PSE FINAL 105107600 WILLOW GLEN IVN
Vicinity Map
46.9445, -122.5849
Owner / Developer Contact Info
officeATTN:
CENTURY COMMUNITIES OF WASHINGTON LLC
20000 NORTH CREEK PKWY. SUITE 201
BOTHELL, WA 98011
STEVE GOINS 253.514.2836
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
GAS
PHONE
CABLE TV
515976068 105107600
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Perm. Service
Relocation
Removal
Temporary
Job Order
Distribution
Service Stubs
HP Svc/MSA
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL TRENCHING, PER THE TRENCH
PROFILE, AND ALL EXCAVATIONS AT THE TRANSFORMER/HANDHOLE VAULT SITES
SUCH THAT PSE FACILITIES WILL MATCH FINAL GRADE. VAULT HOLES WILL HAVE
STABLE LEVEL BOTTOMS. CUSTOMER WILL PROVIDE 6" OF CRUSHED ROCK FOR
VAULT BEDDING. ALL TRENCHES WILL HAVE 6" OF WASHED SAND COVER AND 4"
BEDDING FOR ALL CONDUITS. THE CUSTOMER WILL PROVIDE SELECT BACKFILL, IF
REQUIRED, AND COMPACTION AS NECESSARY. THE CUSTOMER IS RESPONSIBLE FOR
DISPOSAL OF ALL NATIVE SPOILS NOT SUITABLE FOR USE AS BACKFILL. ALL
TRENCHES MAY BE JOINT WITH GAS, TELEPHONE AND TV CABLE.
ALL CABLES/CONDUITS TO BE INSTALLED IN CUSTOMER'S TRENCH AT THE DEPTH
INDICATED IN TRENCH DETAIL (DEPENDENT UPON SIZE OF CONDUIT BEING INSTALLED
TO MEET MIN 36" OF COVER). INSTALL CABLE ID TAGS AT EACH END OF THE PRIMARY
CABLES PER THE CIRCUIT ONE-LINE DIAGRAM.
UNLESS OTHERWISE SPECIFIED BY MUNICIPALITIES, INSTALL PVC (DB-120) ROAD
CROSSINGS AS INDICATED ON THE CROSSINGS CONDUIT TABLE & AS SHOWN ON
WORK SKETCH. CROSSINGS SHALL BE INSTALLED BY CUSTOMER/DEVELOPER PER
PUGET SOUND ENERGY STANDARDS.
AT SYMBOL: INSTALL UNDERGROUND PRIMARY CABLES IN
CONDUIT. CABLE LENGTH AND CONDUIT SIZE AS INDICATED ON PRIMARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL 600 VOLT UG SECONDARY CABLES IN
CONDUIT. CABLE/CONDUIT SIZE AND LENGTH AS INDICATED ON SECONDARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL MINI-PAD HANDHOLE & PADMOUNT TRANSFORMER.
ADDITIONAL EQUIPMENT AS INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY PEDESTAL/HANDHOLE W/ (3)
MULTI-CONNECTORS. SIZE AS INDICATED ON SECONDARY HH/PEDESTAL TABLE.
(EXCAVATION: 3' SQ.)
AT SYMBOL: INSTALL JUNCTION BOX HANDHOLE. ADDITIONAL EQUIPMENT AS
INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY CABLE & CONDUIT STUB-OUT.
AT SYMBOL: INSTALL STREET LIGHTING STANDARD. SIZE AND TYPE OF
STANDARD/LUMINARIE AS INDICATED ON STREET LIGHTING TABLE. (CUSTOMER TO
EXCAVATE & INSTALL CORRUGATED STREET LIGHT TUBES FOR PLACEMENT OF THE
STREET LIGHT STANDARDS. )
INCLEMENT WEATHER CONDITIONS MAY CAUSE DELAYS IN CONSTRUCTION TIMES
AND DATES.
POWER GENERAL NOTES - PLAT PROJECT
10
5
1
0
7
6
0
0
N/
A
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. CALLAHAN 206.503.1520 .
A. DUNN .05.22.25
...
A. DUNN .05.22.25
REDT # ( RW-138620 )YELM
WILLOW GLENN IV
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
9819 GROVE RD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105107600
N/A 1 OF 5
THURSTON N/A N/A QSTHLE
20SE-T17N-R02E N/A N/A
1702E080 1702E116 1702E079 YEL-27
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
11.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:JESSICA CALLAHAN
206.503.1520
JESSICA.CALLAHAN@PSE.COM
x
x
x
Standoff Bracket
15" Min Length
Conduit Clamp
Conduit Field Face
Quadrant
Climbing
SpaceRoad Face
Quadrant
Climbing
Space
5" Min
CL
LC
Direction of Vehicular Traffic
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
NOT TO SCALE
...
