HomeMy WebLinkAboutEngineering CalcsCopyright 2024, SEGA Engineers STRUCTURAL CALCULATIONS FOR THE SOUNDBUILT HOMES RESIDENTIAL PROJECT Plan L2M-2853 July 15, 2024 Job No: 12-021 Location: Lots 230 - 322, Tahoma Terra Yelm, Washington SEGA Engineers Structural & Civil Consulting Engineers 22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010 0 0 0 07777////15151515////24242424 Copyright 2018, SEGA Engineers STATEMENT OF WORK SEGA Engineers was asked to provide a lateral loads analysis, shear wall design, review of major framing members and foundation, and drawing red-lines for a two-story wood framed single family residence. The roof framing is manufactured trusses, the floor framing is 2x dimensional or open-web trusses, and the foundation is typical concrete strip footings with a crawl space. The application and use of these calculations is limited to a single site referenced on the cover sheet. The cover sheet should have an original signature in blue ink over the seal. The attached calculations may or may not apply to other sites and the contractor assumes all responsibility and liability for sites not expressly reviewed and approved. Please contact SEGA Engineers for use at other sites. SEGA Engineers will use that degree of care and skill ordinarily exercised under similar circumstances by members of the engineering profession in this local. No other warranty, either expressed or implied is made in connection with our rending of professional services. For any dispute, claim, or action arising out of this design, SEGA Engineers shall have liability limited to the amount of the total fee received by SEGA Engineers. Questions regarding the attached should be addressed to SEGA Engineers. Greg Thesenvitz, PE/SE SEGA Engineers SEGA Engineers Project Plan L2-2853 Structural & Civil Consulting Engineers Job No.12-021 By:GAT 22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010 Checked Date:07/15/24 Sht 1 Design Criteria International Building Code (IBC), 2021 LOADS Roof DL 15 psf LL 25 psf Floor DL 12 psf LL 40 psf Wind Risk Category II Design Wind Speed 110 mph (Vult) Copyright 2024, SEGA Engineers Design Wind Speed 110 mph (Vult) Kzt 1.00 Exposure B Seismic Design Category D SDS 1.00 Response Factor 6.5 CS =0.154 Importance Factor 1.00 Soil Allowable Bearing 1,500 psf Copyright 2024, SEGA Engineers SEGA Engineers / Structural & Civil Consulting Engineers 22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010 LOADS ROOF DL FLOOR Roofing (Comp) '/Z" OSB 2 x @ 24" Insulation 5/8" GWB Misc. LL Snow, Pf Reduction, Cs 7/12 pitch = 30 deg Total Roof Load DL Flooring 3/4" Plywood 2x12@16"oc 5/8" GWB Misc. LL Residential Total Floor Load DECKS DL 2 x Decking 2x10@16"oc Misc LL Residential Total Deck Load WALLS DL Siding 1/2" Plywood 2x6@16"oc Insul 1/2" GWB Project 1-2-2853 Job No. 12-021 By: GAT Checked Date:11/16/17 Sht 2 3.5 psf 1.8 3.5 1.1 2.8 1.5 14.2 psf 25 psf (115% Load Duration) 0.00 (Ct = 1.1, other surfaces) 39.2 psf 0.5 psf 2.3 3.3 2.8 1.5 10.4 psf 40 psf 50.4 psf 4.3 psf 2.8 1.5 8.6 60 psf 68.6 psf 3.5 1.5 psf 1.7 0.6 2.2 9.5 psf Copyright 2017, SEGA Engineers SEGA En ineers PROJECT L2 - z qe,s3 Structural & Civil Consulting Engineers 22939 SE 292nd Place JOB NO. 1 L _ d 74 FIGURED BY Black Diamond, Washington 98010 0 (360) 886-1017 CHECKED BY DATE 7 SHEET OF — S /k l�SA e ► , 4-7 'S e- DJaak 4, s9 of , ®c- 3 CIA s�/z Y�o, r 6fca �--- 0 Copyright 2012, SEGA Engineers SEGA Engineers/ Structural & Civil Consulting Engineers 22939 SE 292nd Place Black Diamond, Washington 98010 (360) 886-1017 PROJECT it Z — Z`& ,13 JOB NO. GFIIGURED BY CHECKED BY DATE 4Z:(LSHEE`rA OF -ksv(sopy) ( 4)1- = 8. ) p iw �y LYE 14 z,s 1� ,A I f/t f 0 7Z( 3•z' Copyright 2012, SEGA Engineers SEGA Engineers PROJECT LZ — Z��3 Structural & Civil Consulting Engineers JOB NO. Z- J Z/ FIGURED BY 6 A 22939 SE 292nd Place 4C% Black Diamond, Washington 98010 CHECKED BY DATE !u% SHEET,! OF (360) 886-1017 '1Z�4,'►'� i� 4 - G p ? F - )T'0°C (e. •err• WI-C. (3- 3V ZS.