SPS-H4H_Yelm-1345_250526_2021-WSEC-R_Work-Sheet2021 Washington State Energy Code — Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family — New & Additions (effective March 15, 2024)
WASHINGTON STATE UNIVERSITY
Energy Program
Permit#
Address or Lot & Block
city Zip
These requirements apply to all the IRC building types, including detached one- and two-family
dwellings and multiple single-family dwellings (townhouses).
Instructions: This single-family project uses the requirements of the Prescriptive Path below to incorporate
the minimum values listed. Based on the conditioned floor area of the structure, the number of required
additional credits must be selected by the permit applicant.
Provide all information from the following tables in building permit drawings: Table R402.1.2 - Insulation and
Fenestration Requirements by Com nent Tabl 6.2 - Fuel Normalization Credits and R406.3 Energy Credits.
Authorized Representative
'
I
Date
Signal
d^,
I
All Climate Zones Table 402.1.3 and Table R402.1.2
R-Value a
U-Factor a
Fenestration U-Factor b,i
n/a
0.30
Skylight U-Factor b
n/a
0.50
Ceiling e
60
0.024
Above -Grade Wall U-Factor 9,i
20+5 or 13+10
0.056
Floor U-Factor
30
0.029
Below Grade Wall U-Factor `
10/15/21 int + 5TB
0.035
Slab d,POn Grade F-Factor
10, 4 ft
0.54
R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity which is less than the label or design
a
thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified
in the table
b
The fenestration U-factor column excludes skylights.
"10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-
21 cavity insulation plus a thermal break between the slab and the basement wall at the interior of the basement wall. "10/15/21 +5TB" shall
be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or
exterior of the wall. "5TB" means R-5 thermal break between floor slab and basement wall.
d
I R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1.
For single rafter- orioist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends over the top plate of the
e
exterior wall.
R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter slab insulation when applied
f
to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam
plastics.
g
For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for climate zone 5 of ICC 400.
h
Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard framing 16 inches on center,
78 percent of the wall cavity insulated and headers insulated with a minimum of R-10 insulation.
The first value is cavity insulation, the second value is continuous insulation. Therefore, as an example, "R13+10" means R-13 cavity
insulation plus R-10 continuous insulation
A maximum U-factor of 0.32 shall apply to vertical fenestration products installed in buildings located above 4000 feet in elevation above sea
j
level, or in windborne debris regions where protection of openings is required under Section R301.2.1.2 of the International Residential
Code.
Prescriptive Path — Single Family WSEC-R 2021 Edition (V12/12/2024)
2021 Washington State Energy Code — Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family — New & Additions (effective March 15, 2024)
Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (Energy
Equalization credits) and Table 406.3 (energy credits) to achieve the minimum number of credits from the list
below. To claim credits, the building permit drawings shall specify the option selected and the
maximum tested building air leakage, and show the qualifying ventilation system and its control sequence
of operation.
1. Small Dwelling Unit: ............................................. ............................................. 5.0 credits
Dwelling units less than 1500 square feet in conditioned floor area with less than 300 square feet of
fenestration area. Additions to existing building greater than 500 square feet of heated floor area but less
than 1500 square feet.
2. Medium Dwelling Unit: ...................................................................................... 8.0 credits
All dwelling units that are not included in #1, #3 or #4.
3. Large Dwelling Unit: .......................................................................................... 9.0 credits
Dwelling units exceeding 5000 square feet of conditioned floor area.
4. Dwelling units serving Group R-2 occupancies: ................................................ 6.5 credits
Section R401.1 and Residential Building Section R202 for Group R-2.
S. Additions 150 square feet to 500 square feet: ..................................................... 2.0 credits
The drawings included with the building permit application shall identify which options have been selected and the
point value of each option, regardless of whether separate mechanical, plumbing, electrical, or other permits are
utilized for the project
Before selecting your credits on this Summary table, review the option descriptions in Table R406.3 (Single Family).