...
...
x
STEVE.GOINS@CENTURYCOMMUNITIES.COM
TYPICAL NOTCH-OUT FOR TRANSFORMER,
NOT TO SCALE
& SECONDARY PEDESTAL/HANDHOLE
BACK OF EASEMENT
STANDARD
EASEMENT
LINE
ROW
10'
PL
1'
4' - 5'
Min.
1'
7'7'
TRANSFORMER
(WHEN PRESENT)
42"
45°42"
1'
45°
Pr
o
p
e
r
t
y
L
i
n
e
Road Side
Top View of Mainline Trench for
Single Stubout Location
4'
Pr
o
p
e
r
t
y
L
i
n
e
Road Side
Top View of Mainline Trench for Pedestal
or Double Stubout Location
42"45°
4'
45°
STUBOUT EXCAVATION DIMENSIONS
NOT TO SCALE
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
OIL-FILLED EQUIPMENT
TRANSFORMER
APPROVED
AREA
CO
M
B
U
S
T
I
B
L
E
B
U
I
L
D
I
N
G
W
A
L
L
S
&
R
O
O
F
10'
10'
10'
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
3' MIN
@H1A, H2A, H2B, H3A, H3B, H4A, H6A, H9A
& H10A
SHALL BE STAGGERED
CONNECTOR BARS
IN THE FRONT
NEUTRALS SHALL BE 18"
16"
13"
12"10"
2"
10"
Pedestal will accept up to six 3" conduits
SEALED WITH FOAM
CONDUIT SHALL BE
120 PVC CONDUIT ELBOWS
TYPICAL 24" RADIUS DB
SIDE VIEW WITH CONDUIT
10"
18"
16"
13"
10"
2"
36"
FRONT VIEW WITH CONDUIT
SECONDARY PEDESTAL DETAIL
NOT TO SCALE
JOINT TRENCH DETAIL
NOT TO SCALE
ROAD SIDE
MINIPAD
MINIPAD
FIELD SIDE
VAULT
6" of crushed rock
(base for vault)
P/L
Power
Secondary
Power
Primary
Communications
42" Min
21"1'
Feeder
38"
2"
4" Sand Bedding
12" Sand
Cover
36"
Cover
4" Sand Bedding
42"
6" Additional depth when
Feeder is required
PSE 10' FRONTAGE EASEMENT
1'
TRANSFORMER
Final
Backfill
Initial
Backfill
Trench Depth
42" - 48"
ROAD SIDE
NATIVE
SECONDARY POWER
PEDESTAL
MATERIAL
P/L
Power
Secondary
Power
Primary
Conduit
Tel. & TV
Sand
6" or 12"
4" Sand Bedding
1'
36"
Cover
42"
12"
18"
Lower 2"
10"
Pedestal
PSE 10' FRONTAGE
EASEMENT
1'
Cover
JOINT TRENCH DETAIL
NOTES:
1. If the final backfill contains rocks greater than 8 inches in diameter , install 12 inches compacted sand shading across the full width of the trench. *
If the final backfill contains rocks 8 inches in diameter or smaller , install 6 inches compacted sand shading across the full width of the trench. *
2. Rocks greater than 10 inches diameter are not permitted in the final backfill.
3. Sand bedding is required under PSE gas pipe. Bedding is not required for the full width of the trench; it shall extend from the
side of the trench nearest to where the gas main/service is installed to a minimum OF 5 inches on the opposite side of the gas line.
4. Utilities shall not be stacked over the gas line in the trench.
5. If wet utilities will be included in the trench, please contact PSE or local power company directly for clearance requirements.
6. Reduced clearance of 4 inches between power and communication, must have approval of the communications companies.
* Alternatives to full-width trench shading require PSE approval.
Primary & Secondary & Communications (NTS)
Primary
Dirt Pile
Final Grade
24" Min
36"
Min Cover
Over Power
48"
Max
Depth
Final Backfill
4" Sand Bedding
Property Line
intercept (depth varies).
