20130139 HVAC test and balance p2# Address: Date: Page: Testing firm: Technician: u/$t /rs 2ot2 DOLIAR TREE 906 E. YELM AVE i,OUNTAIN AIR DOUG WHITE YELM WA E o U I P M E N T Unit # 4 l\4anufacturer (Packaoe unit or AHU if Solit)CARRIER MIodel#48HCEAO7M Serial#0513G40163 l\,flanufacturer (CU if solit - N/A if packaoe unit) [,lodel# Serial# Ivoe (RTU. solit. chilled water. VAV)RTU Coolinq capacitv (in tons)6 Heat (qas.elec., oil. heat pump, hot water)GAS Aoe / Condition NEW Filter Size 2=2OX25X2 S U P P L Y Desion CFM - Total Per Unit Iotal Diffuser Tvpe (Concentric / Traditional)TRAD Coolinq Zone (Sales floor, Stockroom)Actual uoolv orill# I CFM #1 300 310 Supplv qritl# / CFM #2 150 155 Suoolvorill#/CFM #3 300 300 uoolv qrill# / CFM H 300 310 Suoolvorill#/CFM #5 300 315 upolv orill# l CFM #6 300 300 Suoolv orill# / CFM #7 300 305 Suoolv qrill# / CFM #8 150 155 Supply qrill# / CFM #9 Suoolv orill# / CFM #10 Suoolvorill#/CFM #11 Supplyqrill#/CFM #12 Total Supply-Air (SA) CFM 2100 215C t{ E T U R N RA Confiqurataon (Concentric, Ducted, Plenum)DUCTED letum location (Sales floor, Stockroom)STOCK ROOM lhrouqhthe-wall qrills (Qtv & size) Retumorill&#/CFM #'1805 1800 Retumorill&#/CFM # Returnqrill&#/CFM # Total Return-Air (RA) GFM 1805 1800 (, T H E R 3A DamperTvpe (MOAD, Economizer, None)ECCONO 3A Damper Setting (Economizer minimum)1Oo/ol 1Oo/a Cutside/OtherAir CFM (SA - RA = OA)295 350 Sutside/OtherAir % (OA /SA = OA%)14o/ol '160/a Onlv for uniE that suoplv air to the sales floor wI retums in the stockroom. Do not include doorwav$ in this dimension- lSales Floor Tonnaqe:27.5 Stockroom Tonnage: 6 Remarks: Dollar Tree StoresConstruction Department Were plans engineered? YES or NO Fax:757.321-5300 Was this a Vanilla Box? YES or NO Revised: 02l22loo