20080243 Shea Carr Cmt Ltr 12102012 �
SHEA - CARR - JEWELL
December 10, 2012
ENGINEERING AND PLANNING SERVICES
Karen T. Bennett
City of Yelm
105 Yelm Avenue West
Yelm,WA 98597
Re: Yelm Day Care Center-2nd Review/Response to Comments
#0290.05
Dear Karen:
The following are responses to comments from the second review of the Yelm Day Care plans received.
The responses to comments include the sewer department comments made on the plans. All Shea Carr
Jewell comments are shown in italics.
Our responses are as follows:
Yelm Dav Care Construction Plans:
Sheet CV-01:
1. Conditions of Approval#9, show short term stalls.
Short term stalls are shown.
2. Landscape plans need to be added to Sheet Index.
Landscape plans will be submitted under separate submittal.
Sheet�P-01:
1. Berry Valley Road access does not meet development guidelines.
The 26'driveway approach has been agreed upon through conversations with public works and
submittals.
15t Review Comment:
1. Sheet 13.#2 See page 7-32, 7E.010of sewer spec. (Detail 7-1 needs to
�
updated for service "T" requirements.
Detail was updated as requested.
2102H Carria e Drive SW-OI m ia,WA 98502
9 Y P
OFfice:360352.1465 Fax:360.352.1509 Email:inFo sheacarr ewell.com www.sheacarr ewell.com
I I C� 1 I 1
Karen T. Bennett
December 10, 2012
�~A Page 2
1—�
Utility Department Comments
1. Sheet UT: #8, do you know yet if pump control panels on buildings will be a noise problem?
Not known at this time. The architect has not been chosen.
2. Sheet UT: #12, mainline to end of property?
The waterline has been extended to the end of the property.
f oils and rease into ste tank. A rease tra shall
3. Sheet UT: #17,food preparation causes atty , g p g p
be required.
A note was added to UT-01 stating, "Food preparation is not anticipated inside the building.
Therefore a grease trap shall not be required."
4. Sheet UT: #17, is the sewer main in the street or not?
Yes, the sewer main is in Tahoma Blvd.
Sheet UT-01:
1. Fire lane no parking signs at FH and FDC both sides of lane.
Signs were added as requested.
Sheet UT-04:
1. DWG. No 7-1,these are shown backwards.
Detail was updated as requested.
2. DWG. No 7-1Mainline service tees shall be 4"gasket x 2" gasket or 2" slip glue.
Detail was updated as requested.
3. DWG. No 9-3,000 gallon tanks shall have a 25" down pipe.
Detail was updated as requested.
4. DWG. No 9-this policy is no longer in affect.
A note on the detail was added as requested.
Karen T. Bennett
,� December 10, 2012
=� Page 3
5. City of Yelm Sewer Addendum Notes#5, change 26" above the floor of the tank to 29".
as re uested
Note was revised q
h et UT-05•
S e
.
1. DWG. No 7-11, all step tanks shall be H-20 load rated tanks. This policy shall take effect on May
31, 2007. This policy is no longer in affect.
A note on the detail was added as requested.