SidewalkCurb
Location of roof drain
48" Typical
Width may vary per
Number of Utilities
and Conduits
R/W or
Excavated
12" Typical
Power
Secondary
Power
TV & TEL
12" Min
4,5
1,2
3
6
6" or 12" Min Sand Shading
Over Power after Compaction1
GREENLEAF AVE SE GR
O
V
E
R
D
S
E
VAULT DETAIL @ V01-V10
NOT TO SCALE
EXCAVATION: _____ CUBIC YARDS
3'-6"
SIDE VIEW
2"
6"
CRUSHED
ROCK
TOP VIEW
7'
7'
6 1/3
CLEAR WORKING SPACE FOR VAULTS
NOT TO SCALE
FIELD SIDE (PREFERRED)
ROAD SIDE (PREFERRED)
6' MIN
3'
MIN
3'
MIN
3' MIN
SITE
LOT 1
LOT 2
LOT 3
LOT 4
LOT 5
LOT 6 LOT 7 LOT 8
LOT 9 LOT 10
LOT 11
LOT 12 LOT 13
LOT 14 LOT 15
LOT 16 LOT 17 LOT 18 LOT 19
LOT 20 LOT 21 LOT 22 LOT 23
LOT 24
LOT 25
LOT 26
LOT 27
LOT 28
LOT 29LOT 30LOT 31LOT 32
LOT 33LOT 34LOT 35LOT 36
LOT 37LOT 38
LOT 39LOT 40
LOT 41LOT 42LOT 43LOT 44
LOT 45LOT 46
LOT 47LOT 48LOT 49
LOT 50 LOT 51 LOT 52 LOT 53 LOT 54 LOT 55 LOT 56 LOT 57 LOT 58 LOT 59 LOT 60 LOT 61 LOT 62
LOT 63LOT 64LOT 65LOT 66LOT 67LOT 68LOT 69LOT 70LOT 71LOT 72LOT 73LOT 74LOT 75
#4 ACSR
39
7
.
5
A
A
C
39
7
.
5
A
A
C
39
7
.
5
A
A
C
YEL
27
FE
E
D
FUSE @ 100T
SW#T95640
ROAD A
ROAD B
RO
A
D
C
EX: 1-2"
FUT: 1-2"
IRR
(1) 1/0
GR
O
V
E
R
D
S
E
GR
E
E
N
L
E
A
F
L
O
O
P
S
E
CBA
CBA
C
CBA
DEVELOPER RESPONSIBLE
FOR CONDUIT/WIRE FROM
VAULT TO METER LOCATION
(TYPICAL)
56'
56'
56
'
56'
58'
RO
A
D
B
RO
A
D
B
BO
U
R
B
O
N
S
T
S
E
'A'
'B'
ST.LTS
(1) 10GA
1" = 50'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. CALLAHAN 206.503.1520 .
A. DUNN .05.22.25
...
A. DUNN .05.22.25
REDT # ( RW-138620 )YELM
WILLOW GLENN IV
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
9819 GROVE RD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105107600
1" = 50'2 OF 5
THURSTON N/A N/A QSTHLE
20SE-T17N-R02E N/A N/A
1702E080 1702E116 1702E079 YEL-27
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
SITE PLAN
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
YEL-27
12.04.24
377 332 299
38 48 43
415 380 342
...
...
...
SCHED.SQ. FT.
MAX LRC =
CIRCUIT FEET ADDED: 3720'
17 2448
80 AMPS
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
J-BOX CABLE ENTRY DETAIL
NOT TO SCALE 12kV CABLE ROUTING
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
Oil-Filled Equipment Clearances per PSE Std 0700.1500
If the oil-filled equipment is adjacent to… Clearance
Requirement
Combustible walls or roof (including stucco).10 FT
Noncombustible walls, soffits, and roofs (including brick, concrete,
steel and stone) providing the side of the transformer facing the wall
does not have doors. Materials that pass UBC Std. 2-1 or ASTM
E136-79 are considered to be noncombustible.
3 FT
Fire sprinkler valves, standpipes, and fire hydrants.6 FT
Doors, windows, vents, fire escapes, or other building openings.10 FT
The water's edge of a swimming pool or any body of water.15 FT
Individual domestic and irrigation wells. Clearance not required on
pole mounted transformers (pole placement still applies as stated in
6450.3000), TUT's installed in sealed vaults, 7200V single-phase
padmount transformers 50kva or less, and ones with reduced
flammability oil.
100 FT
Facilities used to dispense or store LP, hazardous liquids, or fuel.20 FT
Gas service meter relief vent.3 FT
Generators, customer-owned transformers, etc.6 FT
10' CLEARANCE REQUIRED TO
TRANSFORMER OR NON-FLAMMABLE
BUILDING MATERIALS REQUIRED
TRANSFORMERS HAVE BEEN SIZED FOR
EXTRA 7KW DEMAND PER LOT FOR EV
Developer Note:
The following Fault Current information MUST BE conveyed
to the builder of the units:
All units may require upgraded house electrical equipment as the
fault current at the meter base may exceed 10,000 amps.