� S/z ylZ i'- = Of � S � /dr� L 1 �? 5)z 7 0 r�� !° Z '/ z 91 rr C_4o 4SIYZ (-L4- �� j ` �j,� jZ,.jK cLI�L- 1 t t,._ Copyright 2012, SEGA Engineers SEGA Engineers PROJECT L2 - SN�,� ��n7 Structural & Civil Consulting Engineers Z'�S3 ( •ru) JOB NO. —pL 1 FIGURED BY 22939 SE 292nd Place • Black Diamond, Washington 98010 (360) 886-1017 • Fax (360) 886-1016 CHECKED BY DATE ', ,1(Vp SHEE� OF C7r'-FE 1'ti(cl ' ks�toz.1,1 r.., - k �cw TPvJSFG� 7" — op 7'j0n1 S' 1L XI low T L. G� - o� �11Z� )Li-r 6td r Copyright 2010, SEGA Engineers SEGA Engineers Structural & Civil Consulting Engineers Project Typical Ftg Job No. By: GAT 22939 SE 292nd Place (360) 886-1017 Black Diamond, WA 98010 Checked Date: 12/03/15 Sht. Square Footing Design Ftg 36 x 36 Design Parameters f', = 2,500 psi Fy = 40,000 psi All. q = 1,500 psf b = 6.0 in - short side of column d = 6.0 in - long side of column Loads: Col DL = 2.4 kip (Service Load) Col LL = 9.6 kip (Service Load) Floor LL = 0 psf Overburden = 0.0 in (120 pcf assumed) Slab Thick. = 0.0 in (150 pcf assumed) Size and Footing Pressure h = 8.0 in qn = 1.40 ksf Req'd Area = 8.57 ft^2 Try 2.95 ft x 2.95 ft Factored Net Soil Pressure = 2.13 ksf < Ftg. Thickness o—Min. Ftg. Size (1.21D + 1.6L) Check for Two -Way Shear Avg d = 4.00 in V„ = 16.76 kips bo = 40.00 in (Critical Shear Perimeter) Bc = 1 (Long Side/Short Side of Column) phi Vc = 27.20 kips Phi VC > V„ OK Check for One -Way Shear V„ = 5.598 kips Phi Vc = 12.04 kips Phi Ve > V„ OK Design Reinforcement M„ = 4.71 kip-ft As = 0.51 in^2 a = 0.27 in Phi M„ = 5.58 kip-ft Phi M, > Mu OK AS min = 0.51 inA2 OK Use (3) - # 4 bars EW _Reinforcement 0.59 inA2 Copyright 2015, SEGA Engineers SEGA Engineers Structural & Civil Consulting Engineers Project Typical Ftg Job No. By: GAT 22939 SE 292nd Place (360) 886-1017 Black Diamond, WA 98010 Checked Date: 12/03/15 Sht. Square Footing Design Ftg 42 x 42 Design Parameters f'e = 2,500 psi Fy = 40,000 psi All. q = 1,500 psf b = 6.0 in - short side of column d = 6.0 in - long side of column Loads: Col DL = 3.2 kip (Service Load) Col LL = 12.8 kip (Service Load) Floor LL = 0 psf Overburden = 0.0 in (120 pcf assumed) Slab Thick. = 0.0 in (150 pcf assumed) Size and Footing Pressure h = 8.0 in qn = 1.40 ksf Req'd Area = 11.43 ft^2 Try 3.40 ft x 3.40 ft - Ftg Thickness F-Min. Ftg. Size Factored Net Soil Pressure = 2.13 ksf (1.21) + 1.6L) Check for Two -Way Shear Avg d = 4.00 in V„ = 22.84 kips bo = 40.00 in (Critical Shear Perimeter) Bc = 1 (Long Side/Short Side of Column) phi Vc = 27.20 kips Phi Vr > Vu OK Check for One -Way Shear V„ = 8.079 kips Phi Vc = 13.87 kips Phi Vc > V„ OK Design Reinforcement Mu = 7.61 kip-ft As = 0.70 inA2 a = 0.32 in Phi Mn = 7.62 kip-ft Phi M„ > Mu As min = 0.59 inA2 Q 01 Use (4) - # 4 bars EW Reinforcement 0.79 inA2 Copyright 2015, SEGA Engineers SEGA Engineers Structural & Civil Consulting Engineers Project L2-2853 Job No. 12-021 Bv: GAT 22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010 Checked Date: 06/08/13 Sht. LATERAL LOADS - (Alternate ASD) SEISMIC Maximum Base Shear, V = F SDS W Eq. 12.14-11 R where, F = 1.1 Two -Story Building SoS =1.00 SS = 1.5 Fa = 1.00 (Table 11.4-1, Ss > 1.25) R = 6.5 Table 12.14-1 W = Seismic Weight For W: W=f= (28ft) (44ft) (16psf) + (2) (28ft+ 44ft) (4.0ft) (9.5psf) = 25kips Wfaor= (28ft) (50ft) (14psf) + (2) (28ft+ 50ft) (8.5ft) (9.5psf) = 32kips W total = 5_ 7 kies Design Base Shear, V = (.169) (57 kip) = 9.7 kip E = 9.7 kip = 6.9 kip 1.4 WIND Design Wind Pressure, ps = X Kzt Ps30 Eq. 28.6-1, Sect. 28.6.3 where, = 1.00 0 - 15 ft Exposure B Figure 28.6-1 = 1.00 20 ft = 1.00 25 ft = 1.00 