3088 Engineering Calcs STRUCTURAL DESIGN FOR PLAN 3088 YELM, WASHINGTON NOTE: This stamp applies to the members and assemblies described in these calculations only and is only valid if it is a wet stamp. K 409110 IST L 04/25// WELLER CONSULTING PROJECT NO, 13-027 21925 8TH PL W DATE 05114113 BOTHELL, WA 98021 PREPARED BY Mark Weller, P.E. (425)488-9868 (425)486 -6715 FAX DESIGN CRITERIA PER THE 2012 INTERNATIONAL BUILDING CODE EARTHQUAKE PER SECTION 1613 Design Per ASCE 7-10 Section 12.8 Equivalent Lateral Force Procedure Base Shear: V=Cs * W Cs=Seismic Response Coefficient W=Effective Seismic Weight Site/Project Specific Design Values: Ss= 1.30 per USGS S, =0.45 per USGS Site Class D (Default) Seismic Design Category D R=6.5 from Table 12.2-1 Risk Category 11 from Table 1.5-1 1,= 1.00 from Table 1.5-2 CS=0.1333 per Section 12.8.1.1 WIND DESIGN PER SECTION 1609 (Allowable Stress Design) Design per ASCE 7-10 Section 28.6 Design Wind Pressure: Ps 1,* KzT * PS30 where: X=Exposure Factor KZT=Topographic Factor le=Importance Factor PS30=Base Design Pressure Site/Project Specific Values: Basic Wind Speed= 110 mph(V.,,) k= 1.40 Exposure"C" (<30') KzT= 1.00 1,= 1.00 PS30=see ASCE 7-10,Figure 28.6.1 STANDARD DESIGN INFORMATION The information described below is to be used unless otherwise noted on the plans WOOD DESIGN per Section 2301,Allowable Strength Design,AF&PA SDPWS 2008&AF&PA NDS 2012 when applicable;per 2308 Conventional Light-Frame Construction MINIMUM NAILING REQUIREMENTS per Table 2304.9.1 ANCHOR BOLTS: 5/8"0 x 10",A307 or better,w/7"min. Embedment, V= 1328#1 bolt CONCRETE DESIGN per Chapter 19&ACI 318-11 Concrete: fe,=2500 psi Rebar: fy=40,000 psi MISCELLANEOUS HARDWARE SIMPSON Strong-Tie Connectors or equal * « U� �K SCHEDULE �� �� �� ��� �� 0 , � ' ���~�� ��� ` , � ����� (SEE ANSI//\FJ6PA80PWS-20N8 Table 4.3A&Section 4.3.3) All shear walls to be sheathed from top plate to bottom plate.Block all panel edges. Nail spacing is for all panel edges. Space nails @ 12"o.c.along intermediate framing members. 8W~6 r=350pK 7/l6"O8B.w/8d(D.l3l"0)common nails @6"u.o. Anchorage(interior wulia only)/o SINGLE joist orb&gbelow: 16d(6ux)6d4''o.c. SW-4 v=5&OyK 7/16"OSB`w/8d(0.13l"0)common nails @,4"oz. Anchorage(interior walls only)to4x(oinJ BEAM urb}kgbelow: 16d(hox)@3"o.o. NOTE: use min 3" nominal studs gadjoining panel edges SW-3 v=715p|f 7/|6"O88'n/8d(U.|3|"0)common nails @3"uz. Anchorage(interior walls only)tn4x hniuj BEAM orh|kgbelow: /6d(6ox)Ca,2"o.o. NOTE: use min 3" nominal studs*adjoining panel edges 8W'2 v=yGOp|f 7/l6"OSB,x/8d(V.|]|"0)common nails @2"o.c.(staggcmd) Anchorage(interior walls only)to4x(minj BEAM orhlkgbelow: Y4"x4k" SDS SCREWS @3"u.o. NOTE: use min 3" nominal studs @ adjoining panel edges The shear values above are based upon the use of 8d common nails with a full head,a shank diameter of 0.131",and u minimum penetration ofY.375"' From Table 4.3A use 15/32: @d values with aO.g3 reduction for Hem-Fir& 1.4 increase for wind. 166101@'0.[ 5HEARYALL EDGE NAILING 0NJ0|5T LOCATE 5MEATM|NG --`--- JOINT 000MMON k4EWDER ��LJ� � � 1-�� � N/���� J� �yT-��//l� WALL DETAIL `/| /�_/ \|`� | r`/ \|�`// �_/~~ Y�/ �_/� | �_|`~|L/m LI LO O o; N t0 00 r- 00 to r - N t35 O O 0) 037 r ® 00 00 1` 077 r o 07 LO M cMy � ((0 N tom- N O Cl) N (.0 0) LO to O N M M 0 r-- p CV) * ct rt r r M v It w fl If If 11 M It II if it 00 > ff fl U) w w It tQ a> U) If 11 C) o w O C) ° O eh ° O 0 0 r r U + + (/) -rzi co vt ay - ai w to (D < i4 00 F- o "� � Nc a@� U UaU UCH? ~ L LL LL L to M co LL LL LL LL U- LL LL LL z U) U) Z u) u3 U) U) to (n U) U) Q ran r~ as ii 11 1; L i c°o CO - N tc) Mu (D � > CO r! N co v CC if u o o a U- r- IN o t c� a � ° 0 � o x (0co0 p J Izr LO M N M L` Cj N fA N 0 0 0 0 O O O O le O O O t> O O O O O V tM tM tM tM M ce) tM tM tM tM tM ce) tM tM tM M T v..OL n+ V V V V V V V V V V V V V V V V N .t] Z C _ O0 O m Q O O , +0 (0 co C C = LO w cu Cd cli (D CL CNI F v- z Cp r {0 r-. M M OMN M N MMO It O Ot0LO M L `mgr O U) 007 r h- M r C3 CO O O h- w M tl- w M r t- N r? CL CL r? 0 Cif r N r- to to N t) to r M 00 M to r r 00 O O QN7 (0 LO 00 Lt) tG r L6 h+ N ei r- L6 tD �+ 06 U `- W 06 °� � r (� 0) w If It If 11 1w II ff ff 11 ILL II 11 If II iw it ff II it ILL U ct) a7 'T 'T 00 U) w w y- LL `t- `+- `t- `t- � `t- v- LL � -0 C}'} O {n N US sn to {n tl} to in to to to (t7 U7 to LL O C .0 r. Q_ Q_ Q_ Q. Q. Q_ Q_ Q. Q_ Q. Q_ Q_ Q. Q. t1.. CL {/� r E r � �- P- tl t0 C0 t0 q t0 to t0 'T CL? t0 C0 'T t0 (0 C0 (L7 N w I-- C') LO W t- d- m � � r �} Cf7 � G t �y 0*) to U} tvn 0 U co to "T m ui 4 ri to v "' m LO Q 0 0 tY H Q tY7 N 0 M N 0 ty7 N 0 c0 N 0 -C LL 0 {n tZ LL LL. LL U- LL LL LL LL " LL LL LL LL LL LL LL LL w www O w www a to wtow O w Inww t} �- a � cj' r r F 00 O r O CL co (o O G5) (L) O O N C' 0 (3 Lo o ft tl II Z m m � r r,. w co LO (0 LO r-. LO to = v4 N ty7 �+ 0 F0- U It If 1f It LL D LL n LL LL �. 