FAULT CURRENT TABLE
1Ø PM TRANSFORMERS (240/120V)
120V WINDINGS 240V WINDINGS
LOCATION SIZE R/X MIN.
%Z
FAULT
CURRENT
MIN.
%Z
FAULT
CURRENT
V01-V04,
V06,V09-V10 100kVA 0.5 2.43 57,300 AMPS 1.90 36,600 AMPS
V05,V07-V08 75kVA 0.5 2.30 36,200 AMPS 1.80 23,100 AMPS
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #STREET LIGHTS
N/A
N/A
100A
N/A
1KW
80A
3.4 @ H2B
1.1 @ H2B
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #IRRIGATION
N/A
N/A
100A
N/A
1KW
80A
3.1 @ H6A
1.6 @ H6A
CUSTOMER OWNED AND INSTALLED SECONDARY WIRE TABLE
BLDG.# OF
METERS SOURCE # OF RUNS WIRE SIZE REMARKS
-1 V02 100 (1) 1/0 STREET LIGHTS
-1 V06 100 (1) 10GA IRRIGATION
ALL CUSTOMER-OWNED WIRE MUST BE INSTALLED ACCORDING TO THIS TABLE
CROSSING CONDUIT TABLE
X-ING
#
LOCATION POWER
XING
LENGTH
ASBUILT
LOCATION
TYPE OF CROSSING
(Feeder, Primary, Secondary, etc.)FROM TO
SIZE
(IN)TYPE QTY
X01 'A'LOT 29 4 DB120 1 170 ( )' ECL PRIMARY
X02 LOT 33 LOT 62 3 DB120 1 65 ( )' WCL SECONDARY
X03 LOT 35 LOT 60 3 DB120 2 65 ( )' ECL SECONDARY
X04 'B'LOT 57 3 DB120 2 65 ( )' ECL SECONDARY
X05 LOT 37 LOT 56 3 DB120 2 65 ( )' WCL SECONDARY
X06 LOT 39 LOT 54 3 DB120 1 65 ( )' WCL SECONDARY
X07 LOT 41 LOT 51 3 DB120 1 65 ( )' WCL SECONDARY
X08 LOT 43 LOT 50 3 DB120 1 65 ( )' ECL SECONDARY
X09 LOT 48 LOT 1
4 DB120 1 65 ( )' WCL PRIMARY
2 DB120 1 65 ( )' WCL PRIMARY
X10 LOT 11 LOT 74 3 DB120 1 65 ( )' WCL SECONDARY
X11 LOT 11 LOT 12 2 DB120 1 65 ( )' NCL PRIMARY
X12 LOT 12 LOT 73 3 DB120 2 65 ( )' ECL SECONDARY
X13 LOT 14 LOT 70 3 DB120 2 65 ( )' ECL SECONDARY
X14 LOT 16 LOT 69 3 DB120 2 65 ( )' WCL SECONDARY
X15 LOT 18 LOT 67 3 DB120 2 65 ( )' WCL SECONDARY
X16 LOT 20 LOT 64 3 DB120 2 65 ( )' WCL SECONDARY
X17 LOT 21 LOT 63 3 DB120 1 65 ( )' WCL SECONDARY
X18 LOT 36 LOT 37
4 DB120 1 65 ( )' SCL PRIMARY
2 DB120 2 65 ( )' SCL PRIMARY
3 DB120 1 65 ( )' SCL SECONDARY
2" DB120 GREY PVC = 260 FT 2" PVC PLUG /CAPS = 8
3" DB120 GREY PVC = 1495 FT 3" PVC PLUG /CAPS = 46
4" DB120 GREY PVC = 300 FT 4" PVC PLUG /CAPS = 6
DEDICATED FACILITIES (105107600) for Dedicated Stub Locations
SITE SPAN ADDITIONAL REMARKS LABOR UNITS
#FROM TO FOOTAGE
-V05 LOT 2 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V05 LOT 4 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V08 LOT 15 50 DED. CONDUIT & WIRE 2-36, 2-54A
-V10 LOT 25 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V02 LOT 30 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V02 LOT 32 45 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 39 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 40 35 DED. CONDUIT & WIRE 2-36, 2-54A
