2603 Structural Calcs STRUCTURAL CALCULATIONS FOR THE SOUNDBUILT HOMES RESIDENTIAL PROJECT Plan 2603 June 26, 2013 SOT MB1yV�T WASyt�B 1 �C s� O ' 6 3 266[x+ Wk, RAL SS�ONALE�b Job No. : 12-034 Location: King County, Washington SEGA Engineers, Structural &Civil Consulting Engineers 22939 SE 292nd PL (360)886-1017 Black Diamond,WA 98010 Copyright 2013,SEGA Engineers STATEMENT OF WORK SEGA Engineers was asked to provide a lateral loads analysis, shear wall design, review of major framing members and foundation, and drawing review for a two story wood framed single family residence. The roof framing is both 2x rafters and manufactured trusses, the floor framing is 2x dimensional or wood (- joists, and the foundation is typical concrete strip footings with a crawl space. The attached calculations are to be used as a `basic' submittal for several potential building sites. The cover sheet should have an original signature in blue ink over the seal. Application and use for individual lots or sub-divisions shall be specifically identified by separate letter for each location. The contractor assumes all responsibility and liability for sites not expressly reviewed and approved. SEGA Engineers will use that degree of care and skill ordinarily exercised under similar circumstances by members of the engineering profession in this local. No other warranty, either expressed or implied is made in connection with our rending of professional services. For any dispute, claim, or action arising out of this design, SEGA Engineers shall have liability limited to the amount of the total fee received by SEGA Engineers for this submittal. Questions regarding the attached should be addressed to SEGA Engineers. Greg Thesenvitz, PE SEGA Engineers SEGA Engineers, Project Plan 2603 Structural&Civil Consulting Engineers Job No. 12-034 By: GAT 22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010 Checked Date: 06/26/13 Sht i Design Criteria International Building Code (IBC), 2012 LOADS Roof DL 15 psf LL 25 psf Floor DL 10 psf LL 40 psf Wind Risk Category II Design Wind Speed 110 mph (V,,,t) KZt 1.00 Exposure B Seismic Design Category D SDS 1.00 Response Factor 6.5 CS= 0.154 Importance Factor 1.00 Soil Allowable Bearing 1,500 psf Copyright 2013,SEGA Engineers SEGA Engineers, Project Plan 2603 Structural&Civil Consulting Engineers Job No. 12-034 By: GAT 22939 SE 292nd PL (360) 886-1017 Black Diamond,WA 98010 Checked Date: 03/21/12 Sht 1 LOADS ROOF DL Roofing(Comp) 3.5 psf '/p"CSB 1.8 2 x @ 24" 3.5 Insulation 1.1 5/8" GWB 2.8 Misc. 1.5 14.2 psf LL Snow, Pt 25 psf (115% Load Duration) Reduction, Cs 0.00 (Ct= 1.1, other surfaces) 5/12 pitch = 23 deg Total Roof Load 39.2 psf FLOOR DL Flooring 0.5 psf 3/4" Plywood 2.3 2x12 @16"oc 3.3 5/8"GWB 2.8 Misc. 1.5 10.4 psf LL Residential 40 psf Total Floor Load 50.4 psf DECKS DL 2 x Decking 4.3 psf 2x10 @16"oc 2.8 Misc 1.5 8.6 LL Residential 40 psf Total Deck Load 48.6 psf WALLS DL Siding 3.5 '/Z"Plywood 1.5 psf 2x6 @16" oc 1.7 Insul 0.6 '/Z"GWB 2.2 9.5 psf Copyright 2012,SEGA Engineers SEGA En ineers PROJECT Structural & Civil Consulting Engineers JOB NO. �Z—d��. FIGURED BY 22939 SE 292nd Place C Black Diamond, Washington 98010 CHECKED BY DATE Y ZI/j, SHEET 7 OF (360) 886-1017 r>=,Ayv1 i,,--'b - 4q to?4ft _ Boaz ��►-� e G��� - �oN r. 11 � = D 1 `[r 0"z1K �119''S�)3 V f -7':5' 7- --1O'� ki ,r1 1/ L 7" Z 3z� 1✓1� ( ,"� ) ��'� — ( �, s'�to?t-'1r � t �= !�r`7x "'" l�S"` 5e41/' 1� Copyright 2012,SEGA Engineers SEGA Engineers PROJECT Structural & Civil Consulting Engineers �L ?J.,0-3 JOB NO. 1Z .03 FIGURED BY ��' 22939 SE 292nd Place Black Diamond,Washington 98010 CHECKED BY DATE'—I//, SHEETS OF (360) 886-1017 e ZLi✓, A-, Y 1P 8 P T;q'M 'ty A-, Wti w. •`C-'��(s����-add rte- +- ���( ¢� ►��� - 1� ���"� �}-,��- 3•sK +tai �-�►- M ' ��-��I'`�(..