20140164 MECH-SUM2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3
2012 Washinqton State Enerqy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
R2 and R3
Revised June 2013
Project Info
Project Address Olympia Federal Savings Yelm
Date 6/3/2013
Corner of Yelm Ave. & Tahoma Blvd.
For Building Dept. Use
Applicant Name: Sunset Air, Inc.
Applicant Address: 5210 Lacey BLVD SE, Lacey WA 98503
Applicant Phone: 360 - 456 -4956
Project Description
Briefly describe mechanical
system type and features.
Includes Plans
New geothermal heatpump system including 5 indoor heat pumps, 1 ground loop, 1
exhaust and outdoor air heat exchanger, 1 exhaust fan.
Drawings must contain notes requiring compliance with commissioning provisions per Section C408
Compliance Option
• Simple System Complex System Systems Analysis
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on
the plans. For projects without plans, fill in the required information below.
Coolin g Equipment
Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Capacity2
Btu /h
OSA CFM
or Econo?
SEER
or EER
IPLV3
Econmizer
Option or
Exception 6
Heat
Recovery
Y/N
See M1.0
Heatin g Equipment
Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Capacity2
Btu /h
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency4
Heat
Recovery
Y/N
See M1.0
Fan Equipment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
CFM
SP'
HP /BHP
Flow Controls
Location of Service
Service Water
Heating Equipment
Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Input
Capacity
Sub -
Category
EF7
Location of Service
See M1.0
1 If available. 2 As tested according to Table C403.2.3(1)A thru C403.2.3(8). 3 If required. 4 COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. 5 Flow control types: variable air volume (VAV), constant volume (CV), or variable speed (VS). 6 Economizer exception number per
Project Address Olympia Federal Savings Yelm Date 6/3/2013
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH -CHK pages.
Applicability
Code Section
Code Provision
Information Required
Location on
Building Department
(yes,no,na)
Plans
Notes
GENERAL PROVISIONS
Equipment Sizing & Performance
Yes
C403.2.1
Load calculations
Load calculations performed per ASHRAE Std 183 or equivalent per
M 1.0
Chapter 3
Yes
C403.2.2
Equipment and system
Output capacity of heating and cooling equipment and systems do not
M1.0
sizing
exceed calculated loads note exceptions taken
Yes
C403.2.5
Minimum ventilation
Ventilation (natural or mechanical) provided per IMC, indicate mechanical
M 1.0
ventilation is capable of being reduced to minimum requirement per IMC
C4032.3 &
minimum
Provide equipment schedules or complete MECH -SUM tables with type,
Yes
0403.2.3.2 &Equipment
efficiency
capacity, efficiency, test standard (or other efficiency source) for all
M 1.0
C4032.12.1
mechanical equipment
Yes
0403.2.13
Electric motor efficiency
Provide equipment schedule with hp, rpm, efficiency for all motors, note
M1.0
except-
Yes
C403.2.10
Fan power limitation
Fan system motor hp or bhp does not exceed limits per Table
M 1.0
C403.2.10.1 1
Yes
04032. 10.3
Fractional h fan motors
p
Indicate fan motors 1/12 to 1 hp are ECM type or meet minimum efficiency
M 1.0
& C403.2.13
re q.
