Loading...
20100145 Material Submittal and Hydraulic Calcs , \ MATERIAL SU BM ITTAL AND HYDRAULIC CALCULATIONS FOR CREEK ROAD MIXED USE 106T" AVENUE SE AND CREEK STREET YELM, WA 98597 BY UMI F1RE PROTECTION PO BOX 1457 MARYSVILLE, WA 98270 ! . CREEK ROAD MIXED USE TABLE OF CONTENTS FIRE SPRINKLERS TYCO SERIES LFII 4.9 K-FACTOR RESIDENTIAL PENDENT SPRINKLER TYCO SERIES LFII 4.4 K-FACTOR RESIDENTtAL DRY SIDEWALL TYCO SERIES DS-1 5.6 K-FACTOR DRY SIDEWALL FIRE SPRINKLER VALVES � AMES 2006 BACKFLOW PREVENTER PIPE AND FITTINGS SPEARS CPVC PIPE AND FITTINGS HANGERS AND SEISMIC BRACING AFCON 514 OFFSET CPVC HANGER AFCON 511 SIDE MOUNT CPVC HANGER MICELLANEOUS MATERIALS AGF RESIDENTIAL RISER HYDRAULIC CALCULATIONS BUILDING E-THIRD FLOOR UNIT C(RESIDENTIAL NFPA 13R) � FIRE SPRINKLERS � ��O 800-381-9312 TechnicalServices +1-401-781-8220 www.tyco-fire.com RAP/D RESPONSE Series LFI/ Residential Sprinklers 4.9 K-factor Pendent Wet Pipe and Dry Pipe Systems General Escutcheon reduces the accuracy to which the pipe drops to the sprinklers Description must be�ut. The Series LFII Residential Sprinklers � ���"°�''�°� � The TYCO RAPID RESPONSE Series have been designed with heat sensi- '�'"� LFII Residential Pendent and Recessed tivity and water distribution charac- Pendent Sprinklers(TY2234)are deco- teristics proven to help in the control ry ��� rative, fast response, frangible bulb of residential fires and to improve the °' ' ,,,�e. � sprinklers designed for use in residen- chance for occupants to escape or be � ° tial occupancies such as homes, apart- evacuated. ments, dormitories, and hotels.When � aesthetics and optimized flow charac- Dry Pipe System Application ��`' teristics are the major consideration, The Series LFII Residential Pendent the Series LFII Residential Sprinklers and Recessed Pendent Sprinklers (TY2234)should be the first choice. offers a laboratory approved option for The Series LFII Residential Sprinklers designing dry pipe residential sprinkier The owner is res onsib/e for main- are intended for use in the following systems, whereas, most residential tainin their fire rotection s stem and scenarios: spnnklers are laboratory approved for 9 P Y wet systems only. devices in proper operafing condition. • wet and dr i e residential s rin- The installing contractor or sprinkler y p p p Through extensive testing and as refer- manufacturer should be contacted with kler systems for one-and two-family enced in U.S. Patent 7,712,543, it has dwellings and mobile homes per been determined that the number of any questions. NFPA 13D design sprinklers (hydraulic design • wet and dry pipe residential sprinkler area) for the Series LFII Residential Sprinkler systems for residential occupancies Pendent and Recessed Pendent �dentification up to and including four stories in Sprinklers (TY2234) need not be height per NFPA 13R increased over the number of design • wet and dr i e s rinkler s stems sprinklers (hydraulic design area) Number (SIN) Y P P P Y as specified for wet pipe sprinkler for the residential portions of any systems, as is accustomed for density/ TY2234 occupancy per NFPA 13 area sprinkler systems designed per The recessed version of the Series NFPA 13. LFII Residential Sprinklers is intended Consequently, the Series LFII for use in areas with finished ceilings. Residential Sprinklers offer the features It employs a two-piece Style 20 of non-water filled pipe in addition to Recessed Escutcheon.The Recessed not having to increase the number of Escutcheon provides 1/4 inch (6,4 design sprinklers (hydraulic design mm) of recessed adjustment or up to area) for systems designed to NFPA 1/2 inch(12,7 mm)of total adjustment 13, 13D, or 13R. Non-water filled pipe from the flush ceiling position. The Will permit options for areas sensitive adjustment provided by the Recessed to freezing. � IMPORTANT The Series LFII Residential Pendent and A/ways refer to Technical Data Recessed Pendent Sprink/ers(TY2234) Sheet TFP700 for the "INSTALLER described herein must be installed and WARNING" that provides cautions maintained in compliance with this with respect to handling and instal- documeni and the app/icable stan- lation of sprinkler systems and dards of fhe Nationa/ Fire Proteciion components. Improper handling and Associafion,in addition to the standards installation can permanently damage of any authorities having jurisdiction. a sprink/er system or its compo- Failure to do so may impair the perfor- nents and cause the sprinkler to fail to mance of these devices. operate in a fire situation or cause it fo operate prematurely. Page 1 of 8 APRIL 2012 TFP400 . TFP400 Page 2 of 8 7/16" (11,1 mm) ESCUTCHEON 1/2" Components: NOMINAL NPT PLATE SEATING 2-7/8" DIA. MAKE-IN � SURFACE (73,0 mm) 1 - Frame I 2 - Button �_ 3 - Sealing Assembly 1 � 4 - 8ulb 5 - Compression 2 � Screw 2-1/4" 6 - Deflector* g � (57,2 mm) A A q 1-5/8" (41,3 mm) WRENCH STYL.E 20 RECESSED *Temperature 5 � FLATS ESCUTCHEON rating is * indicated on 6 Deflector. CROSS SECTION PENDENT RECESSED PENDENT FIGURE i RAPID RESPONSE SERIES LFI!RESlDENTIAL PENDENT AND RECESSED PENDENT SPR/NKLERS(TY2234) 2-7/8" DIA. (73,0 mmj 1/2"(12,7 mm) 7/16±1/8" (11,1±3,2 mm) � 2_1�4" DIA. 1/4"(6,4 mm) / WRENCH RECESS FACE OF I (57,2 mm) � � (END"A" USED SPRINKLER ' MOUNTING FOR TY2234) FITTING PLATE FIGURE 3 W-TYPE 6 - I SPRINKLER WRENCH / � A �i MOUNTING 1/8" WRENCH SURFACE (3,2 mm) RECESS 1-3/8" (34,9 mm) CLOSURE TY2234 --� 1-1/8"(28,6 mm) F/GURE 2 � STYLE 20 RECESSED ESCUTCHEON FOR USE W1TH THE RAP/D RESPONSE SER/ES LFl1 RESIDENTIAL PENDENT SPRINKLER � (TY2234) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 4 W-TYPE 7 RECESSED SPRlNKLER WRENCH TFP400 Page 3 of 8 Technical Desi /� Dry Pipe System Water Delivery g When using the Series LFII Residential Data Criteria klerinsyste�ms22 he �time fo r water The TYCO RAPID RESPONSE delivery must not exceed 15 seconds Approvals Series LFII Residential Pendent for the most remote operating U� Listed for use with wet pipe and and Recessed Pendent Sprinklers sprinkler. dry pipe systems (TY2234) are UL and C-UL Listed for C-UL Listed for use only with wet pipe installation in accordance with this Obstruction to Water Distribution systems section: Sprinklers are to be located in accor- dance with the obstruction rules For details on these approvals, refer Residential Sprinkler Design Guide of NFPA 13D, 13R, and 13 as appli- to the Design Criteria section. When conditions exist that are cable for residential sprinklers as Maximum Working Pressure outside the scope of the provided well as with the obstruction criteria 175 psi(12,1 bar) criteria, refer to the Residential described within the Technical Data Sprinkler Design Guide TFP490 for Sheet TFP490. Discharge Coefficient the manufacturer's recommendations K=4.9 GPM/psi��2(70,6 LPM/bar��2) that may be acceptable to the local Operational Sensitivity Temperature Rating authority having jurisdiction. For "Horizontal Ceilings" (maximum 155°F(68°C)or 175°F(79°C) 2 inch rise for 12 inch run),the sprin- System Types klers are to be installed with a deflector- Finishes Per the UL Listing, wet pipe and dry to-ceiling distance of 1-3/8 to 4 inches White Polyester Coated pipe systems may be utilized. Per the or in the recessed position using only Chrome Plated C-UL Listing, only wet pipe systems the Style 20 Recessed Escutcheon as Natural Brass may be utilized. shown in Figure 2. Refer to Technical Data Sheet TFP485 The "Beam Ceiling Design Criteria" Physical Characteristics about the use of residential sprinklers in section permits deflector-to-ceiling Frame . . . . . . . . . . . . . . . . . . . . Brass residential dry pipe systems. distances up to 15-3/4 inches. Button . . . . . . . . . . . . . . . . . . . Bronze Sealing Assembly . . . . . . . . Beryllium Hydraulic Design For "Sloped Ceilings" (greater than Nickel w/TEFLON {NFPA 13D and 13R) 2 inch rise up to 8 inch rise for 12 inch Bulb(3 mm). . . . . . . . . . . . . . . . Glass For systems designed to NFPA run), the sprinklers are to be installed Compression Screw . . . . . . . .Bronze 13D or NFPA 13R, the minimum With a deflector-to-ceiling distance of Deflector . . . . . . . . . . . . . . . . .Bronze required sprinkler flow rates are 1-3/8 to 4 inches or in the recessed Ejection Spring . . . . . .Stainless Steel given in Tables A and B as a func- Position using only the Style 20 tion of temperature rating and the Recessed Escutcheon as shown in Operation maximum allowable coverage areas. Figure 2. The sprinkler flow rate is the minimum The glass Bulb contains a fluid that required discharge from each of the Sprinkler Spacing expands when exposed to heat.When total number of"design sprinklers"as The minimum spacing between sprin- the rated temperature is reached, the specified in NFPA 13D or NFPA 13R. klers is 8 feet (2,4 m). The maximum fluid expands sufficiently to shatter the The number of "design sprinklers" spacing between sprinklers cannot glass Bulb, allowing the sprinkler to specified in NFPA 13D and 13R for wet exceed the length of the coverage activate and flow water. pipe systems is to be applied when area(Table A or B)being hydraulically designing dry pipe systems. calculated(e.g., maximum 12 feet for a 12 ft.x 12 ft.coverage area, or 20 feet Hydraulic Design for a 20 ft.x 20 ft. coverage area). (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers.The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A or B as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the "design area" comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. The number of "design sprinklers" specified in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. TFP400 Page 4 of 8 WET PIPE SYSTEM Minimum Flow and Residual Pressure�b� Maximum Maximum For Horizontal Covera�e Spacin For Sloped Ceiling(c,d,e) For Sloped Ceiling(c,a,e1 9 Ceiling(c,d,e) Area(a' Ft. (Maximum 21nch Rise (Greater than 2 Inch Rise up to (Greater than 4 Inch Rise up to Ft.x Ft. �m) for 12 Inch Run) Maximum 4 Inch Rise for 12 Inch Run) Maximum 8 Inch Rise for 12 Inch Run) (m x m) 155°F(68°C)or 155°F(68°C) 175°F(79°C) 155°F(68°C) 175°F(79°C) 175°F(79°C) 12 x 12 12 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) (3,7 x 3,7) (3,7) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 14 x 14 14 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) (4,3 x 4,3) (4,3) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 16 x 16 . 16 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) (4,9 x 4,9) (4,9) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 18 x 18 18 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (5,5 x 5,5) (5,5) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 20 x 20 20 20 GPM(75,7 LPM) 20 GPM(75,7 LPM) 20 GPM(75,7 LPM) 21 GPM(79,5 LPM) 22 GPM(83,3 LPM) (6,1 x 6,1) (6,1) 16.7 psi(1,15 bar) 16.7 psi(1,15 bar) 16.7 psi(1,15 bar) 18.4 psi(1,27 bar) 20.2 psi(1,39 bar) (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinklec The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13D 2010 applications,Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch. Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontal ceiling criteria. (dj For NFPA 13R applications,Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when acceptable to the local authority having jurisdiction. (e) For NFPA 13 residential appiications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in this table must be used. TABLE A SERIES LFlI RESlDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA i3D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS DRY PIPE SYSTEM Minimum Flow and Residual Pressure�b1 Maximum Maximum Coverage Area�a1 Spacing For Horizontal Ceiling Ft.x Ft.(m x m) Ft.(m) (Maximum 2 Inch Rise for 12 inch Run) 155°F(68°C) 175°F(79°C) 12 x 12 12 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) (3,7 x 3,7) (3,7) 7.0 psi(0,48 bar) 7.0 psi(0,48 bar) 14 x 14 14 14 GPM(53,0 LPM) 14 GPM(53,0�PM) (4,3 x 4,3) (4,3) 8.2 psi(0,57 bar} 8.2 psi(0,57 bar) 16 x 16 16 15 GPM(56,8 LPM) 15 GPM(56,8 LPM) (4,9 x 4,9) (4,9) 9.4 psi(0,65 bar) 9.4 psi(0,65 bar) 18 x 18 18 18 GPM(68,1 LPM) 18 GPM(68,1 LPM) (5,5 x 5,5) (5,5) 13.5 psi(0,93 bar) 13.5 psi(0,93 bar) 20 x 20 20 21 GPM(79,5 LPM) 21 GPM(79,5 LPM) (6,1 x 6,1) (6,1) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydrauiic design criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. TABLE B SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEMS TFP400 Page 5 of 8 Beam Ceilin When the beam pockets created by g the primary beams exceed 20 feet in p � length,the installation will require the , , Des�gn Criteria use of secondary beams as described �� The TYCO RAPID RESPONSE Series above.Otherwise, secondary beams need not be present. � � LFII Residential Pendent and Recessed �,� Pendent Sprinklers (TY2234) are UL Secondary beams of a cross-sectional �� and C-UL Listed for installation in wet depth greater than one-quarter the V" pipe systems only for residential occu- depth of the primary beams are to be a ;� pancies with horizontal ceilings (that minimum of 3 ft-4 in from the compart- is, slopes up to a 2 inch rise over a ment wall to center of the nearest beam _.__ 12 inch run)with beams when installed and from center to center between in accordance with this section: beams(Figure 6C). � Secondary beams of a cross-sectional N223a General Information depth no greater than one-quarter the The basic concept of this protection depth of the primary beams may be B scheme is to locate the sprinklers placed at any compartment wall to � on the underside of the beams, refer center of the nearest beam distance � � Figure 5,(not in the beam pockets);to and from any center to center distance identify the main beams that princi- between beams(Figure 6C). E� pally run in one direction as"primary �, � beams"; and, to identify the beams Lintels vv that run principally perpendicular to Lintels over doorways exiting the _ _ the main beams, as may be present compartment must be present. The �� (or in some cases may be necessary minimum height for the lintels is "' � for proper sprinkler protection), as 8 inches or no less than the depth of "secondary beams". the Primary Beams, whichever is greater. Primary and Secondary Beam � � Types Sprinkler Types MAXIMUM TY2234 Solid surface, solid or hollow core, Series LFII Pendent and Recessed ONE-HALF BEA � combustible or non-combustibte. Pendent Residential Sprinklers wIOTH P�us (TY2234), 155°F (68°C) and 175°F 2"(50,8 mm) Primary and Secondary Beam (79°C). Positioning Directly attached to the underside of Sprinkler Coverage Area and FIGURE 5 a combustible or non-combustible Hydraulic Design SPRINKLER POSITIONING smooth ceiling at any elevation. The sprinkler coverage areas and UNDER PRIMARY BEAMS hydraulic design criteria as presented WET P/PE SYSTEMS ONtY Primary Beam Cross-Section in the Table A for"Horizontal Ceilings" (Refer to the "Beam Ceiling Maximum depth of 14 inches and the are to be applied. Design Criteria"section.) maximum width is unlimited.The cross- sectional shape of the primary beam Sprinkler Position Beam and Soffit Arrangements may be rectangular to circular. The deflector to bottom of primary beams for the Series LFII Pendent A soffit is permitted to be placed Secondary Beam Cross-Section and Recessed Pendent S rinklers around the perimeter of a compart- Maximum depth to be no greater than p ment with the beam arrangement the rimar beam and the maximum �TY2234) is to be 1-1/4 to 1-3/4 inches Within the soffit area(Figure 7). P Y (Figure 5A).The vertical centerline of width is unlimited.The cross-sectional the Series LFII Pendent Sprinklers is The cross-section of the soffit may be shape of the secondary beam may be to be no greater than half the primary any size as long as it does not create rectangular to circular. beam cross-sectional width plus an obstruction to water distribution 2 inches from the centerline of the per the obstruction rules of NFPA 13 for Primary Beam Spacing primary beam(Figure 5B). residential sprinklers. The primary beams (Figure 6A)are to be 3 ft.