10732 Palisades St. ST Sprinkler planGarage
W D
Fur.WH
Bedroom
Bedroom
Bedroom
Living Room
Dining Room
Kitchen
Bath
Laundry
Bath
Bedroom
Bedroom Bath
Storage
26
241¼1
1¼
1¼
1¼
1¼
1¼
1¼
1
1
1
1
1
11
1
11 1
1
1 1
1
1
1
1
1
1
1
1¼
1
1
1
1
1
1
1
1
1
20123
Finished Attic
211
1
11
1
1
111
118
PUMP & TANK
46
TANK DRAN ½" (GHT)
45
RISER LEGEND
1.5 HP PUMP
1
GPM
PSI 55
6 -
10
40
2 -
2 -
48
Performance values based on multiple pump tests. Not for certification purposes.
8 -
9
6
Performance:
DISCHARGE CHECK VALVE
PUMP SPECIFICATIONS
ALL WIRING OF PUMP, SWITCHES, AND BELL TO BE BY OTHERS
11-
30
1 -
3
350 GALLON TANK
WATER PRESSURE SWITCH
3 -
50
OVERFLOW FITTING 1" (FNPT)
12
7
2
43
4 -
RISER NOTES8
3/4" FILL LINE TO BE PROVIDED BY OTHERS
1.5 HP ELECTRIC MOTOR
SYSTEM DRAIN / TEST LINE
3 -
35
10.9 AMP (FULL LOAD)
4
PRESSURE GAUGE
11
12-5
9 -
AUTO-FILL VALVE 3/4" (FNPT)
10-
1 -
0
40
3 -2 -
1¼" BALL VALVE
50
5 -
25
SUCTION SHUT-OFF VALVE
240 VOLT SINGLE PHASE
20
7 -
51
FLOW SWITCH
52
Hydraulic Information
Remote Area 1
OCCUPANCY CLASSIFICATION Residential
DENSITY (gpm/ft²)0.05 for 900ft² (Actual 320ft²)
TOTAL HOSE STREAMS 100.00
DRY CAPACITY 0.00gal
TOTAL HEADS FLOWING 2
K-FACTOR 4.9
TOTAL WATER REQUIRED 26.40
TOTAL PRESSURE REQUIRED 21.413
BASE of RISER (gpm)26.40
BASE of RISER (psi)21.413
SAFETY MARGIN (psi)+28.492 (57.1%)
SCOPE OF WORK:
INSTALL NEW NFPA 13D FIRE SPRINKLER SYSTEM THROUGHOUT AN EXISTING RESIDENCE.
GENERAL NOTES:
1. IT IS THE RESPONSIBILITY OF THE OWNER TO MAINTAIN THE INTEGRITY OF THE
SPRINKLER SYSTEM.
2. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL AND/OR FM APPROVED.
3. ALL SYSTEM PIPING SHALL BE TESTED AT STATIC PRESSURE PER NFPA 13D.
4. PIPE HANGER AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13D (2019).
5. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN
AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM.
6. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE
RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE.
7. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS.
DESIGN NOTES:
1. RISER ASSEMBLY / PUMP AND TANK TO BE LOCATED IN THE GARAGE (ELEMENT FIRE SPRINKERS START POINT).
2. SYSTEM TO BE DESIGNED IN ACCORDANCE WITH NFPA #13D (2019) SINGLE FAMILY RESIDENCE.
3. PLAN SUBMITTAL TO AND APPROVAL BY City of Yelm.
4. MATERIALS PER NFPA #13D STANDARD.
5. TESTING PER NFPA #13D AND City of Yelm.
6. TYPICAL HANGERS TO BE TOLCO FIG. 24, 28M & 29 UNLESS NOTED OTHERWISE
FIELD NOTES:
1. ALL NEW PIPE IS TO BE CPVC.
2. ALL NEW FITTINGS ARE TO BE CPVC.
3. DESIGN CRITERIA TO BE BASED ON NFPA 13D:
A. SPRINKLER SPACING NOT TO EXCEED (16' x 16') OR (8') OFF OF WALLS MAXIMUM.
B. MINIMUM PRESSURE AND FLOW FOR SPRINKLERS SPACED 16' x 16' = 13 GPM @ 7.0 PSI.
INDICATES BATHROOM OR CLOSET MEETS THE REQUIREMENTS OF NFPA 13D
(2019) 8.3.2 or 8.3.3 AND SPRINKLER PROTECTION SHALL NOT BE REQUIRED.