-H4A LOT 43 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V04 LOT 45 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V04 LOT 46 30 DED. CONDUIT & WIRE 2-36, 2-54A
-H4B LOT 48 40 DED. CONDUIT & WIRE 2-36, 2-54A
-V01 LOT 58 55 DED. CONDUIT & WIRE 2-36, 2-54A
-V01 LOT 59 40 DED. CONDUIT & WIRE 2-36, 2-54A
-V09 LOT 65 45 DED. CONDUIT & WIRE 2-36, 2-54A
-V09 LOT 66 40 DED. CONDUIT & WIRE 2-36, 2-54A
-V08 LOT 68 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V07 LOT 71 80 DED. CONDUIT & WIRE 2-36, 2-54A
TOTAL FT=725
SITE SPECIFIC NOTES
AT P01 (559450-147961) 2013 CLASS 2 - 45'
-INSTALL 3Ø TERM ON NEW FIBERGLASS ARM W/ LOAD INTERRUPTER C/O & SURGE
ARRESTOR (TSU3L1F) 6043.1000
-(3) STIRRUPS (2254100)
-ALUM "H" CONNECTOR (2167700)
-(3) FUSE @ 100T (3412700); TAP 3Ø
-INSTALL SWITCH# T95640
-INSTALL 4" PRIMARY RISER ON NEW STANDOFF BRACKETS (RIS4CSS) 6042.1000
POLE 559433-147945 AND ALL RELATED
FACILITIES TO BE REMOVED ON WILLOW
GLEN IV WRECKOUT, WO#105107600
#4 ACSR
39
7
A
A
C
39
7
A
A
C
YEL
27
FE
E
D
FUSE @ 100T
SW#T95640
CBA
C
CBA
39
7
A
A
C
CBA
NEW 3Ø 1/O AL
EKG206-AØ
EKG207-BØ
EKG208-CØ
NEW 1/O AL
EKG204-CØ
NEW 3Ø 1/O AL
EKG200-AØ
EKG201-BØ
EKG202-CØ
EKG203-CØ
NEW 1/O AL
EKG205-CØ
NEW 1/O ALEKG209-AØ
NEW 1/O AL
EKG210-AØ
NEW 1/O AL
NEW 3Ø 1/O AL
EKG211AØ
EKG212-BØ
EKG213-CØ
EKG214-AØ
NEW 1/O AL
EKG215-BØ
NEW 1/O AL
EKG216-BØ
NEW 1/O AL
EKG217-BØ
NEW 1/O AL
EKG218-BØ
NEW 1/O AL
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. CALLAHAN 206.503.1520 .
A. DUNN .05.22.25
...
A. DUNN .05.22.25
REDT # ( RW-138620 )YELM
WILLOW GLENN IV
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
9819 GROVE RD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105107600
AS SHOWN 3 OF 5
THURSTON N/A N/A QSTHLE
20SE-T17N-R02E N/A N/A
1702E080 1702E116 1702E079 YEL-27
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
...
...
...
NOT TO SCALE
NEW PRIMARY UNDERGROUND CIRCUIT ONE-LINE DIAGRAM
EX UNDERGROUND CIRCUIT MAP 1702E079
NOT TO SCALE
SITE
EX OVERHEAD CIRCUIT MAP 1702E116
SCALE: 6" = 1 MILE
SITE
IRR
ST.LTS
DEVELOPER RESPONSIBLE
FOR CONDUIT/WIRE FROM
VAULT TO METER LOCATION
(TYPICAL)
LOT 1
LOT 2
LOT 3
LOT 4
LOT 5
LOT 6
LOT 7
LOT 8 LOT 9 LOT 10 LOT 11 LOT 12 LOT 13 LOT 14 LOT 15 LOT 16 LOT 17 LOT 18 LOT 19 LOT 20 LOT 21
LOT 22
LOT 23
LOT 24
LOT 25
LOT 26
LOT 27
LOT 28
LOT 29LOT 30LOT 31LOT 32LOT 33LOT 34LOT 35LOT 36LOT 37LOT 38LOT 39LOT 40LOT 41LOT 42LOT 43LOT 44LOT 45LOT 46LOT 47LOT 48LOT 49
LOT 50 LOT 51 LOT 52
LOT 53 LOT 54 LOT 55 LOT 56 LOT 57 LOT 58 LOT 59 LOT 60 LOT 61 LOT 62
LOT 63LOT 64LOT 65LOT 66LOT 67LOT 68LOT 69LOT 70LOT 71LOT 72LOT 73LOT 74LOT 75
FUT: 1-2"
EX: 1-2"
1 (1/0)
(1) 10 GA
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. CALLAHAN 206.503.1520 .
A. DUNN .05.22.25
...