N/A
0403.2.3
Maximum air cooled chiller
Indicate air - cooled chiller capacity does not exceed air - cooled chiller limit
ca acit
N/A
0403.2.1
Non - standard water - cooled
Full -load and NPLV values for water - cooled centrifugal chiller adjusted for
chillers
non - standard operational conditions
N/A
0403.2.12.1 _
Centrifugal fan cooling
Large capacity cooling towers with centrifugal fan(s) meet efficiency
towers
requirements for axial fan open circuit cooling towers
N/A
C403.2.3
Forted air furnace and unit
Indicate intermittent ignition or 1113, flue /draft damper & jacket loss
Yes
C403.2.3.3
Packaged electric
List equipment required to be heat pumps on schedule
M 1.0
heatin /coolin a ui ment
N/A
C403.2.3.4
Humidification
Indicate method of humidification (note requirements for systems with
economizer
HVAC System Controls & Criteria
Yes
C403.2.4.1
Thermostatic controls
Indicate locations of thermostatic control zones on plans, including
M 1.0
perimeter s stems
C4032.4.1.1
Heat pump supplementary
Indicate staged heating (compression /supplemental) & outdoor lockout
Yes
heat
temp
M 1.0
Yes
C403.2.4.2
Setpoint overlap (deadband)
Indicate 5 °F deadband minimum for systems controlling both heating &
M 1.0
cooling
Yes
C403.2.4.3
Automatic setback and
Indicate zone t -stat controls with required automatic setback & manual
M 1.0
shutdown
override
Yes
C4032.4.3.3
Automatic (optimum) start
Indicate system controls that adjust equip start time to match load
M 1.0
conditions
0402.4.5.2 &
Dampers
Indicate location of OSA, exhaust, relief and return air dampers, include
M 1.0
Yes
C403.2.4.4
AMCA rated leakage and control a motorized or ravi note
N/A
C403.2.11
Heating outside a building
Indicate radiant heat system and occupancy controls
N/A
C403.2.4.5
Snow melt systems
Indicate shut -off controls based on outdoor conditions
N/A
C403.2.4.6
Combustion heating
Indicate modulating or staged control
equipment
N/A
C403.2.4.7
Group R1 hotel /motel
Indicate method for guest room automatic setback & set -up of 5 °F minimum
s stems
N/A
C403.2.4.8 / E
Group R2/R3 dwelling unit
Indicate 5 -2 programmable thermostats in primary spaces with minimum of
systems
two setback periods; note exceptions taken
N/A
C403.2.5.1
Demand controlled
Indicate high- occupancy spaces and systems requiring DCV
ventilation
N/A
C403.2.5.2
Occupancy sensors
Indicate spaces requiring occupancy -based system control and method, or
alternate means provided to automatically reduce OSA when partially
C403.2.5.3
Enclosed loading
dock/parking garage
Indicate enclosed loading dock and enclosed parking garage ventilation
N / A
ventilation
system activation and control method
N/A
C4032.5.4.1
Kitchen exhaust hoods
Indicate kitchen hoods requiring make -up air; indicate make -up air source
and conditioning method
Indicate lab exhaust systems requiring heat recovery, method & efficiency,
N/A
C4032.5.4.2
Laboratory exhaust systems
or alternative method taken (VAV, semi - conditioned makeup, or CERM
calculation
C403.2.6.1
Energy recovery -
Indicate ventilation systems requiring ER, method & efficiency, note
Yes
ventilation systems
exceptions
M 1.0
N/A
C403.2.6.2
Energy recovery -
condensates stems
Indicate on -site steam heating systems requiring energy recovery
N/A
C403.2.6.3
Energy recovery -
Indicate remote refrig. condensers requiring ER and use of captured energy
condensers stems
Mechanical Permit Plans Checklist - Page 2 of
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Address Olympia Federal Savings Yelm Date 6/3/2013
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH -CHK pages.
