6-1APPROVED METER BOX
L/D - *MIDSTATES BCF-1418 W/ 1.5"
HOLE FOR TOUCH READ
BOX- *MIDSTATES BCF-14168
*OR PRE APPROVED EQUAL
SERVICE SADDLE
ROMAC 202S OR
ROCKWELL 313 METER BOX
z
~ 1 "x 1 " FORD GRIP JOINT
~
RP ~RATIDN STOP TYPE
a FB
3
14"
1 " PLASTIC LINE (USE 200 P51-
DR7 PHILLIPS DRtSCO PIPE 5100
POLYETHYLENE PIPE)
METER -~
CHECK VALVE
' 19 1
2% SLOPE TO BOX
48" TO CENTER OF BOX
0
CURB ~ °
° a e v
0
v
a ~ _
14 GAUGE INSULATED COPPER
TONING WIRE WRAPPED AROUND THE
PIPE (SEE GENERAL NOTES N0. 7) -
12"
l
12.E
"j' FORD 861-444-G, GRIP
22 ~/2 JOWT BY LP THREADS.
- ~ 1" MALE ADAPTER
3/4" X 1" X 12" BELL -
REDUCER.
~- 1 "x 1 " FORD GRIP
JOINT CORPORATION
STOP TYPE FB i101
SERVICE SADDLE
aN TES:
1. STAINLESS STEEL INSERTS
REQUIRED FOR ALL PACK JOINTS
AND GRIP.
2. ALL SERVICE SADDLES SHALL AND
FITTINGS SHALL kAVE LP. THREADS.
FORD VB 72-i5W 5/8"x 3/4"
COPPER METER SETTI=R WITH
CHECK VALVE AND UNION
NUT AND SWIVEL FOR
CONNECTING 1 " IRON PIPE OR
EQUAL
CITY OF YELM, WASHINGTON
DEPT. OF PUBLIC WORKS
5/8" SINGLE
METER SERVICE
.AP_P DWG N0.
`~`~ _._------ q
PUBLIC WORKS DIRECTOR DATE 6 - 1
DES. DWN. CKD. DATE
E5 JEG JEG 52005