A. DUNN .05.22.25
REDT # ( RW-138620 )YELM
WILLOW GLENN IV
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
9819 GROVE RD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105107600
N/A 4 OF 5
THURSTON N/A N/A QSTHLE
20SE-T17N-R02E N/A N/A
1702E080 1702E116 1702E079 YEL-27
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
NOT TO SCALE
NEW CONDUIT DIAGRAM
SECONDARY HH/PEDESTAL TABLE
Site
Pedestal
or
Handhole
Number of
Positions
Required
Remarks
H1A PEDESTAL 4 - SEPS4 6050.1000
H2A PEDESTAL 4 - SEPS4 6050.1000
H2B PEDESTAL 4 - SEPS4 6050.1000
H3A PEDESTAL 3 - SEPS3 6050.1000
H3B PEDESTAL 3 - SEPS3 6050.1000
H4A PEDESTAL 4 - SEPS4 6050.1000
H4B PEDESTAL 3 - SEPS3 6050.1000
H6A PEDESTAL 4 - SEPS4 6050.1000
H9A PEDESTAL 4 - SEPS4 6050.1000
H10A PEDESTAL 3 - SEPS3 6050.1000
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
CUST. OWNED
PRIMARY 4"
PRIMARY 2"
CONDUIT LEGEND
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT CABLE ASBUILT INFORMATION - FOREMAN COMPLETE
FROM TO SIZE
(IN)QTY.
DESIGN
LENGTH
(FT)
BENDS PULL
(LBS)
PULL
REV
(LBS)
CABLE SIZE
DESIGN
LENGTH
(FT)
PHASE - ID TAG RECORD RECORD PHASE TAPPED & ACTUAL FOOTAGE INSTALLED LUBRICANT (Gal.)
90°45°22°11°A B C MANUFACTURER COMPOUND YEAR NOTES CONDUIT CABLE EST.ACTUAL
P01 J01 4 1 430 1 ---387 940 3Ø 1/0 AL JKT 705 EKG200 EKG201 EKG202 4.9
J01 V01 2 1 55 ----70 59 1/0 AL JKT 130 --EKG203 0.5
V01 V02 2 1 100 ----78 78 1/0 AL JKT 110 --EKG204 0.4
J01 V03 2 1 170 ----79 65 1/0 AL JKT 180 --EKG205 0.7
J01 E01 2 1 85 ----CONDUIT ONLY ----
J01 J02 4 1 690 ----426 426 3Ø 1/0 AL JKT 700 EKG206 EKG207 EKG208 4.9
J02 V04 2 1 210 ----86 71 1/0 AL JKT 220 EKG209 --0.9
J02 V05 2 1 210 1 ---131 111 1/0 AL JKT 285 EKG210 --1.1
J02 J03 4 1 555 1 -4 -629 701 3Ø 1/0 AL JKT 630 EKG211 EKG212 EKG213 4.4
J03 V06 2 1 100 ----64 55 1/0 AL JKT 110 EKG214 --0.4
J03 V07 2 1 55 ----67 57 1/0 AL JKT 130 -EKG215 -0.5
V07 V08 2 1 215 ----105 105 1/0 AL JKT 225 -EKG216 -0.9
V08 V09 2 1 110 ----84 84 1/0 AL JKT 120 -EKG217 -0.5
V09 V10 2 1 325 --3 -314 282 1/0 AL JKT 335 -EKG218 -1.3
J03 E02 2 1 85 ----CONDUIT ONLY ----
2" PVC (FT) & BENDS =1720 1 0 3 0 1/0 AL JKT TOTAL (FT) =1845 TTL (Gal.)21.4
4" PVC (FT) & BENDS =1675 2 0 4 0 3Ø1/0 AL JKT TOTAL (FT) =2035
VAULT & EQUIPMENT TABLE
SITE #GRID #
VAULT SIZE &
COVER
TYPE & SIZE
EQUIPMENT IN
VAULT
PRIMARY
BUSHINGS TRANSFORMER ID NUMBERS
(COMPANY ID)
AS-BUILT INFORMATION
LB DC FOREMAN: INCLUDE PHASE TAPPED
V01 559444
147923
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
2 -
MINU1LL 6045.1010 CØ
V02 559444
147933
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
1 1
MINU1LR 6045.1010 CØ
V03 559445
147895
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
1 1
MINU1LR 6045.1010 CØ
V04 559445
147864
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
1 1
MINU1LR 6045.1010 AØ
V05 559463
147853
54"x54"x38"
Unistrut HH
Matid: 7663002
75KVA MP TRF
120/240
Matid: 6247150
1 1
MINU1LR 6045.1010 AØ
V06 559475
147871
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
1 1
MINU1LR 6045.1010 AØ
V07 559474
147893
54"x54"x38"
Unistrut HH
Matid: 7663002
75KVA MP TRF
120/240
Matid: 6247150
2 -
MINU1LL 6045.1010 BØ
V08 559474
147914
54"x54"x38"
Unistrut HH
Matid: 7663002
75KVA MP TRF
120/240
Matid: 6247150
2 -
MINU1LL 6045.1010 BØ
V09 559474
147925
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
2 -
MINU1LL 6045.1010 BØ
V10 559460
147950
54"x54"x38"
Unistrut HH
Matid: 7663002
100KVA MP TRF
120/240
Matid: 6247200
1 1
MINU1LR 6045.1010 BØ
J01 556444
147912
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
8 4
JBOX15L 6055.1030
3Ø CAP (7630600)
ELB10J 6041.1000
TAP 3Ø
J02 559446
147843
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
8 4
JBOX15L 6055.1030
3Ø CAP (7630600)
ELB10J 6041.1000
TAP 3Ø
J03 559475
147881
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
5 7
JBOX15L 6055.1030
3Ø CAP (7630600)
ELB10J 6041.1000
TAP 3Ø
SECONDARY 3"
