDS 0.6*W (PSF)WEIGHT (PSF)NO 1.00 1.50 0.7*E (PSF)PARTIAL LOADING (WIND)675 1.00 5.50 1200000 20.797 ASCE7 LOAD COMBINATIONS AXIAL (NDS Section 3.7) Emin = 440000 Le/d = 19.00 <= 50 c = 0.80 Fce = 0.822Emin'/(Le/d)^2 = 0.822(440000psi)/19.00^2 = 1001.96psi F*c = Fc(Cd)(Cfc) = 800(1.60)(1.00) = 1280.00psi Fce/F*c = 1001.96psi/1280.00psi = 0.78 A1 = (1 + Fce/F*c)/2c = 1.78/1.60 = 1.11 A2 = (Fce/F*c)/c = 0.78/0.80 = 0.98 Cp = A1-[A1^2-A2]^0.5 = 1.11-[1.24-0.98]^0.5 = 0.60 F'c = F*c(Cp) = 1280.00psi(0.60) = 769.73psi P = 949.84plf*2.00ft = 1899.67# fc = P/A = 1899.67#/8.25in^2 = 230.26psi BENDING (NDS Section 3.3) Le = 9.08ft - (3.00in + 1.50in)(1ft/12in) = 8.71ft M = 157.54#-ft F'b = Fb(Cd)(Cr)(Cfb) = 675(1.60)(1.15)(1.00) = 1242.00psi fb = (12in/1ft)(157.54#-ft)/7.56in^3 = 249.97psi INTERACTION EQUATION (NDS Section 3.9.2) (230.26psi/769.73psi)^2 + (1/(1-(230.26psi/1001.96psi)))(249.97psi/1242.00psi) = 0.35 = 0.351 < 1.000 O.K. THEREFORE, USE 2x6 HEM-FIR STUD GRADE STUDS AT 24in O.C. D D + L D + LR D + S 0.6C&C D + L (NON-CONCURRENT) DESIRED SPACING FOR CALCULATIONS: STOP (FT)800 1.15 8.250 WALL WIDTH (IN)START (FT)440000 0.80 7.563 D + 0.75(0.6W) + 0.75L + 0.75LR D + 0.75(0.6W) + 0.75L + 0.75S D + 0.75(0.6W) + 0.75L + 0.75R D + 0.75(0.7E) + 0.75L + 0.75LR D + 0.75(0.7E) + 0.75L + 0.75S D + 0.75(0.7E) + 0.75L + 0.75R D + R D + 0.75L + 0.75LR D + 0.75L + 0.75S D + 0.75L + 0.75R D + 0.6W D + 0.7E Printed by Larissa.anaya on 02/12/2025 at 09:37 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\Vertical Book1.xlsm CLIENT: FELTENGROUP ARCHITECTURE I ENGINEERING I FORENSICS DATE: SHEET OF BY: MAIN FLOOR UPPER FLOOR BRACED/SHEAR WALL PLAN BRACED/SHEAR WALL PLAN CLIENT:SHEET L3 OF PROJECT:BY 110 mph C (Section 26.7) II (Table 1.5-1) 0.85 (Table 26.6-1) 1.00 (Section 26.8.2) 100 (Section 26.9)Ke = 1.00 (Table 26.9-1) 0.6 (Section 2.4.1) Roof Truss Heel Height:0.333 ft Upper Plate Height:8.083 ft Floor Truss Depth:1.583 ft Lower Plate Height:9.083 ft Length (Dim. Perp. to Truss Span):32.000 ft Width (Dim. Parallel to Truss Span):30.000 ft Roof Pitch:5.00 in/12 in Roof Angle:22.620 deg Mean Roof Height:22.207 ft Ridge Height:25.332 ft Design Edge Strip (a):3.000 ft Design End Zone (2a):6.000 ft Velocity Pressure Coefficient (Kz):0.918 (Table 26.10-1) 0.6*qz (Velocity Pressure):14.44 psf (Equation 26.10-1) 0.6*Pcc,wall (Maximum Volume Wall):15.79 psf (Equation 30.3-1) 0.6*Pcc,wall (Maximum Story Wall):17.42 psf (Equation 30.3-1) 0.6*Pez (End Zone Stud Design Pressure):13.74 psf Load Case A 0.6*Piz (Int. Zone Stud Design Pressure):10.37 psf Load Case A 0.6*Pp (Parapet Pressure 1.5WW and -1.0LW):21.67 psf Windward and -14.44 psf Leeward LGI HOMES PLAN 1623- WIND LA Elevation Label: Basic Wind Speed (3 sec gust): Exposure: Risk Category: Wind Directionality (Kd): Design Code:ASCE 7-16 Design Method:Low-Rise Building (Section 28.3.1) Topographic Factor (Kzt): Ground Elevation Factor (ft) (Ke): ASD Load Combination Factor for W: TWO STORY DIAPHRAGM WIND LOADS FOR ASD LOAD COMBINATIONS Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L4 OF PROJECT:BY p = 0.6 * qz * [GCpf - GCpi](Equation 28.3-1) GCpf interpolated from Figure 28.3-1 GCpi 0.18 enclosed buildings Table 26.13-1 (GCpi acts either inward or outward at any one time) GCpf GCpi Zone 1:0.54 -0.18 Zone 2:-0.45 0.18 Zone 3:-0.47 0.18 Zone 4:-0.41 -0.18 Zone 1E:0.77 -0.18 Zone 2E:-0.72 0.18 Zone 3E:-0.65 0.18 Zone 4E:-0.60 -0.18 GCpf GCpi Zone 1:-0.45 -0.18 Zone 2:-0.69 0.18 Zone 3:-0.37 0.18 Zone 4:-0.45 -0.18 Zone 5:0.40 -0.18 Zone 6:-0.29 -0.18 Zone 1E:-0.48 -0.18 Zone 2E:-1.07 0.18 Zone 3E:-0.53 0.18 Zone 4E:-0.48 -0.18 Zone 5E:0.61 -0.18 Zone 6E:-0.43 -0.18 Note: Plus and minus signs signify pressures acting toward and away from the surfaces, respectively. Gable End Loading Load Case A Load Case B LGI HOMES