20100145 Material Submittal and Hydraulic Calcs ,
\
MATERIAL SU BM ITTAL
AND
HYDRAULIC CALCULATIONS
FOR
CREEK ROAD MIXED USE
106T" AVENUE SE AND CREEK STREET
YELM, WA 98597
BY
UMI F1RE PROTECTION
PO BOX 1457
MARYSVILLE, WA 98270
!
. CREEK ROAD MIXED USE
TABLE OF CONTENTS
FIRE SPRINKLERS
TYCO SERIES LFII 4.9 K-FACTOR RESIDENTIAL PENDENT SPRINKLER
TYCO SERIES LFII 4.4 K-FACTOR RESIDENTtAL DRY SIDEWALL
TYCO SERIES DS-1 5.6 K-FACTOR DRY SIDEWALL
FIRE SPRINKLER VALVES �
AMES 2006 BACKFLOW PREVENTER
PIPE AND FITTINGS
SPEARS CPVC PIPE AND FITTINGS
HANGERS AND SEISMIC BRACING
AFCON 514 OFFSET CPVC HANGER
AFCON 511 SIDE MOUNT CPVC HANGER
MICELLANEOUS MATERIALS
AGF RESIDENTIAL RISER
HYDRAULIC CALCULATIONS
BUILDING E-THIRD FLOOR UNIT C(RESIDENTIAL NFPA 13R)
�
FIRE SPRINKLERS
�
��O 800-381-9312
TechnicalServices +1-401-781-8220
www.tyco-fire.com
RAP/D RESPONSE Series LFI/ Residential Sprinklers
4.9 K-factor Pendent
Wet Pipe and Dry Pipe Systems
General Escutcheon reduces the accuracy to
which the pipe drops to the sprinklers
Description must be�ut.
The Series LFII Residential Sprinklers � ���"°�''�°� �
The TYCO RAPID RESPONSE Series have been designed with heat sensi- '�'"�
LFII Residential Pendent and Recessed tivity and water distribution charac-
Pendent Sprinklers(TY2234)are deco- teristics proven to help in the control ry
���
rative, fast response, frangible bulb of residential fires and to improve the °' ' ,,,�e. �
sprinklers designed for use in residen- chance for occupants to escape or be � °
tial occupancies such as homes, apart- evacuated.
ments, dormitories, and hotels.When �
aesthetics and optimized flow charac- Dry Pipe System Application ��`'
teristics are the major consideration, The Series LFII Residential Pendent
the Series LFII Residential Sprinklers and Recessed Pendent Sprinklers
(TY2234)should be the first choice. offers a laboratory approved option for
The Series LFII Residential Sprinklers designing dry pipe residential sprinkier The owner is res onsib/e for main-
are intended for use in the following systems, whereas, most residential tainin their fire rotection s stem and
scenarios: spnnklers are laboratory approved for 9 P Y
wet systems only. devices in proper operafing condition.
• wet and dr i e residential s rin- The installing contractor or sprinkler
y p p p Through extensive testing and as refer- manufacturer should be contacted with
kler systems for one-and two-family enced in U.S. Patent 7,712,543, it has
dwellings and mobile homes per been determined that the number of any questions.
NFPA 13D design sprinklers (hydraulic design
• wet and dry pipe residential sprinkler area) for the Series LFII Residential Sprinkler
systems for residential occupancies Pendent and Recessed Pendent �dentification
up to and including four stories in Sprinklers (TY2234) need not be
height per NFPA 13R increased over the number of design
• wet and dr i e s rinkler s stems sprinklers (hydraulic design area) Number (SIN)
Y P P P Y as specified for wet pipe sprinkler
for the residential portions of any systems, as is accustomed for density/ TY2234
occupancy per NFPA 13 area sprinkler systems designed per
The recessed version of the Series NFPA 13.
LFII Residential Sprinklers is intended Consequently, the Series LFII
for use in areas with finished ceilings. Residential Sprinklers offer the features
It employs a two-piece Style 20 of non-water filled pipe in addition to
Recessed Escutcheon.The Recessed not having to increase the number of
Escutcheon provides 1/4 inch (6,4 design sprinklers (hydraulic design
mm) of recessed adjustment or up to area) for systems designed to NFPA
1/2 inch(12,7 mm)of total adjustment 13, 13D, or 13R. Non-water filled pipe
from the flush ceiling position. The Will permit options for areas sensitive
adjustment provided by the Recessed to freezing.
�
IMPORTANT The Series LFII Residential Pendent and
A/ways refer to Technical Data Recessed Pendent Sprink/ers(TY2234)
Sheet TFP700 for the "INSTALLER described herein must be installed and
WARNING" that provides cautions maintained in compliance with this
with respect to handling and instal- documeni and the app/icable stan-
lation of sprinkler systems and dards of fhe Nationa/ Fire Proteciion
components. Improper handling and Associafion,in addition to the standards
installation can permanently damage of any authorities having jurisdiction.
a sprink/er system or its compo- Failure to do so may impair the perfor-
nents and cause the sprinkler to fail to mance of these devices.
operate in a fire situation or cause it
fo operate prematurely.
Page 1 of 8 APRIL 2012 TFP400
.
TFP400
Page 2 of 8
7/16" (11,1 mm) ESCUTCHEON
1/2"
Components: NOMINAL NPT PLATE SEATING 2-7/8" DIA.
MAKE-IN � SURFACE (73,0 mm)
1 - Frame I
2 - Button �_
3 - Sealing Assembly 1 �
4 - 8ulb
5 - Compression 2 �
Screw 2-1/4"
6 - Deflector* g � (57,2 mm)
A A
q 1-5/8"
(41,3 mm) WRENCH STYL.E 20
RECESSED
*Temperature 5 � FLATS ESCUTCHEON
rating is *
indicated on 6
Deflector.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE i
RAPID RESPONSE SERIES LFI!RESlDENTIAL
PENDENT AND RECESSED PENDENT SPR/NKLERS(TY2234)
2-7/8" DIA.
(73,0 mmj 1/2"(12,7 mm)
7/16±1/8"
(11,1±3,2 mm) � 2_1�4" DIA. 1/4"(6,4 mm) / WRENCH RECESS
FACE OF I (57,2 mm) � � (END"A" USED
SPRINKLER ' MOUNTING FOR TY2234)
FITTING PLATE
FIGURE 3
W-TYPE 6
- I SPRINKLER WRENCH
/ �
A �i
MOUNTING 1/8" WRENCH
SURFACE
(3,2 mm) RECESS
1-3/8" (34,9 mm)
CLOSURE TY2234 --�
1-1/8"(28,6 mm)
F/GURE 2 �
STYLE 20 RECESSED ESCUTCHEON FOR USE W1TH THE
RAP/D RESPONSE SER/ES LFl1 RESIDENTIAL PENDENT SPRINKLER �
(TY2234)
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRlNKLER WRENCH
TFP400
Page 3 of 8
Technical Desi /� Dry Pipe System Water Delivery
g When using the Series LFII Residential
Data Criteria klerinsyste�ms22 he �time fo r water
The TYCO RAPID RESPONSE delivery must not exceed 15 seconds
Approvals Series LFII Residential Pendent for the most remote operating
U� Listed for use with wet pipe and and Recessed Pendent Sprinklers sprinkler.
dry pipe systems (TY2234) are UL and C-UL Listed for
C-UL Listed for use only with wet pipe installation in accordance with this Obstruction to Water Distribution
systems section: Sprinklers are to be located in accor-
dance with the obstruction rules
For details on these approvals, refer Residential Sprinkler Design Guide of NFPA 13D, 13R, and 13 as appli-
to the Design Criteria section. When conditions exist that are cable for residential sprinklers as
Maximum Working Pressure outside the scope of the provided well as with the obstruction criteria
175 psi(12,1 bar) criteria, refer to the Residential described within the Technical Data
Sprinkler Design Guide TFP490 for Sheet TFP490.
Discharge Coefficient the manufacturer's recommendations
K=4.9 GPM/psi��2(70,6 LPM/bar��2) that may be acceptable to the local Operational Sensitivity
Temperature Rating authority having jurisdiction. For "Horizontal Ceilings" (maximum
155°F(68°C)or 175°F(79°C) 2 inch rise for 12 inch run),the sprin-
System Types klers are to be installed with a deflector-
Finishes Per the UL Listing, wet pipe and dry to-ceiling distance of 1-3/8 to 4 inches
White Polyester Coated pipe systems may be utilized. Per the or in the recessed position using only
Chrome Plated C-UL Listing, only wet pipe systems the Style 20 Recessed Escutcheon as
Natural Brass may be utilized. shown in Figure 2.
Refer to Technical Data Sheet TFP485 The "Beam Ceiling Design Criteria"
Physical Characteristics about the use of residential sprinklers in section permits deflector-to-ceiling
Frame . . . . . . . . . . . . . . . . . . . . Brass residential dry pipe systems. distances up to 15-3/4 inches.
Button . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly . . . . . . . . Beryllium Hydraulic Design For "Sloped Ceilings" (greater than
Nickel w/TEFLON {NFPA 13D and 13R) 2 inch rise up to 8 inch rise for 12 inch
Bulb(3 mm). . . . . . . . . . . . . . . . Glass For systems designed to NFPA run), the sprinklers are to be installed
Compression Screw . . . . . . . .Bronze 13D or NFPA 13R, the minimum With a deflector-to-ceiling distance of
Deflector . . . . . . . . . . . . . . . . .Bronze required sprinkler flow rates are 1-3/8 to 4 inches or in the recessed
Ejection Spring . . . . . .Stainless Steel given in Tables A and B as a func- Position using only the Style 20
tion of temperature rating and the Recessed Escutcheon as shown in
Operation maximum allowable coverage areas. Figure 2.
The sprinkler flow rate is the minimum
The glass Bulb contains a fluid that required discharge from each of the Sprinkler Spacing
expands when exposed to heat.When total number of"design sprinklers"as The minimum spacing between sprin-
the rated temperature is reached, the specified in NFPA 13D or NFPA 13R. klers is 8 feet (2,4 m). The maximum
fluid expands sufficiently to shatter the The number of "design sprinklers" spacing between sprinklers cannot
glass Bulb, allowing the sprinkler to specified in NFPA 13D and 13R for wet exceed the length of the coverage
activate and flow water. pipe systems is to be applied when area(Table A or B)being hydraulically
designing dry pipe systems. calculated(e.g., maximum 12 feet for a
12 ft.x 12 ft.coverage area, or 20 feet
Hydraulic Design for a 20 ft.x 20 ft. coverage area).
(NFPA 13)
For systems designed to NFPA 13,
the number of design sprinklers is
to be the four most hydraulically
demanding sprinklers.The minimum
required discharge from each of the
four sprinklers is to be the greater of
the following:
• The flow rates given in Tables A
or B as a function of temperature
rating and the maximum allowable
coverage area.
• A minimum discharge of 0.1 gpm/ft2
over the "design area" comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
The number of "design sprinklers"
specified in NFPA 13 for wet pipe
systems is to be applied when
designing dry pipe systems.
TFP400
Page 4 of 8
WET PIPE SYSTEM
Minimum Flow and Residual Pressure�b�
Maximum Maximum For Horizontal
Covera�e Spacin For Sloped Ceiling(c,d,e) For Sloped Ceiling(c,a,e1
9 Ceiling(c,d,e)
Area(a' Ft. (Maximum 21nch Rise (Greater than 2 Inch Rise up to (Greater than 4 Inch Rise up to
Ft.x Ft. �m) for 12 Inch Run) Maximum 4 Inch Rise for 12 Inch Run) Maximum 8 Inch Rise for 12 Inch Run)
(m x m)
155°F(68°C)or 155°F(68°C) 175°F(79°C) 155°F(68°C) 175°F(79°C)
175°F(79°C)
12 x 12 12 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM)
(3,7 x 3,7) (3,7) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar)
14 x 14 14 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM)
(4,3 x 4,3) (4,3) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar)
16 x 16 . 16 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM)
(4,9 x 4,9) (4,9) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar)
18 x 18 18 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM)
(5,5 x 5,5) (5,5) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar)
20 x 20 20 20 GPM(75,7 LPM) 20 GPM(75,7 LPM) 20 GPM(75,7 LPM) 21 GPM(79,5 LPM) 22 GPM(83,3 LPM)
(6,1 x 6,1) (6,1) 16.7 psi(1,15 bar) 16.7 psi(1,15 bar) 16.7 psi(1,15 bar) 18.4 psi(1,27 bar) 20.2 psi(1,39 bar)
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which
hydraulic design criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinklec The associated residual pressures are calculated
using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13D 2010 applications,Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch.
Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontal ceiling criteria.
(dj For NFPA 13R applications,Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when acceptable to
the local authority having jurisdiction.
(e) For NFPA 13 residential appiications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in
this table must be used.
TABLE A
SERIES LFlI RESlDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
NFPA i3D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
WET PIPE SYSTEMS
DRY PIPE SYSTEM
Minimum Flow and Residual Pressure�b1
Maximum Maximum
Coverage Area�a1 Spacing For Horizontal Ceiling
Ft.x Ft.(m x m) Ft.(m)
(Maximum 2 Inch Rise for 12 inch Run)
155°F(68°C) 175°F(79°C)
12 x 12 12 13 GPM(49,2 LPM) 13 GPM(49,2 LPM)
(3,7 x 3,7) (3,7) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar)
14 x 14 14 14 GPM(53,0 LPM) 14 GPM(53,0�PM)
(4,3 x 4,3) (4,3) 8.2 psi(0,57 bar} 8.2 psi(0,57 bar)
16 x 16 16 15 GPM(56,8 LPM) 15 GPM(56,8 LPM)
(4,9 x 4,9) (4,9) 9.4 psi(0,65 bar) 9.4 psi(0,65 bar)
18 x 18 18 18 GPM(68,1 LPM) 18 GPM(68,1 LPM)
(5,5 x 5,5) (5,5) 13.5 psi(0,93 bar) 13.5 psi(0,93 bar)
20 x 20 20 21 GPM(79,5 LPM) 21 GPM(79,5 LPM)
(6,1 x 6,1) (6,1) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar)
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage
area for which hydrauiic design criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual
pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
TABLE B
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEMS
TFP400
Page 5 of 8
Beam Ceilin When the beam pockets created by
g the primary beams exceed 20 feet in p
� length,the installation will require the , ,
Des�gn Criteria use of secondary beams as described ��
The TYCO RAPID RESPONSE Series above.Otherwise, secondary beams
need not be present. � �
LFII Residential Pendent and Recessed �,�
Pendent Sprinklers (TY2234) are UL Secondary beams of a cross-sectional ��
and C-UL Listed for installation in wet depth greater than one-quarter the V"
pipe systems only for residential occu- depth of the primary beams are to be a ;�
pancies with horizontal ceilings (that minimum of 3 ft-4 in from the compart-
is, slopes up to a 2 inch rise over a ment wall to center of the nearest beam _.__
12 inch run)with beams when installed and from center to center between
in accordance with this section: beams(Figure 6C). �
Secondary beams of a cross-sectional N223a
General Information depth no greater than one-quarter the
The basic concept of this protection depth of the primary beams may be B
scheme is to locate the sprinklers placed at any compartment wall to �
on the underside of the beams, refer center of the nearest beam distance � �
Figure 5,(not in the beam pockets);to and from any center to center distance
identify the main beams that princi- between beams(Figure 6C). E�
pally run in one direction as"primary �, �
beams"; and, to identify the beams Lintels vv
that run principally perpendicular to Lintels over doorways exiting the _ _
the main beams, as may be present compartment must be present. The ��
(or in some cases may be necessary minimum height for the lintels is "' �
for proper sprinkler protection), as 8 inches or no less than the depth of
"secondary beams". the Primary Beams, whichever is
greater.
Primary and Secondary Beam � �
Types Sprinkler Types MAXIMUM TY2234
Solid surface, solid or hollow core, Series LFII Pendent and Recessed ONE-HALF BEA �
combustible or non-combustibte. Pendent Residential Sprinklers wIOTH P�us
(TY2234), 155°F (68°C) and 175°F 2"(50,8 mm)
Primary and Secondary Beam (79°C).
Positioning
Directly attached to the underside of Sprinkler Coverage Area and FIGURE 5
a combustible or non-combustible Hydraulic Design SPRINKLER POSITIONING
smooth ceiling at any elevation. The sprinkler coverage areas and UNDER PRIMARY BEAMS
hydraulic design criteria as presented WET P/PE SYSTEMS ONtY
Primary Beam Cross-Section in the Table A for"Horizontal Ceilings" (Refer to the "Beam Ceiling
Maximum depth of 14 inches and the are to be applied. Design Criteria"section.)
maximum width is unlimited.The cross-
sectional shape of the primary beam Sprinkler Position Beam and Soffit Arrangements
may be rectangular to circular. The deflector to bottom of primary
beams for the Series LFII Pendent A soffit is permitted to be placed
Secondary Beam Cross-Section and Recessed Pendent S rinklers around the perimeter of a compart-
Maximum depth to be no greater than p ment with the beam arrangement
the rimar beam and the maximum �TY2234) is to be 1-1/4 to 1-3/4 inches Within the soffit area(Figure 7).
P Y (Figure 5A).The vertical centerline of
width is unlimited.The cross-sectional the Series LFII Pendent Sprinklers is The cross-section of the soffit may be
shape of the secondary beam may be to be no greater than half the primary any size as long as it does not create
rectangular to circular. beam cross-sectional width plus an obstruction to water distribution
2 inches from the centerline of the per the obstruction rules of NFPA 13 for
Primary Beam Spacing primary beam(Figure 5B). residential sprinklers.
The primary beams (Figure 6A)are to
be 3 ft.-4 in.to 6 ft.from the compart- When soffits are present, the previ-
ment wall to center of the nearest ously provided 3 ft.-4 in. to 6 ft.
beam and from center to center � compartment wall to adjacent beam"
between beams. Core drilling of beams to allow the distance for the primary and
insfallation of sprink/er drops requires secondary beams is to be measured
Secondary Beam Spacing consulting with a structural engineer. from the face of the soffit as opposed
The secondary beams principally run �yhere core drilling is not permitted, to the compartment wall.
perpendicular to the primary beams. the previous/y sfated sprinkler position Although the distance to the
Secondary beams of a depth equal to criieria for the Series LFII Residentia/ beams is measured from the face of
the primary beam must be placed so Pendent and Recessed Pendent the soffit,the sprinkler coverage area
that the beam pockets created by the Sprinklers(TY2234)a/lows placement is to be measured from the compart-
primary beams do not exceed 20 feet of the sprinkler drop adjacent to the ment wall.
in length(Figure 6B). primary beam.
