20140209 Permit Pkg 07242014 .� ���
�oF t�E,,�, City of Yelm
Permit ►vo.: 20140209
�� �� Community Development Department Issue Date: 7/24/2014
6 �� (Work must be completed within 180 days)
Building Division
Phone: (360)458-8407
YELM rp„
Fax: (360)458-3144
Applicant:
Phone: 360-458-2090
Name: KEY BANK
Address: PO BOX 574
YELM WA 98597
Property Information:
site Address: 1100 YELM AVE E Owner: KEY CORP
Assessor Parcel No.: 22730121700
Subdivision: Lot:
Contractor Information:
Name: KEY BANK
Phone:
Address: D FLETCHER
PO BOX 574
YELM WA 98597
Contractor License No.: Expires: 0/00/0000
Project Information:
Project: FIRE ALARM
Description of Work: INSTALL FIRE ALARM SYSTEM
Sq. Ft. per floor: Heat Type (Electric,Gas, Other):
First
Second
Third
Garage
Basement
Fees: Fees
Item Contractor $ 206.66
FIRE ALARM KEY BANK
TOTAL FEES: $ 206.66
Applicant's Affidavit: OFFICIAL USE ONLY
I ceRify that I have read and examined the information contained within the application and know the same
to be true and correct. I also certify that the proposed structure is in conformity with all applicable City of #Sets of Prints:
Yelm regulations including those governing zoning and land subdivision,and in addition,all covenants,
easements and restrictions of record. If applying as a contractor,I further certify that I am currently Final Inspection:
registered in the State of Washin on. Date:
Date
Signature gy.
Firm
Cit� af Y�lm
(36 ) 458-8407
REC#: OQ167129 7/24/2014 9:21 AM
OPER: CO T'ERM: 001
REF#:
TRAN: 30,OU00 BU�INESS LICENSE
APPLTED TECHNICAL SYSTEMS
BUSINESS LICENSES & 35.00CR
TRAN: 33.0000 BUILDING PERMITS
2014Q209 206.66CR
KFY BANK
11Q0 YELM AVE E
Fp 206.66CR
TENQERE�: 241 .66 OTHER
APPLIEG: 241 .66-
�..__.._.._____--
CHANGE: 0.00
'`N�" Applied Technical Systems�N�
S
800 456 9657 Pete Malone,Rcoo
206 575 1546 Regional Manager
fax:206 575 1547 pmaloneC�3atsdata.com
www.atsdata.com 2063910316direct
ccea a9s t� l3/CS/"
�� ,,�, = �.�� �� H�� �.� ,o�,
� , �" ��.r , u � .�
Ju121 1407:36a Doug Comouche
206-575-1547 P�4
Ct'T'Y OF YELM � `�1 � D��--L"�
CQMMERCIAL BUtLDi�IG PERMIT APPLtCATfON dRM
Pro;ect Address: l'�'�� _.�"�� �P� ��✓P • Pa�cel#:
Zoning: CuRentEJse: ��Qn � Proposed se:.
U New Consin�ction U Re-Madei 1 Re-Roo#!Tenan�Improvement
U Plumbing U Mechanical �'Fise PreventJSuppr+esslAlarm Qther
Project DescripiioM ope of Work: �/ ���" ' �� � r'�
P€oject Value: �
Su'sldir�g Area(sq.ft) Parking Garage 1�'Floor�2n0 F1oor 3rd F{oor
Suilding Height �J�
Are there any es�vironmentally sensitive areas Iocated on ihe Aarcel? !f yes,a
completed environmental check�ist musi accompa�y permit applicaiion.
BUILDING OWiJER/TENANT NAME: � a EMAIL
ADDRESS
CE-ry STATE Z1P �ELEPH�NE
ARCHtTECTJENGINEER LI�ENSE#
ADDR�SS E����'
C�N SjA-�E Z{p TELERHUNt_,_.
GENERAL C�ISTRACT�R ���PH���
ADDRESS �����'
CiTY STATE Z1P F�
CONTRAC7�R'S�lCENSE# EXP DATE,�,CtTY LiCE SE#
PLUMBIhiG CONTRACTOR TELEPHONE
ADDRESS Et�AAIL
GtTY STATE ZIP FAX
C�NTRACTOR'S�ICENSE# EXP D�4TE C1T(LICE SE#
MECHA(�ElCAL CONTRACTOR TELEPH�htE
ADDRESS ����
CiTY STATE ZlP �AX
CONTRACTOR'S LICENSE# EXP DATE C�TY LICE S�#
Copy ot Clty Mkigatlon doeumentation{TFC�_
above�d sc�d p pertY wN�be/n a��°d nce wNh the lawstrules and retg�atfons of th State f�Nas�ngto and lhe
City ot Ye4m_ �
���:, 7�r �
,�'"�/ .�i�-�" Qa e
Applic`anYs Signature
Owner 1 Contractor!Owner's Agent 1 Coniractor's Ageni!Tenant {P�e se circle one-)
All pesrn"tts are nan-transferable and v+ri{t expire if wo�k author'szed by s ch permit is not begun
witf��n 180 days of issuance,or if work is suspended vr abandoned for period of 180 da�►s
(3b0)458-3835
I05 Yetm Aoenue West (360)d58-3Jd9FA.1
PO Bos 479 ���w.ci.yelm.u�a.us
2"etm, WA 98597
' • , DF-52384:C•E-160
SD355(A) Series � F��•1.1Te�ALc�C'1'Y1S
Addressable Photoelectric by Honeywell
Smoke Detectors
.