-4 in.to 6 ft.from the compart- When soffits are present, the previ- ment wall to center of the nearest ously provided 3 ft.-4 in. to 6 ft. beam and from center to center � compartment wall to adjacent beam" between beams. Core drilling of beams to allow the distance for the primary and insfallation of sprink/er drops requires secondary beams is to be measured Secondary Beam Spacing consulting with a structural engineer. from the face of the soffit as opposed The secondary beams principally run �yhere core drilling is not permitted, to the compartment wall. perpendicular to the primary beams. the previous/y sfated sprinkler position Although the distance to the Secondary beams of a depth equal to criieria for the Series LFII Residentia/ beams is measured from the face of the primary beam must be placed so Pendent and Recessed Pendent the soffit,the sprinkler coverage area that the beam pockets created by the Sprinklers(TY2234)a/lows placement is to be measured from the compart- primary beams do not exceed 20 feet of the sprinkler drop adjacent to the ment wall. in length(Figure 6B). primary beam. TFP400 Page 8 of 8 Care and Automatic sprinkler systems are prderinn recommended to be inspected, .7 Maintenance tested, and maintained by a qualified procedure Inspection Service in accordance with The TYCO RAPID RESPONSE Series local requirements and/or national Contact your local distributor for LFII Residential Pendent and Recessed codes. availability. When placing an order, Pendent Sprinklers(TY2234) must be indicate the fuli product name and Part maintained and serviced in accordance ��mited Number(P/N). with this section: Sprinkler Assembly Before closing a fire protection system Warranfy Specify: Series LFII (TY2234), K=4.9, main control valve for maintenance Residential Pendent Sprinkler with Products manufactured by Tyco work on the fire protection system that (specify) temperature rating and it controls, permission to shut down Fire Protection Products (TFPP) are �specify)finish, P/N(specify). the affected fire protection system Warranted solely to the original Buyer 1ss°F(68°c)or must be obtained from the ro er for ten (10) years against defects p p in material and workmanship when Chrome Plated ............P/N 51-201-9-155 authorities and notify all personnel Paid for and properly installed and �5s°F(68°c) who may be affected by this action. maintained under normal use and White Polyester............P/N 51-201-4-155 Absence of the outer piece of an service. This warranty will expire �ss°F(68°c) escutcheon, which is used to cover ten 10 ears from date of shi ment White � � � y p (RAL9010`................P/N 51-201-3-155 a clearance hole, can delay sprinkler by TFPP. No warranty is given for �55°F(68°c� operation in a fire situation. products or components 171a11Uf1C- Natural Brass.............. P/N 51-201-1-155 The owner must assure that the tured by companies not affiliated by i�5°F(79°c>or sprinklers are not used for hanging ownership with TFPP or for products Chrome Plated ............P!N 51-201-9-175 any objects and that the sprinklers and components which have been i�s°F(79°c) subject to misuse, improper If1Stal- White Polyester............P/N 51-201-4-175 are only cleaned by means of gently �ation, corrosion, or which have not i7s°F(�s°c) dusting with a feather duster; other- been installed, maintained, modified wnite wise, non-operation in the event of or repaired in accordance with appli- (RA�so�o)"................P/N 51-201-3-175 a fire or inadvertent operation may cable Standards of the National Fire i75�F(�9��� result. Protection Association, and/or the Natural Brass.............. P/N 51-201-1-175 Sprinklers which are found to be standards of any other Authorities 'Eastern Hemisphere sales only. leaking or exhibiting visible signs of Having Jurisdiction. Materials found corrosion must be replaced. by TFPP to be defective shall be either Recessed Escutcheon repaired or replaced, at TFPP's sole Specify: Style 20 Recessed Automatic sprinklers must never be aption. TFPP neither assumes, nor Escutcheon with (specify`)finish, P/N painted, plated, coated, or other- authorizes any person to assume for (specify'). wise altered after leaving the factory. it, any other obligation in connection �Refer to Technical Data Sheet Modified sprinklers must be replaced. with the sale of products or parts of TFP770. Sprinklers that have been exposed to products. TFPP shall not be respon- corrosive products of combustion, but sible for sprinkler system design S rinkler Wrench have not operated,should be replaced errors or inaccurate or incomplete Specify: W-Type 6 Sprinkler Wrench, if they cannot be completely cleaned information supplied by Buyer or P/N 56-000-6-387. by wiping the sprinkler with a cloth or Buyer's representatives. by brushing it with a soft bristle brush. �n no event shall TFPP be liable, in Specify: W-Type 7 Sprinkier Wrench, Care must be exercised to avoid contract, tort, strict liability or under P�N 56-850-4-001. damage to the sprinklers - before, any other legal theory, for incidental, during, and after installation, indirect, special or consequential Sprinklers damaged by dropping, damages, including but not limited to striking,wrench twist/slippage, or the labor charges, regardless of whether like, must be replaced.Also, replace TFPP was informed about the possi- any sprinkler that has a cracked bulb bility of such damages, and in no or that has lost liquid from its bulb. event shall TFPP's liability exceed an (Ref. Installation Section.) amount equal to the sales price. The owner is responsible for the The foregoing warranty is made in inspection, testing, and mainte- lieu of any and all other warranties. nance of their fire protection system express or implied, including warran- and devices in compliance with this ties of inerchantability and fitness for document, as well as with the appli- �articular purpose. cable standards of the National Fire This limited warranty sets forth the Protection Association (e.g., NFPA exclusive remedy for claims based on 25), in addition to the standards of any failure of or defect in products, mate- authorities having jurisdiction.Contact rials or components, whether the the installing contractor or sprinkler claim is made in contract, tort, strict manufacturer regarding any questions. liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part,of any portion of this warranty will not affect the remainder. Copyright OO 2012 Tyco Fire Protection Products.All rights reserved. *jt�.� TEFLON is trademark of The DuPont Corporation. "� ��O 800-381-9312 TechnicalServices +�-ao�-78�-8220 www.tyco-fire.com RAP/D RESPONSE Series LF// Residential Sprinklers 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe and Dry Pipe Systems Gene�„a, The recessed version is intended for use in areas with finished walis. It employs a Descri �/0/'� two-piece Style 20 Recessed Escutcheon. p The Recessed Escutcheon provides 1/4 �� The TYCO RAPID RESPONSE Series inch(6,4 mm)of recessed adjustment or � � LFII Dry Type Residential Horizontal up to 1/2 inch(12,7 mm)oftotal adjust- ��`�� Sidewall Sprinklers(TY2335)are dry type� ment from the flush mounting surface = ����, � decorative,fast response,frangible bulb Position.The design of this escutcheon �` sprinklers designed for use in residential Provides a level of flexibility in adjusting occupancies such as homes,apartments, sprinkler supply connections. dormitories,and hotels. The Series LFII Dry Type Residential The Series LFII Dry Type Residential Horizontal Sidewall Sprinklers have Horizontal Sidewall Sprinklers are typi- been designed with heat sensitivity and cally used for the following situations: Water characteristics proven to help in the control of residential fires and to • where sprinklers are required on dry improve the chance for occupants to � pipe systems that are exposed to escape or be evacuated. The Series LFII Dry Type Residential freezing temperatures;for example, Horizontal Sidewall Sprink/ers(TY2335) horizontal sprinkler supply from un- Dry Pipe System Application described herein must be installed and heated portions of buildings The Series LFII Residential Pendent and maintained in compliance with this docu- Recessed Pendent Sprinklers offers a ment and the a l�cable standards of •where sprinklers and/or a portion of laboratory approved option for designing the Nationa/Fi e Protection Associa- the connecting piping are exposed to dry pipe residential sprinkler systems, freezing temperatures; for example, Whereas,most residential sprinklers are tion,in addition to the standards of any horizontal sprinkier supply from wet laboratory approved for wet systems only. aufhorities having jurisdiction. Failure systems into unheated areas to do so may impair the performance Through extensive testing and as ref- of these devices. • where sprinklers are used on systems erenced in U.S. Patent 7,712,543, it that are seasonally drained to avoid has been determined that the number The owner is responsi6le for maintaining freezing;for example,vacation areas of design sprinklers(hydraulic design their fire protection system and devices in The Series LFII D T e Residential Hori- area)for the Series LFII Residential Pen- proper operafing condition. The install- zontal Sidewall Sprinklers are intended dent and Recessed Pendent Sprinklers should be ctontacted�w th an anuestionsr for use in Residential Sprinkler systems (TY2234)need not be increased over the 1'q for one-and two-family dwellings and number of design sprinklers(hydraulic mobile homes per NFPA 13D;residential design area)as specified for wet pipe sprinkler systems for residential occu- sprinkler systems,as is accustomed for pancies up to and inctuding four stories density/area sprinkler systems designed Sprinkler in height per NFPA 13R; or, sprinkler Per NFPA 13. �dentification systems for the residential portions of Consequently, the Series LFII Resi- any occupancy per NFPA 13. dential Sprinklers offer the features of Number (S1N) non-water filled pipe in addition to not having to increase the number of design TY2335 sprinklers (hydraulic design area)for systems designed to NFPA 13, 13D,or 13R. Non-water filled pipe will permit IMPORTANT options for areas sensitive to freezing. Always refer to Technical Data Sheet TFP700 for fhe "INSTALLER WARNING"that provides cautions wiih respect to handling and in- stallation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 APRIL 2012 TFP461 TFP461 Page 3 of 10 Technica/ O eration •flow rates listed in Table A or B as a p function of temperature rating and the Data When the TYCO RAPID RESPONSE maximum allowable coverage area. Series LFII Dry Type Residential Horizontal • minimum discharge of 0.1 gpm/ft2 over Approvals Sidewall Sprinkler is in service, water the design area comprised of the four UL Listed is prevented from entering the assem- most hydraulically demanding sprin- For details on approval, refer to the bly by the Plug with Sealing Assembly klers for the actual coverage areas Design Criteria section. (Figure 1)in the Inlet of the Sprinkler. protected by four sprinklers. Maximum Working Pressure The glass Bulb contains a fluid that The number of"design sprinklers"speci- 175 psi(12,1 bar) expands when exposed to heat.When fied in NFPA 13 for wet pipe systems is the rated temperature is reached, the to be•applied when designing dry pipe Discharge Coefficient fluid expands sufficientiy to shatter the systems. K=4.4 GPM/psi'�2(63,4 LPM/bar'�2) glass Bulb to release the Bulb Seat.The Dry Pipe System Water Delivery Inlet Thread Connections system's water or air pressure is then When using the Series LFII Residential 1-inch NPT or ISO 7-Ri able to unseat the Plug with Sealing As- Sprinklers(TY2335)in dry pipe sprinkler sembly.The Plug Spring turns the Plug systems,the time for water delivery must Sprinkler Temperature Rating with Sealing Assembly aside, allowing not exceed 15 seconds for the most 155°F/68°C the sprinkler to activate and flow water. remote operating sprinkler. Finishes Obstruction to Water Distribution Chrome-Plated Design Sprinklers are to be located in accordance White Polyester-Coated Criteria with the obstruction rules of NFPA 13D, Natural Brass 13R,and 13 as applicable for residential Order Lengths The TYCO RAPID RESPONSE Series sprinklers as well as with the obstruction Minimum: 3-3/4 inches (95,3 mm) LFII Dry Type Residential Horizontal criteria described within the Technical Maximum:24 inches(609,6 mm) Sidewall Sprinklers(TY2335) are UL Data Sheet TFP490. Listed for installation in accordance Operational Sensitivity Physical Characteristics with this section: The sprinkler must be located relative Inlet . . . . . . . . . . . . . . . . . . . . . Brass to the mountin surface as shown in Plug . . . . . . . . . . . . . . . . . . . . . Brass Residential Sprinkler Design Guide g Yoke . . . . . . . . . . . . . . Stainless Steel �Nhen conditions exist that are outside Figures 2 and 3. Casing. . . . . . . . . . . Galvanized Steel the scope of the criteria provided in this Sprinkler Spacing Insert . . . . . Bronze section,refer to the technical data sheet The minimum lateral spacing between Bulb Seat. . . . . . . . . . .Stainless Steel entitled