TFP400
Page 8 of 8
Care and Automatic sprinkler systems are prderinn
recommended to be inspected, .7
Maintenance tested, and maintained by a qualified procedure
Inspection Service in accordance with
The TYCO RAPID RESPONSE Series local requirements and/or national Contact your local distributor for
LFII Residential Pendent and Recessed codes. availability. When placing an order,
Pendent Sprinklers(TY2234) must be indicate the fuli product name and Part
maintained and serviced in accordance ��mited Number(P/N).
with this section: Sprinkler Assembly
Before closing a fire protection system Warranfy Specify: Series LFII (TY2234), K=4.9,
main control valve for maintenance Residential Pendent Sprinkler with
Products manufactured by Tyco
work on the fire protection system that (specify) temperature rating and
it controls, permission to shut down Fire Protection Products (TFPP) are �specify)finish, P/N(specify).
the affected fire protection system Warranted solely to the original Buyer 1ss°F(68°c)or
must be obtained from the ro er for ten (10) years against defects
p p in material and workmanship when Chrome Plated ............P/N 51-201-9-155
authorities and notify all personnel Paid for and properly installed and �5s°F(68°c)
who may be affected by this action. maintained under normal use and White Polyester............P/N 51-201-4-155
Absence of the outer piece of an service. This warranty will expire �ss°F(68°c)
escutcheon, which is used to cover ten 10 ears from date of shi ment White �
� � y p (RAL9010`................P/N 51-201-3-155
a clearance hole, can delay sprinkler by TFPP. No warranty is given for �55°F(68°c�
operation in a fire situation. products or components 171a11Uf1C- Natural Brass.............. P/N 51-201-1-155
The owner must assure that the tured by companies not affiliated by i�5°F(79°c>or
sprinklers are not used for hanging ownership with TFPP or for products Chrome Plated ............P!N 51-201-9-175
any objects and that the sprinklers and components which have been i�s°F(79°c)
subject to misuse, improper If1Stal- White Polyester............P/N 51-201-4-175
are only cleaned by means of gently �ation, corrosion, or which have not i7s°F(�s°c)
dusting with a feather duster; other- been installed, maintained, modified wnite
wise, non-operation in the event of or repaired in accordance with appli- (RA�so�o)"................P/N 51-201-3-175
a fire or inadvertent operation may cable Standards of the National Fire i75�F(�9���
result. Protection Association, and/or the Natural Brass.............. P/N 51-201-1-175
Sprinklers which are found to be standards of any other Authorities 'Eastern Hemisphere sales only.
leaking or exhibiting visible signs of Having Jurisdiction. Materials found
corrosion must be replaced. by TFPP to be defective shall be either Recessed Escutcheon
repaired or replaced, at TFPP's sole Specify: Style 20 Recessed
Automatic sprinklers must never be aption. TFPP neither assumes, nor Escutcheon with (specify`)finish, P/N
painted, plated, coated, or other- authorizes any person to assume for (specify').
wise altered after leaving the factory. it, any other obligation in connection �Refer to Technical Data Sheet
Modified sprinklers must be replaced. with the sale of products or parts of TFP770.
Sprinklers that have been exposed to products. TFPP shall not be respon-
corrosive products of combustion, but sible for sprinkler system design S rinkler Wrench
have not operated,should be replaced errors or inaccurate or incomplete Specify: W-Type 6 Sprinkler Wrench,
if they cannot be completely cleaned information supplied by Buyer or P/N 56-000-6-387.
by wiping the sprinkler with a cloth or Buyer's representatives.
by brushing it with a soft bristle brush. �n no event shall TFPP be liable, in Specify: W-Type 7 Sprinkier Wrench,
Care must be exercised to avoid contract, tort, strict liability or under P�N 56-850-4-001.
damage to the sprinklers - before, any other legal theory, for incidental,
during, and after installation, indirect, special or consequential
Sprinklers damaged by dropping, damages, including but not limited to
striking,wrench twist/slippage, or the labor charges, regardless of whether
like, must be replaced.Also, replace TFPP was informed about the possi-
any sprinkler that has a cracked bulb bility of such damages, and in no
or that has lost liquid from its bulb. event shall TFPP's liability exceed an
(Ref. Installation Section.) amount equal to the sales price.
The owner is responsible for the The foregoing warranty is made in
inspection, testing, and mainte- lieu of any and all other warranties.
nance of their fire protection system express or implied, including warran-
and devices in compliance with this ties of inerchantability and fitness for
document, as well as with the appli- �articular purpose.
cable standards of the National Fire This limited warranty sets forth the
Protection Association (e.g., NFPA exclusive remedy for claims based on
25), in addition to the standards of any failure of or defect in products, mate-
authorities having jurisdiction.Contact rials or components, whether the
the installing contractor or sprinkler claim is made in contract, tort, strict
manufacturer regarding any questions. liability or any other legal theory.
This warranty will apply to the full
extent permitted by law.The invalidity,
in whole or part,of any portion of this
warranty will not affect the remainder.
Copyright OO 2012 Tyco Fire Protection Products.All rights reserved. *jt�.�
TEFLON is trademark of The DuPont Corporation. "�
��O 800-381-9312
TechnicalServices +�-ao�-78�-8220
www.tyco-fire.com
RAP/D RESPONSE Series LF// Residential Sprinklers
4.4 K-factor Horizontal Sidewall, Dry Type
Wet Pipe and Dry Pipe Systems
Gene�„a, The recessed version is intended for use
in areas with finished walis. It employs a
Descri �/0/'� two-piece Style 20 Recessed Escutcheon.
p The Recessed Escutcheon provides 1/4 ��
The TYCO RAPID RESPONSE Series inch(6,4 mm)of recessed adjustment or � �
LFII Dry Type Residential Horizontal up to 1/2 inch(12,7 mm)oftotal adjust- ��`��
Sidewall Sprinklers(TY2335)are dry type� ment from the flush mounting surface = ����, �
decorative,fast response,frangible bulb Position.The design of this escutcheon �`
sprinklers designed for use in residential Provides a level of flexibility in adjusting
occupancies such as homes,apartments, sprinkler supply connections.
dormitories,and hotels. The Series LFII Dry Type Residential
The Series LFII Dry Type Residential Horizontal Sidewall Sprinklers have
Horizontal Sidewall Sprinklers are typi- been designed with heat sensitivity and
cally used for the following situations: Water characteristics proven to help in
the control of residential fires and to
• where sprinklers are required on dry improve the chance for occupants to �
pipe systems that are exposed to escape or be evacuated. The Series LFII Dry Type Residential
freezing temperatures;for example, Horizontal Sidewall Sprink/ers(TY2335)
horizontal sprinkler supply from un- Dry Pipe System Application described herein must be installed and
heated portions of buildings The Series LFII Residential Pendent and maintained in compliance with this docu-
Recessed Pendent Sprinklers offers a ment and the a l�cable standards of
•where sprinklers and/or a portion of laboratory approved option for designing the Nationa/Fi e Protection Associa-
the connecting piping are exposed to dry pipe residential sprinkler systems,
freezing temperatures; for example, Whereas,most residential sprinklers are tion,in addition to the standards of any
horizontal sprinkier supply from wet laboratory approved for wet systems only. aufhorities having jurisdiction. Failure
systems into unheated areas to do so may impair the performance
Through extensive testing and as ref- of these devices.
• where sprinklers are used on systems erenced in U.S. Patent 7,712,543, it
that are seasonally drained to avoid has been determined that the number The owner is responsi6le for maintaining
freezing;for example,vacation areas of design sprinklers(hydraulic design their fire protection system and devices in
The Series LFII D T e Residential Hori- area)for the Series LFII Residential Pen- proper operafing condition. The install-
zontal Sidewall Sprinklers are intended dent and Recessed Pendent Sprinklers should be ctontacted�w th an anuestionsr
for use in Residential Sprinkler systems (TY2234)need not be increased over the 1'q
for one-and two-family dwellings and number of design sprinklers(hydraulic
mobile homes per NFPA 13D;residential design area)as specified for wet pipe
sprinkler systems for residential occu- sprinkler systems,as is accustomed for
pancies up to and inctuding four stories density/area sprinkler systems designed Sprinkler
in height per NFPA 13R; or, sprinkler Per NFPA 13. �dentification
systems for the residential portions of Consequently, the Series LFII Resi-
any occupancy per NFPA 13. dential Sprinklers offer the features of Number (S1N)
non-water filled pipe in addition to not
having to increase the number of design TY2335
sprinklers (hydraulic design area)for
systems designed to NFPA 13, 13D,or
13R. Non-water filled pipe will permit
IMPORTANT options for areas sensitive to freezing.
Always refer to Technical Data
Sheet TFP700 for fhe "INSTALLER
WARNING"that provides cautions
wiih respect to handling and in-
stallation of sprinkler systems and
components.Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 APRIL 2012 TFP461
TFP461
Page 3 of 10
Technica/ O eration •flow rates listed in Table A or B as a
p function of temperature rating and the
Data When the TYCO RAPID RESPONSE maximum allowable coverage area.
Series LFII Dry Type Residential Horizontal • minimum discharge of 0.1 gpm/ft2 over
Approvals Sidewall Sprinkler is in service, water the design area comprised of the four
UL Listed is prevented from entering the assem- most hydraulically demanding sprin-
For details on approval, refer to the bly by the Plug with Sealing Assembly klers for the actual coverage areas
Design Criteria section. (Figure 1)in the Inlet of the Sprinkler. protected by four sprinklers.
Maximum Working Pressure The glass Bulb contains a fluid that The number of"design sprinklers"speci-
175 psi(12,1 bar) expands when exposed to heat.When fied in NFPA 13 for wet pipe systems is
the rated temperature is reached, the to be•applied when designing dry pipe
Discharge Coefficient fluid expands sufficientiy to shatter the systems.
K=4.4 GPM/psi'�2(63,4 LPM/bar'�2) glass Bulb to release the Bulb Seat.The Dry Pipe System Water Delivery
Inlet Thread Connections system's water or air pressure is then When using the Series LFII Residential
1-inch NPT or ISO 7-Ri able to unseat the Plug with Sealing As- Sprinklers(TY2335)in dry pipe sprinkler
sembly.The Plug Spring turns the Plug systems,the time for water delivery must
Sprinkler Temperature Rating with Sealing Assembly aside, allowing not exceed 15 seconds for the most
155°F/68°C the sprinkler to activate and flow water. remote operating sprinkler.
Finishes Obstruction to Water Distribution
Chrome-Plated Design Sprinklers are to be located in accordance
White Polyester-Coated Criteria with the obstruction rules of NFPA 13D,
Natural Brass 13R,and 13 as applicable for residential
Order Lengths The TYCO RAPID RESPONSE Series sprinklers as well as with the obstruction
Minimum: 3-3/4 inches (95,3 mm) LFII Dry Type Residential Horizontal criteria described within the Technical
Maximum:24 inches(609,6 mm) Sidewall Sprinklers(TY2335) are UL Data Sheet TFP490.
Listed for installation in accordance Operational Sensitivity
Physical Characteristics with this section: The sprinkler must be located relative
Inlet . . . . . . . . . . . . . . . . . . . . . Brass to the mountin surface as shown in
Plug . . . . . . . . . . . . . . . . . . . . . Brass Residential Sprinkler Design Guide g
Yoke . . . . . . . . . . . . . . Stainless Steel �Nhen conditions exist that are outside Figures 2 and 3.
Casing. . . . . . . . . . . Galvanized Steel the scope of the criteria provided in this Sprinkler Spacing
Insert . . . . . Bronze section,refer to the technical data sheet The minimum lateral spacing between
Bulb Seat. . . . . . . . . . .Stainless Steel entitled Residential Sprinkler Design sprinklers is 8 feet(2,4 m).The maximum
Bulb. . . . . . . . . . . . . . . . . . . . . . Glass Guide(TFP490)for the manufacturer's lateral spacing between sprinklers can-
Compression Screw . . . . . . . . . Brass recommendations that may be acceptable not exceed the length of the coverage
Deflector . . . . . . . . . . . . . . . . . Brass to the local authority having jurisdiction. area(refer to Table A or B) hydrauli-
Frame . . . . . . . . . . . . . . . . . . . . Brass gystem Types cally calculated (e.g., a maximum of
Guide Tube . . . . . . . . .Stainless Steel 12 feet for a 12 ft.x 12 ft.coverage area or
Water Tube . . . . . . . . .Stainless Steel Wet pipe, and dry pipe systems may 1g peet for a 18 ft.x 20 ft.coverage area).
Bushin Brass be utilized.
g. . . . . . . . . . . . . . . . . . .
Plug Spring . . . . . . . . .Stainless Steel Hydraulic Design Sprinkler Fittings
Sealing Assembly . . . . . . . . Beryllium (NFPA 13D and 13R) The following fittings may be used:
Nickel with TEFLON For systems designed to NFPA 13D or .The 1 inch NPT outlet or run of a mal-
Escutcheon . . . . . . . . . .Carbon Steel NFPA 13R,the minimum required sprinkler leable or ductile iron threaded tee
flow rate are given in Table A or B as a fittings that meet the dimensional re-
function of temperature rating and the quirements of ANSI B16.3(Class 150)
maximum allowable coverage areas. .The 1 inch NPT outlet or run of a cast
The sprinkler flow rate is the minimum
required discharge from each of the iron threaded tee fittings that meet
total number of"design sprinklers," as the dimensional requirements of ANSI
specified in NFPA 13D or NFPA 13R.The B16.4(Class 125).
number of"design sprinklers"specified For dry pipe systems, only use the
in NFPA 13D and 13R for wet pipe sys- side outlet of maximum 2-1/2 inch size
tems is to be applied when designing reducing tees when locating the Series
dry pipe systems. LFII Dry Type Residential Recessed
Hydraulic Design Pendent Sprinklers directly below the
(NFPA 13) branch line.Otherwise,use the con-
For systems designed to NFPA 13,the figuration shown in Figure 7 to assure
number of required design sprinklers is complete drainage from above the Se-
the four most hydraulically demanding ries LFII Sprinklers and the branch line.
sprinklers. The minimum required dis- Do not install the Series LFII Dry
charge from each of the four sprinklers Type Residential Recessed Pen-
is the greater of the following: dent Sprinklers into elbow fittings.
The Inlet of the sprinkler can con-
tact the interior of the elbow, po-
tentially damaging the Inlet seal.
TFP461
Page 4 of 10
Only use the configuration in Fig- be sealed, in accordance with the Na- • For plain-barrel horizontal sidewall
ure 6 where the sprinkler fitting and tionai Fire Protection Association. Due sprinklers,apply the Wrench Recess
water-filled pipe above the sprinkler to temperature differences between the End "A" of the W-Type 6 Sprinkler
fitting are not subject to freezing and two areas,the potential for the forma- Wrench(Figure 4)to the Wrench Flat.
where the length of the Series LFII tion of condensation in the sprinkler and . For recessed horizontal sidewall sprin-
Sprinkler has the minimum exposure subsequent ice build-up is increased.If klers, apply the Wrench Recess of
length per Figure 8. Refer to the Ex- this condensation is not controlled,ice the W-Type 7 Sprinkler Wrench to the
posure Length section and Table C. build-up can occur that might damage Wrench Flat(Figure 5).
•The 1 inch NPT outlet of a GRINNELL the dry type sprinkler and/or prevent
Figure 730 Mechanical Tee in wet pipe proper operation in a fire situation. If sprinkler removal is necessary,remove
systems only Use of the Model DSB-2 Dry Sprinkler the sprinkler using the same wrenching
Boot,described in Technical Data Sheet method noted above. Sprinkler removal
•The 1 inch NPT CPVC outlet of a 1"x TFP591 and shown in Figures 6 through �s easier when a non-hardening sealant
1" x 1" NPT Sprinkler Head Adapter g,can provide the recommended seal. `^�as used and torque guidelines were
Tee(P/N 80249)in wet systems only followed. After removal, inspect the
•The 1 inch NPT CPVC outiet of a 1"x . sprinkler for damage.
1" NPT Female Adapter(P/N 80145) /nstal/at�on Step 4.After installing the ceiling or
in wet systems only The TYCO RAPID RESPONSE Series applying a ceiling finish,slide the Style
•The 1 inch NPT outlet of a 1"x 1"x 1" LFII Dry Type Residential Horizontal 20 Recessed Escutcheon Closure over
NPT CPVC Sprinkler Head Adapter Sidewall Sprinklers must be installed in the sprinkler. Push the closure over the
Tee(P/N 80259) in either wet or dry accordance with this section: mounting plate until its flange contacts
pipe systems the wall.
General Instructions
The Series LFII Dry Type Residential
� Horizontal Sidewall Sprinklers must
Do not install the Series LFII Dry Type only be installed in fittings that meet
Residential Horizonta/Sidewall Sprin- the requirements of the Design Criteria
klers into any other fype fitting without section. For other important require-
first consulting the Technical Services �ents regarding piping design and
Department. Failure to use the appro- sealing of the clearance space around
priate fiiting may result in the following: the Sprinkler Casing,refer to the Design
Criteria section.
• failure of the sprinkler to operate po not install any bulb type sprinkler if
properly due to formation of ice over the Bulb is cracked or there is a loss of
the Inlet Plug or binding of the Inlet liquid from the Bulb. With the sprinkler
Plug. held horizontally, a small air bubble
• insufficient engagement of the in- should be present.The diameter of the
let pipe threads with consequent air bubble is approximately 1/16 inch
leakage. (1,6 mm).
Drainage A leak-tight 1 inch NPT sprinkler joint
Branch, cross, and feed-main piping should be obtained by applying a min-
connected to Series LFII Dry Type Resi- imum-to-maximum torque of 20 to 30
dential Sprinklers and subject to freezing ft.-Ibs. (26,8 to 40,2 Nm). Higher levels
temperatures must be pitched to allow of torque can distort the sprinkler Inlet
proper drainage,in accordance with the or Frame with consequent leakage or
minimum requirements of the National impairment of the sprinkler.
Fire Protection Association for dry pipe Do not attempt to compensate for
sprinkler systems. insufficient adjustment in an Escutcheon
Exposure Length Plate by under-or over-tightening the
When using Series LFII Dry Type Resi- sprinkler. Re-adjust the position of the
dential Horizontal Sidewall Sprinklers sprinkler fitting to suit.
in wet pipe sprinkler systems to protect Step 1.Install horizontal sidewall sprin-
areas subject to freezing temperatures, klers only in the horizontal position with
use Table C to determine a sprinkler's their centerline of waterway perpendicular
appropriate exposed barrel length to to the back wall and parallel to the ceil-
prevent water from freezing in the con- ing. The word TOP on the Deflector is
necting pipes due to conduction.The to face towards the cei�ing.
exposed barrel length measurement must
be taken from the face of the sprinkler Step 2.With a non-hardening pipe-thread
fitting to the surface of the structure or sealant such as Teflon tape applied to the
insulation that is exposed to the heated inlet threads,hand-tighten the sprinkler
area. Refer to Figure 8 for an example. into the sprinkler fitting.