General � ���� ��
The SD355(A), SD355T(A), and SD355R(A)addressable, low- � � � � ����
profile plug-in photoelectric detectors use a state-of-the-art pha � �� �, � � ������ �
toelectric sensing chamber with communications to provide � � � � �
open area protection and are used exclusively with Fire•Lite's ,\ ��� ��
Addressable Fire Alarm Control Panels (FACPs). The � � � � � ���y���� �`
SD355T(A)adds thermal sensors that will alarm at a fixed tem- ��,�� ��.� ����g�
perature of 135°F (57°C). Since these detectors are address- . ���--, -
able, they will help emergency personnel quickly locate a fire � �
during its early stages, potentially saving precious rescue time
while also reducing property damage. Two LEDs on each sen-
sor light to provide a local, visible sensor indication. Remote �
LED annunciator capability is available as an optional acces-
sory, PN RA100Z(A). The SD355R(A)is a remote test capable o
detector for use with D355PL(A)or DNR(A)/DNRW duct smoke SD355(A) in 6210LP(A) Base m
detector housings.
Features
s�c ioop Applications
• Two-wire loop connection. Use photoelectric detectors in life-safety applications to provide
• Unit uses base for wiring. a broad range of fire-sensing capability,especially where smol-
Addressing dering fires are anticipated. lonization detectors are often better
than photoelectric detectors at sensing fast,flaming fires.
• Addressable by device.
• Rotary, decimal addressing: 01 – 99 with MS-9200 series, Construction
and 01 –159 with MS-9600 series.
Architecture These detectors are constructed of off-white fire resistant plas-
Unique single-source, dual-chamber design to respond tic. SD355(A) series plug-in, low-profile smoke detectors are
• quickly and dependably to a broad range of fires. designed to commercial standards and offer an attractive
appearance.
• Sleek,low-profile design.
• Integral communications and built-in type identification. �nstallation
• Built-in tamper-resistant feature.
Removable cover and insect-resistant screen for simple field SD355(A) series plug-in detectors use a detachable mountmg
• base to simplify installation,service and maintenance.
cleaning.
Mount base(all base types)on an electrical backbox which is at
Operation least 1.5" (3.81 cm) deep. For a chart of compatible junction
• Withstands air velocities up to 4,000 feet-per-minute (20 m! boxes,see DF-60059.
sec.)without triggering a false alarm. NOTE:Because of the inherent supervision provided by the SLC
• Factory preset at 1.5% nominal sensitivity for panel alarm loop, end-of-line resistors are not required. Wiring 'T-taps" or
threshold level. branches are permitted for Style 4 (Class 8) wiring. SD355R(A)
• Visible LED"blinks"when the unit is addressed(communicat- mounts in a D355PL(A)or DNR(A)/DNRW duct detector housing.
ing with the fire panel)and Iatches on in alarm.
Mechanicals Operation
• Sealed against back pressure. Each SD355(A) series detector uses one of 99 possible
• Direct surface mounting or electrical box mounting. addresses on the MS-9200 series and up to 318(159 on each
• Mounts to:single-gang box,3.5"(8.89 cm)or 4.0"(10.16 cm) loop) on the MS-9600 series Signaling Line Circuit (SLC). It
octagonal box,or 4.0"(10.16 cm)square electrical box(using responds to regular polls from the system and reports its type
a plaster ring—included). and status.
Other system features The addressable photoelectric sensor in the SD355(A) series
Fully coated circuit boards and superior RF/transient protec- has a unique unipolar chamberthat responds quickly and uni-
' formly to a broad range of smoke conditions. It can withstand
tion. wind gusts up to 4,000 feet-per-minute (20 m/sec.) without
• 94-VO plastic flammability rating. sending an alarm level signal. Because of its unipolar chamber,
• Low standby current. the SD355(A) series is approximately two times more respon-
Options sive than most photoelectric sensors.This makes it a more sta-
• Remote LED output connection, PN RA100Z(A). ble detector.
DF-52384:C•12/07/2011—Page 1 of 2
_ �
Detector Sensitivity Test INTELLIGENT BASES
Each detector can have its sensitivity tested(required per NFPA
NOTE:"A"suffix indicates ULC Listed model.
72, Chapter 14 on Inspection, Testing and Maintenance) when NOT ationsaFor detai s'Uabou�intellige�bases and the�r mount!
installed/connected to a MS-9200 series or MS-9600 series app
addressable fire alarm control panel.The results of the sensitiv- ing,see DF-60059.
ity test can be printed off the MS-9200 series or MS-9600 series B2�OLP(A): Plug-in detector base (included); standard U.S.
for record keeping. flanged low-profile mounting base.