47 cc N Z Z3 0 '" + Q) u u cu co co N E c E a) a) �2) . m LM w w w T- C: C:o) co 0 o a) LL 'T a) U- Iq It r ;6 ;6 ry 4:f 4f N a) O a) C14 CN 0 1'- r- 00 (D N U) V) CY)m 0) 1-- 1% " CN CD C:� m CN lq- u t 10 co --- - --- r F CD (6 ztf itf IV 4t ce) 4L rtL 4i 4 riL 4 11 m� rnrn 11 0 lq- CD co C) CN LO CY) m CD (D CY) 0 LO Nr "T C14 U. M m r- I-- U. r - r 00 04 w ui cr- itt af v :tL 4L 4L 4L 0 LO in (D (D t CN - fl- 0 LO 0 u') CY) (D (D co O 0 00 r- 00 0 (f) 0 Lo Iq Iq co co C) 00 (D It (Y) r- 0) Lr) U') rl_ r- 5- a) tl- CF) co CY) r- Lf) U) 00 co Co 00 00 00 .0 00 00 00 00 00 00 C= CL q L CU — ca —s1 - 00 0 C� 0 0 -0 C) 0 0 000 0 cl) M CY) (Y) (Y) CY) C= C') C') C? cy� C') LLJ LO :3 t — , T- :3 — — — -0 cu �o CU (1) LL U- 0 0 L) > E u 0 0 C) CD C) C) > E .0000 000 0 9 C� o 9 9 P in C� 0 C� 000 i r — — — a5 — — — — U- U) W .0 C) 0) a CD m m �o t-- c) o cy) a a LU 15 U? cq C) C) M M C� CN 0 'It w 0- 0 0 04 C14 0 0 0- D cu cu 0) (9 }}g: 3:(9 t0 (9 (>>:9 a > N y:(9 (9 (3:9 CO g (9 M (C� (D 0) U) (n W W U) w w w in U) co U) U) U) 0. 0- CL CL CL D- a a Q Q Q a N (Y) Cl) a) Cl) Cl) fl- I-- r" I- Cl) Cl) Cl) _0 -C LO U') U') 0) a) U) cu U) li �o 70 -C (D 0) M 'It IT U) rU-) U� = 0) 0) 0 0) P-� (6 C14 1- 04 Cl) LO U') Cq t_ U) 'o 001(" 0 U)lo (U wo cu -0 0 73 co dQ 0 cu -0 U It > Cl)0 C) 40 > C) 0 (D 0 CY) (.0 m Cl) to CY) (Y) Cl) CY) LO co t0 03 Lf) Lr) a) N NM 65 M F- z < a) w 0 E- 0 0 U- F- -j ry U v co -0 'o 'D U) co -a 'a m us U') cn to w 6 Of m lY � tf) r 4) 025 06 od q) O 025 025 N V r Lo r N - U) U) I E w E 0) c c� a .0 2 `) U CL `� tL' is 2Y: LPL' LPL' Ofu) �n cn cn 02S 06 °�' 06 b 06 02$ r � v LO L r cn LO J J M r LO N r IY 0 r r M r Q r N N N �r tD l- f- rte. H C CO O N N N N r M M M m D M m C14 af at i= IV 4f Lo LO AAA AA 0 M 11 r YN) r`n N O VM � 0) I I °M 0) CN LO 6) CC) It CD �i.) CD N � 0 to r CD (0 U.LL U- r r J J v v AAA AA :4A o U3 t(D N rte- Iq O h IT � � 0 M M M O O N 0 0 CO f� 0 M V d O 07 It O 0) t- et co r u') C0 r r- � .r+� d~ 1 N O r r r N r r r M r M J 0) 0) 0) 0) 0) 0) 0) r- fl- O) O 0) 0) 0) J = _ - U a c a M - 0 0 Cl 0 0 0 0 Cl 0 0 - 0 0 Cl 0 0 Q p M M M ce) ce) Cl) co co co 0 CO CO M M M U r r r r r r r r r U r r r r r eM- a) tL co a) LL U U 0 r' 'E .0000) 0 OOr- t- t- > E 000 00 m � 00000 C a oU) � X000 00 J (/}� r c- C) r �- . C7 OO D � �- .- r r LL z d o q U) CD V- m a O O 3'} O U) O CD m c0 tt) ONCC) Cpo6O Ud o d OO tnM cQ r Nr OrM MM = � 0 0 r C) C) G @ co a) aaefl (9 co (9 '- N NC� M �� � <4MC7 (9 (9 M sus' s � � L o 5, U) c) cn co co cn cn co w d° w t— cn w cn CO w CO 11 U- aC. aa aaa as aaa as ro ct �i IcT Ct r r N N m 0 0 r r CDCD (0 (D 0NN f- t�- MM MM N N N N N et ct It IT CO Co W N n 4) (D 6() IT tC) to cf tS) M tf) N N d C 0 U) U) M 'o ")IL,) N d t_: 0 c t N MW J J R) S0 U 'C} m m .4 co n co co .t) Lo -0 t Ot t :tt * 4t �t > r CD CAD 00 N M 0) 0 CD 0M) co tt7 c t? co 'fit rn t� O M r r r LO co m LO LO CD NN 0 6t) (D N U) 1 . Z CL M Le) W U) 1� M (1) 04 X I c if Q) Lc)C13 C: Q) 0 it 00 ILO 'l- X Q) x W) to z U') (I) > > 0 0 co x If CL 0 < CL 0 _N O O 0 0 0 0) < _x m 0 7N z 0 Ui Lr) CL < co w If 3� 0 00 . co 0 0 0 co < L) C) 0 4-5 00 < > � !L- Z ca D If CL ui LO co 00 = — = — CC) If C 0 LO co U) M M a) 0 0 D < — LO (.0 C) < = to R— 9 — 4t 0 (N 4t 00 CY) q- a C:> Z-o — I CY) 4t O Lq (Y) CD ca to r- a) CY) Cl) 0 C) 0 'N cv) LO 11 x — 4t 0) Lo CINI < CL It fir ((D Z5 E ry U? CL • M 0) (Y) 'm — (D If z — 0 C� O 0 CN If It 0 4) = = U`) - 0 w = -5� ca 0 c) n W 0 CO co 'It C14 M 0 2 0 C 04 t- ,T CY) cu < X X o , >< Lo - 't W a) r- c 0) -a cl-co 1.0 C,4 6"T CN 0 r� x — x cr CU CU > CN to It - 0 a E cu 0 co > If 0) E It x If 00 cc 00 Co If 0 co > CL if C� > C') - 1 ('4 x (1) > z a) 4) U- C'4 - 'n .0 > a OL Lr) > = - a `o �: 0 r-- > (U C14 LO cu 00 ?i M M = 4) a) U) 00 C14 --.:- �: 3: m V) G- (L < cu o Lo 'Fu zr) Lo tl! -i LO U- C'4 if > a 00 @) w 11 > > > < U- m > b z Z 0 - CL 0 w 0 w 0 5 a. ()� (') !-� LL -j w U- n or_, LL -j U- LL -j A ,T\O. z �' 6040 5t 5- --- c k/A5TER 5EI)ROom 6 4 1O-2": 24,r. ie i:v 1 n VA5TER '-- BAT- c 2 ----- FF E+A N ;0 �'6 r m 5 l ! r-- , i c 206r 5motif1CG c Top 13cdroom 2 2 4V.I C EXnA:I�t Ah: FT`^r i �6" T UILITY p rc 2-�b F)r(fr�`:-n 3 7 2 7. — 5030 Pw 2030 246b Z Z : WA c. - -' 8046 DB?5t - 2 z._ CS16 TO WALL BELOW CS16 TO BEAM BEOW CS16 TO HEADER BEOW NOTE: ALL EXTERIOR WALLS &e GABLE ENDS TO BE SW-6 U.N.O. UPPER FLOOR SnEAR I VALLS nOa6 s: L�O vt All,OF � ItAIZ, ^;noel, KfTCmCN ' Z•JOt�r- i V � tiH � . `NVI:Y ROOM CW 4 5-'- — �- `'� a t ., vA5tD OPtN!NG 2.r 9`A .NG YrALL 1 n -o JY n - !LIVING a e3 2 Y--2 OPT. GARAGE ENTRY - GARAGE G3�5.0'. l 3�N66 °'c : 4-Q-4 =x t1• . � o Onp , Sk(-Z <A d 2 '1 ADD(1)A35 BLOCKING TO WALL TOP PLATE ADD TS22 BEAM TO WALL TOP PLATE EXTEND GARAGE DOOR HEADER TO CORNER, PROVIDE NAILING PER DETAIL B A HTT5 HOLDOWN MAY BE USED IN LIEU OF THE STHD10RJ HOLDOWN, SEE DETAIL C A HTT5 HOLDOWN MAY BE USED IN LIEU OF THE STHD10 HOLDOWN, SEE DETAIL D NOTE: ALL EXTERIOR WALLS TO BE SW-6 U.N.O. MAIN FLOOR SHEAR WALLS i t i 14' 6''H(, iYP ,i "Jr 1 t� . , ;2 a L 4- - r f� I� <i P, i o. c PAD 33-.16" 6 -«.n- TY° Ll i itf _ 1I 7 ' I i -..