Clearance Space Step 3.Wrench-tighten the sprinkler
When connecting an area subject to using a pipe wrench on the Inlet Band
freezing and an area containing a wet- ar the Casing (Figure 1), or using the
pipe sprinkler system, the clearance W-Type 6 or W-lype 7 Sprinkler Wrench
space around the sprinkler barrel of as follows:
Dry Type Residential Sprinklers must
TFP461
Page 5 of 10
::..................................................................................
�: �
ELEVATION
Maximum Maximum Minimum Flow��,".°.n and Residual Pressure for Horizontal Ceiling
Coverage Spacing 155°F(68°C)
Area� Ft.(m) Top-of-Deflector to Ceiling: Top-of-Deflector to Ceiling:
Width x Length ro� 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm)
Ft.x Ft.
(m x m) WET PIPE WET PIPE
12 x 12 12 13 GPM(49,2 LPM) 15 GPM(56,8 LPM)
(3,7 x 3,7) (3,7) 8.7 psi{0,60 bar) 11.6 psi(0,80 bar)
14 x 14 14 14 GPM(53,0 LPM) 15 GPM(56,8 LPM)
(4,3 x 4,3) (4,3) 10.1 psi(0,70 bar) 11.6 psi(0,80 bar)
16 x 16 16 17 GPM(64,3 LPM) 19 GPM(71,9 LPM)
(4,9 x 4,9) (4,9) 14.9 psi(1,03 bar) 18.6 psi(1,28 bar)
16 x 18 16 19 GPM(71,9 LPM) 20 GPM(75,7 LPM)
(4,9 x 5,5) (4,9) 18.6 psi(1,28 bar) 20.7 psi(1,43 bar)
16 x 20 16 25 GPM(94,6 LPM) 25 GPM(94,6 LPM)
(4,9 x 6,1) (4,9) 32.3 psi(2.23 bar) 32.3 psi(2.23 bar)
(a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest
coverage area for which hydraulic design criteria are stated.
(b)This dimension refers to Width(backwall where sprinkler is located)times Length(horizontal throw of the sprinkler).
(c)The requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are
calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section for details.
(d)For NFPA 13D 2010 applications,Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to
8:12 pitch.Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontai ceiling criteria.
(e)For NFPA 13R applications,Horizontal Ceiling criteria may be used for sloped ceiling configuration up to 8:12 pitch when
acceptable to the local authority having jurisdiction.
(f)For NFPA 13 residential application,the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the
criteria in this table must be used.
TABLE A
NFPA 13D, 13R AND 13 HYDRAULIC DESIGN CRlTERIA FOR
SERIES LFIi DRY TYPE RESIDENTIAL SPRlNKLERS(TY2335)
(MAXIMUM 2/NCH RISE FOR 12 INCH RUN)
- WET PIPE SYSTEM-
TFP461
Page 6 of 10
_ . _ _ . __
...................................................................................
�� �
ELEVATION
Maximum Maximum Minimum Flow�`�d�and Residual Pressure for Horizontai Ceiling
Coverage Spacing 155 F(68°C)
Area�a� Ft.(m) Top-of-Defiector to Ceiling: Top-of-Deflector to Ceiling:
Width x Length ro� 4 to 6 Inches(100 to 150 mm) 6 to 121nches(150 to 300 mm)
Ft.x Ft.
(m x m) DRY PIPE DRY PIPE
12 x 12 12 13 GPM(49,2 LPM) 15 GPM(56,8 LPM)
(3,7 x 3,7) (3,7) 8.7 psi(0,60 bar) 11.6 psi(0,80 bar)
14 x 14 14 16 GPM(60,6 LPM) 16 GPM(60,6 LPM)
(4,3 x 4,3) (4,3) 13.2 psi{0,91 bar) 13.2 psi(0,91 bar)
16 x 16 16 17 GPM(64,3 LPM) 19 GPM(71,9 LPM)
(4,9 x 4,9) (4,9) 14.9 psi(1,03 bar) 18.6 psi(1,28 bar)
16 x 18 16 N/A N/A
(4,9 x 5,5) (4,9)
16 x 20 16 N/A N/A
(4,9 x 6,1) (4,9j
(a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest
coverage area for which hydraulic design criteria are stated.
(b)This dimension refers to Width(backwall where sprinkler is located)times Length(horizontal throw of the sprinkler).
(c)The requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are
calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section for details.
(d)For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the
criteria in this table must be used,
TABLE B
NFPA i3D, 13R AND 13 HYDRAULIC DESIGN CRITER/A FOR
SERIES LFII DRY TYPE RESIDENTIAL SPRlNKLERS(TY2335J
(MAXIMUM 2 INCH RISE FOR 12/NCH RUN)
-DRY PIPE SYSTEM-
TFP461
Page 7 of 10
� .• �
PLUG
OUTLEf FACE OF
SPRINKLER SPRINKLER
SPRINKLER FITTING FITTING
FITTING PLUG (SEE DESIGN
(SEE DESIGN OUTLET CR�TERIA DSB-2
CRITERIA SECTION) BOOT
SECTION) i
i
DSB-2 EXPOSURE
DSB-2 � BOOT LENGTH
BOOT (SEE DESIGN
TO DRY CRITERIA
TO WET SYSTEM SECTION)
SYSTEM
FIGURE 6 FIGURE 7 FIGURE 8
SPRINKLER FITTING IN SPRINKLER FITTING IN EXPOSURE LENGTH
HEATED AREA UNHEATED AREA
Temperatures for Heated Area�°�
Ambient Temperature
Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C)
Sprinkler
Minimum Exposed Barrel Length, Inches(mm)jb�
40°F(4°C) 0 0 0
30°F(-1°C) 0 0 0
20°F(-7°C) 4(100) 0 0
10°F(-12°C) 8(200) 1 (25) 0
0°F(-18°C) 12(305) 3(75) 0
-10°F(-23°C) 14(355) 4(100) 1 (25)
-20°F(-29°C) 14(355) 6(150) 3(75)
-30°F(-34°C) 16(405) 8(200) 4(100)
-40°F(-40°C) 18(455) 8(200) 4(100)
-50°F(-46°C) 20(510) 10(255) 6(150)
-60°F(-51°C) 20(510) 10(255) 6(150)
Notes:
(a)For protected area temperatures that occur between values listed above,use the next cooler temperature.
(b)These lengths are inclusive of wind velocities up to 30 mph(18,6 kph).
TABLE C
MINlMUM RECOMMENDED LENGTHS OF EXPOSED SPRINKLER BARRELS
IN WET-PIPE SYSTEMS
TFP461
Page 8 of 10
Care and as with the applicable standards of the This warranty will apply to the full extent
Nationai Fire Protection Association(e.g., permitted by law.The invalidity,in whole
Maintenance NFPA 25),in addition to the standards of or part, of any portion of this warranty
any authorities having jurisdiction.Con- will not affect the remainder.
The TYCO RAPID RESPONSE Series tact the installing contractor or sprinkler
LFII Dry Type Residential Horizontal manufacturer regarding any questions. Ordering
Sidewall Sprinklers (TY2335) must be Automatic sprinkler systems are recom-
maintained and serviced in accordance mended to be inspected,tested, and procedure
with this section: maintained by a qualified Inspection
Before closing a fire protection system Service in accordance with local require- Contact your local distributor for avail-
main control valve for maintenance ments and/or national codes. ability.When placing an order,indicate
work on the fire protection system that the full product name and Part Number
it controls, obtain permission to shut Limited (P/N).Refer to the Price List for a com-
down the affected fire protection systems plete listing of P/Ns.
from the proper authorities and notify Warranty Horizontal Sidewall Sprinkler
all personnel who may be affected by Products manufactured by Tyco Fire Assembly
this action. Protection Products(TFPP)are warranted Specify the following information:
Absence of a Recessed Escutcheon solely to the original Buyer for ten (10) • Series LFII Dry Type Residential Hori-
Plate or a Domed Concealed Cover years against defects in material and zontal Sidewall Sprinkler(TY2335)
Plate to cover a clearance hole can delay workmanship when paid for and properly . W�th Recessed Escutcheon or without
sprinkler operation in a fire situation. installed and maintained under normal Escutcheon
The owner must assure that the sprinklers use and service.This warranty will expire
are not used for hanging any objects and ten(10)years from date of shipment by •4.4 K-factor
that the sprinklers are only cleaned by TFPP.No warranty is given for products or . �55°F(68°C)Temperature Rating
means of gently dusting with a feather components manufactured by companies
duster;otherwise,non-operation in the not affiliated by ownership with TFPP •Sprinkler Finish
event of a fire or inadvertent operation or for products and components which . Escutcheon Finish(if applicable)
ma result. have been subject to misuse,improper
y installation,corrosion,or which have not • Order Length(value from Figure 2 or 3)
A Vent Hole is provided in the Bulb Seat been installed,maintained,modified or . Inlet Thread Connection(1-Inch NPT or
(Figure 1)to indicate if the Series LFII repaired in accordance with applicable ISO 7-R1)
Dry Type Residential Horizontal Sidewall Standards of the National Fire Protection
Sprinkler is remaining dry. Evidence of Association,and/or the standards of any • P/N(from Table D)
leakage from the Vent Hole indicates other Authorities Having Jurisdiction. Separately Ordered
potential leakage past the Plug with Seal- Materials found by TFPP to be defective Sprinkler Wrench
ing Assembly and the need to remove shall be either repaired or replaced, at Specify: W-Type 6 Sprinkler Wrench
the sprinkler to determine the cause TFPP's sole option.TFPP neither as- (Figure 4), P/N 56-000-6-387
of leakage(for example, an improper sumes, nor authorizes any person to
installation or an ice plug). Close the assume for it, any other obligation in Specify:W-Type 7 Recessed Sprinkler
fire protection system control valve connection with the sale of products �Nrench(Figure 5), P/N 56-850-4-001
and drain the system before removing or parts of products.TFPP shall not be
the sprinkler. responsible for sprinkler system design
Sprinklers which are found to be leaking errors or inaccurate or incomplete in-
or exhibiting visible signs of corrosion formation supplied by Buyer or Buyer's
must be replaced. representatives.
Automatic sprinklers must never be In no event shall TFPP be liable,in con-
painted, plated, coated, or otherwise tract,tort,strict liability or under any other
altered after leaving the factory.Modified legal theory,for incidental,indirect,special
sprinklers must be replaced.Sprinklers or consequential damages,including but
that have been exposed to corrosive not limited to labor charges,regardless
products of combustion, but have not of whether TFPP was informed about the
operated, should be replaced if they Possibility of such damages,and in no
cannot be completely cleaned by wiping event shall TFPP's liability exceed an
the sprinkler with a cloth or by brushing amount equal to the sales price.
it with a soft bristle brush. The foregoing warranty is made in lieu
Care must be exercised to avoid damage of any and all other warranties.express
to the sprinklers- before, during, and or implied.including warranties of iner-
after installation. Sprinklers damaged chantability and fitness for aparticular
by dropping, striking, wrench twist/ purpose. ,
slippage,or the like,must be replaced. This limited warranty sets forth the
Also, replace any sprinkler that has a exclusive remedy for claims based on
cracked bulb or that has lost liquid from failure of or defect in products,materi-
its bulb.(Ref. Installation Section.) als or components, whether the claim
The owner is responsible for the in- is made in contract,tort, strict liability
spection, testing, and maintenance of or any other legal theory.
their fire protection system and devices
in compliance with this document,as well
TFP461
Page 9 of 10
P/N* 63 - XXX - X - XXX
ORDER LENGTH
(EXAMPLES)
� O55 5.50"
082 8.25°
MODEUSIN
12 Horizontal Sidewall TY2335
180 18.00"
with Recessed Escutcheon (Figure 3) RECESSED
SPRINKLER FINISH ESCUTCHEON FINISH
Horizontal Sidewall TY2335 187 18.75"
13 without Escutcheon (Figure 2)
9 Chrome Plated Chrome 240 24.00"
White
4 Polyester Coated White
TEMPERATURE RATING
2 Natural Brass Brass Plated
1 155°F(68°C)
Note
`Use Prefix"I°for ISO 7-Ri Inlet Thread Connection;
for example,I-63-121-9-180.
TABLE D
PART NUMBER SELECTION FOR
RAPID RESPONSE SERIES LFII DRY TYPE RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS
TFP461
Page 10 of 10
Copyright m 2012 Tyco Fire Protection Products.All rights reserved. ��CO
TEFLON is trademark of The DuPont Corporation.
't CO Fire Suppression
� & Bui/din Products
g
Technical Services 800-381-9312�+1-401-781-8220
www.tyco-fire.com
Series DS-i Dry-Type Sprinklers
5.6K Pendent, Upright, and Horizontal Sidewa//
Standard Response, Standard Coverage
General the standards of any otherRuthorities
Having Jurisdiction. Failure fo do so
Description de !v c spair the performance of fhese
TYCO Series DS-1 Dry-Type Sprinklers, pwners are responsible for maintaining
5.6K Pendent, Upright, and Horizontal their fire protection system and devices
Sidewall, Standard Response (5 mm in proper operating condition. The
Bulb) and Standard Coverage, are installing contractor or sprinkler manu-
decorative glass bulb automatic sprin- facturer should be contacfed with any
klers typically used where: questions.
• pendent sprinklers are required on Series DS-1 Dry-Type Sprinklers musi
dry pipe systems that are exposed to only be installed in fittings that meet
freezing temperatures; for example, the requirements of the Design Criteria
sprinkler drops from unheated section.
portions of buildings
• sprinklers and/or a portion of the Model/Sprinkler
connecting piping may be exposed to
freezing temperatures; for example, /dentification �`
sprinkler drops from wet systems
into freezers, sprinkler sprigs from Numbers (S/NsJ �
wet systems into unheated attics, or ��
horizontal piping extensions through TY3255- Pendent
a wall to protect unheated areas of a TY3155- Upright
building such as loading docks,over- TY3355-Horizontai Sidewall
hangs,and building exteriors Finishes
• s rinkters are used on s stems that Technical Sprinkler: Natural Brass, Chrome
P Y Plated,White Polyester
are seasonably drained to avoid Escutcheon: White Coated, Chrome
freezing;for example,vacation resort Data Plated,Brass Plated
areas
Approvals Physical Characteristics
� UL and C-UL Listed Inlet. . . . . . . . . . . . . . . . . . . . . Copper
FM Approved
Series DS-1 Dry-Type Sprinklers Plug . . . . . . . . . . . . . . . . . . . . Copper
described herein must be installed LPCB Approved: Ref No.094a/11
CE Certified: EN 122.59-1 Yoke . . . . . . . . . . . . . . Stainless Steel
and maintained in compliance with this NYC A roved under MEA 352-01-E Casin Galvanized
document, as well as with the appli- Pp g ' ' ' ' ' ' ' ' ' ' ' ' ' ' '
Carbon Steel
cab/e standards of the Nationa/ Fire Refer to Table A. Insert . . . . . . . . . . . . . . . . . . . Bronze
Protection Association, in addition to
Maximum Working Pressure Bulb Seat . . . . . . . . . . Stainless Steel
175 psi(12,1 bar) Bulb . . . . . . . . . . . . . . . . . . . . . .Glass
IMPORTANT
Always refer to Technica/ Data Inlet ThPead Connections Compression Screw. . . . . . . . Bronze
Sheet TFP700 for the "INSTALLER �-inch NPT(Standard Order) Deflector. . . . . . . . . . . . . . . . . Bronze
WARNlNG"that provides cautions ISO 7-Ri Frame. . . . . . . . . . . . . . . . . . . Bronze
with respect to handling and instal- Discharge Coefficient Guide Tube. . . . . . . . . Stainless Steel
lation of sprinkler systems and K=5.6 GPM/psi��2 Water Tube. . . . . . . . . Stainless Steel
components.Improper handling and g0,6 LPM/bar��2
installation can permanentlydamage � � Spring. . . . . . . . . . . . . Stainless Steel
a sprinkler system or its compo- Sealing Assembly. . . Beryllium Nickel
nents and cause the sprink/er to fai! Temperature Ratings w/Teflon'
to o erate in a fire situatron or cause Refer to Table A.
P Escutcheon . . . . . . . . . .Carbon Steel
if to operate prematurely.
*DuPont Registered Trademark
Page 1 of 10 MAY 2011 TFP500
TFP500
Page 2 of 10
TY3255 Pendent TY3255 Pendent TY3355 Horizontal Sidewall
with top of Deflector-to-Ceiling
with Standard with Standard Escutcheon distance of 4 to 12 inches
Recessed Escutcheon (Figure 5) (100 to 300 mm)
(Figure 3)
with Wide Flange with Deep Escutcheon with Standard Escutcheon
Recessed Escutcheon (Figure 6) (Figure 9)
(Figure 4)
without Escutcheon with Deep Escutcheon
Temperature Bulb Color (Figure 7) (Figure 10)
Rating Code
TY3155 Upright without Escutcheon
(Figure 13)
without Escutcheon
(Figure 8)
SPRINKLER FINISH
Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Piated Polyester
135°F(57°C) Orange
155°F(68°C) Red
1,2,3,5 1,2,5 1,2,3,4,5 1,2,4,5 1',2',3",4,5 1",2',4,5
175°F(79°C) Yellow
200°F(93°C) Green
286°F(141°C) Blue N/A 4,5
360°F(182°C) Mauve N/A 1',2',5 N/A
Notes
1. Listed by Underwriters Laboratories, Inc.(maximum order 4. Loss Prevention Gertification Board and CE conformity
length of 48 inches) apply to these temperature ratings only
2. Listed by Underwriters Laboratories for use in Canada 5. Approved by the City of New York under MEA 352-01-E
(maximum order length of 48 inches) " Light and Ordinary Hazard Occupancies Only
3. Approved by Factory Mutual Research Corporation '� Light Hazard Occupancies Only
(maximum order length of 48 inches) N/A-Not Available
TABLE A
SERIES DS-1 STANDARD RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS
— LABORATORY LISTINGS AND APPROVALS —
PLUG WITH WLEf
SEALING
ASSEMBLY
YOKE
SPRING -
INLET
BAND WRENCH
WATER RECESS
TUBE //- CASING
_�
GUIDE INSERT
TUBE WRENCH , �
FLAT �
BULB v ��
FRAME '� � SEAT �
� �� PUSH WRENCH
— 5 mm BULB IN TO ENSURE
VENT HOLE ENGAGEMENT
WITH SPRINKLER
COMPRESSION WRENCHING AREA
DEFLECTOR SCREW
FIGURE 1
SERIES DS-1 STANDARD RESPONSE DRY-TYPE SPRINKLERS FIGURE 2
—ASSEMBLY— W-TYPE 7 SPRINKLER WRENCN
TFP500
Page 3 of 10
SPRINKLER FITTING SPRINKLER FITfING SPRINKLER FITTING
(REFER TO DESIGN (REFER TO DESIGN {REFER TO DESIGN
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)
FACE OF \ FACE OF FACE OF
SPRINKLER 1\ SPRINKLER SPRINKLER
FITTING �'�- � FITTING - , FITTING _ ,,
� _ _J � \ L_ _J �L_ _
,
ORDER LENGTHS:
ORDER LENGTHS: ORDER�ENGTHS: 3-1/2"DIA.