Residential Sprinkler Design sprinklers is 8 feet(2,4 m).The maximum Bulb. . . . . . . . . . . . . . . . . . . . . . Glass Guide(TFP490)for the manufacturer's lateral spacing between sprinklers can- Compression Screw . . . . . . . . . Brass recommendations that may be acceptable not exceed the length of the coverage Deflector . . . . . . . . . . . . . . . . . Brass to the local authority having jurisdiction. area(refer to Table A or B) hydrauli- Frame . . . . . . . . . . . . . . . . . . . . Brass gystem Types cally calculated (e.g., a maximum of Guide Tube . . . . . . . . .Stainless Steel 12 feet for a 12 ft.x 12 ft.coverage area or Water Tube . . . . . . . . .Stainless Steel Wet pipe, and dry pipe systems may 1g peet for a 18 ft.x 20 ft.coverage area). Bushin Brass be utilized. g. . . . . . . . . . . . . . . . . . . Plug Spring . . . . . . . . .Stainless Steel Hydraulic Design Sprinkler Fittings Sealing Assembly . . . . . . . . Beryllium (NFPA 13D and 13R) The following fittings may be used: Nickel with TEFLON For systems designed to NFPA 13D or .The 1 inch NPT outlet or run of a mal- Escutcheon . . . . . . . . . .Carbon Steel NFPA 13R,the minimum required sprinkler leable or ductile iron threaded tee flow rate are given in Table A or B as a fittings that meet the dimensional re- function of temperature rating and the quirements of ANSI B16.3(Class 150) maximum allowable coverage areas. .The 1 inch NPT outlet or run of a cast The sprinkler flow rate is the minimum required discharge from each of the iron threaded tee fittings that meet total number of"design sprinklers," as the dimensional requirements of ANSI specified in NFPA 13D or NFPA 13R.The B16.4(Class 125). number of"design sprinklers"specified For dry pipe systems, only use the in NFPA 13D and 13R for wet pipe sys- side outlet of maximum 2-1/2 inch size tems is to be applied when designing reducing tees when locating the Series dry pipe systems. LFII Dry Type Residential Recessed Hydraulic Design Pendent Sprinklers directly below the (NFPA 13) branch line.Otherwise,use the con- For systems designed to NFPA 13,the figuration shown in Figure 7 to assure number of required design sprinklers is complete drainage from above the Se- the four most hydraulically demanding ries LFII Sprinklers and the branch line. sprinklers. The minimum required dis- Do not install the Series LFII Dry charge from each of the four sprinklers Type Residential Recessed Pen- is the greater of the following: dent Sprinklers into elbow fittings. The Inlet of the sprinkler can con- tact the interior of the elbow, po- tentially damaging the Inlet seal. TFP461 Page 4 of 10 Only use the configuration in Fig- be sealed, in accordance with the Na- • For plain-barrel horizontal sidewall ure 6 where the sprinkler fitting and tionai Fire Protection Association. Due sprinklers,apply the Wrench Recess water-filled pipe above the sprinkler to temperature differences between the End "A" of the W-Type 6 Sprinkler fitting are not subject to freezing and two areas,the potential for the forma- Wrench(Figure 4)to the Wrench Flat. where the length of the Series LFII tion of condensation in the sprinkler and . For recessed horizontal sidewall sprin- Sprinkler has the minimum exposure subsequent ice build-up is increased.If klers, apply the Wrench Recess of length per Figure 8. Refer to the Ex- this condensation is not controlled,ice the W-Type 7 Sprinkler Wrench to the posure Length section and Table C. build-up can occur that might damage Wrench Flat(Figure 5). •The 1 inch NPT outlet of a GRINNELL the dry type sprinkler and/or prevent Figure 730 Mechanical Tee in wet pipe proper operation in a fire situation. If sprinkler removal is necessary,remove systems only Use of the Model DSB-2 Dry Sprinkler the sprinkler using the same wrenching Boot,described in Technical Data Sheet method noted above. Sprinkler removal •The 1 inch NPT CPVC outlet of a 1"x TFP591 and shown in Figures 6 through �s easier when a non-hardening sealant 1" x 1" NPT Sprinkler Head Adapter g,can provide the recommended seal. `^�as used and torque guidelines were Tee(P/N 80249)in wet systems only followed. After removal, inspect the •The 1 inch NPT CPVC outiet of a 1"x . sprinkler for damage. 1" NPT Female Adapter(P/N 80145) /nstal/at�on Step 4.After installing the ceiling or in wet systems only The TYCO RAPID RESPONSE Series applying a ceiling finish,slide the Style •The 1 inch NPT outlet of a 1"x 1"x 1" LFII Dry Type Residential Horizontal 20 Recessed Escutcheon Closure over NPT CPVC Sprinkler Head Adapter Sidewall Sprinklers must be installed in the sprinkler. Push the closure over the Tee(P/N 80259) in either wet or dry accordance with this section: mounting plate until its flange contacts pipe systems the wall. General Instructions The Series LFII Dry Type Residential � Horizontal Sidewall Sprinklers must Do not install the Series LFII Dry Type only be installed in fittings that meet Residential Horizonta/Sidewall Sprin- the requirements of the Design Criteria klers into any other fype fitting without section. For other important require- first consulting the Technical Services �ents regarding piping design and Department. Failure to use the appro- sealing of the clearance space around priate fiiting may result in the following: the Sprinkler Casing,refer to the Design Criteria section. • failure of the sprinkler to operate po not install any bulb type sprinkler if properly due to formation of ice over the Bulb is cracked or there is a loss of the Inlet Plug or binding of the Inlet liquid from the Bulb. With the sprinkler Plug. held horizontally, a small air bubble • insufficient engagement of the in- should be present.The diameter of the let pipe threads with consequent air bubble is approximately 1/16 inch leakage. (1,6 mm). Drainage A leak-tight 1 inch NPT sprinkler joint Branch, cross, and feed-main piping should be obtained by applying a min- connected to Series LFII Dry Type Resi- imum-to-maximum torque of 20 to 30 dential Sprinklers and subject to freezing ft.-Ibs. (26,8 to 40,2 Nm). Higher levels temperatures must be pitched to allow of torque can distort the sprinkler Inlet proper drainage,in accordance with the or Frame with consequent leakage or minimum requirements of the National impairment of the sprinkler. Fire Protection Association for dry pipe Do not attempt to compensate for sprinkler systems. insufficient adjustment in an Escutcheon Exposure Length Plate by under-or over-tightening the When using Series LFII Dry Type Resi- sprinkler. Re-adjust the position of the dential Horizontal Sidewall Sprinklers sprinkler fitting to suit. in wet pipe sprinkler systems to protect Step 1.Install horizontal sidewall sprin- areas subject to freezing temperatures, klers only in the horizontal position with use Table C to determine a sprinkler's their centerline of waterway perpendicular appropriate exposed barrel length to to the back wall and parallel to the ceil- prevent water from freezing in the con- ing. The word TOP on the Deflector is necting pipes due to conduction.The to face towards the cei�ing. exposed barrel length measurement must be taken from the face of the sprinkler Step 2.With a non-hardening pipe-thread fitting to the surface of the structure or sealant such as Teflon tape applied to the insulation that is exposed to the heated inlet threads,hand-tighten the sprinkler area. Refer to Figure 8 for an example. into the sprinkler fitting. Clearance Space Step 3.Wrench-tighten the sprinkler When connecting an area subject to using a pipe wrench on the Inlet Band freezing and an area containing a wet- ar the Casing (Figure 1), or using the pipe sprinkler system, the clearance W-Type 6 or W-lype 7 Sprinkler Wrench space around the sprinkler barrel of as follows: Dry Type Residential Sprinklers must TFP461 Page 5 of 10 ::.................................................................................. �: � ELEVATION Maximum Maximum Minimum Flow��,".°.n and Residual Pressure for Horizontal Ceiling Coverage Spacing 155°F(68°C) Area� Ft.(m) Top-of-Deflector to Ceiling: Top-of-Deflector to Ceiling: Width x Length ro� 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) Ft.x Ft. (m x m) WET PIPE WET PIPE 12 x 12 12 13 GPM(49,2 LPM) 15 GPM(56,8 LPM) (3,7 x 3,7) (3,7) 8.7 psi{0,60 bar) 11.6 psi(0,80 bar) 14 x 14 14 14 GPM(53,0 LPM) 15 GPM(56,8 LPM) (4,3 x 4,3) (4,3) 10.1 psi(0,70 bar) 11.6 psi(0,80 bar) 16 x 16 16 17 GPM(64,3 LPM) 19 GPM(71,9 LPM) (4,9 x 4,9) (4,9) 14.9 psi(1,03 bar) 18.6 psi(1,28 bar) 16 x 18 16 19 GPM(71,9 LPM) 20 GPM(75,7 LPM) (4,9 x 5,5) (4,9) 18.6 psi(1,28 bar) 20.7 psi(1,43 bar) 16 x 20 16 25 GPM(94,6 LPM) 25 GPM(94,6 LPM) (4,9 x 6,1) (4,9) 32.3 psi(2.23 bar) 32.3 psi(2.23 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)This dimension refers to Width(backwall where sprinkler is located)times Length(horizontal throw of the sprinkler). (c)The requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section for details. (d)For NFPA 13D 2010 applications,Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch.Refer to TIA 1028R for allowed sloped ceiling limitations when using horizontai ceiling criteria. (e)For NFPA 13R applications,Horizontal Ceiling criteria may be used for sloped ceiling configuration up to 8:12 pitch when acceptable to the local authority having jurisdiction. (f)For NFPA 13 residential application,the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A NFPA 13D, 13R AND 13 HYDRAULIC DESIGN CRlTERIA FOR SERIES LFIi DRY TYPE RESIDENTIAL SPRlNKLERS(TY2335) (MAXIMUM 2/NCH RISE FOR 12 INCH RUN) - WET PIPE SYSTEM- TFP461 Page 6 of 10 _ . _ _ . __ ................................................................................... �� � ELEVATION Maximum Maximum Minimum Flow�`�d�and Residual Pressure for Horizontai Ceiling Coverage Spacing 155 F(68°C) Area�a� Ft.(m) Top-of-Defiector to Ceiling: Top-of-Deflector to Ceiling: Width x Length ro� 4 to 6 Inches(100 to 150 mm) 6 to 121nches(150 to 300 mm) Ft.x Ft. (m x m) DRY PIPE DRY PIPE 12 x 12 12 13 GPM(49,2 LPM) 15 GPM(56,8 LPM) (3,7 x 3,7) (3,7) 8.7 psi(0,60 bar) 11.6 psi(0,80 bar) 14 x 14 14 16 GPM(60,6 LPM) 16 GPM(60,6 LPM) (4,3 x 4,3) (4,3) 13.2 psi{0,91 bar) 13.2 psi(0,91 bar) 16 x 16 16 17 GPM(64,3 LPM) 19 GPM(71,9 LPM) (4,9 x 4,9) (4,9) 14.9 psi(1,03 bar) 18.6 psi(1,28 bar) 16 x 18 16 N/A N/A (4,9 x 5,5) (4,9) 16 x 20 16 N/A N/A (4,9 x 6,1) (4,9j (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)This dimension refers to Width(backwall where sprinkler is located)times Length(horizontal throw of the sprinkler). (c)The requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section for details. (d)For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used, TABLE B NFPA i3D, 13R AND 13 HYDRAULIC DESIGN CRITER/A FOR SERIES LFII DRY TYPE RESIDENTIAL SPRlNKLERS(TY2335J (MAXIMUM 2 INCH RISE FOR 12/NCH RUN) -DRY PIPE SYSTEM- TFP461 Page 7 of 10 � .• � PLUG OUTLEf FACE OF SPRINKLER SPRINKLER SPRINKLER FITTING FITTING FITTING PLUG (SEE DESIGN (SEE DESIGN OUTLET CR�TERIA DSB-2 CRITERIA SECTION) BOOT SECTION) i i DSB-2 EXPOSURE DSB-2 � BOOT LENGTH BOOT (SEE DESIGN TO DRY CRITERIA TO WET SYSTEM SECTION) SYSTEM FIGURE 6 FIGURE 7 FIGURE 8 SPRINKLER FITTING IN SPRINKLER FITTING IN EXPOSURE LENGTH HEATED AREA UNHEATED AREA Temperatures for Heated Area�°� Ambient Temperature Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C) Sprinkler Minimum Exposed Barrel Length, Inches(mm)jb� 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes: (a)For protected area temperatures that occur between values listed above,use the next cooler temperature. (b)These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE C MINlMUM RECOMMENDED LENGTHS OF EXPOSED SPRINKLER BARRELS IN WET-PIPE SYSTEMS TFP461 Page 8 of 10 Care and as with the applicable standards of the This warranty will apply to the full extent Nationai Fire Protection Association(e.g., permitted by law.The invalidity,in whole Maintenance NFPA 25),in addition to the standards of or part, of any portion of this warranty any authorities having jurisdiction.Con- will not affect the remainder. The TYCO RAPID RESPONSE Series tact the installing contractor or sprinkler LFII Dry Type Residential Horizontal manufacturer regarding any questions. Ordering Sidewall Sprinklers (TY2335) must be Automatic sprinkler systems are recom- maintained and serviced in accordance mended to be inspected,tested, and procedure with this section: maintained by a qualified Inspection Before closing a fire protection system Service in accordance with local require- Contact your local distributor for avail- main control valve for maintenance ments and/or national codes. ability.When placing an order,indicate work on the fire protection system that the full product name and Part Number it controls, obtain permission to shut Limited (P/N).Refer to the Price List for a com- down the affected fire protection systems plete listing of P/Ns. from the proper authorities and notify Warranty Horizontal Sidewall Sprinkler all personnel who may be affected by Products manufactured by Tyco Fire Assembly this action. Protection Products(TFPP)are warranted Specify the following information: Absence of a Recessed Escutcheon solely to the original Buyer for ten (10) • Series LFII Dry Type Residential Hori- Plate or a Domed Concealed Cover years against defects in material and zontal Sidewall Sprinkler(TY2335) Plate to cover a clearance hole can delay workmanship when paid for and properly . W�th Recessed Escutcheon or without sprinkler operation in a fire situation. installed and maintained under normal Escutcheon The owner must assure that the sprinklers use and service.This warranty will expire are not used for hanging any objects and ten(10)years from date of shipment by •4.4 K-factor that the sprinklers are only cleaned by TFPP.No warranty is given for products or . �55°F(68°C)Temperature Rating means of gently dusting with a feather components manufactured by companies duster;otherwise,non-operation in the not affiliated by ownership with TFPP •Sprinkler Finish event of a fire or inadvertent operation or for products and components which . Escutcheon Finish(if applicable) ma result. have been subject to misuse,improper y installation,corrosion,or which have not • Order Length(value from Figure 2 or 3) A Vent Hole is provided in the Bulb Seat been installed,maintained,modified or . Inlet Thread Connection(1-Inch NPT or (Figure 1)to indicate if the Series LFII repaired in accordance with applicable ISO 7-R1) Dry Type Residential Horizontal Sidewall Standards of the National Fire Protection Sprinkler is remaining dry. Evidence of Association,and/or the