Hip End Loading Load Case A Load Case B Load Case A Pressures 0.6*qz*GCpf (psf)0.6*qz*GCpi (psf)Pressure (psf) PLAN 1623- WIND LA -6.74 2.60 -9.34 -5.98 -2.60 -3.38 7.77 -2.60 10.37 -6.56 2.60 -9.16 -9.36 2.60 -11.96 -8.64 -2.60 -6.04 11.14 -2.60 13.74 -10.38 2.60 -12.98 -9.97 2.60 -12.57 -5.34 2.60 -7.94 Load Case B Pressures 0.6*qz*GCpf (psf)0.6*qz*GCpi (psf)Pressure (psf) -6.50 -2.60 -3.90 -4.19 -2.60 -1.59 -6.93 -2.60 -4.33 -6.50 -2.60 -3.90 5.78 -2.60 8.38 -6.93 -2.60 -4.33 8.81 -2.60 11.41 -15.46 2.60 -18.06 -7.66 2.60 -10.26 -6.21 -2.60 -3.61 Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L5 OF PROJECT:BY Case A 7.28 psf 7.23 psf Case B 11.00 psf 5.78 psf GCpf GCpf 6.38 psf 4.61 psf GCpf GCpf 8.40 psf 6.48 psf GCpi GCpi 2.60 psf 2.60 psf 14.88 psf 10.98 psf 0.00 psf 9.86 psf 10.99 psf 6925 #5821 # 5088 # Case A 7.28 psf 7.23 psf Case B 9.12 psf 7.66 psf GCpf GCpf GCpf GCpf 8.40 psf 6.48 psf 5.93 psf 4.29 psf GCpi GCpi 2.60 psf 2.60 psf 14.88 psf 10.22 psf 0.00 psf 0.00 psf 9.86 psf 10.99 psf 6925 #4841 # Load Cases A & B total pressures are determined by using a weighted average of end zone total plus interior zone total. This number is then compared to the code required 16psf minimum for the horizontal direction. Roof uplift for the left and right sides of the roof are determined using a weighted average of end zone plus interior zone and then the total roof uplift is the average of the left and right sides. GCpi assumed to act inward for wall design, outward for roof uplift design. TWO STORY DIAPHRAGM GABLE END WIND LOADS FOR ASD LOAD COMBINATIONS LGI HOMES PLAN 1623- WIND LA Total Horizontal Pressure at Wall =Total Horizontal Pressure at Wall = CASE A CASE B GCpf Windward GCpf Leeward ∴Use 14.88|0.00 psf Wall|Roof Horizontal Pressure at Case A ∴Use 10.98 psf Horizontal Pressure at Case B ∴Use 11.00 psf at Wall for Windward Only Case (0.6*W)∴Use 8.98 psf at Wall for Windward Only Case (0.6*W) Total Horizontal Pressure at Roof = Total Uplift Pressure at Roof =Total Uplift Pressure at Roof = Total Base Shear Due to Wind Loads =Total Base Shear Due to Wind Loads = Total Base Shear Due to 0.6*16psf at Wall and 0.6*8psf at Roof =5427 #Total Base Shear Due to 0.6*16psf = Total Horizontal Pressure at Wall =Total Horizontal Pressure at Wall = Total Horizontal Pressure at Roof =Total Horizontal Pressure at Roof = Total Uplift Pressure at Roof =Total Uplift Pressure at Roof = TWO STORY DIAPHRAGM HIP END WIND LOADS FOR ASD LOAD COMBINATIONS Load Case A Load Case B GCpf Windward GCpf Leeward GCpf Windward GCpf Leeward ∴Use 11.00 psf at Wall for Windward Only Case (0.6*W)∴Use 8.53 psf at Wall for Windward Only Case (0.6*W) 4998 # ∴Use 14.88|0.00 psf Wall|Roof Horizontal Pressure at Case A ∴Use 9.60|4.80 psf Wall|Roof Horizontal Pressure at Case B Total Base Shear Due to Wind Loads =Total Base Shear Due to Wind Loads = Total Base Shear Due to 0.6*16psf at Wall and 0.6*8psf at Roof =4977 #Total Base Shear Due to 0.6*16psf at Wall and 0.6*8psf at Roof = Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L6 OF BY WALL ROOF PARAPET TRIB. WALL HEEL TRIB. RIDGE PARAPET SHEAR DISTANCE PRESSURE PRESSURE PRESSURE HEIGHT HEIGHT TO HEEL HEIGHT UNIFORM START STOP #FT PSF PSF PSF FT FT FT FT PLF FT FT 10.98 10.98 4.042 0.333 3.125 2ND FLOOR 1ST FLOOR 10.98 10.166 1236 0.000 1ST FLOOR 10.98 10.166 642 0.000 1236 18.500 1ST FLOOR PROJECT:PLAN 1623- WIND LA LINE CALLOUT % CANT.WIND DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES SHEAR (#) CHORD (#) WINDWARD INFORMATION LEEWARD INFORMATION NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # 1236 1236 290 0 0 82 0.000 B 0.00% 32.000 0 30.000 A 30.000 1236 12360 1236 0 STORY CALC DESCRIPTION 0 0 0 0 0 0 0 0 0.00%0 0 0 0 STORY CALC DESCRIPTION A 11.500 #A ABOVE 112 0.000 11.500 1878 1878 53 0 642 1878 0 A.5* 0.00% 