20100177 Sewer Cmt Email 02102011IPM.Note
Salmon Run Apts. civil review #1 Sewer Comments
Karen Bennett
Jim Doty
Karen Bennett
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=JIMD
Salmon Run Apts. civil review #1 Sewer Comments
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=KARENB
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=KARENB
Jim Doty
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=JIMD
Karen Bennett
Salmon Run Apts. civil review #1 Sewer Comments
Attached are our comments for this review.
Jim Doty
Plant Manager
City of Yelm Water Reclamation Facility
931 N.P. Road
Mail:
105 Yelm Avenue W
Yelm, WA 98597
Ph. (360)458-8411
Fax. (360)458-8166
<DC90029353CCCD468AA2A2858FFCD8F5F77304@server1.ci.yelm.wa.us>
Salmon Run Apts. civil review %231 Sewer Comments.EML
Karen Bennett
12.0
Salmon Run Apts. Civil Review _1 February 10,2011
Karen Bennett
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=KarenB
KarenB@ci.yelm.wa.us
KarenB
Karen Bennett
Karen Bennett
KarenB@ci.yelm.wa.us
Salmon Run Apts. Civil Review #1 February 10,2011.docx
WRFOps
WRFOps
3
Normal
Microsoft Office Word
CITYOFYELM
February 10, 2011
Salmon Run
Apartments (Project #20100177)1
st Civil Review:4000 gallon Tanks should be 6
ft. diameter, for better Settling.There seems to be some confusion whether
tank #7 is a pump tank or a holding tank. If it is a holding tank, it does not need a pump control panel. Same situation with tank #8.Force mains need to be 5 ft. deep per City of Yelm
Development Guidelines. They also need end of line blow-offs.
6” side sewers on commercial projects are the best bet to prevent back-ups. 6” side sewers also only require 1% fall instead of 2% which is required for 4” side sewers. This helps with
Tank depth as well. It was noted that tank depth was at 5 feet to invert elevation on all tanks. Yelm development guidelines call for a Maximum Tank Depth of 5 feet but we prefer tanks
to be as shallow as possible to aid with pumping.There needs to be a 2” gate valve at Vancil Rd. mainline tap.
Looking at plan’s profile, we don’t understand need for Air Release Valve (ARV) on mainline.
Why is there a service box next to ARV?
Pump Control Panels must be located on Remote Posts. They cannot be located on any living space walls.
Need Hose Bibs
connected to Domestic Water meter within 50 feet of tank outlets (pump vaults) for maintenance. These are not to be connected to irrigation meters.Would like to see pump control panel
for pump tank #6 to be located closer to this tank.
Delineate Storage and detention volumes on tank dipstick charts for all tanks.
Generator Transfer Switches will be required for all pump control panels for this project.
City of Yelm Sewer Dept.