Loading...
6-11r- 3' x 3' x 4" CLASS 3000 CONCRETE PAD 12" ~_ RECESSED HANDLE TYPE COVER INLAND FOUNDRY #248 10" ~^~ 6 3/4 YALYE BOX WITH "YELM 8 3/4" WATER" CAST IN LID ~~ SECTION FINISHED GRADE OUT E PAV ~ ~ '~'~' ' ' '~~ ED AREA SID ~ ~ ^* h ~ ~~ TRACER WIRE ~ SEAL WITH AR4000W ~ ~. ~ +-6" SDR 21 PVC PIPE ~ w c~ ~ CONFORMING TO ASTM w ACP o 3034. RISER PIPE TO BE a 1'0' CSTC ('"'I ~ > U, ~ ~ PLUMB AND CENTERED OVER VALVE STEM , ~ ~ 1 4" n , ~ tf) 3 U BALLAST w ~ VALVE STEM RISER 0.5' CONCRETE CL 3000 ~ _ REQUIRED WHEN MAX. 36" IS EXCEEDED ~ (LENGTH VARIES) INSIDE PAVED ROADWAY NOTE: ALL VALVES MUST HAVE 14 GUAGE INSULATED COPPER TRACER WIRE TIED OFF AT VALVE .BODY, EXTENDED OUTSIDE PVG RISER PIPE THEN EXTENDED ONE FOOT TOP OF VALVE BOX. VALVE STEM EXTENSION LEGEND Q YALYE OPERATING NUT OR 1 7/8" X 1 7/8" X 2" HIGH GRADE STEEL WELDED TO RISER SHAFT. C~ 3/16" Thk X 5 1/5" DIA STEEL GUIDE PLATE WELDED TO RISER SHAFT. C7 2"X2"X 3/16" SQUARE STRUCTURAL STEEL TUBING TO FIT OPERATING NUT. LENGTH AS REQUIRED. NOTE; ALL WELDS TO SHAFT SHALL BE 1/4" FILLET WELD ALL AROUND. TRENCH ';BOTTOM GATE VALVE SHC}WN-SIMILAR ~, INSTALLATION REQUIRED FOR BUTTERFLY VALVES. '~ CITY OF YELM, WASHINGTON DEPT. OF PUBLIC WORKS STANDARD' VALVE BOX APP~Q~(E~____r DWG. N0. PUBLIC WORK DIRECTOR DATE': ~ - ~ 1 DES. DWN. CKD. DATE ES JEG JEG S/ZOOS