-. ----- - - CONCRETE STEM WALL TO BE 1"-0"ABOVE GARAGE SLAB 2 A HTT5 HOLDOWN MAY BE USED IN LIEU OF THE STHD10RJ HOLDOWN, SEE DETAIL D A HTT5 HOLDOWN MAY BE USED IN LIEU OF THE STHD10 HOLDOWN, SEE DETAIL E 4 3"x 3"x 1/4" PLATE WASHER SHALL EXTEND TO WITHIN 1/2"OF THE SHEATHING NOTE; USE 5/8" O ANCHOR BOLTS W/3" x 3" x 1/4" WASHERS k 5'-0" O.C. U.N.0 FOUNDATION PLAN WELLER CONSULTING JOB NAME PLAN 3088 w c ENGINEERS,P.C. JOB NUMBER 13-027 PREPARED BY MW .21925 8TH PL W• BOTHELL,WA 98021 DATE 5/ 14/ 13 SHEET NO. Le; OF L-1 PH. (425)488-9868 FAX(425)486-6715 TKU55E5 PER FLAN WINDOW/POOP, FKAMING ROOF SHEATHING WINDOW/DOOR HEADER VENTED 5LOCKING VKUVIPE (2) FOW5 OF Hl 0 24"O.C. &10 2"O.C. 5HEAK WALL TO HEADER DETAIL A BL iL 'NK DETAIL 5 WELLER CONSULTING JOB NAME PLAN 3088 www c ENGINEERS,P.C. JOB NUMBER 13-027 PREPARED BY MW DATE 5/ 14/ 13 SHEET NO. (-q OF L"i 21925 8TH PL W- BOTHELL,WA 98021 PH.(425)488-9868• FAX(425)486-6715 (2)2x_HF#25TUP5 (2) 2x_HF #25TUD5 HTT5 HOLPOWN HTT5 HOLC7OWN 55T616 55TB]6 KIM J015T W/50LID 6LOCKING 51LL PLATE P.T. 5 L PLATE d 6 d O a ° a d 4 ° d Q d d a a DETAIL D d d a DETAIL C MONCi. i 1 I i o ACCE55 j i i i i j i I S:RD°R'RU55 12 12 I 5-"2 ? z J _ --- -- -- ---- - — ----`- `5..` `ND GABLE END HEADERS: 4 x 8 DF # 2 U.N.O. DESIGN LOADS: NOTE.PROVIDE(9) 2 X TRIMMER ROOF DL = 15 P'SF @ ALL HEADERS U.111.0 LL = 25 PSF H1: 3 118 x 9 GLB {24F-V4} ENGINEERED TRUSSES BY TRUSS MANUFACTURER COLUMNS. NOTE:PROVIDE(2t 2X POST @ ALL HIP MASTERS & GIRDER TRUSSES U.N.O Cl: {3} 2x6HF # 2 ROOF FRAMING PLAN (ELEVATION A) —"ONO feu5`_-t8 VZ i VV j-t• i i T s t i r fl t I I I O T < r �❑ t r ; c/ I J1 I t I I i GABtf F`t`> GAB,E f�tD DESIGN LOADS: HEADERS: 4 x 8 DF#2 U.N.O. ROOF DL = 15 PSF NOTE;PRO vin E 1) 2 X TR/MMER LL = 25 PSF @ ALL HEADERS U,N.O H1: 3 1/8 x 9 GLB (24F-V4) ENGINEERED TRUSSES BY TRUSS MANUFACTURER H2: 3 1/8 x 9 GLB (24F-V4) NOTE. PROVIDE(2) 2 X POST/ALL NIP MASTERS & GIRDER TRUSSES U.N.O COLS Cl: (3) 2x6HF # 2 ROOF FRAMING L--N,- ,T (ELEVATION B) I�> 4' w L .J_ t _ s� 1 I i Q N h Z W O vC7 � t7Z � . Z O LL J W O <( OV O Q2' O p 'S O W U- 0 - . ti Q O J R NV s O Q al-= Wcn � wen .� W J `y Q Q 0 a vi ¢ CL ui lii O O z z co U �nZ W0 > 9 IT m °vctRo ci OOWO ` Z v yONN N »cj TZ ~ N a m m N m N N N N U Q Q f.7 V S LU fc/) 0 m .... N N Q y# Q cc M (n U N H N ¢ N N N -j k C N N . N LL J m m ad U. N Q N as ad # � � tLi *k ik 4k � N W rsrsL7 (D0 LL LL �} LLJ � ULL LL LL Nmcrn � o � 22 4k �k � to to O O LL S J 0 0 0 0 N 07 Qi fG w 17 LL LL h LL vj �' N r et S N W 11. co W '^! O N O % W d X X % X X X X X X X C- 0 0 X C. 0 0 0 11 11 II li r r 0 J X O Q r r r — Q Q Z N :!t N E m N N ct 00 AD v tD tD Q J J J J % J v X X X r j M M r r r X X X fL' X % 0 C) DJ NN00 % ! 00@avv ;; Mm -m V, to s y ; Nvmto0ccw � s z s 0 4 wa cri4 w � 0 O LL nLLZ s2 SSix mlZ mmmmmmmm aUL) UC0. 0 00 S2 i I I i 1 ' - J•2c �AU', 'D i r i I AC - z i j r 1 i i 1 4 � 2 i i BEAMS: 4 x 10 DF# 2 U.N.O. DESIGN LOADS: NOTE:PROVIDE 4 x 4 PAST FLOOR DL = 10 PSF car ALL BEAMS U.N.O. LL =40 PSF PROVIDE 4 x 6 POST JOISTS: 2 x 10 HF # 2 (a) 16" O C @ ALL BEAM SPLICES U.N.O. NOTE: PROVIDE LUS28 HANGERS (c� ALL FLUSH FRAMED ENDS NOTE: PROVIDE SOLID FRAMING IN JOIST SPACE TO FOUNDATION FOR ALL PT. LOADS ABOVE MAIN FLOOR FRAMING PLAN, . ^ UeanxC0ekv2012 licensed to:Weller Consulting Engineers, PC. Reg#5234-65779 PLAN 3088 ROOF FRAMING GT1 (FOR REACTIONS ONLY) Date: 5/13/13 Selection Conditions NDS2812 YNin BeahngAma 131= 12.0inzR2= 12.Oinz (1.5) DLDeM= 0,41 in Recnm Camber=0.61 in Data Beam Span 19.0 ft Reaction I LL 4750# Reaction 2 LL 4750# Beam Wt per ft 20.55# Reaction 1 TL 7795# Reaction 2 TL 7795# Max Moment 37027'# Max V(Reduced) 6667# TL Max Defl L/240 TL Actual Defi 1-1274 LL Max Defl L/360 LL Actual Defl L/538 Atttibutes Section Actual 232,55 84.56 0.83 0.42 Chdom| 164.54 3613 0.95 0.63 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E (psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2700 276 1.8 650 Adiustments Cv Volume 0.978 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:500 Uniform TL: 800 =A Uniform Load A R1 =7795 R2=7705 SPAN= 10FT Uniform and partial uniform loads are|bo per lineal ft, BeamChek v2012 licensed to: Weller Consulting Engineers, P.C. Reg#5234-65779 V PLAN 3088 ROOF FRAMING GT2(FOR REACTIONS ONLY) Date: 5/13113 Selection 5-118x 19-1/2 GLB 24F-V4 DFIDF Lu=0.0 Ft Conditions NDS 2012 Min Bearing Area R1=4.4 in2 R2=4.4 in2 (1.5) DL