3-3/4"to 48" 1/2"to 46" (88,9 mm)
2-3/4"to 48" 1-3/4" DIA. (12,7 to 1168,4 mm) � �
(69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm) �N 1/4" 6 4 mm 2-1/2"DIA.
IN 1/4"(6,4 mm) � IN 1/4"(6,4 mm) 2-1/4"DIA. � ' � (63,5 mm)
WCREMENTS INCREMENTS (57,2 mm) WCRE�ENTS (�—y�
FACE OF �
CEILING F CEA OF
� F CEA OF _L � CEILING
CEILING �
4-1/4"t 1/8"
(108,0±3,2 mm)
2-3/16"+1/8" 3"DIA. 1-3/8"±1/8" 2-7/8"DIA.
(55,6±3,2 mm) ��6,2 mm) (34,9 t 3,2 mm) ��3,0 mm)
FIGURE 4
FIGURE 3 PENDENT TY3255 FIGURE 5
PENDENT TY3255 WITH STANDARD PENDENT TY3255
WITH STANDARD ESCUTCHEON RECESSED ESCUTCHEON WITH DEEP ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR
�
FACE OF
SPRINKLER \
FITTING }- ,
� L_ —_� ORDER LENGTHS:
} 5"to 48"
I (127,0 to 12'19,2 mm)
ORDER LENGTHS: IN 1/4"(6,4 mm)
5"to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4"(6,4 mm)
INCREMENTS FACE OF
� SPRINKLER
—_. FITTING
MINIMUM � r- -�
1-3/4"(44,5 mm) /�� -
DEFLECTOR �
TO CEILING SPRINKLER FITTING
� _— (REFER TO DESIGN
CRITERIA SECTION)
FlGURE 6 FlGURE 7
PENDENT TY3255 UPRIGHT TY3155
WITHOUT ESCUTCHEON WlTHOUT ESCUTCHEON
TFP500
Page 4 of 10
Operation
ORDER LENGTHS: When TYCO Series DS-1 Dry-Type
2-3/4"to 48"(69,9 to 1219,2 mm) Spf'InklefS are It1 SefViC2, water IS
IN 1/4"(6,4 mm)WCREMENTS 4„t��8„ prevented from entering the assembly
� ' (ioi,6±3,2mm) by the Plug with Sealing Assembly
' FACE OF FACE OF !'i 1-3/4"DIA. (Figure 1)in the Inlet of the Sprinkler.
—SPRINKLER MOUNTWG —; (44,5 mm) The glass bulb contains a fluid that
FITTING SuRFACE �� expands when exposed to heat.When
, � the rated temperature is reached, the
- � fluid expands sufficiently to shatter
l '� 3"DIA. the glass buib, and the Bulb Seat is
� � (�s,2 mm) released.
�-� 3.5° ! The compressed Spring is then able
to expand and push the Water Tube as
SPRINKLER FITTING \, well as the Guide Tube outward. This
(REFER TO DESIGN CENTERLINE 5/16" action simultaneously puils inward
CRITERIA SECTION) OF WATERWAY (7,9 mm) on the Yoke, withdrawing the Plug
with Sealing Assembly from the Inlet,
allowing the sprinkler to activate and
FIGURE 8 flow water.
TY3355 HORIZONTAL SIDEWALL WITH STANDARD ESCUTCHEON
Design
Criteria
ORDER LENGTHS: FACE OF TYCO Series DS-1 Dr T e S rinklers
1/2"to 45-3/4"(12,7 to 1162,1 mm) MOUNTING y' yp p
IN 1/4°(6,4 mm)INCREMENTS SURFACE are intended for use in fire sprinkler
4-13/16"±1/s" systems designed in accordance
(122,2±3,2 mm) with the standard instaliation rules
FACE OF 2-1/2° DIA. recognized by the applicable Listing
SPRINKLER (63,5 mm) or Approval agency; for example, UL
FITTING � Listing is based on NFPA 13 require-
j } ments. For more information on
� __i__+ I LPCB Approval, contact TYCO Fire
� i — 3-1/2" �IA. Suppression&Building Products at the
�� (ss,9 mm) following office:
�-� 3.5° Kopersteden 1
SPRINKLER FITTING � - / 7547 TJ Enschede
(REFER TO DESIGN CENTERLINE 5/16" The Netherlands
CRITERIA SECTION) OF WATERWAY (7,9 mm) Tel: +31-(0)53-428-4444
Fax:+31-(0)53-428-3377
Sprinkler Fittings
FIGURE 9 Install 1-inch NPT Series DS-1 Dry-Type
TY3355 HOR/ZONTAL SIDEWALL WITH DE'EP ESCUTCHEON Sprinkters are to be installed in the
1-inch NPT outlet or run of the following
fittings:
• malleable or ductile iron threaded
ORDER LENGTHS: tee fittings that meet the dimen-
5-1/2'�to 4s"(139,7 to 121s,2 mm) sional requirements of ANSI B16.3
IN 1/4"(6,4 mm)INCREMENTS MINIMUM (ClasS 150)
2-1/4��(57,2 mm) . cast iron threaded tee fittings that
FACE OF - DEFLECTOR TO meet the dimensional requirements
—SPRINKLER MOUNTING of ANSI 616.4(Class 125).
FITfING SURFACE
Do not install Series DS-1 Dry Type
- + � Sprinklers into elbow fittings.The Inlet
of the sprinkler can contact the interior
II � � of the elbow.
`_� 3.5° 5/16" The unused outlet of the threaded tee is
SPRINKLER FITTING (7,9 mm) plugged as shown in Figure 12.
(REFER TO DESIGN CENTERLINE You can also install Series DS-1
CRITERIA SECTION) OF WATERWAY Ory Type Sprinklers in the 1-inch NPT
outlet of a GRINNELL Figure 730
Mechanical Tee. However, the use of
FIGURE 10 the Figure 730 Tee for this arrangement
TY3355 HORIZON7TAL SIDEWALL WITHOUT ESCUTCHEON is limited to wet pipe systems.
TFP500
Page 5 of 10
Temperatures for Heated Area�
Ambient Temperature
Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C)
Sprinkler
Minimum Exposed Barrel Length, Inches(mm)2
40°F(4°C) 0 0 0
30°F(-1°C) 0 0 0
20°F(-7°C} 4(100) 0 0
10°F(-12°C) 8(200) 1 (25) 0
0°F(-18°C) 12(305) 3(75) 0
-10°F(-23°C) 14(355) 4(100) 1 (25)
-20°F(-29°C) 14(355) 6(150) 3(75)
-30°F(-34°C) 16(405) 8(200) 4(100)
-40°F(-40°C) 18(455) 8(200) 4(100)
-50°F(-46°C) 20(510) 10(255) 6(150)
-60°F(-51°C) 20(510) 10(255) 6(150)
Notes
1. For protected area temperatures that occur between values listed above,use the next cooler temperature.
2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph).
TABLE B
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
— MfNIMUM RECOMMENDED LENGTHS —
The configuration shown in Figure 13 � For protected area temperatures
is only applicable for wet pipe systems Do not insfall Series DS-1 Dry-Type between those given above, the
where the sprinkler fitting and water- Sprinklers into any other type fitting he fac of the ttin nao theeoutside of
filled pipe above the sprinkler fitting are i,y(thout first consulting the Technical the rotected area ma be determined
not subject to freezing and where the Services Departmeni.Failure to use the p y
length of the Dry-Type Sprinkler has the appropriate fitfing may result in one of by interpolating between the indicated
minimum ex osure len th de icted in values.
P 9 p the following:
Figure 11.Refer to the Exposure Length Clearance S aCe
section. •Failure of the sprinkler to operate prop- P
erly due to formation of ice over the In accordance with Section 8.4.9.2
For wet pipe system installations of In/et Plug orbinding of the Inlet Plug. of the 2010 edition of NFPA 13, when
1-inch NPT Series DS-1 Dry Type connecting an area subject to freezing
Sprinklers connected to CPVC piping, •Insufficient engagement of the In/et and an area containing a wet pipe
use only the following TYCO CPVC piPe-threads with consequent leakage. sprinkler system,the clearance space
fittings: Drainage around the sprinkler barrel of Dry-Type
• 1" x 1" NPT Female Adapter (P/N In accordance with the minimum Sprinklers must be sealed. Due to
80145) requirements of the National Fire temperature differences between two
Protection Association for dr i e areas, the potential for the formation
• 1" x 1" x 1" NPT Sprinkler Head sprinkler systems, branch, cro s, and of condensation in the sprinkler and
Adapter Tee(P/N 80249). feed-main piping connected to Dry subsequent ice build-up is increased. If
For dry pipe system installations, use Sprinklers and subject to freezing this condensation is not controlled, ice
only the side outlet of maximum 2-1/2- temperatures must be pitched for build-up can occur that might damage
inch reducing tee when locating Series proper drainage. the dry-type sprinkler and/or prevent
DS-1 Dry-Type Sprinklers directly proper operation in a fire situation.
below the branch line. Otherwise, use Exposure Length Use of the Model DSB-2 Dry Sprinkler
the configuration shown in Figure 12 to When using Dry Sprinklers in wet pipe goot,described in technical data sheet
assure complete water drainage from sprinkler systems to protect areas TFP591 and shown in Figures 14 and
above Series DS-1 Dry Type Sprinklers subject to freezing temperatures, use 15,can provide the recommended seal.
and the branch line. Failure to do so Table B to determine a sprinkler's
may result in pipe freezing and water appropriate exposed barrel length
damage. to prevent water from freezing in the
connecting pipes due to conduction.
The exposed barrel length measure-
ment must be taken from the face of
the sprinkler fitting to the surface of the
structure or insulation that is exposed
to the heated area. Refer to Figure 11
for an example.
TFP500
Page 6 of 10
RUN
FACE OF OUTLET TO WET SIDE
SPRINKLER O PLUGGED SYSTEM OUTLET
FITiING SPRINKLER PLUGGED
� TO DRY FITTING �
� EXPOSURE SYSTEM (SEE DESIGN
LENGTH CRITERIA
(SEE DESIGN SECTION)
DSB-2 CRITERIA DSB_2 SPRINKLER
INTENDED SECTION) DSB'2 INTENDED FITfING
FOR FREEZER . • INTENDED FOR FREEZER (SEE DESIGN
STRUCTURES FOR FREEZER STRUCTURES CRITERIA
STRUCTURES SECTION)
i
� /
FIGURE 12 FIGURE i3
FIGURE 11 SPRINKLER FITTING SPRINKLER F1777NG
— EXPOSURE LENGTH— — UNHEATED AREA — — HEATED AREA —
STRAPTIES 1-3/4" DIA.
(ENDS ON
–OPPOSING (44,5 mm)
SIDES OF CLEARANCE �NSULATED
BOO� HOLE FREEZER
ADHESIVE STRUCTURE
-DSB-2 BOOT
�—ADHESIVE DSB-2
BOOT
1-3/4" DIA.
_ (44,5 mm)
, CLfARANCE
� HOLE
1 f
INSULATED t
—FREEZER
STRUCTURE
DS-1 STRAP TIES DS-1
SHOWN WITH (ENDS ON SHOWN WITH
STANDARD OPPOSING STANDARD
ESCUTCHEON SIDES OF ESCUTCHEON
BOO�
FIGURE 14 FIGURE i5
MODEL DSB-2 DRY SPRINKLER MODEL DSB-2 DRY SPR/NKLER
800T WITH PENDENT SERIES gOOT WITH SIDEWALL SER/ES
DS-1 DRY-TYPE SPRlNKLER DS-1 DRY-TYPE SPRINKLER
TFP500
Page 7 of 10
/nstallation Note:If sprinkler removal becomes Never repaint factory-painted Cover
necessary, remove the sprinkler Plates. When necessary, replace
TYCO Series DS-1 Dry-Type Sprinklers using the same wrenching method cover plates with factory-painted
must be installed in accordance with noted above. Sprink/er removal units. Non-factory applied paint can
the following instructions. is easier when a non-hardening adversely delay or prevent sprinkler
sealant was used and torque guide- operation in the event of a fire.
� lines were followed. After removal, Replace sprinklers that:
inspecf the sprinkler for damage.
Series DS-1 Dry-Type Sprinklers must • were damaged by dropping,striking,
only be installed in fittings that meet 4. After installing the ceiling or wall and Wrench twisting,wrench slippage,or
the requirements of the Design Criteria app�ying a ceiling finish,slide on the the like.
secfion. Refer to fhe Desi n Criteria outer piece of the Escutcheon until
g it comes in contact with the ceiling/ •were modified or over-heated.
section for other important require-
ments regarding piping design and wall. Do not lift the ceiling panel out . have cracked bulbs or have lost liquid
sealing of the clearance space around of its normal position. from the bulbs.Refer to the Installation
the Sprinkler Casing. When using the Deep Escutcheon, Section in this data sheet.
Do not install any bulb type sprinkler if hold the outer piece in contact with . are leaking or exhibiting visible signs
the bulb is cracked or there is a loss of the mounting surface (ceiling or of corrosion.
liquid from the bulb.With the sprinkler wall). Then rotate the inner piece Res onsibilit lies with owners for the
held horizontally, a small air bubble approximately 1/4 turn with respect inspection,testing,and maintenance of
should be present.The diameter of the to the outer piece,to hold the Deep their fire protection system and devices
air bubble is approximately 1/16 inch Escutcheon firmly together.
in compliance with this document, as
(1,6 mm)for the 135°F(57°C) rating to well as with the applicable standards of
1/8 inch(3,2 mm)for the 360°F(182°C) Care and the National Fire Protection Association
rating. (for example, NFPA 25), in addition to
Obtain a leak-tight 1-inch NPT sprinkler Maintenance the standards of any other Authorities
joint by applying a minimum-to- Having Jurisdiction. The installing
maximum torque of 20 to 30 ft. Ibs. TYCO Series DS-1 Dry-Type Sprinklers contractor or sprinkler manufacturer
(26,8 to 40,2 Nm). Higher levels of must be maintained and serviced should be contacted relative to any
torque may distort the sprinkler Inlet in accordance with the following questions.
with consequent leakage or impairment instructions. Automatic sprinkler systems are recom-
of the sprinkler. � mended to be inspected, tested, and
Do not attempt to compensate maintained by a qualified Inspection
for insufficient adjustment in an Before closing a fire protection system Service in accordance with local
Escutcheon Plate by under or over- main control valve for maintenance requirements and/or national codes.
tightening the Sprinkler. Re-adjust the work on the fire protection system
position of the sprinkler fitting to suit. that ii conirols, obtain permission to
1. Install endent s rinklers onl in shut down the affected fire protection
P P Y systems from fhe proper authorities
the pendent position; install upright and notify all personnel who may be
sprinklers only in the upright posi- affected by this action.
tion.The deflector of a pendent or
upright sprinkler is to be parallel to Absence of the outer piece of an
the ceiling. escutcheon, which is used to cover a
Install horizontal sidewali sprinklers clearance hole, may delay the time to
in the horizontal position with their sprinkler operation in a fire situation.
centerline of waterway perpendic- A Vent Hole is provided in the Bulb Seat
ular to the back wall and parallel to (Figure 1)to indicate if the Dry Sprinkler
the ceiling. Ensure the word "TOP" is remaining dry. Evidence of leakage
on the Defiector faces the ceiling. from the Vent Hole indicates potential
2. With a non-hardening pipe-thread �eakage past the Inlet seal and the need
sealant such as Teflon` applied to to remove the sprinkler to determine
the Inlet threads, hand-tighten the the cause of leakage;for example, an
sprinkler into the sprinkler fitting. improper installation or an ice plug.
Close the fire protection system control
3. Wrench-tighten the sprinkler using valve and drain the system before
either: removing the sprinkler.
• a pipe wrench on the Inlet Band or Exercise care to avoid damage before,
the Casing(Figure 1). during, and after installation. Never
• the W-Type 7 Sprinkler Wrench on Paint, plate, coat, or otherwise alter
the Wrench Flat(Figure 2). automatic sprinklers after they leave
the factory.
Apply the Wrench Recess of the
W-Type 7 Sprinkler Wrench to the
Wrench Flat.
'DuPont Registered Trademark
TFP500
Page 8 of 10
Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire Contact your local distributor for avail-
Suppression and Building Products ability.When ptacing an order, indicate
(TFSBP) are warranted solely to the the full product name, including
original Buyer against defects in description and Part Number(P/N).
material and workmanship when paid
for and properly installed and main- Dry Sprinklers
tained under normal use and service. When ordering 5.6 K-Factor Series
This warranty will expire twelve (12) DS-1, Standard Response , Standard
months from installation or eighteen Coverage (5 mm Bulb), Dry Type
(18) months from delivery, whichever Automatic Sprinklers, specify the
occurs first. No warranty is given for following information:
products or components manufac- . Model/SIN
tured by companies not affiliated by Pendent TY3255,Upright TY3155,or
ownership with TFSBP or for products Horizontall Sidewall TY3355
and components which have been '
subject to misuse, improper instal- . Deflector Style �
lation, corrosion, or which have not
been installed, maintained, modified • Order Length
or repaired in accordance with appli- Dry Type Sprinklers are furnished
cable Standards of the National Fire based upon Order Length as
Protection Association, and/or the measured per Figures 3 through 10,
standards of any other Authorities as applicable.After the measurement
Having Jurisdiction. Materials found by is taken, round it to the nearest 1/4
TFSBP to be defective shall be either inch increment.
repaired or replaced, at TFSBP's sole . Inlet Connections
option. TFSBP neither assumes, nor 1_inch NPT or ISO 7-R1
authorizes any person to assume for
it, any other obligation in connection • Temperature Rating
with the sale of products or parts of . Sprinkler Finish
products.TFSBP shall not be respon-
sible for sprinkler system design errors • Escutcheon Style and Finish, as
or inaccurate or incomplete infor- applicable
mation supplied by Buyer or Buyer's . Part Number from Table B. Part
representatives. numbers are for 1-inch NPT standard
In no event shali TFSBP be liable, in order sprinklers. Orders for all other
contract, tort, strict liability or under sprinkler assemblies must be accom-
any other legal theory, for incidental, panied by a complete description.
indirect, special or consequential
damages, including but not limited to Sprinkler Wrench
labor charges, regardless of whether Specify W-Type 7 Sprinkler Wrench,
TFSBP was informed about the possi- P/N 56-850-4-001.
bility of such damages, and in no
event shall TFSBP's liability exceed an Sprinkler Boot
amount equal to the sales price. Specify Model DSB-2 Dry Sprinkler
The foregoina warran�is made in lieu Boot, P/N 63-000-0-002. This Part
of an rLand all other warranties.exoress Number includes one Boot,two Strap
or implied. including warranties of Ties, and 1/3 oz. of Adhesive (a suffi-
merchantability and fitness for a partic- cient quantity for installing one boot).
ular pur�ose.
