EVERGREEN REFRIGERATION, LLC AIR OUTLET TESTREPORT -SUPPLY Page 1 Project; Apple Physical Therapy Job #; 510385 Date; 214111 +I-10% Unit # Zone -Room Outlet Design Target Preliminary Final No Type Size C.F,M, C.F,M, C.F,M, C.F,M, C.F,M, VAV-1 Z18B-111 Sl MCD 10 315 315 585 415 315 Z18B-111 S2 MCD 10 315 315 460 330 315 Z18B-112 S3 MCD 10 315 315 510 360 390 Z18B-112 S4 MCD 10 315 315 600 435 395 VAV-2 Z18A-113 SS MCD 10 315 315 565 430 400 Z18A-113 S6 MCD 10 315 315 410 385 380 Z18A-112 S1 MCD 10 315 315 480 310 380 Z18A-112 S8 MCD 10 315 315 495 380 410 VAV-4 Room 114 S9 MCD 8 200 200 300 230 205 Room 114 S 10 MCD 8 200 200 265 180 215 Room 115 S11 MCD 8 200 200 350 250 210 Room 115 S12 MCD 8 200 200 330 240 205 VAV-5 Z11B-101 S13 MCD 8 200 200 285 225 215 Z11B-100 S14 MCD 8 200 200 260 205 185 Z 11B-118 S 15 MCD 8 200 200 205 160 205 VAV-6 Z19B-104 S16 MCD 8 130 130 205 135 125 Z19B-105 S11 MCD 8 130 130 260 110 120 Z19B-106 S18 MCD 8 130 130 280 160 130 VAV-3 Z19A-101 S19 MCD 10 350 350 310 310 380 Z19A-108 S20 MCD 10 215 215 360 330 215 Z19A-109 S21 MCD 10 215 215 325 295 260 Z19A-110 S22 MCD 10 300 300 310 330 330