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
J. CALLAHAN 206.503.1520 .
A. DUNN .05.22.25
...
A. DUNN .05.22.25
REDT # ( RW-138620 )YELM
WILLOW GLENN IV
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
9819 GROVE RD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105107600
N/A 5 OF 5
THURSTON N/A N/A QSTHLE
20SE-T17N-R02E N/A N/A
1702E080 1702E116 1702E079 YEL-27
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SECONDARY CABLE & CONDUIT TABLE
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER Foreman - Complete
FROM TO (1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in)Design (ft)90°45°22°11°(Percent)(Percent)Actual Amount Installed Cable Conduit
V01 H1A 350 185 3 120 2 3.6 1.5 -
V01 LOT 35 4/O 10 60 3 10 1 3.0 1.5 -
V01 LOT 36 4/O 10 60 3 10 1 3.0 1.5 -
V01 LOT 57 350 145 60 3 80 2 3.5 2.4 -
V01 LOT 58 4/O 150 60 3 85 3 3.9 3.0 -
V01 LOT 59 4/O 130 60 3 65 3 3.8 2.8 -
V01 LOT 60 4/O 125 60 3 60 2 3.8 2.7 -
H1A LOT 37 4/O 60 3 4.3 2.7 -
H1A LOT 55 4/O 100 60 3 35 3 4.6 3.2 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H1A LOT 56 4/O 95 60 3 30 2 4.6 3.2 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V02 H2A 350 210 3 210 2 3.6 1.7 -
V02 H2B 350 120 3 55 3 3.4 1.1 -
V02 LOT 32 4/O 105 60 3 105 1 3.4 2.5 -
V02 LOT 33 4/O 10 60 3 10 1 2.8 1.5 -
V02 LOT 34 4/O 10 60 3 10 1 2.8 1.5 -
H2A LOT 29 4/O 60 3 4.3 2.9 -
H2A LOT 30 4/O 40 60 3 40 1 4.6 3.3 -
H2A LOT 31 4/O 70 60 3 70 1 4.8 3.6 -
H2B LOT 61 4/O 60 3 3.5 2.3 -
H2B LOT 62 4/O 60 3 3.5 2.3 -
V03 H3A 350 160 3 160 3 2.9 1.4 -
V03 H3B 350 105 3 105 3 2.6 1.0 -
V03 LOT 38 4/O 70 60 3 70 1 3.2 2.2 -
V03 LOT 39 4/O 45 60 3 45 1 3.0 1.9 -
V03 LOT 40 4/O 45 60 3 45 1 3.0 1.9 -
V03 LOT 41 4/O 70 60 3 70 1 3.2 2.2 -
H3A LOT 51 4/O 60 3 3.7 2.6 -
H3A LOT 52 4/O 60 3 3.7 2.6 -
H3B LOT 53 4/O 60 3 3.4 2.2 -
H3B LOT 54 4/O 60 3 3.4 2.2 -
V04 H4A 350 115 3 115 2 3.0 1.0 -
V04 H4B 350 115 3 115 2 2.8 1.0 -
V04 LOT 44 4/O 70 60 3 70 1 3.4 2.2 -
V04 LOT 45 4/O 45 60 3 45 1 3.2 1.9 -
V04 LOT 46 4/O 40 60 3 40 1 3.2 1.9 -
V04 LOT 47 4/O 75 60 3 75 1 3.4 2.2 -
H4A LOT 42 4/O 70 60 3 70 1 4.3 3.0 -
H4A LOT 43 4/O 50 60 3 45 1 4.1 28 -
