Loading...
20140164 Mech Sys Design ReportAir System Sizing Summary for WSHPs Project Name: Oly Fed Yelm 05/21/2014 Prepared by: Sunset Air Inc 12:33PM Air System Information - - - - -4 Air System Name --------------------------- -WSHPs ft2 Equipment Class - -- --- - - - - -- TERM Air System Type ----------------------------- - - WSHP Sizing Calculation Information Individual peak space loads Calculation Months _ ____ Jan to Dec BHP Sizing Data - - - - - -- - - - - -- Calculated kW Ventilation Fan Sizing Data - - - 0.00 in wg Actual max CFM - - -- ----- - - - - -- -631 CFM Standard CFM - - - -- ------ - - - - -- 626 CFM Actual max CFM /ft2 - - - - - - - - - - - - 0.11 CFM /ft2 Outdoor Ventilation Air Data Design airflow CFM 631 CFM CFM /ft2 0.11 CFM /ft2 Number of zones ---------------------------------- - - - - -4 Floor Area - - - - 5805.0 ft2 Location ________________________ Olympia, Washington Zone CFM Sizing ----------- Sum of space airflow rates Space CFM Sizing ________ Individual peak space loads Fan motor BHP --0.00 BHP Fan motor kW 0.00 kW Fan static - - - - - - - 0.00 in wg CFM /person 11.17 CFM /person Hourly Analysis Program v4.80 Page 1 of 3 Zone Sizing Summary for WSHPs Project Name: Oly Fed Yelm 05/21/2014 Prepared by: Sunset Air Inc 12:33PM Air System Information Maximum Cooling Sensible (MBH) Design Airflow (CFM) Air System Name ____________________________ WSHPs Number of zones Equipment Class - -- --- - - - - -- TERM Floor Area ---- - AirSystemType ----------------------------- - - WSHP Location --- - - - - -- Sizing Calculation Information 18.1 1323.0 Calculation Months _ ____ Jan to Dec Zone CFM Sizing Sizing Data Calculated Space CFM Sizing Zone Sizing Data --------------- - - - - -- 4 5805.0 ft2 Olympia, Washington Sum of space airflow rates Individual peak space loads Zone Name Maximum Cooling Sensible (MBH) Design Airflow (CFM) Minimum Airflow (CFM) Time of Peak Load Maximum Heating Load (MBH) Zone Floor Area (ftz) Zone CFM /ftz Zone 1 23.8 1167 1167 Jul 1600 18.1 1323.0 0.88 Zone 2 27.01 13261 13261 Aug 15001 15.21 1764.0 0.75 Zone 3 24.01 11771 11771 Jul 16001 13.01 1680.01 0.70 Zone 4 14.51 7151 7151 Jun 15001 12.81 1038.01 0.69 Terminal Unit Sizing Data - Cooling Zone Name Total Coil Load (MBH) Sens Coil Load (MBH) Coil Entering DB / WB ( °F) Coil Leaving DB / WB ( °F) Water Flow @ 10.0 IF (gpm) Time of Peak Load Zone 1 30.8 27.3 76.8/62.9 55.0/53.7 Fan Jun 1500 Zone 2 35.1 31.1 76.8/63.0 55.0/53.7 Flow Aug 1500 Zone 3 31.3 27.4 76.7/63.11 55.0/53.7 DB Jun 1500 Zone 4 19.5 16.9 77.1 /63.21 55.0/53.7 (MBH) Jun 1500 Terminal Unit Sizing Data - Heating, Fan, Ventilation Space Loads and Airflows Zone Name / Space Name Mult. Heating Htg Coil Air Flow (CFM) Heating Load (MBH) Floor Area (ftz) Space CFM /ftz Zone 1 Heating Coil Water Fan OA Vent 1 Community Room Coil Ent /Lvg Flow Design Fan Fan Design 2 Leased Area Load DB @20.0 IF Airflow Motor Motor Airflow Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM) Zone 1 20.2 67.1 /83.21 Aug 1500 11671 0.2591 0.2051 171 Zone 2 17.4 67.6/79.9 - 1326 0.294 0.233 168 Zone 3 15.2 67.5/79.5 Jul 1600 1177 0.261 0.207 160 Zone 4 14.2 66.2/84.7 715 0.159 0.126 132 Space Loads and Airflows Zone Name / Space Name Mult. Cooling Sensible (MBH) Time of Load Air Flow (CFM) Heating Load (MBH) Floor Area (ftz) Space CFM /ftz Zone 1 1 Community Room 1 10.2 Jul 1600 500 7.2 435.0 1.15 2 Leased Area 1 13.6 Jul 1600 6661 10.9 888.0 0.75 Zone 2 3 Open Office 1 27.0 Aug 1500 1326 15.2 1764.0 0.75 Zone 3 6 Teller Work Area 1 24.0 Jul 1600 1177 13.0 1680.0 0.70 Zone 4 4 Conference Room 1 5.3 Jun 1500 2601 4.2 192.0 1.35 5 Back Office 1 9.3 Jun 1600 4551 8.7 846.0 0.54 Hourly Analysis Program v4.80 Page 2 of 3 Air System Design Load Summary for WSHPs Project Name: Oly Fed Yelm 05/21/2014 Prepared by: Sunset Air Inc 12:33PM Hourly Analysis Program v4.80 Page 3 of 3 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1500 COOLING OA DB / WB 87.0 °F / 67.0 °F HEATING DATA AT DES HTG HEATING OA DB / WB 18.0 °F / 14.8 °F ZONE LOADS Details Sensible (BTU /hr) Latent (BTU /hr) Details Sensible (BTU /hr) Latent (BTU /hr) Window & Skylight Solar Loads 1005 ft2 20619 1005 ft2 - Wall Transmission 4404 ft2 9055 4404 ft2 12367 Roof Transmission 6023 ft2 10847 6023 ft2 10678 Window Transmission 1005 ft2 2985 1005 ft2 18291 Skylight Transmission 0 ft2 0 0 ft2 0 Door Loads 21 ft2 107 21 ft2 655 Floor Transmission 5805 ft2 0 5805 ft2 7294 Partitions 0 ft2 0 0 ft2 0 Ceiling 0 ft2 0 0 ft2 0 Overhead Lighting 5805 W 16103 0 0 Task Lighting 0 W 0 0 0 Electric Equipment 1083 W 3695 0 0 - People 56 9823 9875 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous 0 0 - 0 0 Safety Factor 20%/20% 14647 1975 20% 9857 0 >> Total Zone Loads 87880 11850 - 59142 0 Zone Conditioning - 97539 11850 - 57574 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 0 0 Plenum Lighting Load 0% 0 0 0 Exhaust Fan Load 631 CFM 0 - 631 CFM 0 - Ventilation Load 631 CFM 2661 1630 631 CFM 12123 0 Ventilation Fan Load 631 CFM 0 - 631 CFM 0 - Space Fan Coil Fans - 2633 -2633 Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 102833 13481 - 67064 0 Terminal Unit Cooling 102833 13463 0 0 Terminal Unit Heating 0 - 67045 - >> Total Conditioning 1028331 13463 670451 0 Key: Positive values are clg loads Negative values are htg loads Positive values are htg loads Negative values are clg loads Hourly Analysis Program v4.80 Page 3 of 3