B210LPBP:Bulk pack of 6210LP;package contains 10.
Specification B501(A):Standard European flangeless mounting base.
Voltage range: 15-32 VDC(peak). B501 BP:Bulk pack of B501;package contains 10.
Standby current:300 NA @ 24 VDC. B200SR(A): Intelligent sounder base capable of producing
LED current:6.5 mA� 24 VDC(latched"ON"). sound output with ANSI Temporal 3 or continuous tone.
Air velocity:4,000 ft./min.(20 m/sec.)maximum. Replaces 6501 BH series bases in retrofit applications.
Size:2.1"(5.33 cm)high;base determines diameter. 6224R6(A): Plug-in System Sensor relay base. Screw termi-
nals: up to 14 AWG(2.0 mm2). Relay type: Form-C. Rating:2.0
-B210LP(A):6.1"(15.5 cm)diameter. A@ 30 VDC resistive;0.3 A � 110 VDC inductive; 1.0 A � 30
-6501(A):4.1"(10.4 cm)diameter. VDC inductive.
-B200SR(A):6.875"(17.46 cm)diameter. g224B1(A): Plug-in System Sensor isolator detector base.
-6224RB(A):6.2"(15.748 cm)diameter. Maximum 25 devices between isolator bases(see DF-52389).
Weight:3.6 oz.(102 g). ACCESSORIES
Operating temperature range: for SD355(A): 0°C to 49°C F110: Retrofit flange to convert B210LP(A) to match the
(32°F to 120°F); for SD355T(A):0°C to 38°C (32°F to 100°F). g350LP(A)profile,or to convert older high-profile bases to low-
SD355R(A):installed in a DNR(A)/DNRW-20°C to 70°C (-4°F profile.
to 158°F). F1108P:Bulk pack of F110;package contains 15.
Temperature:0°C-49°C(32°F-120°F). F210:Replacement flange for 6210LP(A)base.
Relative humidity:10°/a-93%,non-condensing. RA100Z(A):Remote LED annunciator.3-32 VDC.Mounts to a
U.S. single-gang electrical box. For use with 6501(A) and
Listings B210LP(A)bases only.
Listings and approvals below apply to the SD355(A), SMB600:Surface mounting kit
SD355T(A),and SD355RT(A)detectors. In some cases,certain M02-04-OO:Test magnet.
modules may not be listed by certain approval agencies,or list- M02-09-00:Test magnet with telescoping handle.
ing may be in process.Consult factory for latest listing status.
XR2B: Detector removal tool.Allows installation and/or removal
• UL Listed:S1059. of detector heads from bases in high ceiling applications.
• ULC Listed:S1059. XP-4:Extension pole for XR26.Comes in three 5-foot(1.524 m)
• CSFM:7272-0075:0194. sections.
• MEA:243-02-E. T55-127-010:Detector removal tool without pole.
• FM approved. BCK-200B: Black detector covers for use with SD355(A) only;
box of 10.
Product Line Information WCK-2006:White detector covers for use with SD355(A)only;
NOTE:"A"suffix indicates ULC Listed model. box of 10.
SD355: Adressable photoelectric detector; 6210LP base
included.
SD355A: Sames as SD355 with ULC Listing; B210LPA base
included.
SD355T: Same as SD355 but with thermal element; B210LP
base included.
SD355TA: Same as SD355T with ULC Listing; B210LPA base
included.
SD355R:Remote test capable addressable photoelectric detec-
tor for use with a D355PL(A) or DNRA/DNRW duct detector
housing; B210LP base included.
SD355RA: Same as SD355R with ULC Listing for use with a
D355PLA of DNRA duCt deteCtor hOUSing; B210LPA blse Fire�Litc�Alarms is a registered trademark of Honeywell International Inc.
i11CIUd2d. �011 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is stricUy prohibited.
I�O �oo� This document is not intended to be used for installation purposes.
We try to k2ep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
9YiINEHINC 8 MAIYIFRCTIRIIY& All specifications are subject to change without notice. Made in the U.S.A.
QUALITY S9STEMS
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2-DF-52384:C•12/07/2011
` SD355(A), SD355T(A)� df-52384:b•E-160
SD355R(A) � FII'�•LITE�A�arms
Addressable Photoelectric by Honeywell
Smoke Detectors
0
General �w� � � �= a � � �� ��
The SD355(A)and SD355T(A)addressable, low-profile plug- �
in photoelectric detectors use a state-of-the-art photoelectric t, '°° � ��` '
sensing chamber with communications to provide open area
protection and are used exclusively with Fire•Lite's Address- �����
able Fire Alarm Control Panels(FACPs).The SD355T(A)adds
thermal sensors that will alarm at a fixed temperature of 135°F
(57°C). Since these detectors are addressable, they will help ��
emergency personnel quickly locate a fire during its early
stages, potentially saving precious rescue time while also
reducing property damage. Two LEDs on each sensor light to
provide a local,visible sensor indication. Remote LED annun-
ciator capability is available as an optional accessory (P/N
RA100Z(A)). The SD355R is a remote test capable detector SD355 with B350LP base
for use with D355PL or DNR(W) duct smoke detector hous-
ings.
