20130139 HVAC test and balanceDollar Tree StoresConstruction Department
Yllere plans engineered? YES or NO
Fax:757.321.5300
Was this a Vanilla Box? YES or NO
#
Address:
-6<rt Date:
Page:
Testing firm:
Technician:
rt /r< /rs
1of2
DOLLAR TREE
906 E. YELM AVE MOUNTATN 4rR
DOUG WHITE
YELM WA
E
a
U
I
P
M
E
N
T
Unit #Unit # 2 Unit # 3
Manufacturer (Packaoe unit or AHU if Solit)CARRIER CARRIER CARRIER
N4odel#48HCED 2A 48HCED12A 48HCEDO8A
Serial#1413G20166 1413G20165 0153G40163
Manufacturer (CU if solit - N/A if oackaoe unit)
[,lodel#
Serial#
Iype (RTU, split, chilled water, VAV)RTU RTU RTU
)oolinq capacity (in tons)10 10 7.5
Heat (qas.elec., oil, heat pump, hot water)GAS GAS GAS
Aoe / Condition NEW NEW NEW
Filter Size 4=20D(20)(2 4=2OX20X2 4=2OX20D(.2
S
U
P
P
L
Y
Desion CFM - Total Per Unit Iotal Iotal Iotal
fiffuser Tvoe (Concentric / Traditional)TRAD TRAD TRAD
Soolinq Zone (Sales floor, Stockroom)Actual Desion Actual Desion Actual
Suoolv orill# / CFM #1 500 510 #1 400 410 #1 500 500
Supplvqrill#/CFM #2 550 560 #2 400 405 #2 500 51s
Suoolvorill#/CFM #3 550 550 #3 400 400 #3 500 500
Suoolv orill# / CFM #4 400 415 #400 410 H 375 380
Suootu orill# I CFM #5 400 41C #5 400 415 #5 375 38r
ruoolvorill#/CFM #6 400 40c ffi 400 405 #6 400 40c
Suoolvorill#/CFM #7 400 400 #7 400 415 #7 400 400
Suoolvqrill#/CFM #8 400 405 #8 400 405 #8
Supolyqrill#/CFM #9 400 410 #9 400 40c #9
Suoolvorill#/CFM #10 #10 400 400 #10
ruoolvorill#/CFM #11 #11 #11
Supply qrill# I CFM #12 #12 #12
Total Supplv-Air (SA) GFM 4000 4060 4000 4065 3050 3080
R
E
T
U
R
N
?A Confiquration (Concentric, Ducted, Plenum DUCTED DUCTED DUCTED
letum location (Sales floor. Stockroom)STOCK ROOM SALES SALESISTOCK
Ihrouqhthe-wall qrills (Qtv & size)
letumorill&#/CFM #1610 1600 #1610 1620 #1230 1225
letumqrill&#/CFM #1610 1650 #1610 1625 #1235 1230
Returnqrill&#/CFM ###
Total Return-Air (RA) CFM 3220 3250 3220 3245 2465 2455
(,
T
H
E
R
f,A DamoerTvpe (MOAD. Economizer, None ECCONO ECCONO ECCONO
JA Damoer Settino (Economker minimum)'tOYo 1$o/c 1001 10o/o 10o/o 1Oo/o
)utside/Other Air CFM (SA - RA = OA)780 810 780 820 585 625
)utside/Other Air o/o (OA /SA = OAo/o)2Oo/o 20o/o 200/<20o/c 19o/c 2oo/o
Onlv for units that supplv air to the sales floor wI rctums in the stockroom. Do not include doorways in this dimension.
Sales Floor onnaqe: 27.5 stocKroom lonnaqe: o
Remarks:
Revised: 02122106