standards of any • P/N(from Table D) leakage from the Vent Hole indicates other Authorities Having Jurisdiction. Separately Ordered potential leakage past the Plug with Seal- Materials found by TFPP to be defective Sprinkler Wrench ing Assembly and the need to remove shall be either repaired or replaced, at Specify: W-Type 6 Sprinkler Wrench the sprinkler to determine the cause TFPP's sole option.TFPP neither as- (Figure 4), P/N 56-000-6-387 of leakage(for example, an improper sumes, nor authorizes any person to installation or an ice plug). Close the assume for it, any other obligation in Specify:W-Type 7 Recessed Sprinkler fire protection system control valve connection with the sale of products �Nrench(Figure 5), P/N 56-850-4-001 and drain the system before removing or parts of products.TFPP shall not be the sprinkler. responsible for sprinkler system design Sprinklers which are found to be leaking errors or inaccurate or incomplete in- or exhibiting visible signs of corrosion formation supplied by Buyer or Buyer's must be replaced. representatives. Automatic sprinklers must never be In no event shall TFPP be liable,in con- painted, plated, coated, or otherwise tract,tort,strict liability or under any other altered after leaving the factory.Modified legal theory,for incidental,indirect,special sprinklers must be replaced.Sprinklers or consequential damages,including but that have been exposed to corrosive not limited to labor charges,regardless products of combustion, but have not of whether TFPP was informed about the operated, should be replaced if they Possibility of such damages,and in no cannot be completely cleaned by wiping event shall TFPP's liability exceed an the sprinkler with a cloth or by brushing amount equal to the sales price. it with a soft bristle brush. The foregoing warranty is made in lieu Care must be exercised to avoid damage of any and all other warranties.express to the sprinklers- before, during, and or implied.including warranties of iner- after installation. Sprinklers damaged chantability and fitness for aparticular by dropping, striking, wrench twist/ purpose. , slippage,or the like,must be replaced. This limited warranty sets forth the Also, replace any sprinkler that has a exclusive remedy for claims based on cracked bulb or that has lost liquid from failure of or defect in products,materi- its bulb.(Ref. Installation Section.) als or components, whether the claim The owner is responsible for the in- is made in contract,tort, strict liability spection, testing, and maintenance of or any other legal theory. their fire protection system and devices in compliance with this document,as well TFP461 Page 9 of 10 P/N* 63 - XXX - X - XXX ORDER LENGTH (EXAMPLES) � O55 5.50" 082 8.25° MODEUSIN 12 Horizontal Sidewall TY2335 180 18.00" with Recessed Escutcheon (Figure 3) RECESSED SPRINKLER FINISH ESCUTCHEON FINISH Horizontal Sidewall TY2335 187 18.75" 13 without Escutcheon (Figure 2) 9 Chrome Plated Chrome 240 24.00" White 4 Polyester Coated White TEMPERATURE RATING 2 Natural Brass Brass Plated 1 155°F(68°C) Note `Use Prefix"I°for ISO 7-Ri Inlet Thread Connection; for example,I-63-121-9-180. TABLE D PART NUMBER SELECTION FOR RAPID RESPONSE SERIES LFII DRY TYPE RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS TFP461 Page 10 of 10 Copyright m 2012 Tyco Fire Protection Products.All rights reserved. ��CO TEFLON is trademark of The DuPont Corporation. 't CO Fire Suppression � & Bui/din Products g Technical Services 800-381-9312�+1-401-781-8220 www.tyco-fire.com Series DS-i Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewa// Standard Response, Standard Coverage General the standards of any otherRuthorities Having Jurisdiction. Failure fo do so Description de !v c spair the performance of fhese TYCO Series DS-1 Dry-Type Sprinklers, pwners are responsible for maintaining 5.6K Pendent, Upright, and Horizontal their fire protection system and devices Sidewall, Standard Response (5 mm in proper operating condition. The Bulb) and Standard Coverage, are installing contractor or sprinkler manu- decorative glass bulb automatic sprin- facturer should be contacfed with any klers typically used where: questions. • pendent sprinklers are required on Series DS-1 Dry-Type Sprinklers musi dry pipe systems that are exposed to only be installed in fittings that meet freezing temperatures; for example, the requirements of the Design Criteria sprinkler drops from unheated section. portions of buildings • sprinklers and/or a portion of the Model/Sprinkler connecting piping may be exposed to freezing temperatures; for example, /dentification �` sprinkler drops from wet systems into freezers, sprinkler sprigs from Numbers (S/NsJ � wet systems into unheated attics, or �� horizontal piping extensions through TY3255- Pendent a wall to protect unheated areas of a TY3155- Upright building such as loading docks,over- TY3355-Horizontai Sidewall hangs,and building exteriors Finishes • s rinkters are used on s stems that Technical Sprinkler: Natural Brass, Chrome P Y Plated,White Polyester are seasonably drained to avoid Escutcheon: White Coated, Chrome freezing;for example,vacation resort Data Plated,Brass Plated areas Approvals Physical Characteristics � UL and C-UL Listed Inlet. . . . . . . . . . . . . . . . . . . . . Copper FM Approved Series DS-1 Dry-Type Sprinklers Plug . . . . . . . . . . . . . . . . . . . . Copper described herein must be installed LPCB Approved: Ref No.094a/11 CE Certified: EN 122.59-1 Yoke . . . . . . . . . . . . . . Stainless Steel and maintained in compliance with this NYC A roved under MEA 352-01-E Casin Galvanized document, as well as with the appli- Pp g ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' Carbon Steel cab/e standards of the Nationa/ Fire Refer to Table A. Insert . . . . . . . . . . . . . . . . . . . Bronze Protection Association, in addition to Maximum Working Pressure Bulb Seat . . . . . . . . . . Stainless Steel 175 psi(12,1 bar) Bulb . . . . . . . . . . . . . . . . . . . . . .Glass IMPORTANT Always refer to Technica/ Data Inlet ThPead Connections Compression Screw. . . . . . . . Bronze Sheet TFP700 for the "INSTALLER �-inch NPT(Standard Order) Deflector. . . . . . . . . . . . . . . . . Bronze WARNlNG"that provides cautions ISO 7-Ri Frame. . . . . . . . . . . . . . . . . . . Bronze with respect to handling and instal- Discharge Coefficient Guide Tube. . . . . . . . . Stainless Steel lation of sprinkler systems and K=5.6 GPM/psi��2 Water Tube. . . . . . . . . Stainless Steel components.Improper handling and g0,6 LPM/bar��2 installation can permanentlydamage � � Spring. . . . . . . . . . . . . Stainless Steel a sprinkler system or its compo- Sealing Assembly. . . Beryllium Nickel nents and cause the sprink/er to fai! Temperature Ratings w/Teflon' to o erate in a fire situatron or cause Refer to Table A. P Escutcheon . . . . . . . . . .Carbon Steel if to operate prematurely. *DuPont Registered Trademark Page 1 of 10 MAY 2011 TFP500 TFP500 Page 2 of 10 TY3255 Pendent TY3255 Pendent TY3355 Horizontal Sidewall with top of Deflector-to-Ceiling with Standard with Standard Escutcheon distance of 4 to 12 inches Recessed Escutcheon (Figure 5) (100 to 300 mm) (Figure 3) with Wide Flange with Deep Escutcheon with Standard Escutcheon Recessed Escutcheon (Figure 6) (Figure 9) (Figure 4) without Escutcheon with Deep Escutcheon Temperature Bulb Color (Figure 7) (Figure 10) Rating Code TY3155 Upright without Escutcheon (Figure 13) without Escutcheon (Figure 8) SPRINKLER FINISH Natural Chrome White Natural Chrome White Natural Chrome White Brass Plated Polyester Brass Plated Polyester Brass Piated Polyester 135°F(57°C) Orange 155°F(68°C) Red 1,2,3,5 1,2,5 1,2,3,4,5 1,2,4,5 1',2',3",4,5 1",2',4,5 175°F(79°C) Yellow 200°F(93°C) Green 286°F(141°C) Blue N/A 4,5 360°F(182°C) Mauve N/A 1',2',5 N/A Notes 1. Listed by Underwriters Laboratories, Inc.(maximum order 4. Loss Prevention Gertification Board and CE conformity length of 48 inches) apply to these temperature ratings only 2. Listed by Underwriters Laboratories for use in Canada 5. Approved by the City of New York under MEA 352-01-E (maximum order length of 48 inches) " Light and Ordinary Hazard Occupancies Only 3. Approved by Factory Mutual Research Corporation '� Light Hazard Occupancies Only (maximum order length of 48 inches) N/A-Not Available TABLE A SERIES DS-1 STANDARD RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS — LABORATORY LISTINGS AND APPROVALS — PLUG WITH WLEf SEALING ASSEMBLY YOKE SPRING - INLET BAND WRENCH WATER RECESS TUBE //- CASING _� GUIDE INSERT TUBE WRENCH , � FLAT � BULB v �� FRAME '� � SEAT � � �� PUSH WRENCH — 5 mm BULB IN TO ENSURE VENT HOLE ENGAGEMENT WITH SPRINKLER COMPRESSION WRENCHING AREA DEFLECTOR SCREW FIGURE 1 SERIES DS-1 STANDARD RESPONSE DRY-TYPE SPRINKLERS FIGURE 2 —ASSEMBLY— W-TYPE 7 SPRINKLER WRENCN TFP500 Page 3 of 10 SPRINKLER FITTING SPRINKLER FITfING SPRINKLER FITTING (REFER TO DESIGN (REFER TO DESIGN {REFER TO DESIGN CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION) FACE OF \ FACE OF FACE OF SPRINKLER 1\ SPRINKLER SPRINKLER FITTING �'�- � FITTING - , FITTING _ ,, � _ _J � \ L_ _J �L_ _ , ORDER LENGTHS: ORDER LENGTHS: ORDER�ENGTHS: 3-1/2"DIA. 3-3/4"to 48" 1/2"to 46" (88,9 mm) 2-3/4"to 48" 1-3/4" DIA. (12,7 to 1168,4 mm) � � (69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm) �N 1/4" 6 4 mm 2-1/2"DIA. IN 1/4"(6,4 mm) � IN 1/4"(6,4 mm) 2-1/4"DIA. � ' � (63,5 mm) WCREMENTS INCREMENTS (57,2 mm) WCRE�ENTS (�—y� FACE OF � CEILING F CEA OF � F CEA OF _L � CEILING CEILING � 4-1/4"t 1/8" (108,0±3,2 mm) 2-3/16"+1/8" 3"DIA. 1-3/8"±1/8" 2-7/8"DIA. (55,6±3,2 mm) ��6,2 mm) (34,9 t 3,2 mm) ��3,0 mm) FIGURE 4 FIGURE 3 PENDENT TY3255 FIGURE 5 PENDENT TY3255 WITH STANDARD PENDENT TY3255 WITH STANDARD ESCUTCHEON RECESSED ESCUTCHEON WITH DEEP ESCUTCHEON SPRINKLER FITTING (REFER TO DESIGN TOP OF CRITERIA SECTION) DEFLECTOR � FACE OF SPRINKLER \ FITTING }- , � L_ —_� ORDER LENGTHS: } 5"to 48" I (127,0 to 12'19,2 mm) ORDER LENGTHS: IN 1/4"(6,4 mm) 5"to 48" INCREMENTS (127,0 to 1219,2 mm) IN 1/4"(6,4 mm) INCREMENTS FACE OF � SPRINKLER —_. FITTING MINIMUM � r- -� 1-3/4"(44,5 mm) /�� - DEFLECTOR � TO CEILING SPRINKLER FITTING � _— (REFER TO DESIGN CRITERIA SECTION) FlGURE 6 FlGURE 7 PENDENT TY3255 UPRIGHT TY3155 WITHOUT ESCUTCHEON WlTHOUT ESCUTCHEON TFP500 Page 4 of 10 Operation ORDER LENGTHS: When TYCO Series DS-1 Dry-Type 2-3/4"to 48"(69,9 to 1219,2 mm) Spf'InklefS are It1 SefViC2, water IS IN 1/4"(6,4 mm)WCREMENTS 4„t��8„ prevented from entering the assembly � ' (ioi,6±3,2mm) by the Plug with Sealing Assembly ' FACE OF FACE OF !'i 1-3/4"DIA. (Figure 1)in the Inlet of the Sprinkler. —SPRINKLER MOUNTWG —; (44,5 mm) The glass bulb contains a fluid that FITTING SuRFACE �� expands when exposed to heat.When , � the rated temperature is reached, the - � fluid expands sufficiently to shatter l '� 3"DIA. the glass buib, and the Bulb Seat is � � (�s,2 mm) released. �-� 3.5° ! The compressed Spring is then able to expand and push the Water Tube as SPRINKLER FITTING \, well as the Guide Tube outward. This (REFER TO DESIGN CENTERLINE 5/16" action simultaneously puils inward CRITERIA SECTION) OF WATERWAY (7,9 mm) on the Yoke, withdrawing the Plug with Sealing Assembly from the Inlet, allowing the sprinkler to activate and FIGURE 8 flow water. TY3355 HORIZONTAL SIDEWALL WITH STANDARD ESCUTCHEON Design Criteria ORDER LENGTHS: FACE OF TYCO Series DS-1 Dr T e S rinklers 1/2"to 45-3/4"(12,7 to 1162,1 mm) MOUNTING y' yp p IN 1/4°(6,4 mm)INCREMENTS SURFACE are intended for use in fire sprinkler 4-13/16"±1/s" systems designed in accordance (122,2±3,2 mm) with the standard instaliation rules FACE OF 2-1/2° DIA. recognized by the applicable Listing SPRINKLER (63,5 mm) or Approval agency; for example, UL FITTING � Listing is based on NFPA 13 require- j } ments. For more information on � __i__+ I LPCB Approval, contact TYCO Fire � i — 3-1/2" �IA. Suppression&Building Products at the �� (ss,9 mm) following office: �-� 3.5° Kopersteden 1 SPRINKLER FITTING � - / 7547 TJ Enschede (REFER TO DESIGN CENTERLINE 5/16" The Netherlands CRITERIA SECTION) OF WATERWAY (7,9 mm) Tel: +31-(0)53-428-4444 Fax:+31-(0)53-428-3377 Sprinkler Fittings FIGURE 9 Install 1-inch NPT Series DS-1 Dry-Type TY3355 HOR/ZONTAL SIDEWALL WITH DE'EP ESCUTCHEON Sprinkters are to be installed in the 1-inch NPT outlet or run of the following fittings: • malleable or ductile iron threaded ORDER LENGTHS: tee fittings that meet the dimen- 5-1/2'�to 4s"(139,7 to 121s,2 mm) sional requirements of ANSI B16.3 IN 1/4"(6,4 mm)INCREMENTS MINIMUM (ClasS 150) 2-1/4��(57,2 mm) . cast iron threaded tee fittings that FACE OF - DEFLECTOR TO meet the dimensional requirements —SPRINKLER MOUNTING of ANSI 616.4(Class 125). FITfING SURFACE Do not install Series DS-1 Dry Type - + � Sprinklers into elbow fittings.The Inlet of the sprinkler can contact the interior II � � of the elbow. `_� 3.5° 5/16" The unused outlet of the threaded tee is SPRINKLER FITTING (7,9 mm) plugged as shown in Figure 12. (REFER TO DESIGN CENTERLINE You can also install Series DS-1 CRITERIA SECTION) OF WATERWAY Ory Type Sprinklers in the 1-inch NPT outlet of a GRINNELL Figure 730 Mechanical Tee. However, the use of FIGURE 10 the Figure 730 Tee for this arrangement TY3355 HORIZON7TAL SIDEWALL WITHOUT ESCUTCHEON is limited to wet pipe systems. TFP500 Page 5 of 10 Temperatures for Heated Area� Ambient Temperature Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C) Sprinkler Minimum Exposed Barrel Length, Inches(mm)2 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 20°F(-7°C} 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE B EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS — MfNIMUM RECOMMENDED LENGTHS — The configuration shown in Figure 13 � For protected area temperatures is only applicable for wet pipe systems Do not insfall Series DS-1 Dry-Type between those given above, the where the sprinkler fitting and water- Sprinklers into any other type fitting he fac of the ttin nao theeoutside of filled pipe above the sprinkler fitting are i,y(thout first consulting the Technical the rotected area ma be determined not subject to freezing and where the Services Departmeni.Failure to use the p y length of the Dry-Type Sprinkler has the appropriate fitfing may result in one of by interpolating between the indicated minimum ex osure len th de icted in values. P 9 p the following: Figure 11.Refer to the Exposure Length Clearance S aCe section. •Failure of the sprinkler to operate prop- P erly due to formation of ice over the In accordance with Section 8.4.9.2 For wet pipe system installations of In/et Plug orbinding