Applicability
Code Section
Code Provision
Information Required
Location on
Building Department
(yes,no,na)
Plans
Notes
GENERAL PROVISIONS, CONTINUED
HVAC System Controls & Criteria, Continued
Yes
0:403.2.12
Variable flow control -
Indicate fan & pump motors requiring VF control & method (VSD or equiv
M 1.0
fans/ um Ds
controls
N/A
C4032.12.1
Variable flow control -
Indicate cooling tower fans requiring variable flow control and method
cooling towers
N/A
04032.12.2
Large volume fan systems
Indicate fan systems requiring airflow reduction based on heating and
cooling demand; or exception taken
C4032.12.2
Single zone AC systems
Indicate method of cooling demand -based fan control for sys. > 110,000
N/A
btuh
Yes
C4032.4.10
DDC system capabilities
Identify all DDC system input/output control points and indicate capability
M 1.0
for trendina and demand response set point ad ustment
Ducting Systems
Yes
0403.2.7.1 &
Duct construction
Indicate all ductwork constructed and sealed per IMC, C402 leakage
M 1.0
C403.2.7.3
requirements and IBC vapor retarder requirements
Yes
403.2.7.3.1-
Duct pressure classifications
Identify location of low, medium and high pressure ductwork on plans
M 1.0
C4032.7.3.3
High pressure duct leakage
Indicate high pressure duct leakage testing requirements on plans; provide
Yes
test
test results to jurisdiction when completed
M 1.0
Yes
0:403.2.7.1 /
Duct insulation
Indicate R -value of insulation on ductwork
M 1.0
Piping Systems
Yes
C403.2.8
Piping insulation
Indicate R -value of insulation on piping
M 1.0
N/A
C403.2.8.1
Piping insulation exposed to
Indicate method of protection from damage /degredation
weather
SIMPLE SYSTEMS
Qualifying Systems
Yes
0403.3
Qualifying single zone
Verify unitary or packaged equipment does not exceed capacity limits, does
M1.0
systems
not have active humidifcation or simultaneous heating/cooling
N/A
0403.3
Qualifying 2 -pipe heating
Verify 2 -pipe heating -only system does not exceed capacity limits
s stems
Yes
C403.3.2
Hydronic system controls
Refer to Complex Systems Section C403.4.3
M 1.0
Simple System Economizers
N/A
C403.3.1
Air economizer required
Indicate cooling systems requiring economizer controls, note in equip
sched.
N/A
C403.3.1.1.1
Air economizer capacity
Indicate modulating OSA control capability up to 100% OSA, or exception
N/A
C403.3.1.1.3
Air economizer high limit
Indicate high limit shut -off control method per Table C403.3.1.1.3(2)
controls
N/A
C403.1.12
Integrated air economizer
Indicate capability for partial air economizer operation for systems with
o eration
Icapacity > 65,000 btuh
N/A
C403.3.1
Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with
exce tion s
COMPLEX SYSTEMS
Complex System Economizers
C403.4.1
Air economizer required
Indicate cooling systems requiring economizer controls, note in equip
N/A
sched.
C403.4.1.4
Economizer heating system
Verify control method of HVAC systems with economizers does not
N/A
impact
increase building heating energy usage during normal operation
N/A
C403.4.1.3
Integrated economizer
Indicate capability for partial economizer operation for air or water econo
operation
systems
Moved
Water economizer capacity
Indicate water econo capable of 100% cooling capacity at 50 °F db /45 °F wb
N/A
OSA
C403.4.1.2
Water economizer
Indicate precooling coils and heat exchangers do not exceed pressure drop
N/A
maximum pressure drop
limit
N/A
C403.3.1
Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with
exce tion s
Mechanical Permit Plans Checklist - Page 3 of
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Address Olympia Federal Savings Yelm Date 6/3/2013
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH -CHK pages.
