2068 Energy Calcs 'Orescriptive Energy Code Compliance for Climate Zones 6, 5 and Marine 4
'rcjECt Information Contact Information
2068
This project will use the requirements of the Prescriptive Path below and incorporate the
the minimum values listed. In addition, based on the size of the structure, the appropriate
number of additional credits are checked as chosen by the permit applicant.
Authorized Representative Date -
Climate Zone 5 & Marine 4 6
R-Value' U-Factor a R-Valuea U-Factor"
Fenestration U-Factor b n/a 0.30 n/a 0.30
Skylight U-Factor n/a 0.50 n/a 0.50
Glazed Fenestration SHGCb'e n/a n/a n/a n/a
Ceiling 49' 0.026 49 0.026
Wood Frame Wall9k1 21 int 0.056 21+5ci 0.044
Mass Wall R-Value' 21/21'' 0.056 21+5" 0.044
Floor 309 0.029 309 0.029
Below Grade Wall`k 10/15/21 int+ TB 0.042 10/15/21 int +TB 0.042
Slabs R-Value & Depth 10, 2 ft n/a 10, 4 ft n/a
*Table R402.1.1 and Table R402.1.3 Footnotes included on Page 2.
Each dwelling unit in one and two-family dwellings and townhouses, as defined in Section 101.2 of the
International Residential Code shall comply with sufficient options from Table R406.2 so as to achieve the
following minimum number of credits:
❑1. Small Dwelling Unit: 0.5 points
Dwelling units less than 1500 square feet in conditioned floor area with less than 300 square feet of fenestration
area. Additions to existing building that are less than 750 square feet of heated floor area.
E2. Medium Dwelling Unit: 1.5 points
All dwelling units that are not included in#1 or#3, including additions over 750 square feet.
❑3. Large Dwelling Unit: 2.5 points
Dwelling units exceeding 5000 square feet of conditioned floor area.
Table R406.2 Summary
Option Description Credit(s)
la Efficient Building Envelope 1a 0.5 ❑
lb Efficient Building Envelope 1b 1.0 ❑
1c Efficient Building Envelope 1c 2.0 ❑
2a Air Leakage Control and Efficient Ventilation 2a 0.5 ❑
2b Air Leakage Control and Efficient Ventilation 2b 1.0 ❑
2c Air Leakage Control and Efficient Ventilation 2c 1.5 ❑
3a High Efficiency HVAC 3a 0.5 ❑
3b High Efficiency HVAC 3b 1.0 ❑
3c High Efficiency HVAC 3c 2.0 ❑
3d High Efficiency HVAC 3d 1.0 ❑
4 High Efficiency HVAC Distribution System 1.0 ❑
5a Efficient Water Heating 0.5 ❑
5b Efficient Water Heating 1.5 ❑ 1.5
6 Renewable Electric Energy 0.5 `1200 kwh 0.0
Total Credits 1.50
*Please refer to Table R406.2 for complete option descriptions
http://www.energv.wsu.edu/Documents/2012`/`2ORes`/`2OEnergy.pd f
Glazing Schedule
Project Information Contact Information
2068
R402.3.3 Exception (15 sq. ft. max.)
Vertical Glazing (Windows and glazed doors)
Plan Component Glazing Width Height Glazing
ID Description Ref. U-factor Qt. Feet Inch Feet inch Area UA
Entry 0.30 1 1 5 5.0 1.50
Living Room 0.30 2 2 6 24.0 7.20
Living Room 0.30 1 5 6 30.0 9.00
Dining Room 0.30 1 5 5 25.0 7.50
Kitchen 0.30 1 115 14 6 22.5 6.75
Nook 0.30 1 6 6 8 40.0 12.00
Nook 0.30 1 6 1 6.0 1.80
Family Room 030 1 8 5 40.0 12.00
Utility 0.30 1 3 4 12.0 3.60
Bedroom 4 0.30 3 2 12 6 15.0 4.50
Bedroom 4 0.30 1 5 14 20.0 6.00
Bedroom 3 030 1 4 4 16.0 4.80
Bedroom 2 0.30 1 4 4 16.0 4.80
Master Bath 0.30 1 4 4 16.0 4.80
Master Bedroom 0.30 1 5 4 20.0 6.00
Bonus Room 0.30 1 4 4 18.0 5.40
0.0 0.00
0.01 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0,00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.00
0.0 0.001
0.0 0.00
Sum of Area and UA 1 325.51 97.65
Area Weighted U = UA/Area 1 0.30
Simple Heating System Size: Washington State
This heating system sizing calculator is based on the Prescriptive Requirements of the 2012 Washington State Energy Code(WSEC)and ACCA
Manuals J and S. This calculator will calculate heating loads only.ACCA procedures for sizing cooling systems should be used to determine cooling
loads.
The glazing(window)and door portion of this calculator assumes the installed glazing and door products have an area weighted average U-factor of
0.30. The incorporated insulation requirements are the minimum prescriptive amounts specified by the 2012 WSEC.
Please fill out all of the green drop-downs and boxes that are applicable to your project.As you make selections in the drop-downs for each section,
some values will be calculated for you. If you do not see the selection you need in the drop-down options,please call the WSU Energy Extension
Program at(360)956-2042 for assistance.
Project Information Contact Information
2068
Heating System Type: O Forced Air Furnace O Heat Pump
To see detailed instructions for each section, place your cursor on the word"Instructions".
Design Temperature
Instructions Design Temperature Difference(AT) 41
i 1=a-CO AT=Indoor(70 degrees)-Outdoor Design Temp
- -
Area of Building
Conditioned Floor Area
Instructions Conditioned Floor Area(sq ft) 2,272
Average Ceiling Height Conditioned Volume
InstrU ctions Average Ceiling Height(ft) 8.5 19,312
Glazing and Doors U-Factor X Area = UA
Instructions 0.30 326 97.65
Insulation
Attic U-Factor X Area = UA
Instructions – ------- —
R4v _.__-. 0.026 1,137 29.56
Single Rafter or Joist Vaulted Ceilings U-Factor Area UA
Instructions --- - - - --- - j
s lest R-value . No selection -
t,
Above Grade Walls(see Figure 1) U-Factor Area UA
Ii1St1ULfi0nb R41 - - F 0.056 2,416 135.30
" F-
Floors U-Factor Area UA
Instruction
s
R-30 . ..---- :...—_. - 0.029 1,428 41.41
Below Grade Walls(see Figure 1) U-Factor Area UA
Instructions No selection
Select R-value
Slab Below Grade(see Figure r) F-Factor Length UA
Instructions - - - - -------
Select conditioning No selection ---
Slab on Grade(see Figure 1) F-Factor Length UA
Instructions --- - --- "�
select R value � No selection u ---
Location of Ducts
Instructions Duct Leakage Coefficient
unconditioned Space
1.10
Sum of UA 303.92
Envelope Heat Load 12,461 Btu/Hour
Figure 1. Sumo/UAXAT
Air Leakage Heat Load 8,551 Btu/Hour
VolumeX 06XATX.018
Above Grade Building Design Heat Load 21,012 Btu/Hour
Air Leakage-Envelope Heat Loss
Building and Duct Heat Load 23,113 Btu/Hour
Ducts in unconditioned space Sum of Building Heat Loss X 1.10
Ducts in conditioned space.Sum of Building Heat Loss X 1
Maximum Heat Equipment Output 32,359 Btu/Hour
Building and Duct Heat Loss X 1.40 for Forced Air Furnace
Building and Duct Heat Loss X 1.25 for Heat Pump