�FO�a� :
Features ' �� �� ��� `
,��
SLC loop:
�>.
• Two-wire loop connection. �'�'��
• Unit uses base for wiring.
�' �
Addressing: ,����
• Addressable by device.
• Direct Decade entry of address: 01 – 99 with MS-9200
series,and 01 –159 with MS-9600 series.
Architecture:
• Unique single-source, dual-chamber design to respond SD355T with 6350LP base
quickly and dependably to a broad range of fires.
• Sleek,low-profile design.
A lications
• Integral communications and built-in type identification. pP
• Built-in tamper-resistant feature. Use photoelectric detectors in life-safety applications to pro-
Removable cover and insect-resistant screen for simple vide a broad range of fire-sensing capability,especially where
• field cleaning. smoldering fires are anticipated. lonization detectors are often
better than photoelectric detectors at sensing fast, flaming
Operation: fires.
• Withstands air velocities up to 4,000 feet-per-minute(20 m/
sec.)without triggering a false alarm. COnstruction
• Factory preset at 1.5% nominal sensitivity for panel alarm These detectors are constructed of off-white LEXAN�.
threshold level. SD355(T)plug-in,low-profile smoke detectors are designed to
• Visible LED"blinks"when the unit is addressed(communi- commercial standards and offer an attractive appearance.
cating with the fire panel)and latches on in alarm.
Mechanicals: Installation
• Sealed against back pressure. SD355(Tj plug-in detectors use a detachable mounting base
• Direct surface mounting or electrical box mounting. to simplify installation, service and maintenance. Mount base
• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 on box which is at least 1.5 inches (3.81 cm) deep. Suitable
cm)octagonal box,or 4.0"(10.16 cm)square electrical box boxes include:
(using a plaster ring—included). • 4.0"(10.16 cm)square box with plaster ring.
Other system features: • 4.0"(10.16 cm)octagonal box.
• Fully coated circuit boards and superior RF/transient pro- • 3.5"(8.89 cm)octagonal box.
tection. • Single-gang box.
• 94-VO plastic flammability rating. NOTE:Because of the inherent supervision provided by the SLC
• Low standby current. loop, end-of-line resistors are not required. Wiring `T-taps" or
O tions: branches are permitted for Style 4 (Class 8) wiring. SD355R
P mounts in a D355PL or DNR(W)duct detector housing.
• Remote LED output connection(P/N RA100Z).
df-52384:b•3/12/10—Page 1 of 2
r.
Operation Product Line Information
Each SD355/T/R uses one of 99 possible addresses on the NOTE:'A"suffix indicates ULC-Listed model.
MS-9200 series and up to 318(159 on each loop)on the MS- SD355: Adressable photoelectric detector; 6350LP base
9600 series Signaling Line Circuit(SLC).It responds to regular included.
polls from the system and reports its type and status.
SD355A: Sames as SD355 with ULC Listing (B350LPA base
The SD355fr/R addressable photoelectric sensor's unique included).
unipolar chamber responds quickly and uniformly to a broad SD355T: Same as SD355 but with thermal element; 6350LP
range of smoke conditions and can withstand wind gusts up to base included.
4,000 feet-per-minute (20 m/sec.) without sending an alarm
level signal. Because of its unipolar chamber, the SD355R/R SD355TA: Same as SD355T with ULC Listing(6350LPA base
is approximately two times more responsive than most photo- included).
electric sensors.This makes it a more stable detector. SD355R: Remote test capable addressable photoelectric
detector for use with a D355PL or DNR(W)duct detector hous-
Detector Sensitivity Test i�g.
Each detector can have its sensitivity tested (required per 6350LP(A): Plug-in detector base. Dimensions: 6.1" (15.5
NFPA 72,Chapter 14 on Inspection, Testing and Maintenance) cm). Mounting: 4.0" (10.16 cm) square box with or without
when installed/connected to a MS-9200 series or MS-9600 plaster ring, 4.0" (10.16 cm) octagonal box, 3.5" (8.89 cm)
series addressable fire alarm control panel.The results of the octagonal box,or single-gang box. All mounting boxes have a
sensitivity test can be printed off the MS-9200 series or MS- minimum depth of 1.5"(3.81 cm).
9600 series for record keeping. 8224RB(A): Plug-in System Sensor relay detector base.
Diameter:6.2"(15.75 cm). Mounting:4.0"(10.16 cm)square
Specification box with or without plaster ring,4.0" (10.16 cm)octagonal box,
Voltage range: 15-32 VDC(peak). or 3.5" (8.89 cm) octagonal box. All mounting boxes have a
minimum depth of 1.5"(3.81 cm).