35.000 0 0 642 0 STORY CALC DESCRIPTION A.5 18.500 #A.5*112 0.000 18.500 1675 1675 136 0 2268 1675 0 B 0.00% 35.000 #B ABOVE 0 STORY CALC DESCRIPTION 0 2268 0 Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L7 OF BY WALL ROOF PARAPET TRIB. WALL HEEL TRIB. RIDGE PARAPET SHEAR DISTANCE PRESSURE PRESSURE PRESSURE HEIGHT HEIGHT TO HEEL HEIGHT UNIFORM START STOP #FT PSF PSF PSF FT FT FT FT PLF FT FT 14.88 0.00 4.042 0.333 6.250 14.88 0.00 4.042 0.333 5.521 14.88 0.00 4.042 0.333 3.368 2ND FLOOR 1ST FLOOR 14.88 10.166 1107 0.000 1ST FLOOR 14.88 10.166 1135 0.000 14.88 0.00 4.542 0.333 2.396 1107 19.000 1ST FLOOR PROJECT:PLAN 1623- WIND LA LINE CALLOUT % CANT.WIND DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES SHEAR (#) CHORD (#) WINDWARD INFORMATION LEEWARD INFORMATION NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # 1107 1107 314 65 30.000 32.000 65 65 0.000 32.000 34.000 3 0.00% 30.000 0 30.000 1 34.000 1107 11070 1107 0 STORY CALC DESCRIPTION 0 0 0 0 0 0 0 0 0.00%0 0 0 0 STORY CALC DESCRIPTION 1 15.000 #1 ABOVE 151 0.000 15.000 2242 2242 142 0 1135 2242 0 2* 0.00% 30.000 0 0 1135 0 STORY CALC DESCRIPTION 2 22.000 #2*151 0.000 19.000 2934 2934 357 73 19.000 22.000 2400 2934 0 3 0.00% 30.000 #3 ABOVE 0 STORY CALC DESCRIPTION 0 2400 0 Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L8 OF BY WIND DESIGN: WALL BRACING ANALYSES 110 22.21 2 1 C 6.25 8 2 NO YES NO NO 0.00 0.00 30.00 0.00 1.30 0.78 0.90 1.00 1.00 1.00 1.00 1.00 1.00 5.00 0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP WSP L (ft)9.17 3.67 4.00 ADJ. H (ft) LCONT. (ft)9.17 3.34 4.00 16.51 110 22.21 2 1 C 6.25 8 2 NO YES NO NO 0.00 0.00 30.00 0.00 1.300 0.775 0.900 1.000 1.000 1.000 1.000 1.000 1.000 5.000 0.000 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP L (ft)19.67 7.33 ADJ. H (ft) LCONT. (ft)19.67 7.33 27.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND LA BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL A 4.53 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 16.51>=4.53 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL B 4.53 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 27.00>=4.53 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOORBASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L9 OF BY WIND DESIGN: WALL BRACING ANALYSES 110 22.21 2 2 C 6.25 9 2 NO YES NO NO 0.00 0.00 30.00 0.00 1.30 0.89 0.95 1.00 1.00 1.00 1.00 1.00 1.00 9.50 0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP L (ft)15.83 7.50 ADJ. H (ft) LCONT. (ft)15.83 7.50 23.33 110 22.21 2 2 C 6.25 9 2 NO YES NO NO 0.00 0.00 30.00 0.00 1.300 0.888 0.950 1.000 1.000 1.000 1.000 1.000 1.000 9.500 0.000 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP L (ft)35.00 ADJ. H (ft) LCONT. (ft)35.00 35.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND LA BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL A 10.41 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 23.33>=10.41 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL B 10.41 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 35.00>=10.41 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOORBASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L10 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==1675 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.6WUPLIFT (psf) ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 19.50 9.00 2x6 1.4E+06 1677 1.000 86 324 2.00 10.00 15.00 0.00 15093 22815 2 3 4 5 6 1677 1 72 72 2 3 4 5 6 V ==# WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.6WUPLIFT (psf) ∑MOT (#-ft) ∑MR (#-ft) 1 2 3 4 5 6 1 2 3 4 5 6 TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC LEFT END RIGHT END WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM VTOTAL (#) = TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC LEFT END RIGHT END WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM 0.073 VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND LA A.5 FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L11 OF BY WIND DESIGN: WALL BRACING ANALYSES 110 22.21 2 1 C 6.25 8 2 NO YES NO NO 0.00 0.00 34.00 0.00 1.30 0.78 0.90 1.00 1.00 1.00 1.00 1.00 1.00 5.60 0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP L (ft)20.25 ADJ. H (ft) LCONT. (ft)20.25 20.25 110 22.21 2 1 C 6.25 8 2 NO YES NO NO 0.00 0.00 34.00 0.00 1.300 0.775 0.900 1.000 1.000 1.000 1.000 1.000 1.000 5.600 0.000 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP WSP L (ft)3.92 5.42 3.00 ADJ. H (ft) LCONT. (ft)3.84 5.42 2.25 11.51 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND LA BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL 1 5.08 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 20.25>=5.08 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL 3 5.08 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 11.51>=5.08 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOORBASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L12 OF BY WIND DESIGN: WALL BRACING ANALYSES 110 22.21 2 2 C 6.25 9 3 NO YES NO NO 0.00 0.00 15.00 0.00 1.30 0.89 0.95 1.30 1.00 1.00 1.00 1.00 1.00 5.00 0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD WSP WSP WSP L (ft)4.00 4.75 4.25 ADJ. H (ft) LCONT. (ft)4.00 4.75 4.25 13.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 WALL #1 2 3 4 5 6 7 8 9 10 11 12 13 14 METHOD L (ft) ADJ. H (ft) LCONT. (ft)0.00 CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND LA BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL 1 7.12 LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) 13.00>=7.12 O.K.TOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES BRACED WALL INPUTS AND FACTORS WIND SPEED (mph) MEAN ROOF H (ft) NUMBER OF STORIES STORY LOCATION EXPOSURE MIN. 800# HOLD- DOWN GB ON INSIDE FACE GB 4"O.C. PANEL LENGTH OF BRACING PROVIDED, ADJACENT HEIGHT & CONTRIBUTING LENGTH FOR EACH METHOD (ft) NOT PERMITTEDTOTAL (ft) PLYWOOD BLOCKING OMITTED PARAPET HEEL H (ft) PARAPET H (ft) LINE SPACING 1 (ft) LINE SPACING 2 (ft) REQUIRED LENGTH (ft) EAVE TO RIDGE H (ft) STORY HEIGHT (ft) NUMBER OF LINES METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) METHOD CS-WSP (INCLUDES CS-G & CS-PF)METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT METHOD CS-WSP (INCLUDES CS-G & CS-PF) FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR METHOD WSP (INCLUDES ABW, PFH & PFG)METHOD GB (2 SIDED)METHOD GB (1 SIDED) 3rd FLOORBASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L13 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==2934 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.6WUPLIFT (psf) ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 14.67 9.08 2x6 1.4E+06 2934 1.000 200 324 20.00 10.00 15.00 0.00 26641 42052 2 3 4 5 6 2934 1 96 96 2 3 4 5 6 V ==1424 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.6WUPLIFT (psf) ∑MOT (#-ft) ∑MR (#-ft) 1 4 24 4.33 9.08 2x6 1.4E+06 1426 0.988 329 468 2.00 10.00 15.00 0.00 12948 1134 2 3 4 5 6 1426 1 CONC EXT CORNER 6 CRKD 800 2351 E CONC EXT CORNER 6 CRKD 800 2351 E 2 3 4 5 6 LA 2 VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND 0.172 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC 3 TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = 0.479 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END T2nd FLOOR (#)CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm SHEET L14 OF BY LATERAL LOAD ANALYSIS: APA PORTAL FRAME PER TT-100H V ==976 # 977 # 1.000 9.000 10.000 D =0.457 in Door Height (ft) = Pier Height (ft) = Left Pier (ft) 1.500 APA PORTAL FRAME PER TT-100H 0.430 0.93 Beam Height (ft) = Number of Piers 1 VALLOW = Specific Gravity SG Reduction CLIENT:LGI HOMES PROJECT:PLAN 