Defl= 1.05 in Recom Camber=1.57 in Data [Beam am Span 40.0 ft Reaction 1 LL 1500# Reaction 2 LL 1500# Wt per ft 24.28 # Reaction 1 TL 2886# Reaction 2 TL 2886# Wt Included 971 # Maximum V 2886# x Moment 28857'# Max V(Reduced) 2651 # Max Defl L/240 TL Actual Defl L/266 LL Max Defl L/360 LL Actual Defl L 1634 Attributes Section(in') Shear(in 2) TL Defl(in) LL Defl Actual E43%80 99.94 1.81 0.76 Critical 7 14.41 2.00 1.33 Status OK OK OK Ratio 14% 90% 57% Fb(psi) Fv(psi) E(psi..x mil) Fe-L (psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2465 276 1.8 650 Adjustments Cv Volume 0.893 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress NIA Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Uniform LL:75 Uniform TL: 120 =A Uniform Load A R 1-2886 R2 =2886 SPAN =40 FT Uniform and partial uniform loads are Ibs per lineal ft. i ~ " BeanKJnk v2012 licensed to: Weller Consulting Engineers, PC. Reg#5234-65779 PLAN 3088 ROOF FRAMING GT3(FOR REACTIONS ONLY) Date: 5/13/13 Selection Conditions NDS2O12 Min Bearing Area R1= 12.2 in2 R2=8.8in2 (1.5) DLUeU= 0.60 in Reoom Camber=U.9Oin Data Beam Span 19O ft Reaction 1 LL 4276# Reaction 2 LL 2224# Beam Wt per ft 2055# Reaction 1 TL 7949# Reaction 2 TL 5728# Max Moment 38500'# Max V(Reduced) 6820# TL Max Defl L/240 TL Actual Defi L/242 LL Max Defi L/360 LL Actual Defi L/667 Attributes Section � Actual 232.55 84.56 0.94 0.34 Critical 171.09 3707 O95 0.63 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi.x mil) Fc-L(psi) Values Referenc Values 2400 240 1.8 650 Adjusted Values 2700 276 1.8 650 Adfustments Cv Volume 0.978 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Point TL Distance Par Unif LL Par Unif TL Start Pt lo RI =7949 R2=5728 SPAN= 18FT Uniform and partial uniform loads are/ba per lineal ft. BeamChek v2012 licensed to: Weller Consulting Engineers, P.C. Reg#5234-65779 Vg PLAN 3088 ROOF FRAMING TYPICAL HEADER Date: 5113113 Selection 4x 8 DF-L#2 Lu=0,0 Ft Conditions NDS 2012 Min Bearing Area RI=3.5in 2 R2=3.5 in' (1.5) DL Defl= 0.05 in Data Beam Span 5,5 ft Reaction I LL 1375# Reaction 2 LL 1375# Beam Wt per ft 6.17# Reaction I TL 2217# Reaction 2 TL 2217# Bm Wt Included 34# Maximum V 2217# Max Moment 3048W Max V(Reduced) 1730# TL Max Defl L/240 TL Actual Dell L/595 LL Max Defl L 1360 LL Actual Deft L/>1000 Attributes Section_fW) Shear(W) TL Deft.Qn) LL Defl Actual 30.66 25.38 0.11 0.06 Critical 27.19 12.54 0.28 0A8 Status OK OK OK OK Ratio 89% 49% 40% 32% Fb(psi) Fv(psq E(psi x_.mil) Fc-L(psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1346 207 1.6 625 Adjustments CF Size Factor 1.300 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Uniform LL:500 Uniform TL: 800 =A Uniform Load A Z� R1 =2217 R2=2217 SPAN=5.5 FT Uniform and partial uniform loads are lbs per lineal ft. BeamChek v2012 licensed to:Weller Consulting Engineers, P.C. Reg#5234-65779 PLAN 3088 ROOF FRAMING HI Date: 5/13/13 Selection 4x 10 DF-L#2 Lu=0.0 Ft Conditions NDS 2012 Min Bearing Area R1=4.2 in 2 R2=4.2 in 2 (1.5)DL Defl= 0.05 in Data Beam Span 6.5 ft Reaction I LL 1625# Reaction 2 ILL 1625# Beam Wt per ft 7.87# Reaction 1 TL 2626# Reaction 2 TL 2626# Bm L Included 51 # Maximum V 2626# Beam xMoment 4267'�# Max V(Reduced) 2003# I TL At,(Reduced)r,�, TL Max Defl L/240 TL Actual Defl L 747 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section (in 3) Shear Qn2) TL Defl(in) LL Defl Actual 49.91 32.38 0.10 0.05 Critical 41.22 14.51 0.33 0.22 Status OK OK OK OK Ratio 83% 45% 32% 25% Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1242 207 1.6 625 Adiustments CF Size Factor 1,200 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Uniform LL:500 Uniform TL: 800 =A Uniform Load A Z� R1 =2626 R2 =2626 SPAN=6.5 FT Uniform and partial uniform loads are lbs per lineal ft. ~ u*anxCnexvzo12ocenxeoormexer PLAN 3088 ROOF FRAMING H1 Duhn�5/13/13 Selection Conditions NDS2O12 Min Bearing Area R1=33in' R2=5.3in' (1,5)DLDe8= 0.15in ReoomCamber=O23in Data Beam Span 6.5 ft Reaction 1 LL 406# Reaction 2 LL 1219# Beam Wt per ft 6.83# Reaction 1 TL 2115# Reaction 2 TL 3415# Max Moment 6838'# Max V(Reduced) 2810# TL Max Defl L/240 TL Actual Defi L/424 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section Actual 42.19 28,13 0.18 O03 Critical 29.73 15.27 O33 012 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 2400 240 18 650 Adjusted Values 2760 276 1.8 650 Adjustments Cv Volume 1.000 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1 00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Point TL Distance Par Unif LL Par Unif TL Start B=288G 3.25 500 H=8OO 3.25 8.5 Pt loads: R1 =2115 R2=3415 SPAN=G.5FT Uniform and partial uniform loads are|bs per lineal ft, BeamChek v20121icensedto: Weller Consulting Engineers, P.C. Reg#5234-65779 PLAN 3088 ROOF FRAMING H2 Date: 5/13/13 Selection 