H4A LOT 50 4/O 115 60 3 50 2 4.5 3.4 -
H4B LOT 48 4/O 45 60 3 45 1 3.9 2.7 -
H4B LOT 49 4/O 70 60 3 70 1 4.1 3.0 -
V05 LOT 1 4/O 70 60 3 70 1 3.3 2.3 -
V05 LOT 2 4/O 45 60 3 45 1 3.1 2.0 -
V05 LOT 3 4/O 10 60 3 10 1 2.9 1.6 -
V05 LOT 4 4/O 70 110 3 70 1 1 3.9 3.3 -
V05 LOT 5 4/O 75 110 3 75 1 2 4.0 3.3 -
V05 LOT 6 4/O 105 110 3 105 1 4.1 3.6 -
V06 H6A 4/O 180 3 115 3 3.1 1.6 -
V06 LOT 7 4/O 90 60 3 90 1 3.1 2.4 -
V06 LOT 8 4/O 65 60 3 65 1 3.0 2.1 -
V06 LOT 9 4/O 10 60 3 10 1 2.6 1.5 -
V06 LOT 10 4/O 10 60 3 10 1 2.6 1.5 -
V06 LOT 11 4/O 65 60 3 65 1 3.0 2.1 -
H6A LOT 74 4/O 60 3 4.3 3.3 -
H6A LOT 75 4/O 60 3 4.3 3.3 -
V07 LOT 12 4/O 10 60 3 10 1 2.9 1.6 -
V07 LOT 13 4/O 10 60 3 10 1 2.9 1.6 -
V07 LOT 70 4/O 165 60 3 100 2 3.9 3.3 -
V07 LOT 71 4/O 170 60 3 105 3 3.9 3.3 -
V07 LOT 72 4/O 105 60 3 40 3 3.5 2.6 -
V07 LOT 73 4/O 100 60 3 35 2 3.5 2.6 -
V08 LOT 14 4/O 115 60 3 115 1 3.6 2.7 -
V08 LOT 15 4/O 110 60 3 110 1 3.5 2.7 -
V08 LOT 16 4/O 10 60 3 10 1 2.9 1.6 -
V08 LOT 17 4/O 10 60 3 10 1 2.9 1.6 -
V08 LOT 68 4/O 120 60 3 55 3 3.6 2.8 -
V08 LOT 69 4/O 115 60 3 50 2 3.6 2.7 -
SECONDARY CABLE & CONDUIT TABLE (Cont.)
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER Foreman - Complete
FROM TO (1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in)Design (ft)90°45°22°11°(Percent)(Percent)Actual Amount Installed Cable Conduit
V09 H9A 350 120 3 120 2 3.1 1.1 -
V09 LOT 18 4/O 10 60 3 10 1 3.0 1.5 -
V09 LOT 19 4/O 10 60 3 10 1 3.0 1.5 -
V09 LOT 64 4/O 140 60 3 75 2 3.8 2.9 -
V09 LOT 65 4/O 145 60 3 80 3 3.9 3.0 -
V09 LOT 66 4/O 130 60 3 65 3 3.8 2.8 -
V09 LOT 67 4/O 125 60 3 60 2 3.8 2.7 -
H9A LOT 20 4/O 60 3 3.8 2.3 -
H9A LOT 21 4/O 60 3 3.8 2.3 -
H9A LOT 63 4/O 90 60 3 25 2 4.4 3.2 -
V10 H10A 350 140 3 140 2 3 2.6 1.2 -
V10 LOT 24 4/O 80 110 3 80 1 2 3.7 3.3 -
V10 LOT 25 4/O 75 60 3 75 1 2 3.0 2.2 -
V10 LOT 26 4/O 10 60 3 10 1 2.6 1.5 -
V10 LOT 27 4/O 10 110 3 10 1 3.2 2.5 -
V10 LOT 28 4/O 60 110 3 60 1 3.6 3.1 -
H10A LOT 22 4/O 60 3 3.3 2.4 -
H10A LOT 23 4/O 60 3 3.3 2.4 -
4/O UG Triplex (ft) =4200 3" PVC & BENDS (ft)=4430 111 0 10 0 12.8
350 UG Triplex (ft) =1595 TOTAL QTS OF GLUE 12.8
CONTINUED AT RIGHT