1623- WIND LA 3 FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/04/2025 at 11:17 \\vmwashington\washington\LGI Homes\Seattle\Eldorado Plat\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Wind Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L15 OF PROJECT:BY SEISMIC LOAD CALCULATIONS PER ASCE 7-16 *USING BASIC LOAD COMBINATIONS PER SECTION 2.4* ALL LOAD COMBINATIONS USE: 0.7*E E = Eh + Ev (EQN 12.4-1 and EQN 12.4-3) Eh = ρQE (EQN 12.4-3) ρ = 1.30 (SECTION 12.3.4.2.a) QE = V (SECTION 12.4.2.1) Ev = 0.2SDSD (EV = 0 IF SDS <= 0.125)(EQN 12.4-4a) II (TABLE 1.5-1) D (PER PROJECT SOILS REPORT OR TABLE 20.3-1)DEFAULT 22.207 (MEAN ROOF HEIGHT OF STRUCTURE) 1.288 (MAPPED MCE SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS) 0.465 (MAPPED MCE SPECTRAL RESPONSE ACCELERATION AT A PERIOD OF 1 s) Fa =1.200 (TABLE 11.4-1) Fv =1.835 (TABLE 11.4-2) SMS = FaSs =1.546 (EQN 11.4-1) SM1 = FvS1 =0.853 (EQN 11.4-2) SDS = 2/3SMS =1.030 (EQN 11.4-3) SD1 = 2/3SM1 =0.569 (EQN 11.4-4) 1.000 (TABLE 1.5-2) 0.552 (SECTION 11.4.6) SDC BASED ON SDS =D (TABLE 11.6-1)**EXCEPTION IN SECTION 11.6 CAN BE CHECKED S1<0.75 AND Ta<0.8Ts SDC BASED ON SD1 =N/A (TABLE 11.6-2) DESIGN SDC =D (SECTION 11.6) R FRONT/BACK =6.500 R SIDE/SIDE =6.500 (TABLE 12.2-1 (A.15)) 0.020 (TABLE 12.8-2) x =0.750 (TABLE 12.8-2) 0.205 (EQN 12.8-7) TL =6.000 (TABLE 22-14) V = CSW (EQN 12.8-1) CS = SEISMIC RESPONSE COEFFICIENT (SECTION 12.8.1.1) W = EFFECTIVE SEISMIC WEIGHT (SECTION 12.7.2) FRONT/BACK SIDE/SIDE CS =SDS/(R/IE) =0.159 CS =SDS/(R/IE) =0.159 GOVERNS Csmax = SD1/(T(R/IE)) =0.428 GOVERNS Csmax = SD1/(T(R/IE)) =0.428 Csmax = SD1TL/(T2(R/IE)) =12.544 Csmax = SD1TL/(T2(R/IE)) =12.544 GOVERNS Csmin = 0.044*SDS*IE>=0.01 0.045 GOVERNS Csmin = 0.044*SDS*IE>=0.01 0.045 Csmin = 0.5S1/(R/IE) =0.036 Csmin = 0.5S1/(R/IE) =0.036 EQN 12.8-2 GOVERNS AND QE = V = 0.159 *W EQN 12.8-2 GOVERNS AND QE = V = 0.159 *W SDS SDS EV =0.206 *D 0.7*EV =0.144 *D EV =0.206 *D 0.7*EV =0.144 *D LGI HOMES PLAN 1623- SEISMIC LA Elevation Label: Ct= RISK CATEGORY = SITE CLASS = hn (ft) = Ss = S1 = IE= Ts= **USE TABLE 11.6-1 ALONE IF RIGID DIAPHRAGM AND T<Ts OR WHEN USING BRACING TABLES FOR IRC DESIGN Ta = Cthn x = }0.428 }0.428 }0.045 }0.045 > 0.125, THEREFORE > 0.125, THEREFORE Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm CLIENT:SHEET L16 OF PROJECT: Mass Calculations Area (ft2) Load (psf) Weight (lb) Total Length (ft) Load (psf) Weight (lb) Total Length (ft) Load (psf) Weight (lb) Roof 8.083 985 15 14775 128 10 5173 125 7 3536 23484 Floor 1 9.083 1.5 1119 10 11190 134 10 11259 70 7 5762 28210 0 0 0 0 25965 16432 9298 51695 Base Shear ASD Eh (lb) Eh * 0.7 (lb)Level wx (lb) hx (ft) wxhx (lb-ft) wxhx k ∑wihi k (%) Fx (lb) Fx Ax (psf) 10653 7457 Roof 23484 18.7 438360 0.595 4436 4.50 Floor 1 28210 10.6 298550 0.405 3021 2.70 0 0.0 0 0.000 0 0.00 51695 736911 7457 Base Shear ASD Eh (lb) Eh * 0.7 (lb)Level wx (lb) hx (ft) wxhx (lb-ft) wxhx k ∑wihi k (%) Fx (lb) Fx Ax (psf) 10653 7457 Roof 23484 18.7 438360 0.595 4436 4.50 Floor 1 28210 10.6 298550 0.405 3021 2.70 0 0.0 0 0.000 0 0.00 51695 736911 7457 LGI HOMES PLAN 1623- SEISMIC Total Mass Level Plate Height (ft) Floor Depth (ft) Diaphragm Exterior Walls Interior Walls Total Weight (lb) ρ 1.30 Redundancy Front/Back Vertical Distribution of Seismic Forces (12.8.3) [Ta <= 0.5s k=1] ρ 1.30 Redundancy Side/Side Vertical Distribution of Seismic Forces (12.8.3) [Ta <= 0.5s k=1] Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L17 OF BY SHEAR DISTANCE UNIFORM START STOP #FT PLF FT FT 2ND FLOOR 1ST FLOOR 2221 0.000 1ST FLOOR 625 0.000 2216 18.500 1ST FLOOR PROJECT:PLAN 1623- SEISMIC LA LINE CALLOUT % CANT.SEISMIC DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # SEISMIC LOAD SEISMIC DEPTH PARALLEL TO DIRECTION PSF TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # A 