3-1/8x 9 GLB 24F-V4 DF/DF Lu=0.0 Ft Conditions NDS 2012 Min Bearing Area R1=3.5 in' R2=4.7 in 2 (1.5) DL Defl= 0.09 in Recom Camber-0,14 in LL 1091 # Data Beam Span 5.5 ft Reaction I LL 409# Reaction 2 I Beam Wt per ft 6.83# Reaction I TL 2248# Reaction 2 TL 3076# Bm Beam Included 38# Maximum V 3076# Max Moment 5596'# Max V{Reduced} 2471 # I /q'In T, ," . _, TL Max Defl L/240 TL Actual Defl L/602 LL Max Deft L/360 LL Actual Defl L/>1000 Attributes section(in 3) Shear in 2 TL Deft(in) LL Defl Actual 42.19 28.13 0.11 0,02 Critical L24.33 13.43 0.28 018 Status OK OK OK OK Ratio 58% 48% 40% 10% Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Reference Values 2760 276 1.8 650 Adiustments Cv Volume 1.000 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads F_ Point TL -Distance Par Unif LL Par Unif TL Start End B=2886 2.5 500 H=800 2.5 5.5 H B Pt loads: Z� RI =2248 R2 =3076 SPAN=5.5 FT Uniform and partial uniform loads are lbs per lineal ft. ~ ~ UeenxChekv2012 licensed to: Ne&p PLAN 3088 UPPER FLOOR FRAMING 8l4(FOR REACTION ONLY) Date:5U3/13 Selection Conditions ND02O12 �---- Min Bearing Area R1= 1.7)n' R2= 1.7in" (1.5) DLDe8= 0.31 in ReoumCamber=O.48in Data Beam Span 17.5 ft Reaction I LL 656# Reaction 2 LL 656# Beam Wtperft 7.97# Reaction 1 TL 1120# Reaction 2 TL 1120# Bm Wt Included 140# Maximum V 1120# Max Moment 4899W Max V(Reduced) 1008# TL Max Deft L/240 TL Actual Defl L/350 Attributes Section Actual 57.42 32.81 O60 O29 Chdoa| Status OK OK OK OK Ratio b(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2760 276 1.8 650 AdOstments Cv Volume 1.000 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:75 Uniform TL: 12O =A Uniform Load A R1 = 1120 R2= 1120 SPAN= 17.5FT Uniform and partial uniform loads are|bo per lineal ft. ~ BeamChek v2012 licensed to: Weller Consulting Engineers, PC. Reg#5234-65779 PLAN 3088 UPPER FLOOR FRAMING TYPICAL JOIST Date: 5/13/13 | Selection � Conditions ND82012. Repetitive Use Min Bearing Area R1 1O/ z R Data Beam Span 12.0 ft Reaction I LL 320# Reaction 2 ILL 320# Beam Wt per ft 0# Reaction 1 TL 400# Reaction 2 TL 400# Max Moment 1200'# Max V(Reduced) 337# FTL Max Defl L/29,40 TL Actual Defl L/975 LL Max Defi L/360 LL Actual Defl L/>1000 Attribute Section Actual 31 64 16.88 0.15 0.11 Critical 14.73 3.37 O60 0.40 Status OK OK OK OK Ratio E47% 20% 25% 27% Fb(psi) Fv(psi) E(DSi X Mil) Fc-L(psi) Values Reference Values 850 150 1.3 405 Ad'usted Values 978 150 1.3 405 8diustments CF Size Factor 1.000 Cd F Duration 1.00 1.00 Cr Repetitive 1.15 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:53 Uniform� Uniform Load A RI 400 ---^ R2=400 SPAN= 12FT Uniform and partial uniform loads are/bm per lineal ft. ` ~ BeanKChekv2O/2licensed to: Weller Consulting Engineers, PC. Reg#5234-65779 PLAN 3088 UPPER FLOOR FRAMING FJ1 Date: 5/13/13 Selection Conditions ND82012. Repetitive Use Min Bearing Area R1= 1.1in' R2= 1.1in' (1.5)DLDeU= 0.15in Data Beam Span 18.0 It Reaction 1 LL 360# Reaction 2 LL 360# Beam Wt per ft 0# Reaction 1 TL 450# Reaction 2 TL 450# Max Moment 2025 # Max V(Reduced) 403# TL Max Defl L/240 TL Actual Defl L/385 8ftfibutes Section Actual 31.64 1688 O56 0.41 Chi|co| 24.86 4.03 090 0.60 Status OK OK OK OK Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 850 150 1.3 405 Adjusted Values 978 150 1.3 405 Adjustments CF Size Factor 1.000 Cd Duration 1.00 1 00 Cr Repetitive 1.15 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:4O Uniform TL: 5O =A Uniform Load A RI =450 R2=450 SPAN= 18 FT Uniform and partial uniform loads are|bm per lineal ft. ^ ` ymm/nChexv2o7zxm*nxeutzmexo/ConmumnQ PLAN 3088 UPPER FLOOR FRAMING TYPICAL HEADER Date: 5/13/13 Selection Conditions NDS2Q12 Min Bearing Area R1=2.1 in z R2 2 1 i z (1 5) DLD M 001 in Data Beam Span 4O ft Reaction I LL 860# Reaction 2 LL 860# Beam Wt per ft 6.17# Reaction I TL 1282# Reaction 2 TL 1282# Max Moment 1282W Max V(Reduced) 895# TL Max Defi L/240 TL Actual Defi L/>1000 LL Max Defi L/360 LL Actual Def! L/>1000 Attributes Section Actual 30.66 25.38 0.02 0.01 Ch8ua| Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1170 180 1.6 625 AdiusVments CF Size Factor 1300 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use I 00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:380 Uniform TL: 475 =A Par Unif LL Par Unif TL Start 7En� 50 H =8O O 4.0 / =8Q 0 4.0 Uniform Load A R1 = 1282 R2= 1282 SPAN=4FT Uniform and partial uniform loads are|bm per lineal ft. ^ aeunxCnexv2o/2licensed to: Weller Consulting Engineers, P C. Reg#5234-65779 PLAN 3088 UPPER FLOOR FRAMING H3 Date:5/13/13 Selection Conditions NDS2O12 K8in8eehn A R1 28iz R2 28) a (15) DLOU 0.08 in Data Beam Span 8.5 ft Reaction I LL 1063# Reaction 2 LL 1063# Beam Wt per ft 7,87# Reaction 1 TL 1733# Reaction 2 TL 1733# Max Moment 3684'# Max V(Reduced) 1419# TL