Table R406.2 ENERGY EQUALIZATION CREDITS
_
Credits -
System Description of Primary Heating Source select ONE
Type system
type
1
For combustion heating equipment meeting minimum federal efficiency standards for the
equipment listed in Table C403.3.2(5) or C403.3.2(6)
0
❑
For an initial heating system using a heat pump that meets federal standards for the equipment
2
listed in Table C403.3.2(2) and supplemental heating provided by electric resistance or a
combustion furnace meeting minimum standards listed in Table C403.3.2(5)b found in the 2021
1.5
❑
WSEC- COMMERCIAL ENERGY CODE
3
For heating system based on electric resistance only (either forced air or Zonal)
0.5
❑
For heating system using a heat pump that meets federal standards for the equipment listed in
4`
Table C403.3.2(2) or C403.3.2(9) or Air to water heat pump units that are configured to provide
3.0
El
both heating and cooling and are rated in accordance with AHRI 550/590
For heating system based on electric resistance with:
1. Inverter -driven ductless mini -split heat pump system installed in the largest zone in the
5
dwelling,
2.0
❑
or
2. With 2kW or less total installed heating capacity per dwelling
a. See Section R401.1 and residential building in Section R202 for Group R-2 scope.
b. The gas back-up furnace will operate as fan -only when the heat pump is operating. The heat pump shall operate at
all temperatures above 387 (3.3°C) (or lower). Below that "changeover" temperature, the heat pump would not
operate to provide space heating. The gas furnace provides heating below 38°F (3.3°C) (or lower).
c. Additional points for the HVAC system are included in Table R406.3.
Prescriptive Path — Single Family WSEC-R 2021 Edition (V12/12/2024)
2021 Washington State Energy Code - Residential
Prescriptive Energy Code Compliance for All Climate Zones in Washington
Single Family - New & Additions (effective March 15, 2024)
r Summary of Table R406.3
Credits -
limited to one
Options Energy Credit Option Descriptions energy option, Comments:
from each
cate ry d
1.1
Efficient Building Envelope
0.5
❑
1.2
Efficient Building Envelope
1.0
❑�
Vert. fenestration =0.25+R-10full under slab insulation.
1.3
Efficient Building Envelope
1.5
❑
1.4
Efficient Building Envelope
2.5
❑
2.1
Air Leakage Control and Efficient Ventilation
1.0
❑
2.2
Air Leakage Control and Efficient Ventilation 1
1.5
❑
2.3
Air Leakage Control and Efficient Ventilatio 2.0
❑
3.1a
High Efficiency HVAC
1.0
❑
3.2a
High Efficiency HVAC
0.5
❑
3.3a,c,d
High Efficiency HVAC
0.5
❑
3.4a,d
High Efficiency HVAC
1.5
❑
3.51
High Efficiency HVAC
1.5
❑
3.6'
High Efficiency HVAC
1.0
0
Air -source ducted HP w/min. HSPF2 of 9.4.
3 7a,d,e
High Efficiency HVAC
2.0
❑
3.8a•d
High Efficiency HVAC
1.0
❑
3.9
High Efficiency HVAC
1.5
❑
3.10f
High Efficiency HVAC
2.5
❑
3.11c
High Efficiency HVAC
0.5
❑
4.1
High Efficiency HVAC Distribution System
0.5
❑
5.1
Efficient Water Heating
0.5
❑
5.2
Efficient Water Heating
0.5
❑
5.3
Efficient Water Heating
0.5
❑
5.4
Efficient Water Heating
1.0
❑
5.5
Efficient Water Heating
1.5
❑
5.6
Efficient Water Heating
2.0
0
NEEATie, IV Electric HP WH.
5.7
Efficient Water Heating
2.5
❑
5.8
Efficient Water Heating ❑
2.5
❑
6.1
Renewable Electric Energy (4.5 credits max)
0.5-4.5
o.o
7.1
Appliance Package
0.5
-
❑
Total Credits �.o
a. An alternative heating source sized at a maximum of 0.5 Watts/ft2 (equivalent) of heated floor area or 500 Watts, whichever is bigger, may be
installed in the dwelling unit.
b. See Section R401.1 and residential building in Section R202 for Group R-2 scope.
c. Option 3.11 can only be taken with Options 3.1 and 3.3. To qualify to claim Option 3.11 with 3.3, the system shall be a 1-2 speed heat pump
system. Variable capacity heat pumps are ineligible from claiming this option.
d. This option may only be claimed if serving System Type 4 from Table R406.2.
e. Primary living areas include living, dining, kitchen, family rooms, and similar areas.
f. Option 3.10 may only be taken with Efficient Water Heating Options 5.1 or 5.2. Equipment sizing for space heating shall be calculated as provided
in Section R403.7 with increased capacity to provide a minimum of 75 percent of peak hot water demand or shall be sized in accordance with
approved manufacturer's specifications or guidance. Supplementary heat for water heating system shall be in accordance with Section R403.5.7.
Prescriptive Path - Single Family WSEC-R 2021 Edition (V12/12/2024)