Standby current:300 NA(� 24 VDC.
622461(A): Plug-in System Sensor isolator detector base.
LED current:6.5 mA @ 24 VDC(latched"ON"). Maximum 25 devices between isolator bases(see DF-52389).
Air velocity:4,000 ft./min.(20 m/sec.)maximum. Diameter:6.2"(15.75 cm). Mounting:4.0"(10.16 cm)square
Diameter:6.1"(15.5 cm)installed in B350LP base. box with or without plaster ring,4.0"(10.16 cm)octagonal box,
or 3.5" (8.89 cm) octagonal box. All mounting boxes have a
Height:2.1"(5.33 cm)installed in 6350LP base. minimum depth of 1.5"(3.81 cm).
Weight:3.6 oz.(102 g). B200SR: Sounder base capable of producing temporal-3 or
Operating temperature range: for SD355(A): 0°C to 49°C steady sound output.
(32°F to 120°F); for SD355T(A):0°C to 38°C (32°F to 100°F). qCCESSORIES:
SD355R(A): installed in a DNR(W) -20°C to 70°C (-4°F to
158�F� RA100Z(A): Remote LED annunciator.3-32 VDC. Mounts to
Tem erature:0°C-49°C(32°F-120°F). a U.S. single-gang electrical box. For use with 6501(A) and
P B350LP(A)bases only.
Relative humidity: 10%-93°/a,non-condensing. SMK400E: Surface mounting kit provides for entry of surface
wiring conduit. For use with 8501(A)base only.
Listings RMK400: Recessed mounting kit. For use with 6501(A)base
Listings and approvals below apply to the SD355(A) and only.
SD355T(A) detectors. In some cases, certain modules may M02-04-OO:Test magnet.
not be listed by certain approval agencies,or listing may be in
process.Consult factory for latest listing status. M02-09-00:Test magnet with telescoping handle.
• UL Listed,file S1059. XR2B:Detector removal tool.Allows installation and/or removal
• ULC Listed,file S1059. of detector heads from bases in high ceiling applications.
• CSFM approved:file 7272-0075:194. XP-4: Extension pole for XR26. Comes in three 5-foot(1.524
MEA approved:file 243-02-E. m)sections.
• FM approved. T55-127-010:Detector removal tool without pole.
BCK-200B:Black detector covers,box of 10.
WCK-200B:White detector covers,box of 10.
FlashScanO registered trademark of Honeywell International Inc. Bay-
blendCrsl is a registered trademark of Bayer Corporation.
002010 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
I�O �oo� This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
EN6I�EEIINC 8 MANIFlICIDtlNi All specifications are subject to change without notice.
QUALITY SYSTEMS
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2-df-52384:b•3/12/10
DF-60536:B1
4
Duct Smoke Detector �� �ry�.��T�rtALd�`I'"r11�
Accessories `'��-'`
by I�oneywell
General
Duct smoke detector accessories add functionality to the duct
smoke system by allowing quick, convenient inspections at eye _ _�
level and effective audible and visual notification options. All °
System Sensor duct smoke detectors and accessories are UL ������,�; �
listed.
� � � � � (
Specifications � > �`�'� � � � � �'�'
� '� ��s
APA151 PIEZO ANNUNCIATOR ��,a
The APA151 piezo annunciator, which replaces the APA451 �,
with a new, improved look, provides an audible alarm signal, a
�:�
red LED to indicate alarm status, and a green LED to indicate �'� `� 3:
power status. It is intended for use with System Sensor 4-wire ; �'
conventional duct smoke detector applications without a system � ` `
control panel,to comply with NFPA 90A. r ... ..., �-. ��"'�"'�' �` '-°-------
i �'
� �-�:
��� �s. E
3
>
� �. ,„ o
U
�S,;>,.:: .,y� M
) ln
O
�
E
�
�'v��; � 3 MHR/MHW SpectrAlert Advance Mini-Horns
�
� Regulated 12 DC or FWR(Full
¢ Voltage Wave Rectified)or Regulated
�" ' � �� �� 24 VDC or FWR
APA151 Piezo Annunciator Operating Voltage 8 to 33 VDC(9 to 33 VDC with
Sync-Circuit Module)
Voltage Regulated 24 VDC 22 mA RMS max.at 8 to 17.5
Operating Voltage 16 to 33 VDC Volts DC
17 mA RMS max.at 8 to 17.5
Maximum Alarm Current 30 mA Volts FWR
Temperature Range 32°F to 120°F(0°C to 49°C) Sounder Current Draw 2g mA RMS max.at 16 to 33
Volts DC
Relative Humidity 10 to 93%,non-condensing 25 mA RMS max.at 16 to 33
Wire Gauge 12 to 18 AWG Volts FWR
Dimensions 4.6"H x 2.9"W x.45"D Temperature Range 32°F to 120°F(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
MHR/MHW MINI-HORNS Nominal Sounder Frequency 3 kHz
The MHR and MHW SpectrAlertC�Advance mini-horns feature �re Gauge 12 to 18 AWG
temporal or continuous tones at high and low volume settings.