TOLCO FIG. #28M
NTS
HANGER TYPE CP
TOLCO FIG. #24
NTS
HANGER TYPE CP
ATTIC INSULATION (BY OTHERS).
BOTTOM CHORD OF TRUSS
USE BATT TYPE INSULATION
GWB CEILING
(BY OTHERS). USE BATT TYPE
TENT FIRE SPRINKER PIPEBEFORE INSULATING ATTIC
WET PIPE FREEZE
CPVC FIRE SPRINKLER PIPE
FOR TENTING
INSULATION FOR TENTING.
NTS
PROTECTION DETAIL
NTS
HANGER TYPE CP
TOLCO FIG. #29
Sprinkler Legend
Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature Note
Viking VK494 Freedom 22 4.9 Pendent ½Quick Brass 155°F
Viking VK494 Freedom 1 4.9 Pendent ½Quick Brass 200°F
Total = 23
FP1
1
A
DRAWING SYMBOLS:
AHJ:
REV#BY JOB NUMBER:REVISIONS:
DATE:
REVIEWED BY:
DRAWN BY:
DESCRIPTION
SCALE:
SHEET NUMBER:
DATE
CONTRACT WITH:
- PIPE HANGER
DATUMFFCCACOUPLING
#1
L
0'-10"
(SEE CHART)
NUMBER
- ELEVATION
- PIPE SIZE
DATUM
1AC
- BRANCHLINE
CL
PIPE TAG
10'-10"
TS OF PIPE TO- CENTERLINE
A.1
9'-0
- HYDRAULIC NODE
FF
- WELDED
- RIGID GROOVED
- FLEXIBLE GROOVED
L OF PIPE TODECK
- ELEVATION
TS
L
0'-10"
DECK
COUPLING
& LENGTH CUT
- SEISMIC BRACE
- CENTERLINE
JWH
Catherine Remodel
1050
AS NOTED
08/27/25
Yelm, WA 98597 1 of 1
10732 Palisades St. SE
City of Yelm Auburn, WA 98092
: Catherine Gathara - 253-341-3362
5122 Nathan Loop SE
Catherine Gathara
110 Williams Blvd. NE
Orting, WA 98360
(253) 405-4562
VICINITY MAP
SCALE: NTS
Level 1 - SPRINKLER PIPING PLAN
SCALE: 3/16" = 1'-0"NORTHNO
R
T
H
SCALE: NTS
RISER DETAIL
Street View
SCALE: NTS
Level 2 - SPRINKLER PIPING PLANNORTHSCALE: 3/16" = 1'-0"
"OFFSET" HANGER & RESTRAINER
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
FOR CPVC AND IPS PIPE
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
CPVC DOUBLE FASTENER STRAP TYPE HANGER
"DOUBLE OFFSET" HANGER & RESTRAINER
HARDENED HEX HEAD SELF THREADING SCREWIS FURNISHED WITH THE HANGER AND IS THEMINIMUM FASTENER SIZE ACCEPTABLE
X
THIS AREA HAS BEEN HYDRAULICALLY CALCULATED
TO DELIVER A RESIDENTIAL COVERAGE (NFPA 13D)OF:
REMOTE AREA #1
13 GPM @ 7.0 PSI USING 16' x 16' HEAD SPACING
26.40 GPM @ 21.413 PSI
SYSTEM DEMAND:
08/27/2025