Max Def! L/240 TL Actual Defl L/660 LL Max Defl L/360 LI-Actual Defl L/>1000 Attributes Section Actual 49.91 32.38 OA5 0.08 Chdoa[ 35.59 10.28 0.43 0,28 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 900 180 1,6 625 Adjusted Values 1242 207 1.6 625 8diustments CF Size Factor 1.200 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:25O Uniform TL: 4OO =A Uniform Load A R1 = 1733 R2= 1733 GR4M =8,5FT Uniform and partial uniform loads are lbs per lineal ft. ^ u*a/nchoxv2u/z licensed to: Weller PLAN 3088 UPPER FLOOR FRAMING H4 Date: 5/13/13 Selection Conditions ND82O12 k8)n BemhngAneo R1=2.2in' R2=2.2in2 (1�5)OLDoM= 0.26 in Data Beam Span 16.5 ft Reaction I LL 825# Reaction 2 LL 825# Beam Wt per ft 9.57# Reaction I TL 1399# Reaction 2 TL 1399# Max Moment 5771 '# Max V(Reduced) 1240# TL Max Defi L/240 TL Actual Defl L/387 Attributes S 0 Actual 73.83 39.38 0.51 0.25 Chdoa| Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1139 207 1.6 625 Adjustments CF Size Factor 1.100 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1 00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0,00 Ft Loads Uniform LL: 1OO Uniform TL: 180 =A Uniform Load A R1 = 1399 R2= 1399 SPAN = 18,5FT Uniform and partial uniform loads are|ba per lineal ft. ^ uoaoxCn*xv2o7z licensed to: mexer PLAN 3088 UPPER FLOOR FRAMING H5 Date: 5/13U3 Selection Conditions NDS2O12 Min 8eahngAmea R1=3,3 in' R2=3.3in2 (1.5) OLDeO= 0,04 in Data Beam Span 6.5 ft Reaction I LL 1398# Reaction 2 LL 1398# Beam Wt per ft 7.87# Reaction I TL 2089# Reaction 2 TIL 2089# Max Moment 3395'# Max V(Reduced) 1594# TL Max Def! L/240 TL Actual Defl L/943 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section Actual 49.91 3238 0.08 0.05 Critical 37.72 13.28 0.33 O22 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1080 180 1.6 625 Adiustments CF Size Factor 1.200 Cd Duration 1.00 1 00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:380 Uniform TL: 475 =A Par Unif LL Par Unif TL Start 50 H=O0 O 0.5 | =8U U 0.5 Uniform Load A R1 =2088 R2=2089 SPAN=8.5FT Uniform and partial uniform loads are|ba per lineal ft. ^ oeom^'mwv^v'2 licensed to: ,.mle, ^"°""",*Engineers, . `^ '` PLAN 3088 UPPER FLOOR FRAMING HM Date: 5/13/13 Conditions NDS2O12 N)i Beah Area 131 8O in2 R2=84in2 (1 5)DLDe8= O 12 in Reonm Combor=U 19 in Data Beam Span 65 ft Reaction I LL 1516# Reaction 2 LL 2324# Bm Wt Included 73# Maximum V 5444# Max Moment 10282'# Max V(Reduced) 4438# TL Max Dell L/240 TL Actual Defl L/468 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section(in 3) Shear(W) TL efl LD fl Actual 69A9 46.13 0.17 0.04 Critical 44.71 24.12 0.33 0.22 Status OK OK OK OK Fb(psi) Fv(psi) E(psi x mil) -.Fc-L(psi) Values Reference Values 2400 240 18 650 Adjusted Values 2760 276 1.8 650 Adjustments Cv Volume 1.000 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1 00 1.00 1.00 Cl Stability 1.0000 Rb O00 Le 0.00 Ft Loads Uniform LL:360 Uniform TL: 450 =A Point TL Distance Par Unif LL Par Unif TL Start End |=OU 0 O.5 F- Uniform Load A Ftloads: R1 =3889 R2=5444 SPAN =8�5FT Uniform and partial uniform loads are|bo per lineal ft. , ° uoamco*xvzu/z licensed to: Weller Consulting PLAN 3088 UPPER FLOOR FRAMING B1 Date: 5/13/18 Selection Conditions NDS 2012 Min Bearing Area R1=3.1 in' R2=3.1 inz (1.5)DLDeO= 023 in Raoom Camber=O.35in Data Beam Span 12.5 ft Reaction 1 LL 1063# Reaction 2 LL 1063# Beam Wt per ft 7.97# Reaction 1 TL 1987# Reaction 2 TL 1987# Max Moment 6210'# Max V(Reduced) 1709# TL Max Def! L/240 TL Actual Def! L/367 Attributes Attributes Section LLDmfl Actual 57.42 3281 OA1 0.17 Chhoa| 31.05 10.68 0.63 0.42 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2400 240 1.8 650 Adiustments Cv Volume 1.000 Uniform Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1 00 1.00 Cl Stability 1.0000 Rb 0.00 Le O00 Ft Loads 0 Uniform TL 150 =A Par Unif LL Par Unif TL Start End | =8O U 12.5 Uniform Load A R1 = 1987 R2= 1987 SPAN = 12,5FT Uniform and partial uniform loads are|bn per lineal ft. ^ oeux^^m° ~^.,2 licensed to: Weller Consulting Engineers, PLAN 3088 UPPER FLOOR FRAMING B2 Date: 5/13/13 Selection 6-3/4x 19-1/2 GLB 24F-V4 DF/DF Lu=0.0 Ft Conditions NDS2012 Min Bearing Area R1=21 1inxR2=21 1in2 (15) DLDeO= 0,40 in ReoomCamber=UGUin Data Beam Span 20.0 ft Reaction 1 LL 8400# Reaction 2 LL 8400# Beam Wt per ft 31.98# Reaction I TL 13720# Reaction 2 TL 13720# Max Moment 68599'# Max V(Reduced) 11490# D8 Attributes Section Actual 427.78 131.63 0.82 0.42 Chdoe| 32027 62.45 1.00 O67 Status OK OK OK OK Ratio Fb(psi) Fv.