HomeMy WebLinkAboutCircleK-E093030-rm-RefrigSpec
Refrigeration Specification
Quote #: E093030
Date: 09/02/2025
1 of 4
5200 (Smaller) *** Freezer - Freezer
Room Temperature -10°F
Refrigeration system is designed to maintain -10°F at 80°F ambient
temperature around box and 95°F outdoor ambient temperature
assuming products enter at -10°F with moderate traffic.
28.25" 39.125"
Condensing Unit: LCH0025LCACZC2463 8290 BTUH
Ambient temp 95°F
Low Temp Air Cooled Scroll Condensing Unit with microchannel condenser, Liquid Line
Filter/Drier and Sight Glass.
Compressor Type Refrigerant HP Electrical RLA LRA MCA MOPD
Scroll R448/R449 2.5 208-230/3/60 8.65385 63 28.8 30
Receiver Capacity Liquid Suction Length Width Height Weight
14 0.5 0.875 28.25 39.125 19.75 230
Notice:Air cooled condensing units require a minimum of 1000 cfm of fresh air per horsepower
45.5" 13.25"
Unit Cooler: LEL0080BS6EEAB0200 QTY 1 8400 BTUH
Low profile coil (unit
cooler) with EC fan
motors, Electric
Expansion Valve and
iNtelliGen Controller.
Heaters Fans Qty 2
Voltage 208-230/1/60 Voltage 208-230/1/60
Amps 9.1 Amps Total 1
Drain Connection Inlet Suction Equalizer Length Width Height Weight
3/4 MPT 1/2 OD 5/8 OD 1/4 OD 45.5 13.25 16.44 54
Standard Features:
Condensing Unit Unit Cooler Liquid Line Filter/Drier
Sight Glass Pressure Control
Outdoor Systems Include:
Head Pressure Control Weather Proof Housing Crankcase Heater
Refrigeration Specification
Quote #: E093030
Date: 09/02/2025
2 of 4
5200 - *FOUNTAIN* - Cold Vault Angle/Cooler Combo
- Cold Vault
Room Temperature 35°F
Refrigeration system is designed to maintain 35°F at 80°F ambient
temperature around box and 95°F outdoor ambient temperature
assuming products enter at 35°F with moderate traffic.
28.25" 39.125"
Condensing Unit: LCH0015MCALZA0000 13890 BTUH
Ambient temp 95°F
Med Temp Air Cooled Scroll Condensing Unit with microchannel condenser, Liquid Line
Filter/Drier and Sight Glass.
Compressor Type Refrigerant HP Electrical RLA LRA MCA MOPD
Scroll R448/R449 1.5 208-230/3/60 6.41026 62 15 15
Receiver Capacity Liquid Suction Length Width Height Weight
14 0.5 0.875 28.25 39.125 19.75 221
Notice:Air cooled condensing units require a minimum of 1000 cfm of fresh air per horsepower
53.38" 28.69"
Unit Cooler: LEC0130AS7AMAB0200 QTY 1 13000 BTUH
Center mount coil
(unit cooler) with EC
fan motors, Electric
Expansion Valve and
iNtelliGen Controller.
Heaters Fans Qty 2
Voltage N/A Voltage 115/1/60
Amps 0 Amps Total 1.68
Drain Connection Inlet Suction Equalizer Length Width Height Weight
3/4 MPT 3/8 OD 1 - 1/8
OD
1/4 OD 53.38 28.69 9.56 100
Standard Features:
Condensing Unit Unit Cooler Liquid Line Filter/Drier
Sight Glass Pressure Control
Outdoor Systems Include:
Head Pressure Control Weather Proof Housing Crankcase Heater
Refrigeration Specification
Quote #: E093030
Date: 09/02/2025
3 of 4
Refrigeration Specification
Quote #: E093030
Date: 09/02/2025
4 of 4
5200 - *FOUNTAIN* - Cold Vault Angle/Cooler Combo
- Cooler
Room Temperature 35°F
Refrigeration system is designed to maintain 35°F at 80°F ambient
temperature around box and 95°F outdoor ambient temperature
assuming products enter at 35°F with moderate traffic.
30.25" 43.875"
Condensing Unit: LCH0035MCALZA0000 32610 BTUH
Ambient temp 95°F
Med Temp Air Cooled Scroll Condensing Unit with microchannel condenser, Liquid Line
Filter/Drier and Sight Glass.
Compressor Type Refrigerant HP Electrical RLA LRA MCA MOPD
Scroll R448/R449 3.5 208-230/3/60 11.5385 118 20 25
Receiver Capacity Liquid Suction Length Width Height Weight
20 0.5 0.875 30.25 43.875 29.25 300
Notice:Air cooled condensing units require a minimum of 1000 cfm of fresh air per horsepower
45.5" 13.25"
Unit Cooler: LEL0095AS6AMAB0200 QTY 3 30000 BTUH
Low profile coil (unit
cooler) with EC fan
motors, Electric
Expansion Valve and
iNtelliGen Controller.
Heaters Fans Qty 2
Voltage N/A Voltage 115/1/60
Amps 0 Amps Total 5.4
Drain Connection Inlet Suction Equalizer Length Width Height Weight
3/4 MPT 1/2 OD 5/8 OD 1/4 OD 45.5 13.25 16.44 51
Standard Features:
Condensing Unit Unit Cooler Liquid Line Filter/Drier
Sight Glass Pressure Control
Outdoor Systems Include:
Head Pressure Control Weather Proof Housing Crankcase Heater