of the Inlet Plug. of the 2010 edition of NFPA 13, when 1-inch NPT Series DS-1 Dry Type connecting an area subject to freezing Sprinklers connected to CPVC piping, •Insufficient engagement of the In/et and an area containing a wet pipe use only the following TYCO CPVC piPe-threads with consequent leakage. sprinkler system,the clearance space fittings: Drainage around the sprinkler barrel of Dry-Type • 1" x 1" NPT Female Adapter (P/N In accordance with the minimum Sprinklers must be sealed. Due to 80145) requirements of the National Fire temperature differences between two Protection Association for dr i e areas, the potential for the formation • 1" x 1" x 1" NPT Sprinkler Head sprinkler systems, branch, cro s, and of condensation in the sprinkler and Adapter Tee(P/N 80249). feed-main piping connected to Dry subsequent ice build-up is increased. If For dry pipe system installations, use Sprinklers and subject to freezing this condensation is not controlled, ice only the side outlet of maximum 2-1/2- temperatures must be pitched for build-up can occur that might damage inch reducing tee when locating Series proper drainage. the dry-type sprinkler and/or prevent DS-1 Dry-Type Sprinklers directly proper operation in a fire situation. below the branch line. Otherwise, use Exposure Length Use of the Model DSB-2 Dry Sprinkler the configuration shown in Figure 12 to When using Dry Sprinklers in wet pipe goot,described in technical data sheet assure complete water drainage from sprinkler systems to protect areas TFP591 and shown in Figures 14 and above Series DS-1 Dry Type Sprinklers subject to freezing temperatures, use 15,can provide the recommended seal. and the branch line. Failure to do so Table B to determine a sprinkler's may result in pipe freezing and water appropriate exposed barrel length damage. to prevent water from freezing in the connecting pipes due to conduction. The exposed barrel length measure- ment must be taken from the face of the sprinkler fitting to the surface of the structure or insulation that is exposed to the heated area. Refer to Figure 11 for an example. TFP500 Page 6 of 10 RUN FACE OF OUTLET TO WET SIDE SPRINKLER O PLUGGED SYSTEM OUTLET FITiING SPRINKLER PLUGGED � TO DRY FITTING � � EXPOSURE SYSTEM (SEE DESIGN LENGTH CRITERIA (SEE DESIGN SECTION) DSB-2 CRITERIA DSB_2 SPRINKLER INTENDED SECTION) DSB'2 INTENDED FITfING FOR FREEZER . • INTENDED FOR FREEZER (SEE DESIGN STRUCTURES FOR FREEZER STRUCTURES CRITERIA STRUCTURES SECTION) i � / FIGURE 12 FIGURE i3 FIGURE 11 SPRINKLER FITTING SPRINKLER F1777NG — EXPOSURE LENGTH— — UNHEATED AREA — — HEATED AREA — STRAPTIES 1-3/4" DIA. (ENDS ON –OPPOSING (44,5 mm) SIDES OF CLEARANCE �NSULATED BOO� HOLE FREEZER ADHESIVE STRUCTURE -DSB-2 BOOT �—ADHESIVE DSB-2 BOOT 1-3/4" DIA. _ (44,5 mm) , CLfARANCE � HOLE 1 f INSULATED t —FREEZER STRUCTURE DS-1 STRAP TIES DS-1 SHOWN WITH (ENDS ON SHOWN WITH STANDARD OPPOSING STANDARD ESCUTCHEON SIDES OF ESCUTCHEON BOO� FIGURE 14 FIGURE i5 MODEL DSB-2 DRY SPRINKLER MODEL DSB-2 DRY SPR/NKLER 800T WITH PENDENT SERIES gOOT WITH SIDEWALL SER/ES DS-1 DRY-TYPE SPRlNKLER DS-1 DRY-TYPE SPRINKLER TFP500 Page 7 of 10 /nstallation Note:If sprinkler removal becomes Never repaint factory-painted Cover necessary, remove the sprinkler Plates. When necessary, replace TYCO Series DS-1 Dry-Type Sprinklers using the same wrenching method cover plates with factory-painted must be installed in accordance with noted above. Sprink/er removal units. Non-factory applied paint can the following instructions. is easier when a non-hardening adversely delay or prevent sprinkler sealant was used and torque guide- operation in the event of a fire. � lines were followed. After removal, Replace sprinklers that: inspecf the sprinkler for damage. Series DS-1 Dry-Type Sprinklers must • were damaged by dropping,striking, only be installed in fittings that meet 4. After installing the ceiling or wall and Wrench twisting,wrench slippage,or the requirements of the Design Criteria app�ying a ceiling finish,slide on the the like. secfion. Refer to fhe Desi n Criteria outer piece of the Escutcheon until g it comes in contact with the ceiling/ •were modified or over-heated. section for other important require- ments regarding piping design and wall. Do not lift the ceiling panel out . have cracked bulbs or have lost liquid sealing of the clearance space around of its normal position. from the bulbs.Refer to the Installation the Sprinkler Casing. When using the Deep Escutcheon, Section in this data sheet. Do not install any bulb type sprinkler if hold the outer piece in contact with . are leaking or exhibiting visible signs the bulb is cracked or there is a loss of the mounting surface (ceiling or of corrosion. liquid from the bulb.With the sprinkler wall). Then rotate the inner piece Res onsibilit lies with owners for the held horizontally, a small air bubble approximately 1/4 turn with respect inspection,testing,and maintenance of should be present.The diameter of the to the outer piece,to hold the Deep their fire protection system and devices air bubble is approximately 1/16 inch Escutcheon firmly together. in compliance with this document, as (1,6 mm)for the 135°F(57°C) rating to well as with the applicable standards of 1/8 inch(3,2 mm)for the 360°F(182°C) Care and the National Fire Protection Association rating. (for example, NFPA 25), in addition to Obtain a leak-tight 1-inch NPT sprinkler Maintenance the standards of any other Authorities joint by applying a minimum-to- Having Jurisdiction. The installing maximum torque of 20 to 30 ft. Ibs. TYCO Series DS-1 Dry-Type Sprinklers contractor or sprinkler manufacturer (26,8 to 40,2 Nm). Higher levels of must be maintained and serviced should be contacted relative to any torque may distort the sprinkler Inlet in accordance with the following questions. with consequent leakage or impairment instructions. Automatic sprinkler systems are recom- of the sprinkler. � mended to be inspected, tested, and Do not attempt to compensate maintained by a qualified Inspection for insufficient adjustment in an Before closing a fire protection system Service in accordance with local Escutcheon Plate by under or over- main control valve for maintenance requirements and/or national codes. tightening the Sprinkler. Re-adjust the work on the fire protection system position of the sprinkler fitting to suit. that ii conirols, obtain permission to 1. Install endent s rinklers onl in shut down the affected fire protection P P Y systems from fhe proper authorities the pendent position; install upright and notify all personnel who may be sprinklers only in the upright posi- affected by this action. tion.The deflector of a pendent or upright sprinkler is to be parallel to Absence of the outer piece of an the ceiling. escutcheon, which is used to cover a Install horizontal sidewali sprinklers clearance hole, may delay the time to in the horizontal position with their sprinkler operation in a fire situation. centerline of waterway perpendic- A Vent Hole is provided in the Bulb Seat ular to the back wall and parallel to (Figure 1)to indicate if the Dry Sprinkler the ceiling. Ensure the word "TOP" is remaining dry. Evidence of leakage on the Defiector faces the ceiling. from the Vent Hole indicates potential 2. With a non-hardening pipe-thread �eakage past the Inlet seal and the need sealant such as Teflon` applied to to remove the sprinkler to determine the Inlet threads, hand-tighten the the cause of leakage;for example, an sprinkler into the sprinkler fitting. improper installation or an ice plug. Close the fire protection system control 3. Wrench-tighten the sprinkler using valve and drain the system before either: removing the sprinkler. • a pipe wrench on the Inlet Band or Exercise care to avoid damage before, the Casing(Figure 1). during, and after installation. Never • the W-Type 7 Sprinkler Wrench on Paint, plate, coat, or otherwise alter the Wrench Flat(Figure 2). automatic sprinklers after they leave the factory. Apply the Wrench Recess of the W-Type 7 Sprinkler Wrench to the Wrench Flat. 'DuPont Registered Trademark TFP500 Page 8 of 10 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression and Building Products ability.When ptacing an order, indicate (TFSBP) are warranted solely to the the full product name, including original Buyer against defects in description and Part Number(P/N). material and workmanship when paid for and properly installed and main- Dry Sprinklers tained under normal use and service. When ordering 5.6 K-Factor Series This warranty will expire twelve (12) DS-1, Standard Response , Standard months from installation or eighteen Coverage (5 mm Bulb), Dry Type (18) months from delivery, whichever Automatic Sprinklers, specify the occurs first. No warranty is given for following information: products or components manufac- . Model/SIN tured by companies not affiliated by Pendent TY3255,Upright TY3155,or ownership with TFSBP or for products Horizontall Sidewall TY3355 and components which have been ' subject to misuse, improper instal- . Deflector Style � lation, corrosion, or which have not been installed, maintained, modified • Order Length or repaired in accordance with appli- Dry Type Sprinklers are furnished cable Standards of the National Fire based upon Order Length as Protection Association, and/or the measured per Figures 3 through 10, standards of any other Authorities as applicable.After the measurement Having Jurisdiction. Materials found by is taken, round it to the nearest 1/4 TFSBP to be defective shall be either inch increment. repaired or replaced, at TFSBP's sole . Inlet Connections option. TFSBP neither assumes, nor 1_inch NPT or ISO 7-R1 authorizes any person to assume for it, any other obligation in connection • Temperature Rating with the sale of products or parts of . Sprinkler Finish products.TFSBP shall not be respon- sible for sprinkler system design errors • Escutcheon Style and Finish, as or inaccurate or incomplete infor- applicable mation supplied by Buyer or Buyer's . Part Number from Table B. Part representatives. numbers are for 1-inch NPT standard In no event shali TFSBP be liable, in order sprinklers. Orders for all other contract, tort, strict liability or under sprinkler assemblies must be accom- any other legal theory, for incidental, panied by a complete description. indirect, special or consequential damages, including but not limited to Sprinkler Wrench labor charges, regardless of whether Specify W-Type 7 Sprinkler Wrench, TFSBP was informed about the possi- P/N 56-850-4-001. bility of such damages, and in no event shall TFSBP's liability exceed an Sprinkler Boot amount equal to the sales price. Specify Model DSB-2 Dry Sprinkler The foregoina warran�is made in lieu Boot, P/N 63-000-0-002. This Part of an rLand all other warranties.exoress Number includes one Boot,two Strap or implied. including warranties of Ties, and 1/3 oz. of Adhesive (a suffi- merchantability and fitness for a partic- cient quantity for installing one boot). ular pur�ose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components,whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. TFP500 Page 9 of 10 P/N* 60 - XXX - X - XXX MODEL/SIN SPRINKLER ESCUTCHEON FINISH FINISH(1) 96 Pendent with Standard TY3255 � NATURAL BRASS WHITE Escutcheon(1"NPT) (Figure 3) 93 Pendent with Deep TY3255 4 WHITE POLYESTER WHITE Escutcheon(1"NP� (Figure 5) 9� Pendent with Standard TY3255 g CHROME PLATED CHROME Recessed Escutcheon(1"NP� (Figure 4) 92 Pendent without TY3255 0 CHROME PLATED WHITE Escutcheon(1"NP� (Figure 6) 2 NATURAL BRASS BRASS PLATED 94 Sidewall with Standard TY3355 Escutcheon(1"NPI� (Figure 8) 53 Sidewall with Deep TY3355 Escutcheon(1"NP� (Figure 9) 54 Sidewall without TY3355 TERATING(2)RE L NGTH(3) Escutcheon(1"NP� (Figure 10) 0 135°F(57°C) 055 5.50" 98 Upright without TY3155 � 155°F(68°C) 082 8.25" Escutcheon(1"NP� (Figure 7) 2 175°F(79°C) 180 18.00" Notes 3 200°F(93°C) 187 18.75" " Use Prefix"I"for ISO 7-R1 Connection;for example, I-60-961-1-180). a 2as°F(141°c) s�2 37.25�� 1. Escutcheon Finish applies to sprinklers provided with escutcheons. 5 360°F(182°C) 480 48.00" 2. 286°F(141°C)and 360°F(182°C)temperature ratings apply to non-recessed sprinkler assemblies. 3. Dry-Type Sprinklers are furnished based upon "Order Length"as measured per Figures 3 through 10,as appli- cable, and for each individual sprinkler where it is to be installed.After the measurement is taken, round it to the nearest 1/4 inch increment. TABLE C SERIES DS-1 STANDARD RESPONSE, STANDARD COVERAGE,DRY-TYPE SPRINKLERS — PART NUMBER SELECTION — TFP500 Page 10 of 10 Copyright O 2007,2011 Tyccs Fire Suppressiqn&Building Products.All rights reserved. FIRE SPRINKLER VALVES ES-A-200B • � Ser�es 240B A M E S Double Check Valve Assemblies FIRE&WA.TERWORKS� Sizes �/2"—2° (i5—50mm} �'" �� 2008 Features Series 200B Double Check Valve Assemblies are designed to protect drink- • Cast bronze construction ing water supplies from dangerous cross-connections in accordance with • Separate access, top entry check national plumbing codes and water authority requirements. valve design • Reversible seat disc rubber, This series may be used in only those cross-connections identified by local extends check valve life inspection authorities as non-health hazard applications. Check with the local • Chloramine resistant elastomers authority having jurisdiction regarding vertical orientation, frequency of test- • Replaceable seats and seat discs ing or other installation requirements. Series 2006 meets the requirements of ASSE Std. 1015 and AWWA Std. C510. • Compact design • Top mounted screwdriver slotted ball valve test cocks • Low pressure drop Specifications • �/2"—1" (15—25mm) have Tee Double Check Valve Assembly shall be installed at each noted location. handles Provide assembly with integral shutoff valves that conform to ASSE 1015 • No special tools required for and AWWA C510. The assembly shall have top entry access points for each seNicing check assembly, screw driver slotted test cocks and require the use of no • Plastic on plastic check guiding special tools for servicing. All wetted rubber parts shall be manufactured from reduces potential binding due to silicone or chloramine resistant EPDM rubber. All valve seats and seat discs mineral deposits shall be replaceable. Seat discs shall be reversible to extend check valve life. Check valve guiding shall be plastic to plastic. The assembly shall be an Ames Company Series 200B. Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Representative Ames product specifications in U.S.customary units and metrir,are approximate and are provided for reference only.For precise measurements,please co�tact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materiafs without prior notice and without incurring any obligation to make such changes and motlifications on Ames products previously or subsequently sold. www.amesfi rewater.com Available Models Materials Suffix: Body: Bronze S—bronze strainer Elastomers: Chioramine resistant silicone and EPDM LH—locking handle ball valves Check Seats and Disc Holders: PPO HC—2'/z" inlet/outlet fire hydrant fittings(2" valve) B—quarter-turn ball valves PC—interna)polymer coating Standards C&T—test cock cap&tether AWWA Std C510 compliant LBV—less ball valves A—street elbows with quarter-turn bail valves Appi ovals Prefix: fl55E °P` Sp� U—union connections ° ` "S 1075 Pressure-Temperature Operating Pressure: 175psi(12.07 bar) IMPORTANT:Inquire with governing authorities for local installation requirements. Operating Temperature Range: 33°F—180°F (5°C—82°C) Dimensions — Weights -----------------------------------------------------------a---------------------------------------------------------------- ----------------------------------------- A ------------------------------------------- N-------- ------------ ; ; C ! ' �� ��� B - - - —8 � M � , — G -�— H , , ` ---------•-------•---. E ._...--°-------•---- ------- P ----- 200B, 200B—S , � � • � � A B C D E(L� F G H M N 2008 2006-5 in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm Ibs. kgs. lbs. kgs. '/z 15 99/,e 242 3'�hs 94 215/,s 73 129he 318 513/is 147 2'hs 62 1"hs 43 '/a 19 13I8 35 23/a 70 2.8 1.3 3.8 1J 3/a 20 12'/a 307 4'/a 108 3'/z 88 15'hs 393 7"/is 195 3Ve 79 2'hs 52 1'hs 27 15/e 41 33/,s 81 4.7 2.1 6.4 2.9 1 25 1413/,s 376 49hs 116 37/s 98 19'/z 495 95/s 244 33/a 95 2'/,e 62 15he 33 2'/s 54 33/a 95 7.4 3.4 9.4 4.3 1'/a 32 18t5/�s 480 6'/a 156 5'/e 129 24'/,s 610 11"/is 297 4'/a 108 Z5I8 67 15/e 41 2'/2 64 4�/is 113 14.0 6.3 18.0 8.1 1'/z 40 1875l,s 480 6'/e 156 5'/a 129 25�/a 640 11"/,e 297 43/a 121 3'/a 79 15/e 41 3 76 4'/a 124 16.1 7.3 19.9 9.0 2 50 213hs 538 7'he 179 55/a 142 2875hs 735 133/s 340 53IB 137 3'/,s 87 115/�s 49 39/,s 90 515/,s 151 25.7 11.6 33.4 15.2 2 --------------------------------------------------------------------- � -------------------------------------------- ------------_---------------------------- A ---------------------------------------- N � � C ; � ,,1►�t ' B M . ? G �-- H- � --------------------- E ----------------------- - --- - . -------F�----- U2006, U200B-S � � � � r � A B C D E(LF� F G H M N U200B U200B-S in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm tbs. kgs. Ibs. kgs. '/z 15 1513hs 402 49hs 116 3'/a 98 1813/,s 478 113/s 289 3 76 P'/,e 43 15/is 33 13/a 35 23la 70 7.4 3.4 8.4 3.8 3/a 20 16'/a 412 49hs 116 3'/a 98 195/a 498 1151is 287 33I8 86 2'hs 52 15/is 33 �SIB 41 33/7s 81 7.9 3.6 9.7 4.4 1 25 175hs 439 49he 116 3�/e 98 22 558 113/a 297 33/a 95 2'/,s 62 15/,s 33 Z'/a 54 33/a 95 8.9 4.0 10.9 5.0 1'/a 32 20'/s 530 6'/e 156 5'/e 129 26 660 153/e 390 4'/a 108 Z5I8 67 15/s 41 2'/z 64 4'/,s 1t3 17.6 8.0 21.6 9.8 1'/z 40 219he 547 6'/s 156 5'/e 129 27�/s 708 153/s 390 43/a 121 3'!s 79 15/e 41 3 76 4'/s 124 19.8 9.0 23.5 10.7 2 50 24'hs 621 7'/,s 179 55/a 142 32317s 817 163/a 425 53/a 137 3'/,s 87 1'S/,s 49 39hs 90 5'Shs 151 30.� 13.6 37.7 17.1 D �w� ,��� � � � I , � , , � � , � E; --------------------- ------------------- ; g C i ---G ---1-- H-- �-------------------------------------- A -------------------------------------� -------�F------- 200B A � � � A B C D E(LF� F G H 2O0B A in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. Vz 15 7'/a 200 35/is 84 215/�s 73 215/is 73 513/is 147 2'/is 62 1'Vis 43 3/a 19 3.4 1.5 3!a 20 13'hs 340 413hs 121 49hs 116 3'/z 98 7"/,s 195 3'/a 79 2'/,s 52 1'/,s 27 5.7 2.6 1 25 12"hs 322 5 127 43I8 110 3'/s 98 95/s 244 33/a 95 2'/,s 62 15/,s 33 8.9 4.0 1'/a 32 153/is 386 5��/ie 144 5�Vis 144 5Va 129 11"/,e 297 4�/a 108 25/s 67 15/a 41 15.7 7.1 1'/z 40 1513hs 401 6'/,s 156 63hs 156 5'/a 129 11"/is 297 43/a 121 3'/e 79 �5I6 41 18.4 8.3 2 50 173/s 441 65/s 168 69/,s 167 55/s 142 133/e 340 53/a 137 3�hs 87 175/�s 49 29.0 13.1 3 Capacities `Typical maximUm flow rate(7.5 feeUsec.) 200B 2006 A_ U200B Yz"(15mm) 1'/a"(32mm) kPa psi * kPa psi * 110 16 138 20 97 14 - 69 10 103 15 - 41 6 _ - -- -- � �. 69 10 ,� - � � 28 4 . � ' � 34 5 _ � -: '_ 14 2 0 0 0 0 0 1 2 3 4 5 6 7 S 9 10 11 12 gpm 0 2 4 8 12 16 20 30 40 50 60 70 75 SO 90 100 110 gpm 0 4 8 23 15 19 23 27 30 34 38 42 46 Ipm 8 15 30 46 61 76 114 152 190 228 266 285 304 342 380 418 Ipm 7.5 fps 7.5 fps 229 mPs 2.29 mps '/a" (20mm) 1'/z"(40mm) kPa psi * kPa psi * 172 25 110 i6 97 14 138 20 83 12 103 15 69 10 69 10 55 8 � 41 6 � � _� -� _� 34 5 - - '- � ' 28 4 - - 0 0 14 2 0 0 0 2 4 8 12 16 18 20 24 28 30 34 45 gpm 0 2 4 6 12 16 20 30 40 50 60 70 80 90 100 110120 gpm 8 15 30 46 61 69 76 91 106 114 129 171 Ipm S 15 23 46 61 76 114 152 190 228 266 304 342 380 418 456 Ipm 7.5 fps 7.5 fps 2.29 mPs 2.29 mps 1"(25mm) 2"(50mm) kPa psi * kPa psi * 97 14 97 14 83 12 ' 83 12 69 10 '� � 69 10 55 8 '� 55 8 41 6 ' � 41 6 - 28 4 -- --- 28 4 -- - 14 2 14 2 0 0 0 0 0 2 4 6 12 16 20 30 40 50 60 gpm 0 4 12 20 40 60 80 100 120 140 160 200 gpm 8 15 23 46 61 76 114 152 190 228 ipm 15 46 76 152 228 304 380 456 532 480 760 Ipm 7.5 fps 7.5 fps 2.29 mPs 2.29 mps � A M E S � • 9001-2008 FIRE&WATERWORKS www.amesfirewater.com C E R T 1 F 1 E D A Watts Water Technologies Company USA: Backflow- Sacramento,CA•TeC(916)928-0123•Fax�(916)928-9333 Control Valves- Houston,TX•Tel:(713)943-0688•Fax:1713)944-9445 Canada: Burlington,ON•Tel:(905)332-4090•Fax:(905)332-7068 ES-A-200B 0532 �O 2011 Ames Fire&Waterworks PIPE AND FITTINGS SPEABS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS � The information contained in this publication is based on current information and Product design at the time of pubiication and is subject to change without notification.Our ongoing commitment to product improvement may result in some variation.No representations,guarantees or warranties of any kind are matle as to its accuracy,suitability for particular applications or results to be obtained therefrom.For verification of technical data or additional information not contained herein,please contact Spears�Technical Services Department(West Coast:(818)364-1611—East Coast:(678)985-1263]. General Information RECOMMENQATIONS FOR INSTALLERS AND USERS: Plastic piping systems should be ENGINEERED,INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the instalier andlor user prior to installation of a plastic piping system.Ail Installation and maintenance personnei should be trained in the proper handling and installation requirements and precautions of plastic piping systems. PRIOR TO ASSEMBLY,ail piping system components should be inspected for damage or irregularities.Mating components should be checked to assure that tolerances and engagements are compatible.Do not use any components that appear irregular or do not fit properly.Contact the appropriate manufacturer of the component product in question to determine usability.Consult all applicable codes and regulations for compliance prior to installation. Installation must be made in accordance with Spears�'Manufacturing Company FlameGuard°CPVC Fire Sprinkler Piping Products Installation Instructions-FG-3 NOTE—Individual or group instruction in correct solvent weltling procedures is available by contacting your local distributor or your servicing Spears�Regional Distribution Center. SOLVENT CEMENT CONNECTIONS—Spears��Manufacturing Company recommends the use of Spears�FS-5 One Step solvent cement for joining Spears� products.Use of solvent cementing protlucts not approved for CPVC fire sprinkler systems,or failure to follow installation instructions will automatically void the warranty. THREADED CONNECTION—Spears�Manufacturing Company recommends the use of Spears�BLUE 75TM'Thread Sealant.This product has been tested by Spears�and the sealant manufacturer for compatibility with the Spears�CPVC fire sprinkler products.Consult the sprinkler head manufacturer before using this product.WARNING:OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITfING COMPONENTS.Care must be taken to avoid over torquing-generally 1 to 2 turns beyond finger tight is all that is required to make up a threaded connection.Factory testing has ind�cated 1�-25 ft.Ibs.of torque is adequate to obtain a leak free seal. GASKET SEALED THREAD CONNECTIONS—This type of connection can only be matle with Spears�TorqueSafeT"" style Gasket Sealed Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER.Tape or paste may impair proper sealing and function.Testing has shown that hand tight until snug is all that is needed to seal this special connection. Dimension Reference G = (LAYING�ENGTH)Intersection of center lines to bottom of socketlthread;90°elbows, M = Outside diameter of socket/thread hub;±1116 inch. tees,crosses;±1/32 inch. N = Socket bottom to socket bottom;couplings;±1/16 inch. H = Intersection of center lines to face of fitting;90°elbows tees,crosses;t 1/32 inch. Q = �n/idth of flats;±1/16 inch. J = Intersection of center lines to bottom of sockeUthreaci;45°elbows;±1/32 inch W= Height of cap;±1/16 inch. L = Overall length of fittings;±1/16 inch. CPVC FIRE SPRINKLER PIPE SDR 13.5(ASTM F 442) Nominal Size Average O.D. Average I.D. Part Number Approx.Weight Lbs.IFt. Inches (mm) Inches (mm) Inches (mm) CP-�07 3/4 (19.1) 1.050 (26.7) .574 (22.5) •181 CP-010 1 j25.4) 1.315 (33.4) 1.1D1 (28.2) 280 CP-012 1-114 (,31.8) 1.660 (42.2) 1.394 (35.6) 418 CP-015 1-1/2 (38.1) 1.900 (48.31 1.598 (40.7) 550 CP-�20 2 (50.8) 2.375 (60.3) 2.003 (50.9) 872 CP-Q25 2-1/2 (63.5) 2.875 (73.01 2.423 (61.5) 1.260 CP-030 3 (76.�) 3.500 (88.9) 2.950 (75.0) 1.°00 � SPEARS'�MANUFACTURING COMPANY r FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS � TEE S ocket x S ocket x S ocket , � ' PA -- --�-- - t G � H �� t � -_ Part Number Size G H L M Approx.Wt (Lbs.) 4201-007 3/4 9/I 6 1-1 R 2-31 r32 1-5/I 6 11 4201-010 1 13A 6 1-13A 6 3-5�8 1-58 .20 4201-012 1-1/4 15l32 2-3/32 4-7/32 2 29 4201-015 1-12 1-5/32 2-9/I 6 5-3/32 2-11/32 .54 4201-020 2 1-13/32 2-15/16 5-78 2-78 86 4201-025 2-12 1-23/32 3-12 7 3-15/32 1.62 4201-030 3 2-1/I 6 3-15/16 7-78 4-3A 6 302 REDUCING TEE S ocket x S ocket x S ocket I�--►�-Ml � T I �M M2 t j - � �, � G2 H -�—H 2� L Part Number Size G G1 G2 H H1 H2 L M � Np Approx.Wt (Lbs.) 4201-102 3/4x3/4x1 3/4 25%�'s2 3/4 1-11/16 1-13/I 6 1-11/i 6 3-38 1-5/I 6 1-21/32 1-5/I 6 13 4201-125 1 x3/4x3/4 21/32 13-16 5�8 1-25/32 1-13lI 6 1-5i$ 3-13/32 1-17/32 1-5/I 6 1-5A 6 15 4201-126 1 x3/4x1 3/4 1=�$ 1-3/32 1-27/32 2-31/32 1-31/32 3-13/I 6 1-23/32 1-23/32 1-13/32 26 4201-131 1 xl x3/4 21/32 13r"6 21/32 1-25/32 1-13/I 6 1-25132 3-9/I 6 1-58 1-5A 6 1-58 .16 4201-157 1-1/4x1 x3/4 11/I 6 1-1�32 11/I 6 1-15(I 6 2-1/32 1-13/I 6 3-25/32 2-3/32 1-13/32 1-23/32 3Z 4201-158 1-1/4x1 xl 27/32 29Li2 25l32 2-1/I 6 2-1/32 1-29/32 3-15/16 1-31!32 1-SB 1-58 .24 4201-159 1-1/4x1 x1-1/4 31/32 31 32 31/32 2-7/32 2-7/32 2-3/32 4-11!32 2-3/32 23/32 1-23/32 35 A201-167 1-1/4x1-1/4x3/4 21/32 1 21/32 1-29/32 2 1-29/32 3-13/I 6 2 1-5�16 2 .22 4201-168 1-1/4xl-1/4x1 13/I 6 31'32 13/I 6 2-1 il 6 2-3/32 2-1/I 6 4-1 B 1-31/�2 1-21/32 2 Z4 4201-169 1-1/4x1-1 i4xt-1/2 1-1 Pd 15�16 1-1 B 2-3/8 2-11/32 Z-3/i3 4-3l4 2-3/32 2-11/32 23/32 .51 4201-201 1-12x1-1/4x3/4 11 i16 1 1/4 2-1/I 6 2 1-15/I 6 4 2-5/I 6 1-3i$ 2-1/l 6 41 4201-202 1-12x1-1/4x1 27/�2 1-1:32 1 2-7l32 2-5I32 2-1/4 4-15/32 2-5A 6 1-11 Ji 6 2-1/I 6 .42 4201-210 1-12x1-12x3/4 23l32 1=I,16 23l32 Z-3/32 2-1/32 2-3/32 4-3/I 6 2-5A 6 1-3� 2-5A 6 37 4201-211 1-12x1-12x1 13/16 1-;�,16 13/I 6 2-3/16 2-1/4 2-3/I 6 4-38 2-11/32 1-23/32 2-11�32 .41 4201-212 1-1 I2x1-12x1-1/4 1 1-?B 1 2-3i$ 2-11!32 2-3i8 4-13/I 6 2-11/32 2-3/32 2-11/32 48 4201-213 1-12x1-12x2 1-5/I 6 1-'��8 1-5116 2-11!I 6 2-21!32 2-11 A 6 5-3i8 2-11/32 2-27,32 2-11�32 .72 MADE IN THE U.S.A. 2 SPEARS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS � REDUCING TEE (continued) S ocketx S ocketx S ocket �—►-r M1 --� � I � H1 M - M2 � � j c, � G2 N fH2�- L PartNumber Size G G1 G2 N H1 H2 L M Mi � pPProx.Wt (Lbs.) 4201-248 2x2x3/4 11JI6 1-13/32 11/I6 2-7/32 2-7/I6 2-7/32 4-7/I6 2-27/32 1-38 2-27/32 52 A201-249 2x2x1 27/32 1-7/I 6 27/32 2-11/32 2-9A 6 2-11/32 423/32 2-78 t-3/4 2-7�$ .57 4201-250 2x2x1-1/4 1 1-11/32 1 2-17/32 2-19(32 2-17/32 5-3/32 2-27/32 2-3/32 2-27/32 .63 4201-251 2x2x1-1!2 1-7/32 1-13/32 1-7/32 2-11/16 2-25/3'L 2-11/16 53B 2-27/32 2-11/32 2-27/32 .