This limited warranty sets forth the
exclusive remedy for claims based
on failure of or defect in products,
materials or components,whether the
claim is made in contract, tort, strict
liability or any other legal theory.
This warranty will apply to the full
extent permitted by law.The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
TFP500
Page 9 of 10
P/N* 60 - XXX - X - XXX
MODEL/SIN SPRINKLER ESCUTCHEON
FINISH FINISH(1)
96 Pendent with Standard TY3255 � NATURAL BRASS WHITE
Escutcheon(1"NPT) (Figure 3)
93 Pendent with Deep TY3255 4 WHITE POLYESTER WHITE
Escutcheon(1"NP� (Figure 5)
9� Pendent with Standard TY3255 g CHROME PLATED CHROME
Recessed Escutcheon(1"NP� (Figure 4)
92 Pendent without TY3255 0 CHROME PLATED WHITE
Escutcheon(1"NP� (Figure 6)
2 NATURAL BRASS BRASS PLATED
94 Sidewall with Standard TY3355
Escutcheon(1"NPI� (Figure 8)
53 Sidewall with Deep TY3355
Escutcheon(1"NP� (Figure 9)
54 Sidewall without TY3355 TERATING(2)RE L NGTH(3)
Escutcheon(1"NP� (Figure 10)
0 135°F(57°C) 055 5.50"
98 Upright without TY3155 � 155°F(68°C) 082 8.25"
Escutcheon(1"NP� (Figure 7)
2 175°F(79°C) 180 18.00"
Notes 3 200°F(93°C) 187 18.75"
" Use Prefix"I"for ISO 7-R1 Connection;for example,
I-60-961-1-180). a 2as°F(141°c) s�2 37.25��
1. Escutcheon Finish applies to sprinklers provided with
escutcheons. 5 360°F(182°C) 480 48.00"
2. 286°F(141°C)and 360°F(182°C)temperature ratings apply
to non-recessed sprinkler assemblies.
3. Dry-Type Sprinklers are furnished based upon "Order
Length"as measured per Figures 3 through 10,as appli-
cable, and for each individual sprinkler where it is to be
installed.After the measurement is taken, round it to the
nearest 1/4 inch increment.
TABLE C
SERIES DS-1 STANDARD RESPONSE, STANDARD COVERAGE,DRY-TYPE SPRINKLERS
— PART NUMBER SELECTION —
TFP500
Page 10 of 10
Copyright O 2007,2011 Tyccs Fire Suppressiqn&Building Products.All rights reserved.
FIRE SPRINKLER VALVES
ES-A-200B
• �
Ser�es 240B A M E S
Double Check Valve Assemblies FIRE&WA.TERWORKS�
Sizes �/2"—2° (i5—50mm}
�'"
��
2008
Features Series 200B Double Check Valve Assemblies are designed to protect drink-
• Cast bronze construction ing water supplies from dangerous cross-connections in accordance with
• Separate access, top entry check national plumbing codes and water authority requirements.
valve design
• Reversible seat disc rubber, This series may be used in only those cross-connections identified by local
extends check valve life inspection authorities as non-health hazard applications. Check with the local
• Chloramine resistant elastomers authority having jurisdiction regarding vertical orientation, frequency of test-
• Replaceable seats and seat discs ing or other installation requirements. Series 2006 meets the requirements of
ASSE Std. 1015 and AWWA Std. C510.
• Compact design
• Top mounted screwdriver slotted
ball valve test cocks
• Low pressure drop Specifications
• �/2"—1" (15—25mm) have Tee Double Check Valve Assembly shall be installed at each noted location.
handles Provide assembly with integral shutoff valves that conform to ASSE 1015
• No special tools required for and AWWA C510. The assembly shall have top entry access points for each
seNicing check assembly, screw driver slotted test cocks and require the use of no
• Plastic on plastic check guiding special tools for servicing. All wetted rubber parts shall be manufactured from
reduces potential binding due to silicone or chloramine resistant EPDM rubber. All valve seats and seat discs
mineral deposits shall be replaceable. Seat discs shall be reversible to extend check valve
life. Check valve guiding shall be plastic to plastic. The assembly shall be an
Ames Company Series 200B.
Job Name Contractor
Job Location Approval
Engineer Contractor's P.O. No.
Approval Representative
Ames product specifications in U.S.customary units and metrir,are approximate and are provided for reference only.For precise measurements,please co�tact Ames Technical Service.Ames
reserves the right to change or modify product design,construction,specifications,or materiafs without prior notice and without incurring any obligation to make such changes and motlifications
on Ames products previously or subsequently sold.
www.amesfi rewater.com
Available Models Materials
Suffix: Body: Bronze
S—bronze strainer Elastomers: Chioramine resistant silicone and EPDM
LH—locking handle ball valves Check Seats and Disc Holders: PPO
HC—2'/z" inlet/outlet fire hydrant fittings(2" valve)
B—quarter-turn ball valves
PC—interna)polymer coating Standards
C&T—test cock cap&tether AWWA Std C510 compliant
LBV—less ball valves
A—street elbows with quarter-turn bail valves Appi ovals
Prefix: fl55E °P` Sp�
U—union connections ° ` "S
1075
Pressure-Temperature
Operating Pressure: 175psi(12.07 bar) IMPORTANT:Inquire with governing authorities for
local installation requirements.
Operating Temperature Range: 33°F—180°F (5°C—82°C)
Dimensions — Weights
-----------------------------------------------------------a----------------------------------------------------------------
----------------------------------------- A -------------------------------------------
N-------- ------------ ; ;
C ! '
�� ��� B
- - - —8 �
M �
,
— G -�— H
,
,
` ---------•-------•---. E ._...--°-------•---- ------- P -----
200B, 200B—S
, � � • � �
A B C D E(L� F G H M N 2008 2006-5
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm Ibs. kgs. lbs. kgs.
'/z 15 99/,e 242 3'�hs 94 215/,s 73 129he 318 513/is 147 2'hs 62 1"hs 43 '/a 19 13I8 35 23/a 70 2.8 1.3 3.8 1J
3/a 20 12'/a 307 4'/a 108 3'/z 88 15'hs 393 7"/is 195 3Ve 79 2'hs 52 1'hs 27 15/e 41 33/,s 81 4.7 2.1 6.4 2.9
1 25 1413/,s 376 49hs 116 37/s 98 19'/z 495 95/s 244 33/a 95 2'/,e 62 15he 33 2'/s 54 33/a 95 7.4 3.4 9.4 4.3
1'/a 32 18t5/�s 480 6'/a 156 5'/e 129 24'/,s 610 11"/is 297 4'/a 108 Z5I8 67 15/e 41 2'/2 64 4�/is 113 14.0 6.3 18.0 8.1
1'/z 40 1875l,s 480 6'/e 156 5'/a 129 25�/a 640 11"/,e 297 43/a 121 3'/a 79 15/e 41 3 76 4'/a 124 16.1 7.3 19.9 9.0
2 50 213hs 538 7'he 179 55/a 142 2875hs 735 133/s 340 53IB 137 3'/,s 87 115/�s 49 39/,s 90 515/,s 151 25.7 11.6 33.4 15.2
2
--------------------------------------------------------------------- � --------------------------------------------
------------_---------------------------- A ----------------------------------------
N � �
C ;
� ,,1►�t ' B
M .
? G �-- H-
� --------------------- E ----------------------- -
--- -
. -------F�-----
U2006, U200B-S
� � � � r �
A B C D E(LF� F G H M N U200B U200B-S
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm tbs. kgs. Ibs. kgs.
'/z 15 1513hs 402 49hs 116 3'/a 98 1813/,s 478 113/s 289 3 76 P'/,e 43 15/is 33 13/a 35 23la 70 7.4 3.4 8.4 3.8
3/a 20 16'/a 412 49hs 116 3'/a 98 195/a 498 1151is 287 33I8 86 2'hs 52 15/is 33 �SIB 41 33/7s 81 7.9 3.6 9.7 4.4
1 25 175hs 439 49he 116 3�/e 98 22 558 113/a 297 33/a 95 2'/,s 62 15/,s 33 Z'/a 54 33/a 95 8.9 4.0 10.9 5.0
1'/a 32 20'/s 530 6'/e 156 5'/e 129 26 660 153/e 390 4'/a 108 Z5I8 67 15/s 41 2'/z 64 4'/,s 1t3 17.6 8.0 21.6 9.8
1'/z 40 219he 547 6'/s 156 5'/e 129 27�/s 708 153/s 390 43/a 121 3'!s 79 15/e 41 3 76 4'/s 124 19.8 9.0 23.5 10.7
2 50 24'hs 621 7'/,s 179 55/a 142 32317s 817 163/a 425 53/a 137 3'/,s 87 1'S/,s 49 39hs 90 5'Shs 151 30.� 13.6 37.7 17.1
D �w� ,���
�
� � I
,
�
, , �
�
,
� E; --------------------- ------------------- ;
g C
i
---G ---1-- H--
�-------------------------------------- A -------------------------------------� -------�F-------
200B A
� � �
A B C D E(LF� F G H 2O0B A
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.
Vz 15 7'/a 200 35/is 84 215/�s 73 215/is 73 513/is 147 2'/is 62 1'Vis 43 3/a 19 3.4 1.5
3!a 20 13'hs 340 413hs 121 49hs 116 3'/z 98 7"/,s 195 3'/a 79 2'/,s 52 1'/,s 27 5.7 2.6
1 25 12"hs 322 5 127 43I8 110 3'/s 98 95/s 244 33/a 95 2'/,s 62 15/,s 33 8.9 4.0
1'/a 32 153/is 386 5��/ie 144 5�Vis 144 5Va 129 11"/,e 297 4�/a 108 25/s 67 15/a 41 15.7 7.1
1'/z 40 1513hs 401 6'/,s 156 63hs 156 5'/a 129 11"/is 297 43/a 121 3'/e 79 �5I6 41 18.4 8.3
2 50 173/s 441 65/s 168 69/,s 167 55/s 142 133/e 340 53/a 137 3�hs 87 175/�s 49 29.0 13.1
3
Capacities
`Typical maximUm flow rate(7.5 feeUsec.)
200B 2006 A_ U200B
Yz"(15mm) 1'/a"(32mm)
kPa psi * kPa psi *
110 16 138 20
97 14 -
69 10 103 15 -
41 6 _ - -- -- � �. 69 10 ,� - � �
28 4 . � ' � 34 5 _ � -: '_
14 2
0 0 0 0
0 1 2 3 4 5 6 7 S 9 10 11 12 gpm 0 2 4 8 12 16 20 30 40 50 60 70 75 SO 90 100 110 gpm
0 4 8 23 15 19 23 27 30 34 38 42 46 Ipm 8 15 30 46 61 76 114 152 190 228 266 285 304 342 380 418 Ipm
7.5 fps 7.5 fps
229 mPs 2.29 mps
'/a" (20mm) 1'/z"(40mm)
kPa psi * kPa psi *
172 25 110 i6
97 14
138 20 83 12
103 15 69 10
69 10 55 8
� 41 6 � � _� -�
_�
34 5 - - '- � ' 28 4 - -
0 0 14 2
0 0
0 2 4 8 12 16 18 20 24 28 30 34 45 gpm 0 2 4 6 12 16 20 30 40 50 60 70 80 90 100 110120 gpm
8 15 30 46 61 69 76 91 106 114 129 171 Ipm S 15 23 46 61 76 114 152 190 228 266 304 342 380 418 456 Ipm
7.5 fps 7.5 fps
2.29 mPs 2.29 mps
1"(25mm) 2"(50mm)
kPa psi * kPa psi *
97 14 97 14
83 12 ' 83 12
69 10 '� � 69 10
55 8 '� 55 8
41 6 ' � 41 6 -
28 4 -- --- 28 4 -- -
14 2 14 2
0 0 0 0
0 2 4 6 12 16 20 30 40 50 60 gpm 0 4 12 20 40 60 80 100 120 140 160 200 gpm
8 15 23 46 61 76 114 152 190 228 ipm 15 46 76 152 228 304 380 456 532 480 760 Ipm
7.5 fps 7.5 fps
2.29 mPs 2.29 mps
�
A M E S � • 9001-2008
FIRE&WATERWORKS www.amesfirewater.com C E R T 1 F 1 E D
A Watts Water Technologies Company USA: Backflow- Sacramento,CA•TeC(916)928-0123•Fax�(916)928-9333
Control Valves- Houston,TX•Tel:(713)943-0688•Fax:1713)944-9445
Canada: Burlington,ON•Tel:(905)332-4090•Fax:(905)332-7068
ES-A-200B 0532 �O 2011 Ames Fire&Waterworks
PIPE AND FITTINGS
SPEABS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS
�
The information contained in this publication is based on current information and Product design at the time of pubiication and is subject to change without
notification.Our ongoing commitment to product improvement may result in some variation.No representations,guarantees or warranties of any kind are matle
as to its accuracy,suitability for particular applications or results to be obtained therefrom.For verification of technical data or additional information not contained
herein,please contact Spears�Technical Services Department(West Coast:(818)364-1611—East Coast:(678)985-1263].
General Information
RECOMMENQATIONS FOR INSTALLERS AND USERS:
Plastic piping systems should be ENGINEERED,INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS
AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the instalier andlor user prior to
installation of a plastic piping system.Ail Installation and maintenance personnei should be trained in the proper handling and installation requirements and
precautions of plastic piping systems. PRIOR TO ASSEMBLY,ail piping system components should be inspected for damage or irregularities.Mating
components should be checked to assure that tolerances and engagements are compatible.Do not use any components that appear irregular or do
not fit properly.Contact the appropriate manufacturer of the component product in question to determine usability.Consult all applicable codes and
regulations for compliance prior to installation.
Installation must be made in accordance with Spears�'Manufacturing Company
FlameGuard°CPVC Fire Sprinkler Piping Products Installation Instructions-FG-3
NOTE—Individual or group instruction in correct solvent weltling procedures is available by contacting your local distributor or your servicing Spears�Regional
Distribution Center.
SOLVENT CEMENT CONNECTIONS—Spears��Manufacturing Company recommends the use of Spears�FS-5 One Step solvent cement for joining Spears�
products.Use of solvent cementing protlucts not approved for CPVC fire sprinkler systems,or failure to follow installation instructions will automatically void
the warranty.
THREADED CONNECTION—Spears�Manufacturing Company recommends the use of Spears�BLUE 75TM'Thread Sealant.This product has been tested
by Spears�and the sealant manufacturer for compatibility with the Spears�CPVC fire sprinkler products.Consult the sprinkler head manufacturer before using
this product.WARNING:OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN
THE CPVC OR OTHER FITfING COMPONENTS.Care must be taken to avoid over torquing-generally 1 to 2 turns beyond finger tight is all that is required
to make up a threaded connection.Factory testing has ind�cated 1�-25 ft.Ibs.of torque is adequate to obtain a leak free seal.
GASKET SEALED THREAD CONNECTIONS—This type of connection can only be matle with Spears�TorqueSafeT"" style Gasket Sealed Female Sprinkler
Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER.Tape or paste may impair proper sealing and
function.Testing has shown that hand tight until snug is all that is needed to seal this special connection.
Dimension Reference
G = (LAYING�ENGTH)Intersection of center lines to bottom of socketlthread;90°elbows, M = Outside diameter of socket/thread hub;±1116 inch.
tees,crosses;±1/32 inch. N = Socket bottom to socket bottom;couplings;±1/16 inch.
H = Intersection of center lines to face of fitting;90°elbows tees,crosses;t 1/32 inch. Q = �n/idth of flats;±1/16 inch.
J = Intersection of center lines to bottom of sockeUthreaci;45°elbows;±1/32 inch W= Height of cap;±1/16 inch.
L = Overall length of fittings;±1/16 inch.
CPVC FIRE SPRINKLER PIPE SDR 13.5(ASTM F 442)
Nominal Size Average O.D. Average I.D.
Part Number Approx.Weight Lbs.IFt.
Inches (mm) Inches (mm) Inches (mm)
CP-�07 3/4 (19.1) 1.050 (26.7) .574 (22.5) •181
CP-010 1 j25.4) 1.315 (33.4) 1.1D1 (28.2) 280
CP-012 1-114 (,31.8) 1.660 (42.2) 1.394 (35.6) 418
CP-015 1-1/2 (38.1) 1.900 (48.31 1.598 (40.7) 550
CP-�20 2 (50.8) 2.375 (60.3) 2.003 (50.9) 872
CP-Q25 2-1/2 (63.5) 2.875 (73.01 2.423 (61.5) 1.260
CP-030 3 (76.�) 3.500 (88.9) 2.950 (75.0) 1.°00
� SPEARS'�MANUFACTURING COMPANY
r
FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS
�
TEE
S ocket x S ocket x S ocket
,
� '
PA -- --�-- -
t
G
� H ��
t � -_
Part Number Size G H L M Approx.Wt (Lbs.)
4201-007 3/4 9/I 6 1-1 R 2-31 r32 1-5/I 6 11
4201-010 1 13A 6 1-13A 6 3-5�8 1-58 .20
4201-012 1-1/4 15l32 2-3/32 4-7/32 2 29
4201-015 1-12 1-5/32 2-9/I 6 5-3/32 2-11/32 .54
4201-020 2 1-13/32 2-15/16 5-78 2-78 86
4201-025 2-12 1-23/32 3-12 7 3-15/32 1.62
4201-030 3 2-1/I 6 3-15/16 7-78 4-3A 6 302
REDUCING TEE
S ocket x S ocket x S ocket
I�--►�-Ml
�
T I �M M2 t
j - � �,
� G2
H -�—H 2�
L
Part Number Size G G1 G2 H H1 H2 L M � Np Approx.Wt
(Lbs.)