Their small footprint allows mounting to single-gang back Dimensions 4.6"H x 2.9"W x 0.45"D
boxes for applications where a small device is desired.
���. -..
�
� �
�
� � �
� _
�
E
3
� �..�. l:i =
�
DF-60536:B1•1/27l12—Page 1 of 4
RA100LRA100ZA REMOTE ANNUNCIATORS RTS151 KEY Remote Test Station with Key
The RA100Z and RA100ZA remote annunciators are designed
for both conventional and intelligent applications.Their red LED Power LED(Green):14 to 35
provides visual indication of an alarm condition. power Requirements VDC,12 mA max.
Alarm LED(RED):2.8 to 32
VDC,12 mA max.
Alarm Response Time 40 seconds max.
Temperature Range 14°F to 140°F(-10°C to 60°C)
�
� ; Relative Humidity 95%non-condensing
� 1[ Wire Gauge 14 to 18 AWG
Dimensions 4.6"H x 2.75W x 1.8"D
e Y� ��" 3 RTS2/RTS-AOS MULTI-SIGNALLING ACCESSORIES
N
�?;;� o The RTS2 and RTS2-AOS multi-signaling accessories are
� "%,� `�r%t=' """ � designed to work with InnovairFlex 4-wire conventional duct
smoke detectors. These accessories include a key switch that
can be used to select one of two connected sensors to be
RA100ZIRA100ZA Remote Annunciator tested, reset,or both by a push button switch.They also enable
Conventional System:3.1 to 32 sensitiv�ty measurements using the SENS-RDR sensitivity
reader (sold separately). The AOS (Add-On Strobe) is an
Voltage Range nDCigent System:18 to 32 optional accessory included with the RTS2-AOS model.
VDC
Maximum Alarm Current 10 mA ��� � '
Dimensions 4.6"H x 2.8"W x 1.3"D � ��'��� � ` ;
RTS151/RTS151 KEY REMOTE TEST STATIONS �
��.tia�� � �`��� "' � �
The RTS151 and RTS151 KEY remote test stations are auto �"`��� -�
matic fire detector accessories designed to test duct smoke � �� � �F �� �� �'
;� �� o
detectors from a convenient location. For 4-wire detectors, the '� ?
RTS151 KEY test station features a multi-colored LED that alter- �' 3
nates between steady green and red. For 2-wire detectors, the �;
LED illuminates red for alarm. °¢
�«� � �
. „ �w ���� ¢
- -----� RTS2 and RTS-AOS Multi-signaling Accessory
� � � Voltage 20 to 29 VDC
E
��,�� � 3 Standby:3.0 mA max.
�, , �.:� w
Y Trouble:16.0 mA max.
', ,�, Power Requirements Alarm without Strobe:30 mA
�, max.
; ,�y,���� � Alarm with Strobe:55 mA max.
�^ � Sounder 85 dBA at 10 ft.
3
��,��, � Temperature Range 14°F to 140°F(-10°C to 60°C)
,%��;
� I Relative liumidity 95%non-condensing
Wire Gauge 14 to 22 AWG
RTS151 Remote Test Station Dimensions 4.8"W x 5.3"H x 1.6"D
Alarm LED 2.8 to 32 VDC,10
Power Requirements mA max.
Total Current:95 mA max.
Test Switch 10 VA @ 32 VDC
Reset Switch 10 VA @ 32 VDC
Alarm Response Time 40 seconds max.
Temperature Range 14°F to 140°F(-10°C to 60°C)
Relative Humidity 95%non-condensing
Wire Gauge 14 to 18 AWG
Dimensions 4.8"H x 2.9W x 1.4"D
Page 2 of 4—DF-60536:81•1l27/12
_
,Product Line Information Agency Listings and Approvals
APA151:Piezo Annunciator The listings and approvals below apply to the basic products. In
MHR:Mini-Horn,Red some cases, certain modules may not be listed by certain
approval agencies,or listing may be in process.Consult factory
MHW:Mini-Horn,White for latest listing status.
RA100Z/RA100ZA: Remote Annunciator • UL: S4011 (APA 151, MHR, MHW), S2522 (RTS2,
RTS151: Remote Test Station RA100Z,RTS151,RTS151 KEY,RTS2-AOS)
RTS151 KEY:Remote Test Station with Key • FM Approved
RTS2:Multi-signaling Accessory • CSFM:7135-1653:0212
AOS:Add-On Strobe
RTS2-AOS: Multi-Signaling Accessory
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0—
49°C/32—120°F and at a relative humidity 93%t 2%RH
(noncondensing)at 32°C t 2°C(90°F t 3°F). However,the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15—27°C/60—80°F.