$5 4201-239 2-12x2-1 ILx1 29/32 25/32 29/32 2-21/.32 1-29/32 2-21/32 5-5/16 3-12 1-23l32 3-12 1.03 4201-290 2-12x2-12x1-1/4 1-3/32 1-23l32 1-3/32 2-27/32 2-31/32 2-27/32 5-21/32 3-17/32 2-3/32 3-17/32 1.13 4201-291 2-12x2-12x1-12 1-3/16 12 1-3/I 6 2-15/I 6 1-78 Z-15/16 5-78 3-15/�2 2-11!32 3-15(.i2 1.26 4201-292 2-12x2-12x2 1-13/32 1-58 I-13/32 3-3/I 6 3-1�8 3-3/I 6 6-11/�2 3-1/2 3-7�$ 3-12 1.34 4201-335 3x3x1 7�$ 1-15116 7B 2-3/4 3-1/I 6 2-3/4 5-15/32 4-3/I 6 1-23/32 4-3/I 6 1.26 42Q1-336" 3x3x1-1/4 1-3�8 1-3/4 1-38 3-5/I 6 3-1�2 3-5/I 6 6-58 4-1 B 2-7�$ 4-1 B 1.94 ' A201-337 3x3x1-12 1-5/32 2-1/I 6 1-5/32 3-1/32 3-7/I 6 3-1/.32 6-3/32 4-3/I 6 2-38 4-3/16 1.46 4201-338 3x3x2 1-7�6 1-13A 6 1-7i16 3-5/I 6 3-5A 6 3-5A 6 6-19/32 4-3/I 6 2-78 4-3/I 6 1.69 4201-339 3x3x2-12 1-3/A 1-31/32 1-3l4 3-58 3-23/32 3-Si8 7-1!4 4-3/I 6 3-17/32 4-3/I 6 2.11 *Branch Outlet Sized with Bushing TorqueSafeT'" SPRINKLER HEAD TEE Gasket Sealed Brass M�-- Thread Insert Style ' c� t SocketxSocketxGasketflPT � ( � � I With E Iast�merSeal-Use NO Thread Sealant � � M -- �- -- �z —�- . � G G2 H H2 L Part Number Size G G1 GZ H H1 H2 L M Mi M2 Approx.Wt (Lbs.) 4202-101 G 3/4x3/4x1�L 7A 6 1-3lI 6 �16 1-1/I 6 1-7116 1-17l32 2-29/32 1-38 1-38 1-38 .22 4202-124 G 1 x3/4x12 7!I 6 1-11/32 ':316 1-9lI 6 1-11/16 1-9/I 6 3-1�$ 1-11/I 6 1-3� 1-3� .26 4202-130 G 1 x1 x12 7/I 6 1-11/32 ?16 1-9/I 6 1-11/I 6 1-9/I 6 3-1 i8 1-23132 1-3r$ 1-23/32 .28 4202-166 G 1-1/4x1-1/4x12 7/I 6 1-SB ,'16 1-11�16 1-15/I 6 1-11/I 6 33B 2-1/I 6 1-38 2-1/I 6 .34 4202-209 G 1-12x1-12x12 12 1-13A 6 12 1 JB 2-3/32 1-7 B 3-3/4 2-11/32 1-38 2-11/32 41 4202-247 G 2x2x1!2 1!1 2-1!I 6 12 2 2-11/32 2 4-1/32 2-27/32 1-38 2-27/32 .54 Notintended tn convey or dispense water for human consumption through drinking or cooking 3 SPEARS�MANUFACTURING COMPANY FlameGuard� CPWC FIRE SPRINKLER PIPING PRODUCTS SPEARS il � SPRINKLER HEAD TEE Brass Thread Insert Style S ocket x S ocket x f ipt �M� G1 H1 M -- --�-- - M2 � � G G2 r H—► H 2---► �— L —_ PartNumber Size G G1 G2 H H1 H2 L M MI IVQ Approx.Wt (Lbs.) 4202-101 3/4x3/4x12 7/16 1-5/�2 7/I 6 1-7A 6 1-17/32 1-7lI 6 2-29/32 1-3i8 1-7/32 1-3�8 27 4202-124 1 x3/4x12 7/I 6 1-11/32 9/I 6 1-9/I 6 1-11/I 6 1-9/I 6 3-1 r$ 1-11/I 6 1-38 1-38 .26 4202-130 1 xl x12 7/I 6 1-7/32 7/I 6 1-9lI 6 1-25/32 1-9/I 6 3-1 B 1-3/4 1-3/I 6 1-3/4 26 4202-010 1 x1 x1 11/I 6 1-3/32 11/I 6 1-13/I 6 1-29/32 1-13/I 6 3-19I32 1-23/32 1-23132 1-23l32 .37 4202-156 1-1 J4x1 x1 Q 7/16 1-15,32 9l16 1-11/I 6 2-1/32 1-11/I 6 3-38 2-3/32 1-7/32 1-3/4 30 4202-166 1-1/4x1-1/4x12 7/l 6 1-1,2 7/I 6 1-11/I 6 2-1/I 6 1-11 A 6 3-13/32 2-3l32 1-3/I 6 2-3/32 .32 4202-199 1-12x1-1/4x1 IL 1 i2 1-58 9/I 6 1 JB 2-3A 6 1-13/I 6 3-11/I 6 2-5116 1-7l32 2-1/I 6 37 4202-209 1-12x1-12x12 12 1-23,32 1/2 1-7 B 2-3132 1-78 3-3/4 2-5/I 6 1-17I32 2-5/I 6 .45 4202-237 2x1-tl2x12 12 1-7,8 17/32 2 2-7/I 6 1-29/32 3-15/I 6 2-27l32 1-7/32 2-5/I 6 48 4202-247 2xZx12 12 1-31/32 12 2 2-38 2 4-1/32 2-27132 1-17/32 2-27/32 .58 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE Special Reinforced Plastic Thread Style S ocket x S ocket x S R F ipt �+--Mt� I !,'� G1 � � H1 M - -t- - M2 � � � � G2 H H2 L Part Number Size G G1 G2 H H1 H2 L M Ntl M2 Approx.Wt (Lbs.) 4202-101 S R 3/4x3/4x12 19I32 3/4 19/32 1-19l32 1-7/I 6 1-19/32 3-7/32 1-13/32 1-3/I 6 1-13/32 .16 4202-124SR 1 x3/4xl 2 7/16 29l32 9/I 6 1-19/32 1-SB 1-9/I 6 3-5/32 1-23/32 1-3A 6 1-17/32 19 4202-130SR 1 xl x12 7A 6 29l32 7/16 1-9/I 6 1-58 1-9/I 6 3-1� 1-23/32 1-3/I 6 1-23/32 .20 4202-010S R 1 xl x1 21/32 3i4 21/32 1-25/32 1-58 1-25/32 3-19/32 1-23/32 1-11/I 6 1-23/32 26 4202-1565 R 1-1/4x1 x12 15/32 1-5/3� 19l32 1-23i32 1-78 1-23/32 3-13/32 2-3/32 1-3A 6 1-23/32 26 4202-166S R 1-1 l4x1-1 l4x12 7/I 6 1-1 B 7/I 6 1-11116 1-27/32 1-11/I 6 3-38 2-3/32 1-3A 6 2-3/32 26 4202-1685 R 1-1/4x1-1/4x1 27/32 1-1�32 27/32 2-3l32 1-29/32 2-3l32 4-7/32 2-3/32 1-11/I 6 2-3/32 .34 4202-199SR 1-12x1-1/4x12 9/16 1-9�32 17/32 1-15/I6 2 1-25/�2 3-23/32 2-11/.32 1-3/16 2-3/32 33 4202-2095 R 1-12x1-12x12 12 1-1!4 12 1-7�8 1-31/32 1-7,$ 3-3/4 2-11/32 1-3A 6 2-11!32 35 4202-211 SR 1-12x1-12x1 27/32 1-7/�2 27/32 2J/32 2-1�$ 2-7/32 4-15/32 2-11/32 1-23/32 2-11/32 .44 4202-2375 R 2x1-12x12 23/32 1-9:7 6 3B 2-7i32 2-9/32 1-3/4 3-31/32 2-7 B 1-3/I 6 2-1132 45 4202-2475R 2x2x1/2 12 31�32 12 2 1-11/I 6 19/�2 4 2JB 13/I 6 2-78 48 4202-287SR 'L-12x2-12x12 17/�2 1-3/4 17/32 2-9l32 2-1l2 2-9/32 4-19/32 3-12 1-7/32 3-12 .78 MADE IN THE U.S.A. � SPEABS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS � TORQUESAFET"" SPRINKLER HEAD TEE Gasket Sealed Brass Thread Insert Style Socketx G asketF IPT x SocketWith E lasmmer Seal- Use NO Thread5ealant M1� G1 � , � H1 M -- -+-- ` M2 � L I G G2 f+--H H2 �—L PartNumber Size G G1 G2 H H1 H2 L M Ml M2 Approx.Wt (Lbs.) 4203-122 G 1 xt 2x1 19/32 13/I 6 1-13/3"L 1-19l32 1-27/.i2 1-3/4 3-11/32 1-58 1-5� 1-38 25 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE Brass Thread Insert Style S ocket x F ipt x S ocket M1 —►I G1-� � � H1 M -�-- M2 -'= � �� G2 H H 2--► L —+ Part Number Size G G1 G2 H H1 H2 L M Mt MZ Approx.Wt (Lbs.) 4203-122 1 xl IZxI 23/32 3/4 1-1/4 1-58 1-58 1-15/I 6 3-1!L 1-23l32 1-23/32 1-3/I 6 25 Not intended to convey or dispense water for human consump6on through drinking or cooking SPRINKLER HEAD TEE Special Reinforced Plastic Thread Style SocketxSR FiptxSocket ~M��� � ? � � "j M - -�- M2 L � J H-�-� Part Number Size G G1 G2 H H1 H2 L M Mt M2 Approx.UVt. (Lbs.) 4203-1225 R 1 x12x1 27/32 23/32 1-3-"s2 1-23/32 1-SB 1-25/32 3-13/�2 1-3/4 1-3l4 1-3/I 6 'Ll 5 SPEARS�MANUFACTURING COMPANY � FIRE SPRINKLER PIPING PRODUCTS SPERBS FlameGuard cPVC � STREET TEE Spigotx Socketx Socket nm�- �-irr 0.[?. Hl I -----i---- i� j G G2 �—H —'.I.—H2—� -�— L - PartNumber Size G G1 G2 H H1 H2 � Mt M2 Approx.Wt (Lbs.) 4244-007 3/4 13A 6 271�2 27/32 1-13/I 6 1-78 1-78 3-5�8 1-13/32 1-13I32 16 4244-010 1 1-5I32 1-1/32 1-1/32 2-1 B 1-29/32 1-29/32 4-3/I 6 1-3/4 13/4 27 4244-012 1-1/4 1-1/4 1 1 2-7i16 2-9/32 2-9/�2 4-27132 2-3/32 2-3/32 .42 4244-015 1-12 1-13/I 6 1-1�$ 1-1 B 2-7� 2-9A 6 2-9/I 6 5-11�32 2-11/32 2-11!32 56 4244-020 2 1-23f32 1-7/I 6 1-13/32 3-1!4 2-15/I 6 2-15/I 6 6-5/�2 2-7� 2-7�8 84 9� ELBOW S ocket x S ocket G �--- H �I I I•—(�---►{ Part Number Size G H M Approx.Wt (Lbs.) 4206-007 3/4 9A 6 1-12 1-5lI 6 .O7 4206-010 1 3I4 1-58 1-58 11 4206-012 1-1/4 7/8 2-5/32 Z .21 4206-015 1-12 1-5l32 2-17/32 2-38 .41 4206-020 2 1-13/32 2-29/32 2-7 B 45 4206-025 2-12 1-58 3-7/I 6 3-7A 6 1.17 4206-030 3 1-29/�'L 3-23/32 4-3/I6 1.80 SIDE OUTLET ELBOW S ocket x S ocket x S ocket I � -- M � G �H Part Number Size G H M Approx.Wt (Lbs.) 4213-007 3/4 27/32 1-19l32 1-5/I 6 09 4213-010 1 13/I 6 1-78 1-5i$ 18 MADE IN THE U.S.A. 6 SPEARS ; FlameGuard� CPVC PIRE SPRINKLER PIPING PRODUCTS � REDUCING 9� ELBOW S ocketx S ocket Nt� G1 G � f" - M� H �I N--M� Part Number Size G G1 H H1 M Mt Approx.Vlh. (Lbs.) 4206-131 1 x3/4 25/32 11/16 1-25/32 1-25/32 1-19/32 1-5116 11 TorqueSafeT"' 9(p SPRINKLER HEAD ELBOW Gasket Sealed Brass Thread Insert Style Socketx G asketF IPT With E lasmmer Seal- Use NO Thread Sealant H1 G1 G � _ M1 1 � � H 1 � M Part Number Size G G1 H H1 M MI Approx.Wt (Lbs.) 4207-101 G 3/4x12 9ll 6 1-7/32 1-13/32 1-17/32 1-13/32 1-38 19 4207-130 G 1 x12 15/32 1-13/32 1-9/I 6 1-11/I 6 1-23/32 1-38 .23 4207-166 G t-1/4x12 15/32 1-19/32 1-15/I 6 1-11 A 6 2-3/32 1-3i$ .25 Notintended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD 9� ELBOW Brass Thread Insert Style SocketxFipt �� ��� G � � --- Ml � H I �I I� M � Part Number Size G G1 H H1 M Ml Approx.Wt (Lbs.) 4207-101 3J4x12 7A 6 1-5/32 1-23/32 1-17/32 1-13/32 1-17/32 25 4207-130 1 x12 15/32 1-58 1-9/I 6 1-11/I 6 1-23l32 1-17/32 28 A207-131 1 x3/4 17/32 1-114 1-21/32 2 1-23/.32 1-38 '1.5 4207-166 1-1/4x12 15/32 1-17i32 1-11/16 1-15A 6 2-3/32 1-17l32 .33 Not intended to convey or dispense water for human consumpUOn through drinking or cooking 7 SPEARS"MANUFACTURING COMPANY FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPERRS � SPRINKLER HEAD 9(� ELBOW Special Reinforced Plastic Thread Style S ocket x S R F ipt H1�G1 G � - ` Ml � + H � - �I I I-�M--►I Part Number Size G G1 H H1 M MI Approx.UVt (Lbs.) 4207-101 S R 3/4xl!2 11�32 13/I 6 1-15/32 1-12 1-13l32 1-3/I 6 .14 4207-1305 R 1 x1 CL 7/I 6 7B 1-9/I 6 1-58 1-23/32 1-38 20 4207-131 S R 1 x3/4 12 7i8 1-5�$ 1-9/I 6 1-23/32 1-38 16 4207-166S R 1-1/4x12 13/32 1-1/32 1-21/�2 1-23l32 2-3/32 1-7/32 .19 9(p STREET E�BOW S pigot x S ocket H1�G1 G � - M1 � � H � �.---.�- P IP E 0.D, Part Number Size G G1 H H1 M1 Approx.W�. (Lbs.) 4209-007 3/4 29/32 19/32 1-15/I 6 1-11 A 6 1-13/32 .12 4209-010 1 1 3/32 23/32 2-13/32 1-27/32 1-3/4 .21 4209-012 1-1/4 1-9lI 6 27/32 2-13lI 6 2-3/32 2-3/32 .32 4209-015 1-12 1 15132 1-3/I 6 2-27/32 2-9/I 6 2-11/32 .42 4209-020 2 1 '1.3C32 1-38 3-7/32 2-15/16 2-27/32 .65 MADE IN THE U.S.A. 8 SPEABS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS � 22-1I'Z' E L BOW S ocket x S ocket J 1 H I i (-�-M--►� Part Number Size H J M Approx.Wt (Lbs.) 4216-007 3/4 13116 7/32 1-13/32 .09 4216-Q10 1 1-38 9/32 1-25132 14 4216-012 1-1/4 1-12 5/I 6 2-3/�2 .20 4216-015 1-12 1-7/I 6 13/.32 1-3�$ .19 4216-020 2 1-7�$ 3B 2-27/32 43 4216-030 3 2-38 12 4-5/32 1.00 221l� STREET ELBOW S pigotx S ocket H1 �� � ��./ t H � I � �PIPE O.D. Part Number Size H H1 J J 1 Mt Approx.Wt (Lbs.) 4242-007 3/4 1-1/4 1-12 1/4 12 1-3i$ .08 4242-010 1 1-7/I 6 1-11/32 5/I 6 7/32 1-23/32 .14 42A2-Ol 2 1-1 l4 1-9/I 6 1-25/32 17/32 11/I 6 2-1 A 6 21 4242-Ot 5 1-12 1-13/32 1-23/�2 12 11/32 2-11/32 28 4242-020 2 1-29/32 2-1 B 7/32 5B 2-7i$ 42 4242-025 2-12 2-1 B 2-1/4 13/�2 12 3-1/L 68 4242-030 3 2-13/32 2-13/32 9/i 6 11/32 4-5/32 99 g SPEARS�MANUFACTURING COMPANY FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPE�RS y � a� E�BOw S ocket x S ocket J /, = I H I � I�—nn--�.l Part Number Size H 1 M Approx.Wt (Lbs.) 4217-007 3/4 1-5/I 6 5ll 6 1-5/I 6 07 4217-010 1 1-13/�2 3B 1-5�$ 11 4217-012 1-1/4 1-58 3B 2-5/32 21 4217-015 1-1,2 1-27/32 15/32 2-11/32 .32 4217-020 2 2-1 B 21/32 2-7�8 .48 4217-025 2-12 2-17/32 3/4 3-12 .B8 4217-030 3 Z-29/32 29/�2 4-5/32 1.17 4�i STREET ELBOW S pigot x S ocket H1�� J1 � � H � I J , � I• -�PtPE O.D. Part Number Size H H1 J J 1 Mi Approx.Wt. (Lbs.) 4227-010 1 1-12 1-5lI 6 1!2 1/4 1-5�8 .10 4227-012 1-1/4 1-25/32 1-9/I 6 9/I 6 11/�2 1-31/32 .15 4227-015 1-1/2 2 1/32 2-1 B 19/32 25/32 2-11/3Z .29 4227-020 2 2-`:/I 6 1-15/I 6 25/32 13/32 2-78 .44 MADE IN THE U.S.A. 10 , SPEARS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS � CROSS S ocket x S ocket x S ocket x S ocket G1� t � M - � � LIl � � H1 G H L PartNumber Size G G1 H H1 L L1 M Approx.Wt (Lbs.) 4220-007 3/4 5B 5,� 1-21 f32 1-21 32 3-5II 6 3-5lI 6 1-13/32 22 4220-010 1 3/4 'i,'9 1-58 1-58 3-1/4 3-1/4 1-23l32 .20 4220-012 1-1/4 1-1� 1-1 B 2-38 2-38 4-3/4 4-3/4 2-3/32 63 4220-015 1-12 1-7/32 1-i,32 2-58 2-5i8 5-7/32 5-7/32 2-3i$ 80 4220-020 2 1-12 1 12 3 3 6 6 3 1.43 A220-025 2-12 1-11li 6 1-11/I6 3J/I 6 3-7A 6 6-78 6-7� 3-17/32 2.16 4220-030 3 2-3i32 2-3,32 3-31/32 3-31/32 7-15/16 7-15/16 4-7/16 3.37 REDUCING CROSS S ocket x S ocket x S ocket x S ocket i---r� � � Hi M ---'-- L1 � � G1 � G� H L -� Part Num6er Size G G1 H H1 L L1 M Ml Approx.Wt (Lbs.) 4220-131 1 x3/4 23/32 5B 1-SB 1-58 3-1/4 3-1/4 1-78 1-12 31 4220-167 1-1/4x3/4 1-1/I 6 23/32 2-1/I 6 1-31/32 4-3/32 3-31/32 2-1/i 6 1-13/32 35 4220-210 1-12x3/4 11/I 6 1-5/32 23/32 2-3/I 6 4-3/I 6 4-11/32 2-38 1-13/32 42 4220-248 2x3/4 11/16 1-7A6 2J/32 2-7/16 4-13/32 4-78 2-29/32 1-13/32 56 4220-289 2-12x1 29/32 1-314 2-11/I 6 2-78 5-11/32 5-3/4 3-12 1-3/4 98 �� SPEARS°'MANUFACTURING COMPANY FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS � COUPLING S ocket x S ocket I --- --- M � F.-� I � Part Number Size L M N Approx.Wt (Lbs.) 4Z29-007 3/4 2-t B 1-5lI 6 3/I 6 .05 4229-010 1 2-3/I 6 1-58 3/32 O8 4229-012 1-1/4 2-19/32 2 3/32 .13 4229-015 1-12 Z-7B 2-11/32 3/32 .22 4229-020 2 3-1� 2-7� 1 B .33 4229-025 2-12 3-11/I 6 3-15/32 3/I 6 48 4229-030 3 4 4-3/16 1/4 .89 REDUCER COUPLING S ocket x S ocket � � M ---- --- Nil 1 -� _I. N L -� Part Number Size L M Mi N Approx.UVt. (Lbs.) 4229-131 1 x3/4 2-38 1-23/32 1-13/32 7/.32 10 4229-167 1-1/4x3/4 2-19/�2 2-3/32 1-58 11/32 .17 4229-168 1-1/4x1 2-11/I 6 2-3/32 1-23/32 5/16 .18 4229-210 1-12x3/4 2-13/I 6 2-11/32 1-13I32 15/32 .19 4229-211 1-12x1 2-7�$ 2-11/32 1-15/I 6 3�$ .24 4229-212 1-12x1-1/4 2-13/I 6 Z-13/32 2-1 B 5/32 23 4229-248 2x3/4 3-3/16 2-7�$ 1-7/I 6 23/32 32 4229-249 2x1 3-18 2-78 1-23I32 12 31 4229-250 Zx1-1%4 3-3/I 6 2-78 2-1 B 17/32 33 4229-251 2x1-12 3-3lI 6 2-27/32 2-11/32 9/32 .31 4229-291 2-12x1-1,2 3-23/�2 3-15/32 2-11/�2 21/32 51 4229-292 2-12x2 3-21/32 3-12 2-78 13/32 52 MADE IN THE U.S.A. �Z SPEARS FlameGuard� CPVC FIRE SPRINKLER PIPING PRODUCTS � GROOVED COUPLING ADAPTER G roove x S ocket � � PIPE ---- --- � O.D. �- 1 � L � Part Number Size L Mi N Approx.Wt (Lbs.) 4233-012 1-1/4 3-SB 2-3�32 2-11/32 .72 4233-015 1-12 3-3/4 2-11/�2 2-11/32 .83 AZ33-020 2 3-27/32 2-27/32 2-11l32 1.27 4233-025 2-12 4-3/16 3-15/32 2-7/16 2.02 4233-030 3 4-5/16 4-1� 1-7/I 6 2.76 FE M4LE ADAPTE R Brass Thread Insert Style S ocketx F ipt � M —- - M1 � I��� Part Number Size L M M1 N Approx.Wt (Lbs.) 4235-007 3/4 2 1-13/32 1-38 5/I 6 .23 4235-010 1 2-3/I 6 1-3l4 1-11/I 6 11/32 .25 4235-012 1-1/4 2-38 2-3/32 2-1/I 6 11/32 36 4235-015 1-1 i2 2-9/I 6 2-3�$ 2-7/I 6 11/32 47 4235-020 2 2-25/32 2-27/32 3-3/16 7/16 1.05 Notintended to convey or dispense water for human consumpUOn through drinking or cooking 13 SPEARS�MANUFACTURING COMPANY HANGERS AND SEISMIC BRACING , ���U�J P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 514 CPVC — COPPER �05 ` �os • 5TEEL i OFFSET HANGER ,Saoo 3�0 � l SIZE-SYSTENT PIPE: 3/4"thru 3" • MATERIAL-Carbon Steel. FINISH-Mil.Galvanized.. LISTING/APPROVAL- `OU=203-EX 4231,EX 2551 PATENT-No.6,648,278. FUNCTION- Support horizontal piping: 3/4"-3" CPVC or Copper. • Support horizontal piping: 3/4"-2" Steel. Size 3/4"-2"provides listed verticaUlateral restraint and prevcnts upward movement of pipe that supplies a pendent sprinkler below a ceiling. Stabilize vertical piping. INSTALLATION- Per these instructions includin NFPA 13, 13R 13D and CPVC manufacturers instructions. usted Resc�a�nt g , 314"thru 2" lnstall on horizontal or vertical mounting surface. Snap over pipe then squeeze strap back allowing pipe to slide freely. � � When #905 threads are exposed in wood, install#906 backing nut. FASTENERS-UL Listed per NFPA 13 WOOD- 3/4" -3" CPVC pipe-#905 screw-no pre-drill. 3/4"-2" Copper pipe- #905 screw- no pre-drilL 3/4"-2" Steel pipe- 1/4"xl 1/2" lag screw- no pre-drill. � � � Thni 5!8" gypsum board- 1/4"x 2"lag screw. �' STEEL-min. 18 GA. - 3/4"-3"CPVC pipe- 1/4" or#14 Tek Screw. ' � 3/4" -2"Co er i e- 1/4" or#14 Tek Screw. ' ��'� PP PP -� ', , 3/4" -2" Steel pipe- 1/4"or#14 Tek Screw. � ""� CONCRETE: Required minimum load eaeh fastener= S(tivt)+ZSOIbs. �;, �� FEATURES Z 1-�'��°� I * 1 1/2" Offset:loose fit allows pipe to slide. ��,� ,�� �ist d Restra�n� 3/4 and 1 p�pe size made with common center-line. ��y' sia^mru z�� *Patented design for superior strengtl�. * Offset edge eliminates abrasiou. *AFCON#905 screw included-5/16"hex head. ORDERING-Part#and pipe size. AFCON#906 backing nut sold separately. Specitic.4FCONproducts are excluaively designeJ to be compatible ONL�'�vith other.4FCONproducts including pahs und fnsteners,resulting in u lieled sway brace.�estrainer or haneer asszmbly. Be advised the loilowing wurranty resiriction will apply. DiSCI.;U�[ER-.4FCON will NOT w�Irant against the failure oP its products when used in combination with other products�ports or.y,tems not manufactured or sold hy AFCOIY..4FCON sha11?lOT be liabla�mder any circumstances whal.oever for uny direct or indirect,incidental or eonseyuential damages of any kind,including bw not limited tn loss of business or protit,w'hen non-.4FCOh'products huve h2en.nr are uved. �`� . �y _ ' v� �i � ,`�""4d, sa"'m�e. 1���� ...,..._ y U �D� P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 511 CPVC - COPPER SIDE MOUNT HANGER � - -i 0 I � __II O II o II II -_�_ Side Vie�v-For Drawings Bzlow � � SiZE-SYSTEM PiPE: 3/4"thru 2" MATERIAL-Carbon Steel. FINISH-Mil. Galvanized. LISTING/APPROVAL- `,��'203-EX 4231,EX 2551 FUNCTION- Support horizontal piping-CPVC ar Copper. Stabilize vertical piping. INSTALLATION-Per these instrucrions xan�er-wood sn�d including NFPA 13, 13R, 13D and CPVC manufacturers instiuctions. Install on vertical mounting surface. f FASTENERS-UL Listed per NFPA 13. in WOOD: 3/4"-2"CPVC pipe-#905 screw- no pre-drill. �� T�,� 3/4"-2"Copper pipe-#905 screw- no pre-drill. � in STEEL-min. 18 GA. 3/4"-2"CPVC pipe- 1/4"or#14 Tek Screw. `! 