(psi) E(psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2570 276 1.8 650 Adjustments Cv Volume 0.931 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL 240 Uniform TL: 300 =A Par Unif LL Par Unif TL Start End (=80 0 200 Uniform Load A R1 = 13720 R2= 13720 SPAN =2OFT Uniform and partial uniform loads are|bm per lineal ft. ~ uoanxCnexv2u12 licensed to: vveoeruonuumng Engineers, PC. PLAN 3088 UPPER FLOOR FRAMING B3 Date:5/13/13 Selection Conditions NDS2O12 MinBearingArea R1=4.0in' R2 40 in a (1.5) DLD O 0.18 in Data Beam Span 12.5 ft Reaction 1 LL 719# Reaction 2 LL 719# Max Moment 5123W Max V(Reduced) 1393# TL Max Defl L/240 TL Actual Defl L/540 LL Max Def! L/360 LL Actual Defl L/>1000 Attributes Section Actual 94.92 50.63 0.28 0.09 Critical 62.89 12.12 O63 0.42 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 850 150 1.3 405 Adjusted Values 978 173 1.3 405 4diustments CF Size Factor 1.000 Cd Duration 1.15 1,15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:40 Uniform TL: 50 =A Par Unif LL Par Unif TL Start End 75 H= 120 O 12.5 |=80 O 12.5 Uniform Load A R1 = 1639 R2= 1039 SPAN= 12,5FT Uniform and partial uniform loads are|bn per lineal ft. " ° uounKJe6 PLAN 3088 UPPER FLOOR FRAMING B4 Date: 5/13/13 Conditions NDS 12 Data Beam Span 6'0 ft Reaction 1 LL 1380# Reaction 2 LL 1380# Beam Wt per ft 6.17# Reaction 1 TL 1743# Reaction 2 1743# Max Moment 26 '# Max V(Reduced) 1392# TL Max Defl L/240 TL Actual Defl L/685 LL Max Defl L/360 ctual Defl L/956 Actual 30.66 25.38 0.1 .08 Critical 26.82 11.60 0.30 0,20 Status OK OK OK OK Values Reference Values 900 180 1.6 625 I Adjusted Values 1170 180 1.6 625 Cd uration 1.00 1.00 Cr Repetitive 1.00 Ch Shear ess N/A CI ility 1 0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:460 Uniform TL: 575 =A Uniform Load A R1 = 1743 �--` x2= 1743 SPAN=6FT Uniform and partial uniform loads are|by per lineal ft, � � B=a'"^=" ,2"'^licensed to: Weller Consulting~ PLAN 3088 UPPER FLOOR FRAMING B4 [ate: 5/13/13 Conditions NDS2O12 MinBearingArea R1=08inz R2=68in2 (1.5) DL Defi= 019in Rocom Camber=O2Qin Data Beam Span 15.0 ft Reaction 1 LL 3450# Reaction 2 LL 3450# Beam Wt per ft 17.22# Reaction 1 TL 4442# Reaction 2 TL 4442# Max Moment 16656 # Max V(Reduced) 3923# TL Max Defi L/240 TL Actual Defl L/282 LL Max Defl L/360 LL Actual Defl L/403 Attributes TL Deft LDeO Actual 124.03 70.88 0.64 0.45 Chdou| 83.28 2452 0.75 0.50 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2400 240 1.8 650 Adiustments Cv Volume 1.000 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:4O0 Uniform TL: 575 =A Uniform Load A R1 =4442 R2=4442 GRAN= 15 FT Uniform and partial uniform loads are|bs per lineal ft, * ooan/Cnekvzo7z licensed to: Weller Consulting PLAN 3088 UPPER FLOOR FRAMING Bx Date: 5/13/13 Selection Conditions NDS2O12 Min Bearing Area R1=3.8in2 R2=3.8/n2 (1�5)DLDeO= <0.01 /n. Data Beam Span 4,5 ft Reaction 1 LL 1215# Reaction 2 LL 1215# Beam Wtperft 8.2# Reaction 1 TL 1537# Reaction 2 TL 1537# Max Moment 1729 # Max V(Reduced) 897# TL Max Defl L/240 TL Actual Defl L/>1000 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section i " Shear Actual Chdoul 24A1 8.97 0.23 0.15 Status OK OK OK OK Ratio b(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 850 150 1.3 405 Adjusted Values 850 150 1.3 405 Adiustments CF Size Factor 1.000 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1 00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:54U Uniform TL: 87S =A Uniform Load A R1 = 1537 R2= 1537 SPAN=4.5FT Uniform and partial uniform loads are|ba per lineal ft. � ° WellerConsulting Engineers, PC. Reg#5234-65779 PLAN 3088 UPPER FLOOR FRAMING BG Dote: 5/13/13 Selection 5-118x 21 GLB 24F-V4 DF/DF Lu=0.0 Ft Conditions NDS2O12 KAkn8eehn Anym R1 2O8i zR2 2O8/nz (15) DLDefl 0.48 in Recom Camber--0.72 i Data Beam Span 21O ft Reaction 1 LL 8295# Reaction 2 LL 8295# Beam Wt per ft 26,15# Reaction I TL 13505# Reaction 2 TL 13505# Max Moment 70899W Max V(Reduced) 11254# TL Max Defl L/240 TL Actual Defl L/256 LL Max Def! L/360 LL Actual Defi L/500 Attributes Section Actual 376.69 107.63 O98 0.50 Critical 32600 61.16 1.05 0.70 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E (psi x mil) Fc-L(psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2610 276 1.8 650 Adfustments Cv Volume 0.946 Cd Duration 1A5 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:240 Uniform TL: 300 =A Par Unif LL Par Unif TL Start End 550 H=88O O 21.0 1 --80 O 21.0 Uniform Load A R1 = 13505 R2= 13505 SPAN=21FT Uniform and partial uniform loads are|bm per lineal ft, 4 b BeamCttek v2012 licensed to: Weller Consulting Engineers, P.G. Reg#5234-65779 vn r PLAN 3088 UPPER FLOOR FRAMING B7 Date: 5/13/13 Selection 5-1/8x 9 GLI3 24F-V4 DF/DF Lu=0.0 Ft Conditions NOS 2012 Min Bearing Area R1=3.5 in2 R2= 1.8 in2 (1.5)DL Defl= 0.29 in Recom Camber=0.43 in Data FTL m Span 12.0 ft Reaction 1 LL 1013# Reaction 2 LL 338# m Wt per ft 11.21 # Reaction 1 TL 2247# Reaction 2 TL 1167# Wt Included 135# Maximum V 2247# Moment 6802'# Max V(Reduced) 1969# ax Deft L/240 TL Actual Deft L/374 1.LL