DF-60536:B1•1/27/12—Page 3 of 4
� DF-52121:C•E-325
MMF-300(A) Series, . ��•�fTe�A�arms
. �
MDF 300(A) by Honeywel)
Addressable Mon�tor Modules
,
General
� ,,. �ry:
Four different monitor modules are available for Fire•Lite's ����������� >;»�� ,� ��
intelligent control panels to suit a variety of applications. Moni- \
tor modules are used to supervise a circuit of dry-contact input � � � ��.
devices,such as conventional heat detectors and pull stations, �� �� ` � � ���
or monitor and power a circuit of two-wire smoke detectors � R�� �• � ��.
(MMF-302(A)). �� �, ,E �.
MMF-300(A)is a standard-sized module(typically mounts to a � �
4" [10.16 cm] square box) that supervises either a Style D , „ 94f ,
(Class A) or Style B (Class B) circuit of dry-contact input M.
devices. �� �a, ��_.�
MMF-301(A)is a miniature monitor module a mere 1.3"(3.302 '
cm)H x 2J5"(6.985 cm)W x 0.5"(1.270 cm)D used to super- � � $,
vise a Style B(Class B)circuit of dry-contact input devices. Its � ; � �
compact design allows the MMF-301(A) to be mounted in a ���' � '
� ���`�, � �;a
single-gang box behind the device it monitors. �� ',
MMF-302(A)is a standard-sized module used to monitor and e
supervise compatible two-wire, 24 volt, smoke detectors on a
Style D(Class A) or Style B(Class B)circuit.
MDF-300(A)is a standard-sized dual monitor module used to MMF-300(A)(Type H)
monitor and supervise two independent two-wire Style B
(Class B) dry-contact initiating device circuits (IDCs) at two may be wired as an NFPA Style B(Class B)or Style D(Class
separate,consecutive addresses in intelligent,two-wire systems. A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
LiteSpeedT"' is a communication protocol developed by (provided) terminates the Style B circuit. No resistor is
Fire•Lite Engineering that greatly enhances the speed of com- required for supervision of the Style D circuit.
munication between analog intelligent devices. Intelligent MMF-300(A) OPERATION
devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU Each MMF-300(A) uses one of the available module
stops the group poll and concentrates on single points. The addresses on an SLC loop. It responds to regular polls from
net effect is response speed greater than five times that of the control panel and reports its type and the status(open/nor-
other designs.designs. mal/short)of its Initiating Device Circuit(IDC).A flashing LED
indicates that the module is in communication with the control
MMF-300(A) Monitor Module panel. The LED latches steady on alarm (subject to current
limitations on the loop).
• Built-in type identification automatically identifies this device
as a monitor module to the control panel. MMF-300(A) SPECIFICATIONS
• Powered directly by two-wire SLC loop.No additional power Nominal operating voltage: 15 to 32 VDC.
required. Maximum current draw:5.0 mA(LED on).
• High noise(EMF/RFI)immunity. Average operating current: 350 uA (LED flashing), 1 com-
• SEMS screws with clamping plates for ease of wiring. munication every 5 seconds,47k EOL.
• Direct-dial entry of address: 01 —159 on MS-9600 series Maximum IDC wiring resistance:40 ohms.
panels,01 —99 on other compatible systems.
LED flashes during normal operation and latches on steady EOL resistance:47K ohms.
• to indicate alarm. Temperature range:32°F to 120°F(0°C to 49°C).
The MMF-300(A) Monitor Module is intended for use in intelli- Humidity range: 10%to 93%noncondensing.
gent, two-wire systems, where the individual address of each Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
module is selected using the built-in rotary switches. It pro- 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
vides either a two-wire or four-wire fault-tolerant Initiating 2.125"(5.398 cm)deep box.
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The MMF-300(A) can be used to replace M300(A)
modules in existing systems.
MMF-300(A)APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
DF-52121:C•10/06/2010—Page 1 of 4
�MMF-301(A) Mini Monitor Module Dimensions: 1.3° (3.302 cm) high x 2.75�� (6.985 cm) wide x
0.65"(1.651 cm)deep.
• Built-in type identification automatically identifies this device
as a monitor module to the panel. Wire length:6"(15.24 cm)minimum.
• Powered directly by two-wire SLC loop.No additional power MMF-302 A Interface Module
required. � �
• High noise(EMF/RFI)immunity. • Supports compatible two-wire smoke detectors.
• Tinned,stripped leads for ease of wiring. • Supervises IDC wiring and connection of external power
• Direct-dial entry of address: 01 — 159 on MS-9600 series source.
panels,01 —99 on other compatible systems • High noise(EMF/RFI)immunity.
_______ ___ • SEMS screws with clamping plates for ease of wiring.
°� - _
� 15 0 � ADDRESS 0 • Direct-dial entry of address: 01 — 159 on MS-9600 series
� �31 j�'y\Z I ��.��2 panels,01 —99 on other compatible systems.
� ���I� ;'��%'�I ;3� LO.OP � ��! �3 • LED flashes during normal operation.
11� � � �� l; �4 �--, I(� i/�� !4
� <,; i ; `��// �; ; • LED latches steady to indicate alarm on command from
10�, - �i 5 � `� �5 control panel.