30.000 4.50 30.000 4.50 34.000 3.500 2221 2221 498 153 3.500 19.666 30.000 FT SHEAR (#) CHORD (#) 2221 4.50 32.000 144 19.666 135 0.000 0 STORY CALC DESCRIPTION 0 22160B 0.00% 34.000 2216 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 2692 2692 43 31 0.000 7.333 0 A 11.500 #A ABOVE 2.70 16.000 2.70 11.500 2692 2.70 49.000 132 7.333 11.500 43 0.000 7.333 0 STORY CALC DESCRIPTION 6250A.5* 0.00% 35.000 625 1787 1787 140 94 7.833 18.500 0 A.5 18.500 #A.5*2.70 43.000 2.70 35.000 1787 2.70 8.000 22 0.000 9.670 116 0.000 7.833 0 STORY CALC DESCRIPTION 31810B 0.00% 35.000 #B ABOVE 3181 Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L18 OF BY SHEAR DISTANCE UNIFORM START STOP #FT PLF FT FT 2ND FLOOR 1ST FLOOR 2290 0.000 48.5989 0.000 1ST FLOOR 607 0.000 2147 19.000 124.197 22.000 1ST FLOOR PROJECT:PLAN 1623- SEISMIC LA LINE CALLOUT % CANT.SEISMIC DESIGN SHEAR DIAPHRAGM CLIENT:LGI HOMES NEXT LINE FROM NEXT CHORD DIST. FT SOURCE LINE NEXT LINE # SEISMIC LOAD SEISMIC DEPTH PARALLEL TO DIRECTION PSF TARGET LINE TO TARGET LINE SPACING FT POINT SHEAR FROM OTHER LINES UNIFORM LOADS BETWEEN TARGET LINE AND NEXT LINE TARGET LINE # 1 34.000 4.50 30.000 4.50 26.500 30.000 2290 2290 647 119 30.000 32.000 34.000 FT SHEAR (#) CHORD (#) 2290 4.50 16.160 73 32.000 135 0.000 0 STORY CALC DESCRIPTION 0 214703 0.00% 30.000 2147 0 0 0 0 0 0 0 0 0 STORY CALC DESCRIPTION 00 0.00% 0 2946 2946 76 0 0 1 15.000 #1 ABOVE 2.70 30.000 #PATIO 2946 0 81 0.000 15.000 0 STORY CALC DESCRIPTION 60702* 0.00% 30.000 607 2342 2342 404 31 20.000 22.000 0 2 20.00% 22.000 #2*2.70 30.000 2.70 11.500 2342 0 81 0.000 20.000 0 STORY CALC DESCRIPTION 2219#PORCH 03 20.00% 30.000 #3 ABOVE 2219 Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L19 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==2221 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 9.17 8.00 2x6 1.4E+06 954 1.000 104 232 16.00 10.00 15.00 0.14 9573 13454 2 3 24 13.67 18.50 2x6 1.4E+06 547 1.000 40 232 16.00 10.00 15.00 0.14 15845 39686 3 3 24 3.67 8.00 2x6 1.4E+06 352 0.978 96 227 16.00 10.00 15.00 0.14 3127 2155 4 3 24 4.00 8.00 2x6 1.4E+06 388 1.000 97 232 16.00 10.00 15.00 0.14 3473 2560 5 6 2241 1 800 0 800 0 2 800 0 800 0 3 800 20 800 20 4 800 4 800 4 5 6 V ==2216 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 19.67 8.08 2x6 1.4E+06 1632 1.000 83 232 16.00 10.00 15.00 0.14 22135 62035 2 3 24 7.33 8.08 2x6 1.4E+06 587 1.000 80 232 16.00 10.00 15.00 0.14 5987 8625 3 4 5 6 2219 1 800 0 800 0 2 800 0 800 0 3 4 5 6 LA A VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC 0.080 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC B TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = 0.063 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM WOOD/ CONC LEFT END RIGHT END CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L20 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==2145 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 7.50 9.00 2x6 1.4E+06 675 1.000 90 232 1.00 10.00 15.00 0.14 6501 2953 2 3 24 15.83 9.00 2x6 1.4E+06 1488 1.000 94 232 1.00 10.00 15.00 0.14 15291 13161 3 4 5 6 2163 1 800 151 800 151 2 800 0 800 0 3 4 5 6 V ==1787 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 19.50 9.00 2x6 1.4E+06 1794 1.000 92 232 2.00 10.00 15.00 0.14 19437 22815 2 3 4 5 6 1794 1 800 0 800 0 2 3 4 5 6 LA A VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC 0.080 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC A.5 TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = 0.078 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM WOOD/ CONC LEFT END RIGHT END CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L21 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==3181 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 35.00 9.08 2x6 1.4E+06 3185 1.000 91 232 1.00 