Max Deft L/360 LL Actual Defl L/>1000 Attributes Section (in3) Shear(in2) TL Defl(in) LL Defl Actual L29�57 9 46.13 0.39 0.10 Critical 10.70 0.60 0.40 Status OK OK OK Ratio 23% 64% 25% Fb(psi) Fv(psi) E psi x mil) Fc I (psi) Values Reference Values 2400 240 1.8 650 Adjusted Values 2760 276 1.8 650 Adjustments Cv Volume 1.000 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Point TL Distance Par Unif LL Par Unif TL Start End B= 1120 6.0 225 H=360 0 6.0 H Pt loads: R1-2-247 R2= 1167 SPAN= 12 FT Uniform and partial uniform loads are Ibs per lineal ft. BearnChek v2012 licensed to: Weller Consulting Engineers, P.C. Reg#5234-65779 VG PLAN 3088 UPPER FLOOR FRAMING B8 Date: 5113113 Selection 5-1/8x 9 GLB 24F-V4 DF/DF Lu=0.0 Ft Conditions NDS 2012 Min Bearing Area R1= 1.6 in' R2= 1.6 in' (1.5) DL Deft= 0.22 in Recom Camber--0,33 in Data Beam Span 16.0 ft Reaction I LL 600# Reaction 2 LL 600# Beam Wt per ft 11.21 # Reaction I TL 1050# Reaction 2 TL 1050# Bm Wt Included 179# Maximum V 1050# Max Moment 4199W Max V(Reduced) 951 # L I TL Max Defl L/240 TL Actual Defl L/459 LL Max Defl L/360 LL Actual Defi L/975 Attributes Section(in' Shear QnD TL Defl(in) LL Deft Actual 69.19 46.�13 0.42 0.20 Critical 1& 5 26 .17 0.80 0.53 Status OK OK OK OK 11% 1 1, Ratio 26% 52% 37% Fb psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference'Values 2400 240 1.8 650 1 Adjusted Values 2760 276 1.8 650 Adjustments Cv Volume 1.O O0 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Uniform LL:75 Uniform TL: 120 =A Uniform Load A Z� R1 - 1050 R2= 1050 SPAN = 16 FT Uniform and partial uniform loads are lbs per lineal ft. BeamChek v20121icensed to: Weller Consulting Engineers, P.C. Reg#5234-65779 V-71 PLAN 3088 MAIN FLOOR FRAMING TYPICAL JOIST Date:5/13113 Selection 2x 10 NF#2 @ 16 in oc Lu=0.0 Ft Conditions NDS 2012, Repetitive Use Min Bearing Area R1= I.1 in 2 R2= 1.1 in 2 (1.5)DL Defl= 0.10 in Data Beam Span 13.0 ft Reaction I LL 347# Reaction 2 LL 347# Beam Wt per ft 0# Reaction 1 TL 433# Reaction 2 TL 433# Beam Wt Included 0# Maximum V 433# Max Moment 1408W Max V(Reduced) 382# TL Max,Def) L/240 TL Actual Defl L/426 LL Max Defl L 1360 LL Actual Defl L 1586 Attributes Section(inD Shear(W) TL Dell (in) LL Deft Actual 21.39 13.88 0.37 0.27 Critical 15.72 3.82 0.65 0.43 Status OK OK OK OK Ratio L_73% 28% 56% 61% Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 850 150 1.3 405 Ad Adjusted Values 1075 150 1.3 405 Adjustments CF Se Factor 1.100 Cd Duration 1.00 1.00 Cr kRepetitive 1.15 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Uniform LL:53 Uniform TL: 67 =A Uniform Load A R1 =433 Z� R2=433 SPAN= 13 FT Uniform and partial uniform loads are lbs per lineal ft, � � � MeanxCo*xv2V7x licensed to: Ne8orConoultinP Engineers, PC. Reg#5234-05779 PLAN 3088 MAIN FLOOR FRAMING TYPICAL BEAM Date: 5/13/13 Selection Conditions NDS2U12 Min Bearing Area R1=3.8 in' R2=3.8|n" (1.5) DLDa8= 0.01 in Data Beam Span 4.0 ft Reaction 1 LL 1880# Reaction 2 LL 1880# Beam Wt per ft 6.17# Reaction 1 TL 2362# Reaction 2 TL 2362# Bm Wt Included 25# Maximum V 2362# Max Moment 2362W Max V(Reduced) 1649# TL Max Defl L/240 TL Actual Defl L/>1000 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section i Actual 30.66 2538 0.04 0.03 ChUoo| 24.23 1174 0.20 0.13 Status OK OK OK OK Ratio Fb(psi) Fv(psi) E(psi x mil) Fc-L(psi) Values Reference Values 900 180 16 625 Adjusted Values 1170 180 1.6 625 Adjustments CF Size Factor 1.300 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1,00 1.00 1.00 1.00 Cl Stability 1.0000 Rb 0.00 Le 0.00 Ft Loads Uniform LL:Q4O Uniform TL: 1175 =A Uniform Load A R1 =2362 R2 =2362 SPAN=4FT Uniform and podio|uniform loads are|bm per lineal ft, ,rte N BeamChek v2012 licensed to: Weller Consulting Engineers, P.C. Reg#5234-65779 ` f PLAN 3088 MAIN FLOOR FRAMING TYPICAL BEAM Date:5113113 a Selection 4x 10 DF-L#2 Lu=0.0 Ft Conditions NDS 2012 Min Bearing Area R1=3.6 ins R2=3.6 ins (1.5)DL Deft= 0.01 in Data Beam Span 5.5 ft Reaction 1 LL 1760# Reaction 2 LL 1760# Beam Wt per ft 7.87# Reaction 1 TL 2222# Reaction 2 TL 2222# Bm Wt Included 43# Maximum V 2222# Max Moment 3055'# Max V{Reduced} 1599# TL Max Deft L/240 TL Actual Defl L/>1000 LL Max Defl L/360 LL Actual Defl L/>1000 Attributes Section in-) Shear(in2) TL Defl(in) LL Defl Actual 49.91 32.38 0.05 0.04 Critical 33.94 13.32 0.28 0.18 Status OK OK OK OK Ratio 68% 41% 18% 19% Fb(psi) Fv(psi) E psi x mil} Fc I (psi) Values Reference Values 900 180 1.6 625 Adjusted Values 1080 180 1.6 625 Adiustment I CF Size Factor 1.200 Cd Duration 1.00 1.00 [Ch r Repetitive 1.00 Shear Stress N/A m Wet Use 1.00 1.00 1.00 1.00 I Stability 1.0000 Rb=0.00 Le=0.00 Ft Loads Uniform LL:640 Uniform TL: 800 =A Uniform Load A RI-222222 R2=2222 SPAN=5.5FT Uniform and partial uniform loads are Ibs per lineal ft.