Applicability
Code Section
Code Provision
Information Required
Location on
Building Department
(yes,no,na)
Plans
Notes
COMPLEX SYSTEMS, CONTINUED
Specific System Requirements
N/AC403.4.2
/
&
C403.2.12
Variable flow control - fans
Indicate fans requiring variable flow control and method
N/A
C403.4.2.1
VAV fan static pressure
Indicate sensor locations on plans, include at least one sensor per major
sensors
duct branch
C403.4.22
VAV fan static pressure
Indicate fan system static pressure setpoint based on zone requiring most
N/A
setpoint
pressure
VAV systems serving multi-
Indicate supply air systems serving multiple zones that are required to be
C403.4.5
VAV, method of primary air control, and zones served, note exceptions
N/A
zones
taken
N/A
C403.4.5.4
VAV system supply air reset
Indicate controls that automatically reset supply air temp in response to
loads
N/A
C403.4
Large capacity cooling
Indicate method of multi -stage or variable control for building cooling
s stems
system capacity > 300 tons
N/A
C403.4.7
Hot gas bypass limitation
Indicate cooling equipment unloading or capacity modulation method
N/A
C403.4.3
Large capacity boiler
Indicate multi -stage or modulating burner for single boilers > 500,000 btuh
systems
N/A
C403.4.3
Boiler sequencing
Indicate automatic controls that sequence operation of multiple boilers
N/A
C403.4.3.5
Chiller / boiler plant pump
Indicate capability to automatically reduce overall plant flow and shut -off
isolation
flow through chillers & boilers when not in use
N/A
C403.4.2 &
Variable flow control -
Indicate pumps requiring variable flow control & method
C403.4.3.6
pumps
N/A
C4032.12.1
Variable flow control -
Indicate cooling tower fans requiring variable flow control and method
& C403.4.4
cooling towers
N/A
C403.4.34
.
Hydronic system part load
automatically reset supply water temp AND reduce flow by ? 50% for
controls
N/A
C403.4.32
Two -pipe changeover
Indicate deadband, heating /cooling mode scheduling and changeover
systems
temperature range
N/A
C403.4.3.3.1
Water loop heat pump -
Indicate capability of central equipment to provide min. 20 °F water supply
deadband
temp, deadband between heat re ection and heat addition modes
N /A
C403.4.3.3
Water loop heat pump -
Provide heat exchanger that separates cooling tower and heat pump loop in
heat re ection
Climate Zone 5
N/A
C403.4.3.3.3
Water loop heat pump -
Indicate 2 -way isolation valve on each heat pump and variable flow control
isolation
fors stems with total pump power > 10 h
N/A
C403.4.6
Condenser water heat
Indicate system provided to pre -heat service water and efficiency
recovery
N /A
C403.5
Cooler / freezer - anti -sweat
Indicate w /sf & control method for walk -in cooler /freezer door anti -sweat
heaters
heaters
N/A
C403.5 / 6
Cooler / freezer - evaporator
land
Indicate motor type for evaporator and condenser fans < 1 hp
SERVICE WATER HEATING
Service Water Systems
YES
C404.2
Water- heating equip min.
Provide equipment schedule or complete MECH -SUM table with type,
P -1
efficiency
capacity, efficiency, test standard or other efficiency source
YES
C404.3
Temperature controls
Indicate temperature controls have required setpoint capability
P -1
N/A
C404.4
Heat traps
Indicate piping connected to equipment have heat traps on supply &
discharge
YES
C404.5
Insulation underwater
Indicate R -10 insulation under tank
P -1
heater
YES
C404.6
Service water piping
Indicate R -value of insulation on piping, note exceptions taken
P -1
insulation
C404.7 / g
Circulation systems and
Indicate shut -off capability based on occupancy and periods of limited
YES
heat trace shut -off
demand
P -1
N/A
C404.9
Group R -2 service hot water
Indicate method of usage metering for dwell. units served by central HW
meters
System
Pools & In- Ground Permanently Installed Spas
Pool heating equip min.
Provide equipment schedule or complete MECH -SUM table with type,
N/A
C404.10.1
efficiency
capacity, efficiency, test standard (or other eff. source), heat pump heaters
4 COP
N/A
C404.10.1 / 2
Pool heater on / off controls
Indicate automatic on /off control based on scheduling & accessible on /off
switch on heater that operates independent of thermostat setting, or
N/A
C404.10.3
Pool covers
Indicate vapor retardant cover and insulation rating as required
N/A
C404.10.3
Pool assembly insulation
Indicate rating of insulation on sides and bottom of pools heated to > 90 °F
I N/A
C404.10.4
Heat recovery
Indicate method, exhaust air temperature reduction and recovered energy
use