10.00 15.00 0.14 38268 64803 2 3 4 5 6 3185 1 0 0 2 3 4 5 6 V ==# WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 2 3 4 5 6 1 2 3 4 5 6 LA B VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC 0.077 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM WOOD/ CONC LEFT END RIGHT END CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L22 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==2290 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 20.25 8.08 2x6 1.4E+06 1883 1.000 93 232 2.00 10.00 15.00 0.14 18492 22717 2 3 24 4.75 8.08 2x6 1.4E+06 409 1.000 86 232 2.00 10.00 15.00 0.14 3485 1250 3 4 5 6 2292 1 800 0 800 0 2 800 96 800 96 3 4 5 6 V ==# WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 2 3 4 5 6 1 2 3 4 5 6 LA 1 VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC 0.070 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM WOOD/ CONC LEFT END RIGHT END CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L23 OF BY LATERAL LOAD ANALYSIS: FORCE TRANSFER AROUND OPENINGS (FTAO) SDPWS 4.3.5.2 V ==993 # 993 # 2.00 15.00 0.14 993 # 1.083 →→ ←← 5.000 →→ ←← 2.000 →→→ ←←← 3.000 5.000 2.333 D =0.149 in CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC LA 3 → VALLOW = Left Header Strap Force (#) Stud Spacing (inches o.c.) Right Header Strap Force (#)CS20 ATRIB. (ft) =Roof DL (psf) =0.7*0.2*SDS =← VALLOW = CS20 Top Pier (ft) = 709 24 551 Left Strap (Name/Value (#)) Right Strap (Name/Value (#)) Material Material Wall Weight (psf) 1030 1030 709 551 Left Holdown Right Holdown Window (ft) = Location Location 10 Stem Stem 709 551 709 551 Position Position Left Sill Strap Force (#) Right Sill Strap Force (#) Left Holdown Strap Force (#) Max. Shear Panel Force (plf) Right Holdown Strap Force (#)Bottom Pier (ft) = Concrete Concrete Name / Value (#) / D Name / Value (#) / D Left Restraint (#) Right Restraint (#)Left Pier (ft) =Window (ft) =Right Pier (ft) = 800 800 250 250 208 252 0 0.000 0.000 0 252 208 WOOD 252 Left Uplift from Above (#) Right Uplift from Above (#) 0 0 Type of Shear (Wall/Value (plf)) 3 FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm LATERAL LOAD ANALYSIS: FORCE TRANSFER AROUND OPENINGS (FTAO) SDPWS 4.3.5.2 V ==1154 # 1275 # 2.00 15.00 0.14 1275 # →→→→ ←←←← Left Right Window Window →→→→ ←←←← →→→ ←←← D =0.076 in PR O J E C T : CL I E N T : PL A N 1 6 2 3 - S E I S M I C LG I H O M E S 3 → VALLOW = ATRIB. (ft) =Roof DL (psf) =0.7*0.2*SDS =← VALLOW = Left Window Left Strap (Name/Value (#)) Right Strap (Name/Value (#))Left Header Strap Force (#) Right Header Strap Force (#) Left Header Strap Force (#) Right Header Strap Force (#)NO STRAP NO STRAP Top Pier (ft)Top Pier (ft) 1.083 162 252 329 292 1.083 252 252 162 252 329 CS20 CS20 10 292 Right Window Left Strap (Name/Value (#)) Right Strap (Name/Value (#))Wall Weight (psf) 1030 1030 Left Holdown Right Holdown Window (ft) Window (ft) Material Material 5.000 Left Sill Strap Force (#) Right Sill Strap Force (#) Left Sill Strap Force (#) 292 Right Sill Strap Force (#) 5.000 Location Location 162 252 329 292 Position Position Left Holdown Strap Force (#) Shear Panel Force (plf) 162 252 329 Right Holdown Strap Force (#)Stem Stem Bottom Pier (ft)Bottom Pier (ft) 2.000 0 207 Name / Value (#) / D Name / Value (#) / D 0 2.000 Concrete Concrete 0 207 0 Right Window (ft)Right Pier (ft) 2.833 2.000 4.416 3.000 3.916 250 250 0.000 0.000 Left Restraint (#) Right Restraint (#) 800 800 Left Uplift from Above (#) Right Uplift from Above (#) 0 0 Left Pier (ft)Left Window (ft)Middle Pier (ft) OF BY : SH E E T : Type of Shear (Wall/Value (plf)) Stud Spacing (inches o.c.) 3 24 LA L2 4WOOD 252 FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L25 OF BY LATERAL LOAD ANALYSIS: PERFORATED SHEAR WALLS (PSW) SDPWS 4.3.2.3 V ==2946 # 7.92 10.00 15.00 0.14 26754 94296 1 4.000 0 0 2 3.000 3 4.750 4 4.250 SDPWS Equation (4.3-6) C0 = Awall / (3SA0+SAfhs) 5 SDPWS Equation (4.3-5) VALLOW = vMAXC0Sbi 6 7 8 9 0.710 4 322 3253 >=2946 OK ∑Afhs =145.280 ∑AO =∑bi =14.235 V ==# 1 2 3 4 SDPWS Equation (4.3-6) C0 = Awall / (3SA0+SAfhs) 5 SDPWS Equation (4.3-5) VALLOW = vMAXC0Sbi 6 7 8 9 0 ∑Afhs =∑AO =∑bi = ∑MOT = Vh ∑MR = [DLATRIB.