30 ft = 1.05 35 ft KZt = 1.00 Section 26.8 P30 = 17.7 psf 110 mph Figure 28.6-1 (ASD) PO _ 15 = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf (x 0.6 = 10.62 psf) P20 = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf ( x 0.6 = 10.62 psf) P25 = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf ( x 0.6 = 10.62 psf) Pao = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf ( x 0.6 = 10.62 psf) P35 = ( 1.05 ) ( 1.00) (17.7 psf) = 18.59 psf ( x 0.6 = 11.15 psf) Design Base Shear: (Wind) Vflb= (30ft) (10ft) (17.7psf) + (30ft) (5ft) (17.7psf) + (30ft) (5ft) (17.7psf) + (30ft) (5ft) (17.7psf) + (30ft) (1ft) (18.6psf) =13.8x0.6=8.3kips V,/S= (57ft) (10ft) (17.7psf) + (52ft) (5ft) (17.7psf) + (45ft) (5ft) (17.7psf) + (17ft) (5ft) (17.7psf) + (5ft) (1ft) (18.6psf) =20.3x0.6=12.2kips Therefore, Wind Loads Govern for Lateral Design - Front/Back Wind Loads Govern for Lateral Design - Side/Side Copyright 2013, SEGA Engineers SEGA Engineers PROJECT Structural & Civil Consulting Engineers JOB NO. %Z ��� FIGURED BYOW C— CHECKED BY DATES Z1/�Z SHEET-7-OF 22939 SE 292nd Place Black Diamond, Washington 98010 (360) 886-1017 LZ— z c:s -4vr-PIC �� D V�_ = z, spy'' 4 Cz�Cta)��d,�)L 4�aP�� " Lo l 3 •S I & �4�11z F"OoF-- UR = z, ;Q = / $ ' f-13,,-' a- Ito, 4 ' gam gD41 j ` � Gz 4, 4:4 G43_G4R 'OPT wnj T -, .4-4 Copyright 2012, SEGA Engineers SEGA Engineers PROJECT, LZ,— L Structural & Civil Consulting Engineers 22939 SE 292nd Place JOB NO. IZ Z FIGURED BY G Black Diamond, Washington 98010 CHECKED BY DATE IC SHEET F OF (360) 886-1017 kl= hcuun1 Ccorr) .5� W43 or- " -V ")L /73��, 3, 57 3'� �� z So�►�+` U em-t4 /LL 3'' 1-Sn1'aW N� t K�sb as A"D w ,V44j).. #'� (101^3 -- 4 gn# Copyright 2012, SEGA Engineers SEGA En ineers PROJECT Structural & Civil Consulting Engineers JOB NO. ' � , � Z t FIGURED BY 6A 7- CHECKED BY DATE / ZSHEEf (?OF 22939 SE 292nd Place Black Diamond, Washington 98010 (360) 886-1017 L Z- - ZS S3 fit taot� pL=7�o�0 S1 Sys 1--� L � Fr 7c :24-7ft" �> Copyright 2012, SEGA Engineers it A 1 ' N Structural & Civil Consulting Engineers 22939 SE 292nd Place • Black Diamond, Washington 98010 (360) 886-1017 • FAX 886-1016 SMEAR WALL KEG' FLAN PROJECT L2-2a53 JOB NO. 12 - 02 1 FIGURED BY GAT CHECKED BY DATE 02/21/12 SHEET J OF e SHEAR WALL SCHEDULESHEAR WALL SCHEDULESHEAR WALL SCHEDULE Mark Minimum Sheathing Anchor Remarks (4)Mark Minimum Sheathing Anchor Remarks (4)Mark Minimum Sheathing Anchor Remarks (4) Sheathing (1)Nailing (1)Bolts (3)Sheathing (1)Nailing (1)Bolts (3)Sheathing (1)Nailing (1)Bolts (3) 1/" OSB or 5/" @ 60" o.c.A 1/2" OSB or 8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA1/2" OSB or 8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA/2" OSB or 8d @ 6" o.c./8" @ 60" o.c.Qall = 230 plf CDXCDXCDX B 1/" OSB or 8d @ 4" o.c.5/" @ 32" o.c.Qall = 350 plfB1/2" OSB or 8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB/2" OSB or 8d @ 4" o.c./8" @ 32" o.c.Qall = 350 plf CDXCDXCDX 1 5C1/2" OSB or 8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC1/2" OSB or 8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC/2" OSB or 8d @ 3" o.c./8" @ 16" o.c.Qall = 450 plf CDX Use minimum 3x studsCDXUse minimum 3x studsCDXUse minimum 3x studs at abutting panel edgesat abutting panel edgesat abutting panel edges and stagger nails.and stagger nails.and stagger nails. R See Detail 12/S2.0 for ConstructionRSee Detail 12/S2.0 for ConstructionRSee Detail 12/S2.0 for Construction Notes:Notes:Notes: 1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing Notes: 1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1. 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO). 3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5" from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete. 4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.