3/4"-2"Copper pipe- 1/4"or#14 Tek Screw. FEATURES i * Offset edge eliminates abrasion. �--� *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw included-5/16"hex head. ORDERING-Part#and pipe size. Hangzr-Metal Stud Specilic AFCONproducis are exclusively desi�,med to be computible ONCY with other.4FCONpruduct.including pans and fastenerc.res�lting in a listeJ sway brace,restrainer or hun,�er assembly. Be advised�he(ol lowing warranty restrictinn will apply. DISCI.AIVIF.ft-.AFCO�V will NOT wa`rant.�gains[the Cailure of its producis when used in combination with other products,p:�rts or.ry,tems not manufaemced or sold by AFCOIY..4FCON sliall VOT be liabla undz�any circumstauces wha�soever for any direct or indireet,incideutal or conseyuential damages ot any kind,including but not limired to loss of busine,s or pratit,wheu non>4FCON product.h:ive heen,or are used. , r`��°�� '� '�E" �`. � �� . 9/08 MISCELLANEOUS MATERIALS Y 1 I ' i � � � i � ' � , a , � � � � ' + . • � ' ' � � •The AGF Manufacturing, Inc. Mode18000l8011 �y����� � RESIDENTIAL RISERPACK� is a prepackaged eco nomical riser assembly designed for NFPA 13D and13R residential fire sprinkler systems. • The Model 8000/8011 complies with the NFPA 13D and 13R requirement regarding testing through a properly sized test orifice. 1" Model 8000/8011 are available to meet nominal K-factor requirements of 2.8 to 5.6. •The 1�/a", 1�/z" and 2" Model 8000/8011 are avail able with 3/s", '/�s", '/2", "/sz", and 5/a° (ELO) orifiCes ,. � �,. ; � to meet K-factors of 2.8 to 11.2. • Cast and machined of bronze in the U.S.A. � � :��; �� • Rise�PACK� is a one-piece casting, lettered on `��� _ both sides allowing right or left installation and � f providing required signage for flow direction, test and drain outlet, and gauge location. • NPT male threaded ends allow easy connection to popular plastic piping systems and are designed to fit within most standard stud wall framing. •The 1'h" and 2" RESIDENTIAL RISERPACK°s are also available with grooved or threaded x grooved ends °"� '''� for use with approved rubber gasketed couplings. ' - " " ' • Includes UL Listed/FM Approved AGF Model 7500 300-PSI Pressure Gauge.Those for 13R systems also include'/a" 3-way globe valve. • 1" Model 8000 utilize a 3/a" ball valve with patented TESTnNDRA1N�orifice specific outlet designed '• " '"' to accept either a standard garden hose or hard " • ' " " piped drain line. •The 1�/a", 1'/z" and 2" Model 8000 utilize the UL Listed/FM Approved patented AGF Model 3011 BV INSPECroR'sTEST`� ball valve. • Available as the Model 8011 with UL Listed/FM Approved Model 7000 Pressure Relief Valve (1'/a" —2") or Model 7200 Pressure Relief Valve (1") which is designed to provide relief, test, and drain through a single valve. ��� �� �� • Larger size risers available on special order. NOTE:It is important to note that the pressure rating of the relief valve indicates an operating range of pressure for both opening and ciosing of the valve. Standard relief valves are required to OPEN in a range of pressure between 90%and 105%of their rating.The valves are required to CLOSE at a pressure above 80°%of that rating.The relief valve should be instailed where it is easily accessible for maintenance.Care should be taken that the relief valve CAN- NOT be isolated from the system when the system is operational.A relief valve should NEVER have a shutoff vaive or a plug downstream of its outlet. � ' . • � • i � 1 1 r ! RISERPACK,TESTANDRAIN,and INSPECTORSTEST are registered trademarks of AGF Manufacturing Ina CS8000R 2/11 � . 1 1 ' i � � � i � � • , . , � � � / 1° MODEL SCIOO '�° MODEL SO�� 11�4° — `�c° MODEL$��� '���411 —��� MODEL +SO'I'� B 4 B B ��e� B a�°'"�`. g ,��� ti',, � �an��� '' e�c ti. s�p� A If�He� �!��;! /� m� \��tx� �,��' �.�act !z'�� 1 9 t'� ,m " yq 10 � \�� Y ,x � �eqY * � � 4 �4 � g 10 gu. �3 � q 7 j r. �:_:.o... .,.�.,. A 5 �i a A A �....�... R,i. � 'SS ^iT\ -= a �r 2 6 'aT g� � ~+• 3 �q s 5 5 f' �s 5 �� � = t � il 8� _ �—D 12 17 o h �� � _ — 11 16 — I 13� � I C C—'I--D I !—D—i—C^ C—I 15 DIMENSIONS COMPONENTS Model SIZE A B C D Item No. Part Qty. 1,� 10�/z" 12�/a" 43/a"* 61/a" 1 RiserPACK-Bronze Casting 1 (267 mm) (311 mm) (121 mmi (159 mm) � 3/a" Male x Female Ball Valve 1 ° 11" 12�/a"*" 4" 6�/z" o°0 1��4�� (vs mm� (st�mm� (�oz mm� (165 mm) 3 1° M3011 BV INSrECroR'sTEST ValV2 1 0 1�h„ 12�� 12��Z�� ** 4��8�� gs�s° 4 M7500 Pressure Gauge('/a"3-Way Globe 1 � (305 mm) �sn mmi (105 mm� (168 mm) Valve Included for 13R Systems Only) 2�� 12" 13" 43/a" 6�/s" 5 Water Flow Alarm Switch 1 (305 mm) (329 mm) (111 mm) (174 mm) 10�/z" 12�/a" 2�/s" "�* 6�/a" 6 3/4" MNPT x'/z" FNPT Hose Atlaptor Orifice 1 1�� (267 mm) �a7�mmi p3 mm� (159 mm) 7 M7200 3/4" Pressure Relief Valve 1 0 1��4,� 14�/a" 15" 4" 6�/z" 8 M7000 Y2" Pressure Relief Valve 1 ap (375 mm) (381 mm) (102 mm) (165 mm) 0 1��Z�� 15�/a" 15�/a" 4�/s" 65/a" � 1" Brass Nipple 1 � (387 mm) (ss�mm) (�os mmi (�sa mm) 10 1" Brass Street Elbow 1 2,� 15�/a" 153/a" 43/s" 6�/a" 11 �/2" Brass System Access Port Plug 1 (387 mm) (399 mm) (111 mm1 (V4 mm) 12 1" Relief Valve Bypass Nipple 1 'Additional space may be necessary to allow fcr hard drain fitting if required. 13 1" Relief Valve Bypass Tee 1 *'Valve handie clearance required — add 2". 14 '/z" NPT x-Bafb Straight Fitting 1 `"' Lift handle clearance required — add 3�/e". 15 '/z" NPT x�Barb Elbow Fitting 1 16 Clamps 2 /=��� 17 Nylobraid Relief Valve Drain Tubing 1 MADE IN U:S.�. � - . � . . AGF Manufacturing Inc. Job Name: 100 Quaker Lane,Malvern, PA 19355 , Phone:610-240-4900 AI'CIlIt2Ct: Fax:610-240-4906 Engineer: www.testandrain.com Contractor: HYDRAULIC CALCULATIONS N ONLY FO a0�0G�e Cert//kf�lp • ` � * � �t i ��0 J 'r. ir �i nw' ' s . +��a � �,� ��io`Rb De��`i�� a ���� � - F� _�` ii���,�� '�: �i ti���k �'. JOb NUmb@�:CR04 i p �� Re ort Descri tion:Residential ��w�w.�����I'�I��:',� ��-�y,�r`����mW� i s;��,a`x��� n;- ��������`,:�+x.�r�,a.���N���`�i����h��l-�'z���������ai'���iu. iI� .�r� p� =��` � iN'"id�� _-� . �'i�s�'ut`'�'��. �y Job Number Desgn Ergineer CR04 Job Name'. � Ph°^° FAX Creek Road Mixed Use Address 1 � SWte Certifiqtbnlliceme Numbet 106th Avenue SE and Creek Street UNLIMM1096M6 Atltl�ex 2 � AHJ Yelm,WA 98597 City of Yelm Atltlreu 7 JoC S�eiBUiltling Building E `�,. h �iii " � " �. � a .=yi� �.��.. 216 =wF � '� �.�I�.Vii�i�� 4 �k,`�' "'� ,�,� �?� ��: ���",M;`,C�F4�' — �d���"�7�i�ry4p j���7u � �-_.��"��+��,�i�i} 35,� - `s�"`�i,•, � _'��,N7'r y-'�,.��i�� i.i `'�F��""a���;� t��", �-��3t���e�" ' ti.�-u� i ,... _. . - - ,..�, � . � a _ , . .- �p��iN Aree alApplkaHOn 0.050gpmlft' 367.00ft'(Actual 367.28ft� AAOSI DameMirg Sprinkk�Oala Hose Sireams 4.9 K-Factor 12.96 at 7.000 100.00 Coverega Per Spnnklar Number Of Sprinkkrs CakWatetl 256.�Oft� 4 System Pressure Demartl � System Fbw Demand 44.537 54.41 To�al Oemantl Precsure Rewlt 154.41 @ 44.537 +5.016(10.1%) � s � 3"�I k '�`��,t*.`3� ��& !��(i = — � �3�°, - �- `�a ` i r �& '-�._�, �" ��� �� ,r,�tr,.' j'�� �"'d'�� r. P� =w' h1�F ,�,`*;�p iv� — -�°�:�n,i! �r�'.��. '.,��r�;e �T���, i i I ,�3`,� -°-���I�i�^�� 4 fl Node Name Flow(apml Hose Flow(qpml Static si Residual(psil Identifier Pressure(osil K-Factor(Kl Flow(ppm) 100 Water Supply 1500.00 100.00 50.000 20.000 i F' ���i������w . ' �� i.�,.° �' �U �N�Ct�tl'tQ�M` �'�.0�`1�'��: 5t��IE#�`2t1 ��i'��i������G°�fis°:'°` `Y� ���"�.��by�"�Inh��'�� � � �'�. ' , I i: � P�di" � ��� w. _� } � i 100 90 i. .i ��•, 80 4 — — v. �a �a � _ _ r �e •� 1• a� 70 — — � � — — — — — — — — — -- — — — — _ 60 �N a �' S0 Static Pressure 50.000 �.o o� ��° i--' —; � �`•: ..o o . N 4.41 �44.537 — — P ';�O:P �J a �1 N � , ,� � qQ 154.4*1 with hose streams •` '' �'' '• a ( I\ I � ��.� ' , , ' �.'• • • • • • • • • • • gp System demand curve 20 1500.00�20.000 �� � ; � 10 0 �q3001200 1500 1 S00 2�00 2�� 2700 3000 Water flow,gpm �,O M.E.P.CAD,Inc. 6;��AutoSPRINK�1 VR'0 v10.0.59.0 S116/2013 8:32:50PM Page 1 . � ���� �' �� ���� �����T �. �, � � � � � t�����F �� Job Number.CR04 Re ort Descri tion:Residential to"� " �h�.,�— � '�.�� .'� `� i i n_ na: i ' �'�`"'r�i�i�i i i � ��- �, : y s ,�g;- ^! - r �..� -�� �°'�r°��•'�, .���G f� �, � �. �.� ,��,,��u� � � ��� ,�-��,��p��"�nM�� E., ,n, ���� �� � � �� Job Number oesre�e�e�M�r CR04 Job Name: Sbte CMifimtiaNLkeiwa Number Creek Road Mixed Use UNLIMM1096M6 Atltlrescl � AHJ 106th Avenue SE and Creek Street City of Yelm Atltlress 2 Job S�elBUlltllig Yelm,WA 98597 Building E Atldress J Dravnng Name Yelm Creek Building E2 '��N"��'� i&.'i i i�i��� a" — _;� IN�' �i in)�°�- _ � � .:� .�.0 - � `���)i� �.�-��� �s:,5��n. �� ,..t�,�,._�''`.�,��. �ta�i, r r'��=� 41a�.G�I) i d (�(i II� �.a.t��, . ���d�u i I 1E`� ,�-` MoN DemaMing 3prinkler Data Occupanry JoC Sullx 4.9 K-Factor 12.96 at 7.000 Residential HouAYovranceAtSOU�ce �ensily AreaalApplkaM1On � 100.00 0.050gpm/ft� 367.00ft2(Actual 367.28ft') Atltlilional Hoae Suppliea Numbe�OlSpnnklen CalcuhteE Coverage Per Sprinkbr Node Flow(qpm) 4 256.00ft' AutoPeak Resulb'.Pressure Fa�Remo�e A2a(s)AOjacent To hlos[Ramote Area Left:44.537 ToUI Hoa S�roams �Q�.�Q System Fbw�emantl Totnl VJdter Requirttl(Inclutlmg Hose Apowance) 54.41 154.41 Maximum Preacure Unbaprce In Loops Q.�O� hlaximum Vebcily Abave GrouiW � 11.44 between nodes 99 and 111 Mezimum Vebdty UMet Gmuik � � 5.54 between nodes 100 and 99 Volume dpacM of�Akt Pipes Volume wpacRy o�Dry Pipes 161.73ga1 �� 4 ��V��'��,��I��i��dll ' �� a : II����� i i�il�z-; iFF�:` ;�"�Fi�I° ��'„`'I��I���� �I N�tuw m4a, F�'�?����w •�-.�`=�i"�m?�y�i,��.�,�=diir'�. i�� (I) 'si 9�ih ir,r � - !�w,�i :.�r Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name m si si � m si � m si si 100 Water Su I 100.00 50.000 20.000 1500.00 49.553 154.41 44.537 5.016 ' �i9i p�i wiip � � ��` � I � ' , ! . 5� .dt k� <a�"aiN, ( . �fi�Gter� . sio ����i����i� � °a �� r ��. �, '�, �N6����� i�,���, ,n�l��`�si�i.er 6'��rl� rig(�iui��i�iN�ii�i��i��i s� ��'.� � ���' r _ .. . coMr.�ar N�moar com.a N.m: co�m�ruo 22 Name of CaMrac�or: PMne Ex�empn UMI Fire Protection Adtlress 1 � FAX PO BOx 1457 AEErass 2 � Eanail Marysville,WA 98270 nao�ess a —-� �o-sa� �,O M.E.P.CAD,Inc. r,��AutoSPRINK�VR10 v10.0.59.0 5/16/2013 832:54PM Page 2 . . ���� �„ _ �� i�,�� �'°� ����: Job Number.CR04 Report Description:Residential Actual Flow Minimum Flow K-Factor Pressure Device m m K si �3 S rinkler 101 12.96 72.80 4.9 7.000 Sprinkler 102 13.79 _ 12.80 4.9 7.920 Sprinkler 105 13.70 _ 12.80 4.9 7.813 Sprinkler 106 13.95 _ 12.80 4.9 8.111 � Most Demanding Sprinkler Data /� OO M.E.P.CAD,Inc. +�AutoSPRINK�VR10 v10.0.59.0 5116/2013 8:32:57PM Page 3 , � Il��� , .,5--.� .y�. ;9 r %i� "`x�_ �i���i;�,�,. �},,� �§ d i Job Number:CR04 � ��� =� ��� ���'�,�,. � w: Report Description:Residential Node Elevation Foot Fittin s Pressure si Dischar e m 100 -5'-0 S 44.537 54.41 101 26'-0 Spr-7.000 7.000 12.96 102 26'-0 S r�_7.920 7.920 13.79 105 26'-0 S rS-7.813 7.813 13.70 106 26'-0 S r�_8.111 8.111 13.95 gg 3'-6 BFP(-5.738 38.043 103 26'-6 T 5'-0 7•891 104 26'-6 T 5'-0 9•�57 107 26'-6 T 5'-0 8.086 108 26'-6 C 5'-0 9.046 109 17'-6 T(6'-0 16.534 110 17'-6 T 6'-0 17.844 111 8'-6 T 6'-0 22.930 �,O M.E.P.CAD,Inc. a;�AutoSPRINK�VR'0 v10.0.59.0 5I16I2013 8:33:OOPM Page 4 . , � ���� i Tm .a . � '` �� ����,.�,���� �� Job Number:CR04 Report Description:Residential Pi e T e Diameter Flow Veloci HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary U stream Total Len th �•••••Route1• BL •• 1.1010 12.96 _4,37 150 0.030510 8'-3'/, Pf 1.108 101 26'-0 12.96 4.9 7.000 Sprinkler 28'-0 Pe -0.217 103 26'-6 7.891 4E(7'-0) 36'-3'/. Pv BL 1.1010 26.75 9.02 150 0.116555 5'-0 Pf 1.166 103 26'-6 13.79 7.891 Flow(q)from Route 3 5'-0 Pe 104 26'-6 9.057 T(5'-0) 10'-0 Pv BL 1.3940 30.28 6,37 150 0.046454 99'-2 Pf 4.885 t04 26'-6 3.53 9.057 Flow(q)from Route 2 6'-0 Pe 3.902 110 17'-6 17.844 T(6'-0) 105'-2 Pv BL 1.3940 40.34 8.48 150 0.078953 9'-0 Pf 1.184 110 17'-6 10.05 17.844 Flow(q)from Route 5 6'-0 Pe 3.902 111 8'-6 22.930 T(6'-0) 15'-0 Pv BL 1.3940 54.41 11.44 150 0.137323 27'-6 Pf 12.946 111 S'-6 22.930 25'-0 Pe 2.168 99 3'-6 38.043 3E(8'-0),cplg(1'-0),BFP(-5.738j 52'-6 Pv UG 2.0030 54.41 5.54 150 0.023503 108'-6 pf 2.809 99 3'-6 38.043 11'-0 Pe 3.685 100 -5'-0 44.537 E(11'-O),S 119'-6 Pv 100.00 Hose Allowance At Source 100 154.41 �•••••Route 2••••• BL 1.1010 13.70 4.62 150 0.033775 9'-6 Pf 0.490 105 26'-0 13.70 4.9 7.813 Sprinkler 5'-0 Pe -0.217 107 26'-6 8.086 T(5'-0) 14'-6 Pv BL 1.1010 27.65 9.32 150 0.123890 2'-9 Pf 0.960 107 26'-6 13.95 8.086 Flow(q)from Route 4 5'-0 Pe ias Zs�-s s.oas c�s-o� ��-s P� BL 1.3940 3.53 0.74 150 0.000871 12'-0 Pf 0.010 108 26'-6 9.046 Pe 104 26'-6 9.057 12'-0 Pv �•••••Route3••••• BL 1.1010 13.79 4.65 150 0.034201 0'-6 Pf 0.188 102 26'-0 13.79 4.9 7.920 Sprinkler 5'-0 Pe -0.217 103 26'-6 7.891 T(5'-0) 5'-6 Pv �•••••Route4••••• BL 1.1010 13.95 4.70 150 0.034962 0'-6 Pf 0.192 106 26'-0 13.95 4.9 8.111 Sprinkler 5'-0 Pe -0.217 107 26'-6 8.086 T(5'-0) 5'-6 Pv �•••••Route5••••• BL 1.3940 10.05 2.11 150 0.006042 204'-9 Pf 1.310 109 17'-6 24.12 16.534 T(6'-0),Flow(q)from Route 7 12'-0 Pe 110 17'-6 17.844 T(6'-0) 216'-9 Pv �•••••Route6••••• BL 1.3940 14.07 2.96 150 0.011247 213'-9 Pf 2.494 109 17'-6 24.12 16.534 Flow(q)from Route 7 8'-0 Pe 3.902 111 8'-6 22.930 E(8'-0) 221'-9 Pv +�•••••Route7••••• BL 1.3940 24.12 5.07 150 0.030499 111'-7 Pf 3.586 108 26'-6 9.046 6'-0 Pe 3.902 109 17'-6 16.534 T(6'-0) 117'-7 Pv �1N8�13� �iw�hi � ����I�" iCikt�'r=.�t.� s, _: .. _ � �, . � Actual Inside Diameter 4 87 Value Of C 100 130 140 150 � Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 �M, �O M.E.P.CAD,Ina �;�AutoSPRINK�VR i 0 v10.0.59.0 5116/2013 833:04PM Page 5 � a ` ���� ��� �� � `�"�� ` a '�" � Job Number.CR04 ��� � ���� °�� �������� ��� � Report Description:Residential Pi e T e Diameter Flow Veloci HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary U tream Total Len th :�` s� -- � ���' `� � � �y�; �'� i�,�� . � iiii {€ i"���IIq�1���tYt��,'dfli�PY �� �'-'`ii����°-�d�i�����! ��[� ,a�k�?�'� _` ��F��, , . 4 . �.. �r �. . ..«i. en ..:,< °.?. ...µn P!. : .�.t.,rr e . .. ..- . AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BaIV Ball Valve DR Drop Velocity fps BFP Backflow Preventer DY Dynamic Pressure psi BV Butterfly Valve FM Feed Main Length Foot C Cross Flow Turn 90° FR Feed Riser Friction Loss psi/Foot cplg Coupling MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run OR Outrigger pt Total pressure at a point in a pipe CV Check Valve RN Riser Nipple p� Normal pressure at a point in a pipe DeIV Deluge Valve SP Sprig pf Pressure loss due to friction between points DPV Dry Pipe Valve ST Stand Pipe Pe Pressure due to elevation difference beriveen indicated points E 90°Elbow UG Underground p� Velocity pressure at a point in a pipe EE 45°Elbow Eel 11'/<°EIbOw Ee2 22%z Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node ff FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap �O M.E.P.CAD,Ina ',�;��AutoSPRINK�VR10 v10.0.59.0 5116/2013 833:04PM Page 6