Loading...
20090210 Seismic Brace Calcs•~ ~- Seismic Brace Calculations Project: Yelm School Support Operation Center Contractor: Hydro Tech Fire Protection, Inc. Address: 406 Railroad Street Address: 15218 N.E. Caples Road Yelm, Washington 98597 Brush Prairie, WA 98606 Date: 07-27-12 Telephone: (360) 256-2816 *Seismic Calculations Per NFPA 13 2010* Fax: (360) 256-2817 Brace Information Seismic Brace Attachments Structure Attachment Fitting or tension-only bracing system: Make: Afcon Model: 077 Length of Brace: Max. 7'--0" Listed Load: 2,015 Adjusted Load: 1.744 Diameter of Brace: 1 in. (per 9.3.5.10.3) Type of Brace: Schedule 4D Pipe Sway Brace (pipe attachment) Fitting: brocing system: Angle of Brace: 60' to 90' Make: Afcon Model; 410 _ Least. Radius of Gyration: 0.42 Listed Load: 2,015 Adjusted Load: 1 ,744 (per 9.3.5.1D.3) L/R Value: 200 Seismic Brace Assembly Detail Maximum Horizontal Load: 2,124 Ibs STEEL BEAM ADAPTER STEEL BEAM Fastener Information s•~s 9• EQ EAR Orientation of connecting surface: "F" 1 ° SCH. 40 PIPE Fastener: EQ BEAM CLAMP PIPE CLAMP o Type: Afcon 087 Diameter: 1 /2 in. FIRE PPpE KLER Length (in wood): n/a LONC~DUTINAL EARTH GIUAKE BRACE Maximum Load: 2,015 Ibs Brace ID: Lateral Brace XQ Longitudinal Brace Sprinkler System Load Calculations Diameter Type Length (ft) Total (f#) Weight per ft Wp Total Weight 4'~ SCH. 10 80~ 80 ft 11.8 Ibs/ft 0.57 538.08 Ibs ~t ie cereln yrp .~ c v tl r D~c ~~ ~ ~ [ i y ~ n ~ 3 rrrr' Her n 1+ s d, ~`""""'° ~ Total Weight 538.08 Ibs "~~d~h~'rk°Sprlnkk~s,~tti~ ° °~ Fp x 1.15 618.79 Ibs ueb n-,..mb . - - Seismic Brace Calculations Project: Yelm School Support Operation Center Contractor: Hydro Tech Fire Protection, Inc. Address: 406 Railroad Street Address: 15218 N.E. Caples Road Yelm, Washin gton 98597 Brush Prairie, WA 98606 Date: 07-27-12 Telephone: (360) 256-2816 *Seismic Calculations Per NFPA 13 2010* Fax: (360) 256-2817 Brace Information Seismic Brace Attachments Structure Attachment Fitting or tension-only bracing system: Make: Afcon Model: 077 Length of Brace: Max. 7'-0" Listed Load: 2,015 Adjusted Load: 1 744 Diameter of Brace: 1 in. (per 9.3.5.10.3) Type of Brace: Schedule 40 Pipe Sway Brace (pipe attachment) Fitting: bracing system: Angle of Brace: 60' to 90' Make: Afcon Model: 001 /020 E Least Radius of Gyration: 0.42 Listed Load: 2,015 Adjusted Load: 1,744 ', (per 9.3.5.10.3) L/R Value: 200 S i B bl D l Maximum Horizontal Load: 2,124 Ibs eism c race Assem y etai STEEL BEAM ADAPTER STEEL BEAM Fastener Information QUIK CLAMP a use' EQ EAR Orientation of connecting surface: "F" Fastener: EQ BEAM CLAMP Type: Afcon 087 1" SCH. 40 PIPE Diameter: 1 /2 in. FIRE SPRINKLER PIPE Length (in wood): n/a LATERAL EAFITH DUAKE BRACE Maximum Load: 2,015 Ibs Brace {D: Q Lateral Brace ~ Longitudinal Brace Sprinkler System Load Calculations Diameter Type Length (ft) Total (ft) Weight per ft Wp Total Weight 4" SCH. 10 40' 40 ft 11.8 Ibs/ft 0.57 269.04 Ibs 2" SCH. 10 2'+2'+2'+2' 8 ft 4.2 Ibs/ft 0.57 19.15 Ibs l~z'~ SCH. 10 36'+36'+36'+36' pro ~ 144 ft 3.0 Ibs/ft 0.57 246.24 Ibs 1 " Sch. 40 10' '~`` ~s„'~ c ~»~,. oft 2.1 Ibs/ft 0.57 1 1.97 Ibs ~ •r er 9 ~ Total Weight 546.40 Ibs +~,~ d ~ ti Fp x 1.15 ,,~ . 628.36 Ibs