�') -- (c�►�(�,I►�»)( �� � /��1 cr 3'lz x�o, r G-us 4-.- zr- w t io0 9'Lr IL OIL r-z Copyright 2012,SEGA Engineers SEGA Engineers Project Plan 2603 Structural&Civil Consulting Engineers Job No. 12-034 By: GAT 22939 SE 292nd PL (360)886-1017 Black Diamond,WA 98010 Checked Date: 06/26/13 Sht. LATERAL LOADS - (Alternate ASD) SEISMIC Maximum Base Shear,V= F SoS W Eq. 12.14-11 R where, F= 1.1 Two-Story Building SoS= 1.00 Ss = 1.5 Fa = 1.00 (Table 11.4-1, SS> 1.25) R= 6.5 Table 12.14-1 W = Seismic Weight For W: W.ot= ( 40ft) ( 36ft) (16 psf)+ ( 2 ) ( 40ft+ 36ft) ( 4.0ft ) ( 9.5psf) = 29kips Wryoor= (40ft) ( 42ft) (14 psf)+ ( 2 ) ( 40 ft+ 42ft ) ( 8.5 ft ) ( 9.5 psf) = 37 kips W total = 66 kips Design Base Shear ,V= ( .169 ) (66 kip ) = 11.1 kip E = 11.1 kip_ = 7.9 kip WIND Design Wind Pressure, pg = X Kn p630 Eq. 28.6-1, Sect. 28.6.3 where, = 1.00 0- 15 ft Exposure B Figure 28.6-1 = 1.00 20 ft = 1.00 25 ft = 1.00 30 ft Kri= 1.00 Section 26.8 P30 = 17.7 psf 110 mph Figure 28.6-1 (ASD) PU.15= ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf (x 0.6= 10.62 psf) P20 = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf (x 0.6= 10.62 psf) P25 = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf (x 0.6= 10.62 psf) P30 = ( 1.00 ) ( 1.00 ) (17.7 psf) = 17.70 psf (x 0.6= 10.62 psf) Design Base Shear: (Wind) V11b= ( 40ft) ( 10ft) (17.7 psf) + (40ft ) ( 5ft) (17.7 psf) + ( 40ft) ( 5ft ) (17.7 psf) + (40ft ) ( 1ft) (17.7 psf) =14.9 x 0.6 8.9 kips V,jS= ( 44ft) ( 10ft) (17.7 psf) + (43ft) ( 5ft) (17.7psf) + ( 39ft) ( 5ft) (17.7 psf) + ( 29ft) ( 2ft ) (17.7 psf) =1 6.1 x 0.6 9.6 kips Therefore, Wind Loads Govern for Lateral Design - Front/Back Wind Loads Govern for Lateral Design-Side/Side Copyright 2013,SEGA Engineers SEGA Engineers PROJECT �Lp'.j -Z Structural & Civil Consulting Engineers 03 JOB NO. )Z_O 3 4 FIGURED BY Gl� 22939 SE 292nd Place Black Diamond, Washington 98010 CHECKED BY DA'I'S Z��Z SHEET 5OF (360) 886-1017 Zi •V ',r' n,°�P��Fr. ZiZ 5(e) Az-f '7ZI -jz '-oaf 1b �o�aL•• ® � Vf4 l S l yr = � 3C,4, � 1��►��,,� h t D f,N")`1'vrr ✓`: ��S' 4415 t g Copyright 2012,SEGA Engineers SEGA Engineers / PROJECT structural & Civil Consulting Engineers �L�� 3 JOB NO. 1 Z —O 3 � FIGURED BY C-,A- 22939 SE 292nd Place Black Diamond,Washington 98010 CHECKED BY DATE 11? SHEET(p OF (360) 886-1017 14'4u— / s/&r/ CO"J r) - W46L I 40 — p. Z-7 l VP V COQ�• 'I / - f7i 71L /Z 7, c, ve- / 1X.0 � rt Ir Vr 00"P::�' ) 't 1127 �L = cf e V-A-0 pti N r r Copyright 2012,S£GA Engineers SEGA Engineers PROJECT �l p�, zt,0 3 Structural & Civil Consulting Engineers JOB NO. 7 �p 3 FIGURED BY 22939 SE 292nd Place Black Diamond,Washington 98010 CHECKED BY DATE .�f�L SHEET'/ OF (360) 886-1017 C0IrL.0I " IZl' �lcy y 6 Z / � Copyright 2012,SEGA Engineers SEGA Engineers PROJECT PLAN 2603 Structural & Civil Consulting Engineers 22939 SE 292nd Place • Black Diamond, Washington 98010 JOB No. 12-034 FIGURED BY GAT T (360) 886-1017•FAX 886-1016 Q Q CHECKED BY DATE 03/21/12 SHEET 8 OF 8 SHEAR LUALL KEY PLAN -j" I E, _ LA t 9f UPPER FLOOR A • 1,338 80 FT 1 i 1-9TA30-FOR 4 61LL TO 3x BLOCKlY RYP.2 PLACES! l MAIN FLOOR A A •162 40 FT A• 614 8Q FT Lj o A•414 5Q F1 re. ❑ —O ' 4 L M.OF L F2 \ % a g \ 2 0 £ 5 (1) c \ 0 \ / z E 2 _ / § a § ƒ k \ CL ± c \ \ _ \ c \ ° k n / / % 0 2 0 _ ° \ \ \ \ o 0 c � = e w = 2 / ± % $ ®_ a 0 5 m c a = a \ \ 0 0 0 E _ a a { } / § \ .( 0 -0 X C: V = % & Q o ° / $ _ / n = § % m 2 = nw n = 0 c �� \ f \ \ ® : y ) 3 \ E E \ 2 \ t a # G ® 2 \ 2 / 'ƒ 2 \ -0 c e c g . d d / \ \ ( / f \ - ƒ \ \ � n ± (EE, o d / n a 2$ k a G \ o n 2 2 p p / �� § \ \ f 0c- - \00 c 6 \ \_ 3 7 f q b ~ S % 0 _ � ° � /_ / / � = / \ 3 / \< ?5 0 ° E 0 2 7 \ $ 0 .� 2 o 14 2 L ¥ @ Q . . / A A A \ TL C/)