20130139 HVAC test and balance p2#
Address:
Date:
Page:
Testing firm:
Technician:
u/$t /rs
2ot2
DOLIAR TREE
906 E. YELM AVE i,OUNTAIN AIR
DOUG WHITE
YELM WA
E
o
U
I
P
M
E
N
T
Unit # 4
l\4anufacturer (Packaoe unit or AHU if Solit)CARRIER
MIodel#48HCEAO7M
Serial#0513G40163
l\,flanufacturer (CU if solit - N/A if packaoe unit)
[,lodel#
Serial#
Ivoe (RTU. solit. chilled water. VAV)RTU
Coolinq capacitv (in tons)6
Heat (qas.elec., oil. heat pump, hot water)GAS
Aoe / Condition NEW
Filter Size 2=2OX25X2
S
U
P
P
L
Y
Desion CFM - Total Per Unit Iotal
Diffuser Tvpe (Concentric / Traditional)TRAD
Coolinq Zone (Sales floor, Stockroom)Actual
uoolv orill# I CFM #1 300 310
Supplv qritl# / CFM #2 150 155
Suoolvorill#/CFM #3 300 300
uoolv qrill# / CFM H 300 310
Suoolvorill#/CFM #5 300 315
upolv orill# l CFM #6 300 300
Suoolv orill# / CFM #7 300 305
Suoolv qrill# / CFM #8 150 155
Supply qrill# / CFM #9
Suoolv orill# / CFM #10
Suoolvorill#/CFM #11
Supplyqrill#/CFM #12
Total Supply-Air (SA) CFM 2100 215C
t{
E
T
U
R
N
RA Confiqurataon (Concentric, Ducted, Plenum)DUCTED
letum location (Sales floor, Stockroom)STOCK ROOM
lhrouqhthe-wall qrills (Qtv & size)
Retumorill&#/CFM #'1805 1800
Retumorill&#/CFM #
Returnqrill&#/CFM #
Total Return-Air (RA) GFM 1805 1800
(,
T
H
E
R
3A DamperTvpe (MOAD, Economizer, None)ECCONO
3A Damper Setting (Economizer minimum)1Oo/ol 1Oo/a
Cutside/OtherAir CFM (SA - RA = OA)295 350
Sutside/OtherAir % (OA /SA = OA%)14o/ol '160/a
Onlv for uniE that suoplv air to the sales floor wI retums in the stockroom. Do not include doorwav$ in this dimension-
lSales Floor Tonnaqe:27.5 Stockroom Tonnage: 6
Remarks:
Dollar Tree StoresConstruction Department
Were plans engineered? YES or NO
Fax:757.321-5300
Was this a Vanilla Box? YES or NO
Revised: 02l22loo