Loading...
Creek Road Plan Review Creek Road Plan Review Accessibility: Refer to 1107.6.2.1.1 as amended by the State of Washington. Type A units need to be dispersed among all units and the total number needs to be 5. G103 Accessibility Notes (B) Reach ranges: Note 2 change 15 inches to 44 inches Note 3 change 9 inches to 15 inches A 102 shower. Note clear floor space starts at the control end 4. A 100 a. Door notes 11 should read ½”, with the exception at sliding glass doors which may be ¾” when beveled 1:2. 5. A 401 create barrier under stairs when risers at 80 inches above finish floor Energy: Design or plan notes reference the 2004, 2006 and 2009 WEC. The 2006 is still in force, though you may use the 2009. Ventilation is regulated by the 2009 IBC and 2009 IMC. G103 Mechanical Notes Change note 1 to reflect electric heat Change note 3 to reflect electric heat Supply heating and power loads per selected WEC General Notes: Correctly state the jurisdiction on cover sheet LT1 change Note 5 to read 2 foot candle per City of Yelm design guideline and note 4 foot candles at entries Verify illumination meets guidelines with photometric plan 3. G103: a. General Notes change reference 16 F to current code notation b. Electrical notes change 5 A as allowed under Energy note 2 c. Electrical notes 21 C. cite 2009 IMC equivilant d. Mechanical notes cite IMC 504 for dryer duct installation 4. A200 a. No draft stops noted. This does trigger NFPA 13 system vs. NFPA 13R 5. A 401 a. verify riser height b. open stair risers allowed per IBC 1009.4.5 exception. Show maximum of 4 inch opening Structural: S 100 Change Codes 1.1 to 2009 IBC Change Code to 2009 IBC on structural Calcs. Stamp with current license date S 200 Unit A structural calcs.. L 39.2 refer to L1 as requiring HDU5’s. Plan calls out STDH14’s. Clarify Unit A structural calcs. L 39.2 refer to L3 as requiring HDU11’s. Plan calls out HDU5’s. Clarify S 201 Unit C structural calcs. L 70.2 refer to L2 as requiring HDU11’s. Plan calls out HDU8’s. Clarify Unit C structural calcs. L 70.2 refer to L3 as requiring HDU5’s. Plan calls out both HDU5’s and STDH10’s. Clarify