4201-102 3/4x3/4x1 3/4 25%�'s2 3/4 1-11/16 1-13/I 6 1-11/i 6 3-38 1-5/I 6 1-21/32 1-5/I 6 13
4201-125 1 x3/4x3/4 21/32 13-16 5�8 1-25/32 1-13lI 6 1-5i$ 3-13/32 1-17/32 1-5/I 6 1-5A 6 15
4201-126 1 x3/4x1 3/4 1=�$ 1-3/32 1-27/32 2-31/32 1-31/32 3-13/I 6 1-23/32 1-23/32 1-13/32 26
4201-131 1 xl x3/4 21/32 13r"6 21/32 1-25/32 1-13/I 6 1-25132 3-9/I 6 1-58 1-5A 6 1-58 .16
4201-157 1-1/4x1 x3/4 11/I 6 1-1�32 11/I 6 1-15(I 6 2-1/32 1-13/I 6 3-25/32 2-3/32 1-13/32 1-23/32 3Z
4201-158 1-1/4x1 xl 27/32 29Li2 25l32 2-1/I 6 2-1/32 1-29/32 3-15/16 1-31!32 1-SB 1-58 .24
4201-159 1-1/4x1 x1-1/4 31/32 31 32 31/32 2-7/32 2-7/32 2-3/32 4-11!32 2-3/32 23/32 1-23/32 35
A201-167 1-1/4x1-1/4x3/4 21/32 1 21/32 1-29/32 2 1-29/32 3-13/I 6 2 1-5�16 2 .22
4201-168 1-1/4xl-1/4x1 13/I 6 31'32 13/I 6 2-1 il 6 2-3/32 2-1/I 6 4-1 B 1-31/�2 1-21/32 2 Z4
4201-169 1-1/4x1-1 i4xt-1/2 1-1 Pd 15�16 1-1 B 2-3/8 2-11/32 Z-3/i3 4-3l4 2-3/32 2-11/32 23/32 .51
4201-201 1-12x1-1/4x3/4 11 i16 1 1/4 2-1/I 6 2 1-15/I 6 4 2-5/I 6 1-3i$ 2-1/l 6 41
4201-202 1-12x1-1/4x1 27/�2 1-1:32 1 2-7l32 2-5I32 2-1/4 4-15/32 2-5A 6 1-11 Ji 6 2-1/I 6 .42
4201-210 1-12x1-12x3/4 23l32 1=I,16 23l32 Z-3/32 2-1/32 2-3/32 4-3/I 6 2-5A 6 1-3� 2-5A 6 37
4201-211 1-12x1-12x1 13/16 1-;�,16 13/I 6 2-3/16 2-1/4 2-3/I 6 4-38 2-11/32 1-23/32 2-11�32 .41
4201-212 1-1 I2x1-12x1-1/4 1 1-?B 1 2-3i$ 2-11!32 2-3i8 4-13/I 6 2-11/32 2-3/32 2-11/32 48
4201-213 1-12x1-12x2 1-5/I 6 1-'��8 1-5116 2-11!I 6 2-21!32 2-11 A 6 5-3i8 2-11/32 2-27,32 2-11�32 .72
MADE IN THE U.S.A. 2
SPEARS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS
�
REDUCING TEE (continued)
S ocketx S ocketx S ocket
�—►-r M1
--�
� I � H1
M - M2 �
� j c,
� G2
N fH2�-
L
PartNumber Size G G1 G2 N H1 H2 L M Mi � pPProx.Wt
(Lbs.)
4201-248 2x2x3/4 11JI6 1-13/32 11/I6 2-7/32 2-7/I6 2-7/32 4-7/I6 2-27/32 1-38 2-27/32 52
A201-249 2x2x1 27/32 1-7/I 6 27/32 2-11/32 2-9A 6 2-11/32 423/32 2-78 t-3/4 2-7�$ .57
4201-250 2x2x1-1/4 1 1-11/32 1 2-17/32 2-19(32 2-17/32 5-3/32 2-27/32 2-3/32 2-27/32 .63
4201-251 2x2x1-1!2 1-7/32 1-13/32 1-7/32 2-11/16 2-25/3'L 2-11/16 53B 2-27/32 2-11/32 2-27/32 .$5
4201-239 2-12x2-1 ILx1 29/32 25/32 29/32 2-21/.32 1-29/32 2-21/32 5-5/16 3-12 1-23l32 3-12 1.03
4201-290 2-12x2-12x1-1/4 1-3/32 1-23l32 1-3/32 2-27/32 2-31/32 2-27/32 5-21/32 3-17/32 2-3/32 3-17/32 1.13
4201-291 2-12x2-12x1-12 1-3/16 12 1-3/I 6 2-15/I 6 1-78 Z-15/16 5-78 3-15/�2 2-11!32 3-15(.i2 1.26
4201-292 2-12x2-12x2 1-13/32 1-58 I-13/32 3-3/I 6 3-1�8 3-3/I 6 6-11/�2 3-1/2 3-7�$ 3-12 1.34
4201-335 3x3x1 7�$ 1-15116 7B 2-3/4 3-1/I 6 2-3/4 5-15/32 4-3/I 6 1-23/32 4-3/I 6 1.26
42Q1-336" 3x3x1-1/4 1-3�8 1-3/4 1-38 3-5/I 6 3-1�2 3-5/I 6 6-58 4-1 B 2-7�$ 4-1 B 1.94
' A201-337 3x3x1-12 1-5/32 2-1/I 6 1-5/32 3-1/32 3-7/I 6 3-1/.32 6-3/32 4-3/I 6 2-38 4-3/16 1.46
4201-338 3x3x2 1-7�6 1-13A 6 1-7i16 3-5/I 6 3-5A 6 3-5A 6 6-19/32 4-3/I 6 2-78 4-3/I 6 1.69
4201-339 3x3x2-12 1-3/A 1-31/32 1-3l4 3-58 3-23/32 3-Si8 7-1!4 4-3/I 6 3-17/32 4-3/I 6 2.11
*Branch Outlet Sized with Bushing
TorqueSafeT'" SPRINKLER HEAD TEE
Gasket Sealed Brass M�--
Thread Insert Style ' c� t
SocketxSocketxGasketflPT � ( � � I
With E Iast�merSeal-Use NO Thread Sealant � �
M -- �- -- �z —�-
. �
G G2
H H2
L
Part Number Size G G1 GZ H H1 H2 L M Mi M2 Approx.Wt (Lbs.)
4202-101 G 3/4x3/4x1�L 7A 6 1-3lI 6 �16 1-1/I 6 1-7116 1-17l32 2-29/32 1-38 1-38 1-38 .22
4202-124 G 1 x3/4x12 7!I 6 1-11/32 ':316 1-9lI 6 1-11/16 1-9/I 6 3-1�$ 1-11/I 6 1-3� 1-3� .26
4202-130 G 1 x1 x12 7/I 6 1-11/32 ?16 1-9/I 6 1-11/I 6 1-9/I 6 3-1 i8 1-23132 1-3r$ 1-23/32 .28
4202-166 G 1-1/4x1-1/4x12 7/I 6 1-SB ,'16 1-11�16 1-15/I 6 1-11/I 6 33B 2-1/I 6 1-38 2-1/I 6 .34
4202-209 G 1-12x1-12x12 12 1-13A 6 12 1 JB 2-3/32 1-7 B 3-3/4 2-11/32 1-38 2-11/32 41
4202-247 G 2x2x1!2 1!1 2-1!I 6 12 2 2-11/32 2 4-1/32 2-27/32 1-38 2-27/32 .54
Notintended tn convey or dispense water for human consumption through drinking or cooking
3 SPEARS�MANUFACTURING COMPANY
FlameGuard� CPWC FIRE SPRINKLER PIPING PRODUCTS SPEARS il
�
SPRINKLER HEAD TEE
Brass Thread Insert Style
S ocket x S ocket x f ipt �M�
G1
H1
M -- --�-- - M2
� �
G G2
r H—► H 2---►
�— L —_
PartNumber Size G G1 G2 H H1 H2 L M MI IVQ Approx.Wt (Lbs.)
4202-101 3/4x3/4x12 7/16 1-5/�2 7/I 6 1-7A 6 1-17/32 1-7lI 6 2-29/32 1-3i8 1-7/32 1-3�8 27
4202-124 1 x3/4x12 7/I 6 1-11/32 9/I 6 1-9/I 6 1-11/I 6 1-9/I 6 3-1 r$ 1-11/I 6 1-38 1-38 .26
4202-130 1 xl x12 7/I 6 1-7/32 7/I 6 1-9lI 6 1-25/32 1-9/I 6 3-1 B 1-3/4 1-3/I 6 1-3/4 26
4202-010 1 x1 x1 11/I 6 1-3/32 11/I 6 1-13/I 6 1-29/32 1-13/I 6 3-19I32 1-23/32 1-23132 1-23l32 .37
4202-156 1-1 J4x1 x1 Q 7/16 1-15,32 9l16 1-11/I 6 2-1/32 1-11/I 6 3-38 2-3/32 1-7/32 1-3/4 30
4202-166 1-1/4x1-1/4x12 7/l 6 1-1,2 7/I 6 1-11/I 6 2-1/I 6 1-11 A 6 3-13/32 2-3l32 1-3/I 6 2-3/32 .32
4202-199 1-12x1-1/4x1 IL 1 i2 1-58 9/I 6 1 JB 2-3A 6 1-13/I 6 3-11/I 6 2-5116 1-7l32 2-1/I 6 37
4202-209 1-12x1-12x12 12 1-23,32 1/2 1-7 B 2-3132 1-78 3-3/4 2-5/I 6 1-17I32 2-5/I 6 .45
4202-237 2x1-tl2x12 12 1-7,8 17/32 2 2-7/I 6 1-29/32 3-15/I 6 2-27l32 1-7/32 2-5/I 6 48
4202-247 2xZx12 12 1-31/32 12 2 2-38 2 4-1/32 2-27132 1-17/32 2-27/32 .58
Not intended to convey or dispense water for human consumption through drinking or cooking
SPRINKLER HEAD TEE
Special Reinforced Plastic Thread Style
S ocket x S ocket x S R F ipt
�+--Mt�
I
!,'� G1
� � H1
M - -t- - M2 �
� �
� G2
H H2
L
Part Number Size G G1 G2 H H1 H2 L M Ntl M2 Approx.Wt (Lbs.)
4202-101 S R 3/4x3/4x12 19I32 3/4 19/32 1-19l32 1-7/I 6 1-19/32 3-7/32 1-13/32 1-3/I 6 1-13/32 .16
4202-124SR 1 x3/4xl 2 7/16 29l32 9/I 6 1-19/32 1-SB 1-9/I 6 3-5/32 1-23/32 1-3A 6 1-17/32 19
4202-130SR 1 xl x12 7A 6 29l32 7/16 1-9/I 6 1-58 1-9/I 6 3-1� 1-23/32 1-3/I 6 1-23/32 .20
4202-010S R 1 xl x1 21/32 3i4 21/32 1-25/32 1-58 1-25/32 3-19/32 1-23/32 1-11/I 6 1-23/32 26
4202-1565 R 1-1/4x1 x12 15/32 1-5/3� 19l32 1-23i32 1-78 1-23/32 3-13/32 2-3/32 1-3A 6 1-23/32 26
4202-166S R 1-1 l4x1-1 l4x12 7/I 6 1-1 B 7/I 6 1-11116 1-27/32 1-11/I 6 3-38 2-3/32 1-3A 6 2-3/32 26
4202-1685 R 1-1/4x1-1/4x1 27/32 1-1�32 27/32 2-3l32 1-29/32 2-3l32 4-7/32 2-3/32 1-11/I 6 2-3/32 .34
4202-199SR 1-12x1-1/4x12 9/16 1-9�32 17/32 1-15/I6 2 1-25/�2 3-23/32 2-11/.32 1-3/16 2-3/32 33
4202-2095 R 1-12x1-12x12 12 1-1!4 12 1-7�8 1-31/32 1-7,$ 3-3/4 2-11/32 1-3A 6 2-11!32 35
4202-211 SR 1-12x1-12x1 27/32 1-7/�2 27/32 2J/32 2-1�$ 2-7/32 4-15/32 2-11/32 1-23/32 2-11/32 .44
4202-2375 R 2x1-12x12 23/32 1-9:7 6 3B 2-7i32 2-9/32 1-3/4 3-31/32 2-7 B 1-3/I 6 2-1132 45
4202-2475R 2x2x1/2 12 31�32 12 2 1-11/I 6 19/�2 4 2JB 13/I 6 2-78 48
4202-287SR 'L-12x2-12x12 17/�2 1-3/4 17/32 2-9l32 2-1l2 2-9/32 4-19/32 3-12 1-7/32 3-12 .78
MADE IN THE U.S.A. �
SPEABS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS
�
TORQUESAFET"" SPRINKLER HEAD TEE
Gasket Sealed Brass Thread Insert Style
Socketx G asketF IPT x SocketWith E lasmmer Seal-
Use NO Thread5ealant
M1�
G1
� , � H1
M -- -+-- ` M2 �
L
I G G2
f+--H H2
�—L
PartNumber Size G G1 G2 H H1 H2 L M Ml M2 Approx.Wt (Lbs.)
4203-122 G 1 xt 2x1 19/32 13/I 6 1-13/3"L 1-19l32 1-27/.i2 1-3/4 3-11/32 1-58 1-5� 1-38 25
Not intended to convey or dispense water for human consumption through drinking or cooking
SPRINKLER HEAD TEE
Brass Thread Insert Style
S ocket x F ipt x S ocket
M1 —►I
G1-�
� � H1
M -�-- M2 -'=
�
�� G2
H H 2--►
L —+
Part Number Size G G1 G2 H H1 H2 L M Mt MZ Approx.Wt (Lbs.)
4203-122 1 xl IZxI 23/32 3/4 1-1/4 1-58 1-58 1-15/I 6 3-1!L 1-23l32 1-23/32 1-3/I 6 25
Not intended to convey or dispense water for human consump6on through drinking or cooking
SPRINKLER HEAD TEE
Special Reinforced Plastic Thread Style
SocketxSR FiptxSocket
~M���
�
? � � "j
M - -�- M2
L �
J H-�-�
Part Number Size G G1 G2 H H1 H2 L M Mt M2 Approx.UVt. (Lbs.)
4203-1225 R 1 x12x1 27/32 23/32 1-3-"s2 1-23/32 1-SB 1-25/32 3-13/�2 1-3/4 1-3l4 1-3/I 6 'Ll
5 SPEARS�MANUFACTURING COMPANY
� FIRE SPRINKLER PIPING PRODUCTS SPERBS
FlameGuard cPVC �
STREET TEE
Spigotx Socketx Socket nm�-
�-irr
0.[?. Hl
I -----i---- i� j
G G2
�—H —'.I.—H2—�
-�— L -
PartNumber Size G G1 G2 H H1 H2 � Mt M2 Approx.Wt (Lbs.)
4244-007 3/4 13A 6 271�2 27/32 1-13/I 6 1-78 1-78 3-5�8 1-13/32 1-13I32 16
4244-010 1 1-5I32 1-1/32 1-1/32 2-1 B 1-29/32 1-29/32 4-3/I 6 1-3/4 13/4 27
4244-012 1-1/4 1-1/4 1 1 2-7i16 2-9/32 2-9/�2 4-27132 2-3/32 2-3/32 .42
4244-015 1-12 1-13/I 6 1-1�$ 1-1 B 2-7� 2-9A 6 2-9/I 6 5-11�32 2-11/32 2-11!32 56
4244-020 2 1-23f32 1-7/I 6 1-13/32 3-1!4 2-15/I 6 2-15/I 6 6-5/�2 2-7� 2-7�8 84
9� ELBOW
S ocket x S ocket
G
�---
H
�I I
I•—(�---►{
Part Number Size G H M Approx.Wt (Lbs.)
4206-007 3/4 9A 6 1-12 1-5lI 6 .O7
4206-010 1 3I4 1-58 1-58 11
4206-012 1-1/4 7/8 2-5/32 Z .21
4206-015 1-12 1-5l32 2-17/32 2-38 .41
4206-020 2 1-13/32 2-29/32 2-7 B 45
4206-025 2-12 1-58 3-7/I 6 3-7A 6 1.17
4206-030 3 1-29/�'L 3-23/32 4-3/I6 1.80
SIDE OUTLET ELBOW
S ocket x S ocket x S ocket
I �
-- M
�
G �H
Part Number Size G H M Approx.Wt (Lbs.)
4213-007 3/4 27/32 1-19l32 1-5/I 6 09
4213-010 1 13/I 6 1-78 1-5i$ 18
MADE IN THE U.S.A. 6
SPEARS ; FlameGuard� CPVC PIRE SPRINKLER PIPING PRODUCTS
�
REDUCING 9� ELBOW
S ocketx S ocket Nt�
G1
G �
f" - M�
H
�I
N--M�
Part Number Size G G1 H H1 M Mt Approx.Vlh. (Lbs.)
4206-131 1 x3/4 25/32 11/16 1-25/32 1-25/32 1-19/32 1-5116 11
TorqueSafeT"' 9(p SPRINKLER HEAD ELBOW
Gasket Sealed Brass Thread Insert Style
Socketx G asketF IPT With E lasmmer Seal-
Use NO Thread Sealant
H1
G1
G �
_ M1
1 � �
H
1 �
M
Part Number Size G G1 H H1 M MI Approx.Wt (Lbs.)
4207-101 G 3/4x12 9ll 6 1-7/32 1-13/32 1-17/32 1-13/32 1-38 19
4207-130 G 1 x12 15/32 1-13/32 1-9/I 6 1-11/I 6 1-23/32 1-38 .23
4207-166 G t-1/4x12 15/32 1-19/32 1-15/I 6 1-11 A 6 2-3/32 1-3i$ .25
Notintended to convey or dispense water for human consumption through drinking or cooking
SPRINKLER HEAD 9� ELBOW
Brass Thread Insert Style
SocketxFipt �� ���
G �
� --- Ml
�
H I
�I
I� M �
Part Number Size G G1 H H1 M Ml Approx.Wt (Lbs.)
4207-101 3J4x12 7A 6 1-5/32 1-23/32 1-17/32 1-13/32 1-17/32 25
4207-130 1 x12 15/32 1-58 1-9/I 6 1-11/I 6 1-23l32 1-17/32 28
A207-131 1 x3/4 17/32 1-114 1-21/32 2 1-23/.32 1-38 '1.5
4207-166 1-1/4x12 15/32 1-17i32 1-11/16 1-15A 6 2-3/32 1-17l32 .33
Not intended to convey or dispense water for human consumpUOn through drinking or cooking
7 SPEARS"MANUFACTURING COMPANY
FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPERRS
�
SPRINKLER HEAD 9(� ELBOW
Special Reinforced Plastic Thread Style
S ocket x S R F ipt
H1�G1
G �
- ` Ml
� +
H � -
�I I
I-�M--►I
Part Number Size G G1 H H1 M MI Approx.UVt (Lbs.)