+WWALLh][LTOT]2/2 Wall Length, LTOT (ft)Wall Height, h (ft)Stud Spacing (in)TDESIGN = [∑MOT-(0.6-0.7*0.2*SDS)∑MR]/[CO∑bi]-(0.6-0.7*0.2*SDS)WINT.WALL+T2nd FLOOR {EQN 4.3-8} CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC LA 1 ATRIB. (ft) WWALL (psf) DL (psf) 0.7*0.2* SDS ∑MOT (#-ft) ∑MR (#-ft)LOCATION POSITION 30.000 9.080 24 LEFT END RIGHT END Full Height Wall Segment, Li (ft) Openings Adjusted Segment, bi (ft) WOOD/ CONC TDESIGN (#)HOLDOWN STEM CONCRETE WINT.WALL (#)STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)LOCATION POSITION TDESIGN (#)HOLDOWN Height (ft)Width (ft)Area, AO (ft2) T2nd FLOOR (#) 4.500 3.000 13.500 3.524 6.833 6.000 40.998 1.982 WOOD/ CONC 5.000 5.000 25.000 4.750 3.979 V (#) DESIGN CHECK PERFORATED SHEAR WALL RESULTS CO WALL TYPE vMAX (plf) VALLOW (#) ∑MOT = Vh ∑MR = [DLATRIB.+WWALLh][LTOT]2/2 Wall Length, LTOT (ft)Wall Height, h (ft)Stud Spacing (in)TDESIGN = [∑MOT-(0.6-0.7*0.2*SDS)∑MR]/[CO∑bi]-(0.6-0.7*0.2*SDS)WINT.WALL+T2nd FLOOR {EQN 4.3-8} 79.498 ATRIB. (ft) WWALL (psf) DL (psf) 0.7*0.2* SDS ∑MOT (#-ft) ∑MR (#-ft)LOCATION POSITION 24 LEFT END RIGHT END Full Height Wall Segment, Li (ft) Openings Adjusted Segment, bi (ft) WOOD/ CONC TDESIGN (#)HOLDOWN STEM CONCRETE WINT.WALL (#)STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)LOCATION POSITION TDESIGN (#)HOLDOWN Height (ft)Width (ft)Area, AO (ft2) T2nd FLOOR (#) WOOD/ CONC PERFORATED SHEAR WALL RESULTS CO WALL TYPE vMAX (plf) VALLOW (#) V (#) DESIGN CHECK FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L26 OF BY LATERAL LOAD ANALYSIS: SEGMENTED SHEAR WALLS SDPWS 4.3.5.1 V ==2342 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 3 24 14.67 9.00 2x6 1.4E+06 2347 1.000 160 232 20.00 7.00 10.00 0.14 25205 28300 2 3 4 5 6 2347 1 800 81 800 81 2 3 4 5 6 V ==1522 # WALL n Wall Type Studs (in o.c.) 2 SIDED Ln (ft) hn (ft) Wall Width Chord En (psi) D (in) Vdesign (#)CWSP vdesign (plf) vallow (plf) ATRIB. (ft) WWALL (psf) DL (psf) 0.7* 0.2*SDS ∑MOT (#-ft) ∑MR (#-ft) 1 5 24 4.33 9.08 2x6 1.4E+06 1525 0.988 352 430 2.00 10.00 15.00 0.14 14011 1134 2 3 4 5 6 1525 1 CONC EXT MIDWALL 6 CRKD 800 2596 F CONC EXT CORNER 6 CRKD 800 2596 F 2 3 4 5 6 LA 2 VTOTAL (#) = CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC 0.136 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM LEFT END RIGHT END WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN WOOD/ CONC 3 TDESIGN (#)HOLDOWNLOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#)CONCRETE VTOTAL (#) = 0.454 WALL n WOOD/ CONC LOCATION OR NAME POSITION STEM WOOD/ CONC LEFT END RIGHT END CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN LOCATION OR NAME POSITION STEM CONCRETE WINT.WALL (#) T2nd FLOOR (#) TDESIGN (#)HOLDOWN FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOOR 3rd FLOOR BASEMENT BASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm SHEET L27 OF BY LATERAL LOAD ANALYSIS: APA PORTAL FRAME PER TT-100H V ==697 # 698 # 1.000 9.000 10.000 D =0.457 in CLIENT:LGI HOMES PROJECT:PLAN 1623- SEISMIC LA 3 1 VALLOW = Specific Gravity SG Reduction 0.430 0.93 Beam Height (ft) = Number of Piers Door Height (ft) = Pier Height (ft) = Left Pier (ft) 1.500 APA PORTAL FRAME PER TT-100H FRONT-BACK SIDE-SIDE 1st FLOOR 2nd FLOOR 3rd FLOORBASEMENT Printed by larissa.anaya on 02/07/2025 at 10:28 \\vmwashington\washington\LGI Homes\Seattle\Shelm Meadows\30 Wide Series\Plan 1623\00 - Engineering\Structural Calculations\PLAN 1623- ASCE7-16 Seismic Lateral Book 2021 IRC1.xlsm