Yelm Food Co-op Gordon’s Garden Center
Building PermitsProjects will be reviewed and permits issued concurrently. This requires application
and plans submitted as a package. Plans shall be scalable and dimensioned.Co-op plan submittal
Site plan of ADA parking (van accessible)stall
Site plan showing location and pedestrian path to ent
ryShow emergency lighting plan
Show egress plan out of north door.
Reverse swing on exit door
. Feather or level land where elevation change is greater than ½ inch. Use ADA thresholdPanic hardware on all doors along exit path
. All doors swing in the direction of travelIf shelving used to demark exit path thru storage show anchorage to floor
Show display and check
/service counter planParallel ADA approach for
check out counters is 38 inches. Service counters are 36 inches for parallel approachRaised work area will require hand rails on both sides of the stairs
Plumbing permit required for 3 compartment sink and grease interceptor.
Submit grease interceptor plan for review
If the wall furnace is to be used in the storage are maintain a minimum of 3 feet clearance around the unit
Remove sign requiring door to be open during working hours on the mutual door and place it on the west entry door.
Gordon
plan SubmittalSite plan showing exiting plan, location and access to public restrooms and accessible path to ADA parking.
Provide plan detail of accessible path improvements required to meet ADA specificationsBuilding and plumbing and mechanical plan for the public restrooms
Number of required exits 2.
Separation 159 feet. Both must be ADA accessible.