4207-101 S R 3/4xl!2 11�32 13/I 6 1-15/32 1-12 1-13l32 1-3/I 6 .14
4207-1305 R 1 x1 CL 7/I 6 7B 1-9/I 6 1-58 1-23/32 1-38 20
4207-131 S R 1 x3/4 12 7i8 1-5�$ 1-9/I 6 1-23/32 1-38 16
4207-166S R 1-1/4x12 13/32 1-1/32 1-21/�2 1-23l32 2-3/32 1-7/32 .19
9(p STREET E�BOW
S pigot x S ocket
H1�G1
G �
- M1
� �
H
�
�.---.�- P IP E 0.D,
Part Number Size G G1 H H1 M1 Approx.W�. (Lbs.)
4209-007 3/4 29/32 19/32 1-15/I 6 1-11 A 6 1-13/32 .12
4209-010 1 1 3/32 23/32 2-13/32 1-27/32 1-3/4 .21
4209-012 1-1/4 1-9lI 6 27/32 2-13lI 6 2-3/32 2-3/32 .32
4209-015 1-12 1 15132 1-3/I 6 2-27/32 2-9/I 6 2-11/32 .42
4209-020 2 1 '1.3C32 1-38 3-7/32 2-15/16 2-27/32 .65
MADE IN THE U.S.A. 8
SPEABS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS
�
22-1I'Z' E L BOW
S ocket x S ocket
J
1
H I
i
(-�-M--►�
Part Number Size H J M Approx.Wt (Lbs.)
4216-007 3/4 13116 7/32 1-13/32 .09
4216-Q10 1 1-38 9/32 1-25132 14
4216-012 1-1/4 1-12 5/I 6 2-3/�2 .20
4216-015 1-12 1-7/I 6 13/.32 1-3�$ .19
4216-020 2 1-7�$ 3B 2-27/32 43
4216-030 3 2-38 12 4-5/32 1.00
221l� STREET ELBOW
S pigotx S ocket
H1 �� �
��./
t
H � I
�
�PIPE O.D.
Part Number Size H H1 J J 1 Mt Approx.Wt (Lbs.)
4242-007 3/4 1-1/4 1-12 1/4 12 1-3i$ .08
4242-010 1 1-7/I 6 1-11/32 5/I 6 7/32 1-23/32 .14
42A2-Ol 2 1-1 l4 1-9/I 6 1-25/32 17/32 11/I 6 2-1 A 6 21
4242-Ot 5 1-12 1-13/32 1-23/�2 12 11/32 2-11/32 28
4242-020 2 1-29/32 2-1 B 7/32 5B 2-7i$ 42
4242-025 2-12 2-1 B 2-1/4 13/�2 12 3-1/L 68
4242-030 3 2-13/32 2-13/32 9/i 6 11/32 4-5/32 99
g SPEARS�MANUFACTURING COMPANY
FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPE�RS y
�
a� E�BOw
S ocket x S ocket
J /,
= I
H I
�
I�—nn--�.l
Part Number Size H 1 M Approx.Wt (Lbs.)
4217-007 3/4 1-5/I 6 5ll 6 1-5/I 6 07
4217-010 1 1-13/�2 3B 1-5�$ 11
4217-012 1-1/4 1-58 3B 2-5/32 21
4217-015 1-1,2 1-27/32 15/32 2-11/32 .32
4217-020 2 2-1 B 21/32 2-7�8 .48
4217-025 2-12 2-17/32 3/4 3-12 .B8
4217-030 3 Z-29/32 29/�2 4-5/32 1.17
4�i STREET ELBOW
S pigot x S ocket
H1��
J1 �
�
H � I
J ,
�
I• -�PtPE O.D.
Part Number Size H H1 J J 1 Mi Approx.Wt. (Lbs.)
4227-010 1 1-12 1-5lI 6 1!2 1/4 1-5�8 .10
4227-012 1-1/4 1-25/32 1-9/I 6 9/I 6 11/�2 1-31/32 .15
4227-015 1-1/2 2 1/32 2-1 B 19/32 25/32 2-11/3Z .29
4227-020 2 2-`:/I 6 1-15/I 6 25/32 13/32 2-78 .44
MADE IN THE U.S.A. 10
,
SPEARS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS
�
CROSS
S ocket x S ocket x S ocket x S ocket
G1� t
�
M - � � LIl
� � H1
G
H
L
PartNumber Size G G1 H H1 L L1 M Approx.Wt (Lbs.)
4220-007 3/4 5B 5,� 1-21 f32 1-21 32 3-5II 6 3-5lI 6 1-13/32 22
4220-010 1 3/4 'i,'9 1-58 1-58 3-1/4 3-1/4 1-23l32 .20
4220-012 1-1/4 1-1� 1-1 B 2-38 2-38 4-3/4 4-3/4 2-3/32 63
4220-015 1-12 1-7/32 1-i,32 2-58 2-5i8 5-7/32 5-7/32 2-3i$ 80
4220-020 2 1-12 1 12 3 3 6 6 3 1.43
A220-025 2-12 1-11li 6 1-11/I6 3J/I 6 3-7A 6 6-78 6-7� 3-17/32 2.16
4220-030 3 2-3i32 2-3,32 3-31/32 3-31/32 7-15/16 7-15/16 4-7/16 3.37
REDUCING CROSS
S ocket x S ocket x S ocket x S ocket
i---r�
� � Hi
M ---'-- L1
� � G1
�
G� H
L -�
Part Num6er Size G G1 H H1 L L1 M Ml Approx.Wt (Lbs.)
4220-131 1 x3/4 23/32 5B 1-SB 1-58 3-1/4 3-1/4 1-78 1-12 31
4220-167 1-1/4x3/4 1-1/I 6 23/32 2-1/I 6 1-31/32 4-3/32 3-31/32 2-1/i 6 1-13/32 35
4220-210 1-12x3/4 11/I 6 1-5/32 23/32 2-3/I 6 4-3/I 6 4-11/32 2-38 1-13/32 42
4220-248 2x3/4 11/16 1-7A6 2J/32 2-7/16 4-13/32 4-78 2-29/32 1-13/32 56
4220-289 2-12x1 29/32 1-314 2-11/I 6 2-78 5-11/32 5-3/4 3-12 1-3/4 98
�� SPEARS°'MANUFACTURING COMPANY
FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS
�
COUPLING
S ocket x S ocket
I
--- --- M
�
F.-� I
�
Part Number Size L M N Approx.Wt (Lbs.)
4Z29-007 3/4 2-t B 1-5lI 6 3/I 6 .05
4229-010 1 2-3/I 6 1-58 3/32 O8
4229-012 1-1/4 2-19/32 2 3/32 .13
4229-015 1-12 Z-7B 2-11/32 3/32 .22
4229-020 2 3-1� 2-7� 1 B .33
4229-025 2-12 3-11/I 6 3-15/32 3/I 6 48
4229-030 3 4 4-3/16 1/4 .89
REDUCER COUPLING
S ocket x S ocket
� �
M ---- --- Nil
1 -�
_I. N
L -�
Part Number Size L M Mi N Approx.UVt. (Lbs.)
4229-131 1 x3/4 2-38 1-23/32 1-13/32 7/.32 10
4229-167 1-1/4x3/4 2-19/�2 2-3/32 1-58 11/32 .17
4229-168 1-1/4x1 2-11/I 6 2-3/32 1-23/32 5/16 .18
4229-210 1-12x3/4 2-13/I 6 2-11/32 1-13I32 15/32 .19
4229-211 1-12x1 2-7�$ 2-11/32 1-15/I 6 3�$ .24
4229-212 1-12x1-1/4 2-13/I 6 Z-13/32 2-1 B 5/32 23
4229-248 2x3/4 3-3/16 2-7�$ 1-7/I 6 23/32 32
4229-249 2x1 3-18 2-78 1-23I32 12 31
4229-250 Zx1-1%4 3-3/I 6 2-78 2-1 B 17/32 33
4229-251 2x1-12 3-3lI 6 2-27/32 2-11/32 9/32 .31
4229-291 2-12x1-1,2 3-23/�2 3-15/32 2-11/�2 21/32 51
4229-292 2-12x2 3-21/32 3-12 2-78 13/32 52
MADE IN THE U.S.A. �Z
SPEARS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS
�
GROOVED COUPLING ADAPTER
G roove x S ocket
� �
PIPE ---- --- �
O.D.
�- 1
� L �
Part Number Size L Mi N Approx.Wt (Lbs.)
4233-012 1-1/4 3-SB 2-3�32 2-11/32 .72
4233-015 1-12 3-3/4 2-11/�2 2-11/32 .83
AZ33-020 2 3-27/32 2-27/32 2-11l32 1.27
4233-025 2-12 4-3/16 3-15/32 2-7/16 2.02
4233-030 3 4-5/16 4-1� 1-7/I 6 2.76
FE M4LE ADAPTE R
Brass Thread Insert Style
S ocketx F ipt
�
M —- - M1
�
I���
Part Number Size L M M1 N Approx.Wt (Lbs.)
4235-007 3/4 2 1-13/32 1-38 5/I 6 .23
4235-010 1 2-3/I 6 1-3l4 1-11/I 6 11/32 .25
4235-012 1-1/4 2-38 2-3/32 2-1/I 6 11/32 36
4235-015 1-1 i2 2-9/I 6 2-3�$ 2-7/I 6 11/32 47
4235-020 2 2-25/32 2-27/32 3-3/16 7/16 1.05
Notintended to convey or dispense water for human consumpUOn through drinking or cooking
13 SPEARS�MANUFACTURING COMPANY
HANGERS AND SEISMIC BRACING
,
���U�J
P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
CPVC — COPPER �05 ` �os
• 5TEEL i
OFFSET HANGER ,Saoo 3�0
� l
SIZE-SYSTENT PIPE: 3/4"thru 3" •
MATERIAL-Carbon Steel.
FINISH-Mil.Galvanized..
LISTING/APPROVAL-
`OU=203-EX 4231,EX 2551
PATENT-No.6,648,278.
FUNCTION- Support horizontal piping: 3/4"-3" CPVC or Copper.
• Support horizontal piping: 3/4"-2" Steel.
Size 3/4"-2"provides listed verticaUlateral restraint and prevcnts upward movement
of pipe that supplies a pendent sprinkler below a ceiling.
Stabilize vertical piping.
INSTALLATION- Per these instructions
includin NFPA 13, 13R 13D and CPVC manufacturers instructions. usted Resc�a�nt
g , 314"thru 2"
lnstall on horizontal or vertical mounting surface.
Snap over pipe then squeeze strap back allowing pipe to slide freely. � �
When #905 threads are exposed in wood, install#906 backing nut.
FASTENERS-UL Listed per NFPA 13
WOOD- 3/4" -3" CPVC pipe-#905 screw-no pre-drill.
3/4"-2" Copper pipe- #905 screw- no pre-drilL
3/4"-2" Steel pipe- 1/4"xl 1/2" lag screw- no pre-drill. � � �
Thni 5!8" gypsum board- 1/4"x 2"lag screw. �'
STEEL-min. 18 GA. - 3/4"-3"CPVC pipe- 1/4" or#14 Tek Screw. ' �
3/4" -2"Co er i e- 1/4" or#14 Tek Screw. ' ��'�
PP PP -� ', ,
3/4" -2" Steel pipe- 1/4"or#14 Tek Screw. � ""�
CONCRETE: Required minimum load eaeh fastener= S(tivt)+ZSOIbs. �;, ��
FEATURES Z 1-�'��°�
I
* 1 1/2" Offset:loose fit allows pipe to slide. ��,� ,�� �ist d Restra�n�
3/4 and 1 p�pe size made with common center-line. ��y' sia^mru z��
*Patented design for superior strengtl�.
* Offset edge eliminates abrasiou.
*AFCON#905 screw included-5/16"hex head.
ORDERING-Part#and pipe size.
AFCON#906 backing nut sold separately.
Specitic.4FCONproducts are excluaively designeJ to be compatible ONL�'�vith other.4FCONproducts including pahs und fnsteners,resulting in u lieled sway brace.�estrainer or haneer asszmbly.
Be advised the loilowing wurranty resiriction will apply. DiSCI.;U�[ER-.4FCON will NOT w�Irant against the failure oP its products when used in combination with other products�ports or.y,tems
not manufactured or sold hy AFCOIY..4FCON sha11?lOT be liabla�mder any circumstances whal.oever for uny direct or indirect,incidental or eonseyuential damages of any kind,including bw not
limited tn loss of business or protit,w'hen non-.4FCOh'products huve h2en.nr are uved.
�`� .
�y _ '
v� �i �
,`�""4d, sa"'m�e.
1���� ...,..._
y
U �D�
P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
CPVC - COPPER
SIDE MOUNT HANGER
�
- -i
0 I �
__II
O II
o II
II
-_�_
Side Vie�v-For
Drawings Bzlow
� �
SiZE-SYSTEM PiPE: 3/4"thru 2"
MATERIAL-Carbon Steel.
FINISH-Mil. Galvanized.
LISTING/APPROVAL-
`,��'203-EX 4231,EX 2551
FUNCTION- Support horizontal piping-CPVC ar Copper.
Stabilize vertical piping.
INSTALLATION-Per these instrucrions xan�er-wood sn�d
including NFPA 13, 13R, 13D and CPVC manufacturers instiuctions.
Install on vertical mounting surface. f
FASTENERS-UL Listed per NFPA 13.
in WOOD:
3/4"-2"CPVC pipe-#905 screw- no pre-drill. �� T�,�
3/4"-2"Copper pipe-#905 screw- no pre-drill. �
in STEEL-min. 18 GA.
3/4"-2"CPVC pipe- 1/4"or#14 Tek Screw. `!
3/4"-2"Copper pipe- 1/4"or#14 Tek Screw.
FEATURES
i
* Offset edge eliminates abrasion. �--�
*Retainer dimples secure hanger to pipe during installation.
*Required AFCON#905 screw included-5/16"hex head.
ORDERING-Part#and pipe size.
Hangzr-Metal Stud
Specilic AFCONproducis are exclusively desi�,med to be computible ONCY with other.4FCONpruduct.including pans and fastenerc.res�lting in a listeJ sway brace,restrainer or hun,�er assembly.
Be advised�he(ol lowing warranty restrictinn will apply. DISCI.AIVIF.ft-.AFCO�V will NOT wa`rant.�gains[the Cailure of its producis when used in combination with other products,p:�rts or.ry,tems
not manufaemced or sold by AFCOIY..4FCON sliall VOT be liabla undz�any circumstauces wha�soever for any direct or indireet,incideutal or conseyuential damages ot any kind,including but not
limired to loss of busine,s or pratit,wheu non>4FCON product.h:ive heen,or are used. ,
r`��°�� '�
'�E" �`.
� ��
.
9/08
MISCELLANEOUS MATERIALS
Y
1 I ' i � � � i �
' � ,
a
, � � � �
' + . • � ' '
� �
•The AGF Manufacturing, Inc. Mode18000l8011 �y����� �
RESIDENTIAL RISERPACK� is a prepackaged eco
nomical riser assembly designed for NFPA 13D
and13R residential fire sprinkler systems.
• The Model 8000/8011 complies with the NFPA
13D and 13R requirement regarding testing
through a properly sized test orifice. 1" Model
8000/8011 are available to meet nominal K-factor
requirements of 2.8 to 5.6.
•The 1�/a", 1�/z" and 2" Model 8000/8011 are avail
able with 3/s", '/�s", '/2", "/sz", and 5/a° (ELO) orifiCes ,. � �,. ; �
to meet K-factors of 2.8 to 11.2.
• Cast and machined of bronze in the U.S.A. � � :��; ��
• Rise�PACK� is a one-piece casting, lettered on `��� _
both sides allowing right or left installation and � f
providing required signage for flow direction, test
and drain outlet, and gauge location.
• NPT male threaded ends allow easy connection to
popular plastic piping systems and are designed
to fit within most standard stud wall framing.
•The 1'h" and 2" RESIDENTIAL RISERPACK°s are also
available with grooved or threaded x grooved ends °"� '''�
for use with approved rubber gasketed couplings. ' - " " '
• Includes UL Listed/FM Approved AGF Model
7500 300-PSI Pressure Gauge.Those for 13R
systems also include'/a" 3-way globe valve.
• 1" Model 8000 utilize a 3/a" ball valve with patented
TESTnNDRA1N�orifice specific outlet designed '• " '"'
to accept either a standard garden hose or hard " • ' " "
piped drain line.
•The 1�/a", 1'/z" and 2" Model 8000 utilize the UL
Listed/FM Approved patented AGF Model
3011 BV INSPECroR'sTEST`� ball valve.
• Available as the Model 8011 with UL Listed/FM
Approved Model 7000 Pressure Relief Valve
(1'/a" —2") or Model 7200 Pressure Relief Valve
(1") which is designed to provide relief, test, and
drain through a single valve. ��� �� ��
• Larger size risers available on special order.
NOTE:It is important to note that the pressure rating of the relief valve indicates an operating range of pressure for both opening and ciosing of the valve.
Standard relief valves are required to OPEN in a range of pressure between 90%and 105%of their rating.The valves are required to CLOSE at a pressure
above 80°%of that rating.The relief valve should be instailed where it is easily accessible for maintenance.Care should be taken that the relief valve CAN-
NOT be isolated from the system when the system is operational.A relief valve should NEVER have a shutoff vaive or a plug downstream of its outlet.
� ' . • � • i � 1 1 r !
RISERPACK,TESTANDRAIN,and INSPECTORSTEST are registered trademarks of AGF Manufacturing Ina CS8000R 2/11
�
.
1 1 ' i � � � i �
� •
, . ,
� � � /
1° MODEL SCIOO '�° MODEL SO�� 11�4° — `�c° MODEL$��� '���411 —��� MODEL +SO'I'�
B
4 B B ��e� B a�°'"�`. g
,��� ti',, � �an��� '' e�c ti. s�p� A
If�He� �!��;! /� m� \��tx� �,��' �.�act !z'�� 1 9
t'� ,m " yq 10
� \�� Y ,x �
�eqY * � � 4 �4 � g 10 gu. �3
� q 7 j r. �:_:.o... .,.�.,. A 5 �i a A
A �....�... R,i. � 'SS ^iT\ -= a
�r 2 6 'aT g� � ~+•
3 �q
s 5 5 f' �s
5 �� � = t � il 8� _ �—D 12 17
o h ��
� _ — 11 16
— I 13�
� I C C—'I--D I !—D—i—C^ C—I 15
DIMENSIONS COMPONENTS
Model SIZE A B C D Item No. Part Qty.
1,� 10�/z" 12�/a" 43/a"* 61/a" 1 RiserPACK-Bronze Casting 1
(267 mm) (311 mm) (121 mmi (159 mm) � 3/a" Male x Female Ball Valve 1
° 11" 12�/a"*" 4" 6�/z"
o°0 1��4�� (vs mm� (st�mm� (�oz mm� (165 mm) 3 1° M3011 BV INSrECroR'sTEST ValV2 1
0 1�h„ 12�� 12��Z�� ** 4��8�� gs�s° 4 M7500 Pressure Gauge('/a"3-Way Globe 1
� (305 mm) �sn mmi (105 mm� (168 mm) Valve Included for 13R Systems Only)
2�� 12" 13" 43/a" 6�/s" 5 Water Flow Alarm Switch 1
(305 mm) (329 mm) (111 mm) (174 mm)
10�/z" 12�/a" 2�/s" "�* 6�/a" 6 3/4" MNPT x'/z" FNPT Hose Atlaptor Orifice 1
1�� (267 mm) �a7�mmi p3 mm� (159 mm) 7 M7200 3/4" Pressure Relief Valve 1
0 1��4,� 14�/a" 15" 4" 6�/z" 8 M7000 Y2" Pressure Relief Valve 1
ap (375 mm) (381 mm) (102 mm) (165 mm)
0 1��Z�� 15�/a" 15�/a" 4�/s" 65/a" � 1" Brass Nipple 1
� (387 mm) (ss�mm) (�os mmi (�sa mm) 10 1" Brass Street Elbow 1
2,� 15�/a" 153/a" 43/s" 6�/a" 11 �/2" Brass System Access Port Plug 1
(387 mm) (399 mm) (111 mm1 (V4 mm)
12 1" Relief Valve Bypass Nipple 1
'Additional space may be necessary to allow fcr hard drain
fitting if required. 13 1" Relief Valve Bypass Tee 1
*'Valve handie clearance required — add 2". 14 '/z" NPT x-Bafb Straight Fitting 1
`"' Lift handle clearance required — add 3�/e". 15 '/z" NPT x�Barb Elbow Fitting 1
16 Clamps 2
/=��� 17 Nylobraid Relief Valve Drain Tubing 1
MADE IN U:S.�.
� - . � . .
AGF Manufacturing Inc. Job Name:
100 Quaker Lane,Malvern, PA 19355
, Phone:610-240-4900 AI'CIlIt2Ct:
Fax:610-240-4906 Engineer:
www.testandrain.com
Contractor:
HYDRAULIC CALCULATIONS
N ONLY FO
a0�0G�e Cert//kf�lp
•
` � * � �t
i
��0
J 'r.
ir �i nw' '
s .
+��a � �,�
��io`Rb De��`i��
a
���� � - F� _�` ii���,�� '�: �i ti���k �'. JOb NUmb@�:CR04
i p ��
Re ort Descri tion:Residential
��w�w.�����I'�I��:',� ��-�y,�r`����mW� i s;��,a`x��� n;- ��������`,:�+x.�r�,a.���N���`�i����h��l-�'z���������ai'���iu. iI� .�r� p� =��` � iN'"id�� _-� . �'i�s�'ut`'�'��.
�y
Job Number Desgn Ergineer
CR04
Job Name'. � Ph°^° FAX
Creek Road Mixed Use
Address 1 � SWte Certifiqtbnlliceme Numbet
106th Avenue SE and Creek Street UNLIMM1096M6
Atltl�ex 2 � AHJ
Yelm,WA 98597 City of Yelm
Atltlreu 7 JoC S�eiBUiltling
Building E
`�,. h �iii " � " �. � a .=yi� �.��.. 216 =wF � '� �.�I�.Vii�i�� 4 �k,`�' "'� ,�,� �?� ��:
���",M;`,C�F4�' — �d���"�7�i�ry4p j���7u � �-_.��"��+��,�i�i} 35,� - `s�"`�i,•, � _'��,N7'r y-'�,.��i�� i.i `'�F��""a���;� t��", �-��3t���e�" ' ti.�-u�
i ,... _. . - - ,..�, � . � a _ , . .-
�p��iN Aree alApplkaHOn
0.050gpmlft' 367.00ft'(Actual 367.28ft�
AAOSI DameMirg Sprinkk�Oala Hose Sireams
4.9 K-Factor 12.96 at 7.000 100.00
Coverega Per Spnnklar Number Of Sprinkkrs CakWatetl
256.�Oft� 4
System Pressure Demartl � System Fbw Demand
44.537 54.41
To�al Oemantl Precsure Rewlt
154.41 @ 44.537 +5.016(10.1%)
� s � 3"�I k '�`��,t*.`3� ��& !��(i = — � �3�°, - �- `�a ` i r �& '-�._�, �"
��� �� ,r,�tr,.' j'�� �"'d'�� r. P� =w' h1�F ,�,`*;�p iv� — -�°�:�n,i! �r�'.��. '.,��r�;e �T���, i i I ,�3`,� -°-���I�i�^��
4
fl
Node Name Flow(apml Hose Flow(qpml Static si Residual(psil Identifier Pressure(osil K-Factor(Kl Flow(ppm)
100 Water Supply 1500.00 100.00 50.000 20.000
i F' ���i������w . ' �� i.�,.° �' �U �N�Ct�tl'tQ�M` �'�.0�`1�'��: 5t��IE#�`2t1 ��i'��i������G°�fis°:'°`
`Y� ���"�.��by�"�Inh��'�� � � �'�. ' , I i: � P�di" � ��� w. _� } � i
100
90
i. .i ��•, 80
4 —
— v. �a �a �
_ _ r
�e •� 1• a� 70
— — � � — — — — — — — — — -- — — — — _ 60
�N
a
�' S0 Static Pressure 50.000
�.o o� ��° i--' —; � �`•: ..o o . N 4.41 �44.537
— — P ';�O:P �J a �1 N
� , ,� � qQ 154.4*1 with hose streams
•` '' �'' '• a ( I\ I �
��.� ' , , ' �.'• • • • • • • • • • • gp System demand curve
20 1500.00�20.000
�� � ; � 10
0
�q3001200 1500 1 S00 2�00 2�� 2700 3000
Water flow,gpm
�,O M.E.P.CAD,Inc. 6;��AutoSPRINK�1 VR'0 v10.0.59.0 S116/2013 8:32:50PM Page 1
. �
���� �' �� ���� �����T �.
�, � � � � � t�����F �� Job Number.CR04
Re ort Descri tion:Residential
to"� " �h�.,�— � '�.�� .'� `� i i n_ na: i ' �'�`"'r�i�i�i i i � ��- �, : y s ,�g;- ^! - r �..� -��
�°'�r°��•'�, .���G f� �, � �. �.� ,��,,��u� � � ��� ,�-��,��p��"�nM�� E., ,n, ���� �� � �
��
Job Number oesre�e�e�M�r
CR04
Job Name: Sbte CMifimtiaNLkeiwa Number
Creek Road Mixed Use UNLIMM1096M6
Atltlrescl � AHJ
106th Avenue SE and Creek Street City of Yelm
Atltlress 2 Job S�elBUlltllig
Yelm,WA 98597 Building E
Atldress J Dravnng Name
Yelm Creek Building E2
'��N"��'� i&.'i i i�i��� a" — _;� IN�' �i in)�°�- _ � � .:� .�.0 - � `���)i� �.�-��� �s:,5��n. �� ,..t�,�,._�''`.�,��.
�ta�i, r r'��=� 41a�.G�I) i d (�(i II� �.a.t��, . ���d�u i I 1E`� ,�-`
MoN DemaMing 3prinkler Data Occupanry JoC Sullx
4.9 K-Factor 12.96 at 7.000 Residential
HouAYovranceAtSOU�ce �ensily AreaalApplkaM1On �
100.00 0.050gpm/ft� 367.00ft2(Actual 367.28ft')
Atltlilional Hoae Suppliea Numbe�OlSpnnklen CalcuhteE Coverage Per Sprinkbr
Node Flow(qpm) 4 256.00ft'
AutoPeak Resulb'.Pressure Fa�Remo�e A2a(s)AOjacent To hlos[Ramote Area
Left:44.537
ToUI Hoa S�roams
�Q�.�Q
System Fbw�emantl Totnl VJdter Requirttl(Inclutlmg Hose Apowance)
54.41 154.41
Maximum Preacure Unbaprce In Loops
Q.�O�
hlaximum Vebcily Abave GrouiW �
11.44 between nodes 99 and 111
Mezimum Vebdty UMet Gmuik � �
5.54 between nodes 100 and 99
Volume dpacM of�Akt Pipes Volume wpacRy o�Dry Pipes
161.73ga1
�� 4 ��V��'��,��I��i��dll ' �� a : II����� i i�il�z-; iFF�:` ;�"�Fi�I° ��'„`'I��I���� �I N�tuw m4a, F�'�?����w •�-.�`=�i"�m?�y�i,��.�,�=diir'�.
i�� (I) 'si 9�ih ir,r � - !�w,�i :.�r
Hose Flow Static Residual Flow Available Total Demand Required Safety Margin
Node Name m si si � m si � m si si
100 Water Su I 100.00 50.000 20.000 1500.00 49.553 154.41 44.537 5.016
' �i9i p�i wiip � � ��` � I � ' , ! . 5� .dt k� <a�"aiN, ( .
�fi�Gter� . sio ����i����i� � °a �� r ��. �, '�, �N6����� i�,���, ,n�l��`�si�i.er 6'��rl� rig(�iui��i�iN�ii�i��i��i s� ��'.� � ���'
r _ .. .
coMr.�ar N�moar com.a N.m: co�m�ruo
22
Name of CaMrac�or: PMne Ex�empn
UMI Fire Protection
Adtlress 1 � FAX
PO BOx 1457
AEErass 2 � Eanail
Marysville,WA 98270
nao�ess a —-� �o-sa�
�,O M.E.P.CAD,Inc. r,��AutoSPRINK�VR10 v10.0.59.0 5/16/2013 832:54PM Page 2
. .
���� �„ _ �� i�,�� �'°� ����: Job Number.CR04
Report Description:Residential
Actual Flow Minimum Flow K-Factor Pressure
Device m m K si
�3 S rinkler 101 12.96 72.80 4.9 7.000
Sprinkler 102 13.79 _ 12.80 4.9 7.920
Sprinkler 105 13.70 _ 12.80 4.9 7.813
Sprinkler 106 13.95 _ 12.80 4.9 8.111
� Most Demanding Sprinkler Data
/� OO M.E.P.CAD,Inc. +�AutoSPRINK�VR10 v10.0.59.0 5116/2013 8:32:57PM Page 3
, �
Il��� , .,5--.� .y�. ;9 r %i� "`x�_ �i���i;�,�,. �},,� �§
d i Job Number:CR04
� ��� =� ��� ���'�,�,. � w:
Report Description:Residential
Node Elevation Foot Fittin s Pressure si Dischar e m
100 -5'-0 S 44.537 54.41
101 26'-0 Spr-7.000 7.000 12.96
102 26'-0 S r�_7.920 7.920 13.79
105 26'-0 S rS-7.813 7.813 13.70
106 26'-0 S r�_8.111 8.111 13.95
gg 3'-6 BFP(-5.738 38.043
103 26'-6 T 5'-0 7•891
104 26'-6 T 5'-0 9•�57
107 26'-6 T 5'-0 8.086
108 26'-6 C 5'-0 9.046
109 17'-6 T(6'-0 16.534
110 17'-6 T 6'-0 17.844
111 8'-6 T 6'-0 22.930
�,O M.E.P.CAD,Inc. a;�AutoSPRINK�VR'0 v10.0.59.0 5I16I2013 8:33:OOPM Page 4
. , �
���� i Tm .a .
� '` �� ����,.�,���� �� Job Number:CR04
Report Description:Residential
Pi e T e Diameter Flow Veloci HWC Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary
U stream Total Len th
�•••••Route1•
BL •• 1.1010 12.96 _4,37 150 0.030510 8'-3'/, Pf 1.108
101 26'-0 12.96 4.9 7.000 Sprinkler 28'-0 Pe -0.217
103 26'-6 7.891 4E(7'-0) 36'-3'/. Pv
BL 1.1010 26.75 9.02 150 0.116555 5'-0 Pf 1.166
103 26'-6 13.79 7.891 Flow(q)from Route 3 5'-0 Pe
104 26'-6 9.057 T(5'-0) 10'-0 Pv
BL 1.3940 30.28 6,37 150 0.046454 99'-2 Pf 4.885
t04 26'-6 3.53 9.057 Flow(q)from Route 2 6'-0 Pe 3.902
110 17'-6 17.844 T(6'-0) 105'-2 Pv
BL 1.3940 40.34 8.48 150 0.078953 9'-0 Pf 1.184
110 17'-6 10.05 17.844 Flow(q)from Route 5 6'-0 Pe 3.902
111 8'-6 22.930 T(6'-0) 15'-0 Pv
BL 1.3940 54.41 11.44 150 0.137323 27'-6 Pf 12.946
111 S'-6 22.930 25'-0 Pe 2.168
99 3'-6 38.043 3E(8'-0),cplg(1'-0),BFP(-5.738j 52'-6 Pv
UG 2.0030 54.41 5.54 150 0.023503 108'-6 pf 2.809
99 3'-6 38.043 11'-0 Pe 3.685
100 -5'-0 44.537 E(11'-O),S 119'-6 Pv
100.00 Hose Allowance At Source
100 154.41
�•••••Route 2•••••
BL 1.1010 13.70 4.62 150 0.033775 9'-6 Pf 0.490
105 26'-0 13.70 4.9 7.813 Sprinkler 5'-0 Pe -0.217
107 26'-6 8.086 T(5'-0) 14'-6 Pv
BL 1.1010 27.65 9.32 150 0.123890 2'-9 Pf 0.960
107 26'-6 13.95 8.086 Flow(q)from Route 4 5'-0 Pe
ias Zs�-s s.oas c�s-o� ��-s P�
BL 1.3940 3.53 0.74 150 0.000871 12'-0 Pf 0.010
108 26'-6 9.046 Pe
104 26'-6 9.057 12'-0 Pv
�•••••Route3•••••
BL 1.1010 13.79 4.65 150 0.034201 0'-6 Pf 0.188
102 26'-0 13.79 4.9 7.920 Sprinkler 5'-0 Pe -0.217
103 26'-6 7.891 T(5'-0) 5'-6 Pv
�•••••Route4•••••
BL 1.1010 13.95 4.70 150 0.034962 0'-6 Pf 0.192
106 26'-0 13.95 4.9 8.111 Sprinkler 5'-0 Pe -0.217
107 26'-6 8.086 T(5'-0) 5'-6 Pv
�•••••Route5•••••
BL 1.3940 10.05 2.11 150 0.006042 204'-9 Pf 1.310
109 17'-6 24.12 16.534 T(6'-0),Flow(q)from Route 7 12'-0 Pe
110 17'-6 17.844 T(6'-0) 216'-9 Pv
�•••••Route6•••••
BL 1.3940 14.07 2.96 150 0.011247 213'-9 Pf 2.494
109 17'-6 24.12 16.534 Flow(q)from Route 7 8'-0 Pe 3.902
111 8'-6 22.930 E(8'-0) 221'-9 Pv
+�•••••Route7•••••
BL 1.3940 24.12 5.07 150 0.030499 111'-7 Pf 3.586
108 26'-6 9.046 6'-0 Pe 3.902
109 17'-6 16.534 T(6'-0) 117'-7 Pv
�1N8�13� �iw�hi � ����I�" iCikt�'r=.�t.� s, _: .. _
� �, . �
Actual Inside Diameter 4 87 Value Of C 100 130 140 150
� Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51
�M, �O M.E.P.CAD,Ina �;�AutoSPRINK�VR i 0 v10.0.59.0 5116/2013 833:04PM Page 5
�
a `
���� ��� �� � `�"�� ` a '�" � Job Number.CR04
��� � ���� °�� �������� ��� � Report Description:Residential
Pi e T e Diameter Flow Veloci HWC Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary
U tream Total Len th
:�` s� -- � ���' `� � � �y�;
�'� i�,�� . � iiii {€ i"���IIq�1���tYt��,'dfli�PY �� �'-'`ii����°-�d�i�����! ��[� ,a�k�?�'� _` ��F��,
, . 4 . �.. �r �. .
..«i. en ..:,< °.?. ...µn P!. : .�.t.,rr e . .. ..- .
AO Arm-Over Diameter Inch ALV Alarm Valve
BL Branch Line Elevation Foot AngV Angle Valve
CM Cross Main Flow gpm b Bushing
DN Drain Discharge gpm BaIV Ball Valve
DR Drop Velocity fps BFP Backflow Preventer
DY Dynamic Pressure psi BV Butterfly Valve
FM Feed Main Length Foot C Cross Flow Turn 90°
FR Feed Riser Friction Loss psi/Foot cplg Coupling
MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run
OR Outrigger pt Total pressure at a point in a pipe CV Check Valve
RN Riser Nipple p� Normal pressure at a point in a pipe DeIV Deluge Valve
SP Sprig pf Pressure loss due to friction between points DPV Dry Pipe Valve
ST Stand Pipe Pe Pressure due to elevation difference beriveen indicated points E 90°Elbow
UG Underground p� Velocity pressure at a point in a pipe EE 45°Elbow
Eel 11'/<°EIbOw
Ee2 22%z Elbow
f Flow Device
fd Flex Drop
FDC Fire Department Connection
fE 90°FireLock(TM)Elbow
fEE 45°FireLock(TM)Elbow
flg Flange
FN Floating Node
ff FireLock(TM)Tee
g Gauge
GIoV Globe Valve
GV Gate Valve
Ho Hose
Hose Hose
HV Hose Valve
Hyd Hydrant
LtE Long Turn Elbow
mecT Mechanical Tee
Noz Nozzle
P1 Pump In
P2 Pump Out
PIV Post indicating Valve
PO Pipe Outlet
PRV Pressure Reducing Valve
PrV Pressure Relief Valve
red Reducer/Adapter
S Supply
sCV Swing Check Valve
Spr Sprinkler
St Strainer
T Tee Flow Turn 90°
Tr Tee Run
U Union
WirF Wirsbo
WMV Water Meter Valve
Z Cap
�O M.E.P.CAD,Ina ',�;��AutoSPRINK�VR10 v10.0.59.0 5116/2013 833:04PM Page 6