9 8�6 _..._ 9\'g—�"6
TENS ONES The MMF-302(A)Interface Module is intended for use in intelli-
•� ;�� ,�� ��� gent, addressable systems, where the individual address of
�� -� each module is selected using built-in rotary switches. This
� module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors.It transmits the status(nor-
{ mal,open,or alarm)of one full zone of conventional detectors
� ' -w-i QW� ; Q back to the control panel. All two-wire detectors being moni-
W °� � � m tored must be UL compatible with the module. The MMF-
�' ' 302(A) can be used to replace M302(A) modules in existing
�I ' systems.
� $' h�1'� MMF-302(A)APPLICATIONS
�1 � u Use the MMF-302(A) to monitor a zone of two-wire smoke
The MMF-301(A) Mini Monitor Module can be installed in a detectors. The monitored circuit may be wired as an NFPA
single-gang junction directly behind the monitored unit. Its Style B(Class B)or Style D(Class A) Initiating Device Circuit.
small size and light weight allow it to be installed without rigid A 3.9 K ohm End-of-Line Resistor (provided) terminates the
mounting. The MMF-301(A) is intended for use in intelligent, end of the Style B or D (class B or A) circuit(maximum IDC
two-wire systems where the individual address of each module loop resistance is 25 ohms). Install ELR across terminals 8
is selected using rotary switches. It provides a two-wire initiat- and 9 for Style D application.
ing device circuit for normally-open-contact fire alarm devices.
The MMF-301(A)can be used to replace M301(A)modules in MMF-302(A)OPERATION
existing systems. Each MMF-302(A) uses one of the available module
MMF-301(A)APPLICATIONS addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status(open/nor-
Use to monitor a single device or a zone of four-wire smoke mal/short)of its Initiating Device Circuit(IDC). A flashing LED
detectors,manual fire alarm pull stations,waterflow devices,or indicates that the module is in communication with the control
other normally-open dry-contact devices. May also be used to panel. The LED latches steady on alarm (subject to current
monitor normally-open supervisory devices with special super- limitations on the loop).
visory indication at the control panel. Monitored circuiUdevice
is wired as an NFPA Style B(Class B) Initiating Device Circuit. MMF-302(A)SPECIFICATIONS
A 47K ohm End-of-Line Resistor(provided)terminates the cir- Nominal operating voltage: 15 to 32 VDC.
cuit. Maximum current draw:5.1 mA(LED on).
MMF-301(A)OPERATION Maximum IDC wiring resistance:25 ohms.
Each MMF-301(A) uses one of the available module Average operating current: 300 NA, 1 communication and 1
addresses on an SLC loop. It responds to regular polls from LED flash every 5 seconds,3.9k eol.
the control panel and reports its type and the status(open/nor-
mal/short)of its Initiating Device Circuit(IDC). EOL resistance:3.9K ohms.
MMF-301(A) SPECIFICATIONS External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
Nominal operating voltage: 15 to 32 VDC. maximum.Current:90 mA per module maximum.
Average operating current: 350 �A, 1 communication every Temperature range:32°F to 120°F(0°C to 49°C).
5 seconds, 47k EOL; 600 UA Max. (Communicating, IDC
Shorted). Humidity range: 10%to 93%noncondensing.
Maximum IDC wiring resistance:40 ohms. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
Maximum IDC Voltage: 11 Volts. 2.125"(5.398 cm)deep box.
Maximum IDC Current:400 NA.
EOL resistance:47K ohms.
Temperature range:32°F to 120°F(0°C to 49°C).
Humidity range: 10%to 93%noncondensing.
Page 2 of 4—DF-52121:C•10/06/2010
_
MDF-300(A) Dual Monitor Module Product Line Information
The MDF-300(A) Dual Monitor Module is intended for use in NOTE:°A"suffix indicates ULC-listed model.
intelligent, two-wire systems. It provides two independent two- MMF-300(A):Monitor module.
wire initiating device circuits(IDCs)at two separate,consecutive
addresses. It is capable of monitoring normally open contact fire MMF-301(A):Monitor module,miniature.
alarm and supervisory devices.The module has a single panel- MMF-302(A): Monitor module,two-wire detectors.
controlled LED.
MDF-300(A): Monitor module, dual,two independent Class B
NOTE: The MDF-300(A)provides two Style 8(Class 8) !DC cir- cirCUits.
cuits ONLY. Sryle D(Class A)IDC circuits are NOT supported in
anyapplication. SM6500:Optional surtace-mount backbox.
MDF-300(A)SPECIFICATIONS NOTE: See installation instructions and refer to the SLC Wiring
Manual,PN 51309.
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw:6.4 mA(LED on). AI'ChlteCtS'/Engineers' Specifications
Average operating current:750 uA(LED flashing). Specifications of these devices and all FireLite products are
Maximum IDC wiring resistance: 1,500 ohms. available from FireLite.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current:240 NA
EOL resistance:47K ohms.
Maximum SLC Wiring resistance:40 Ohms.
Temperature range:32°to 120°F(0°to 49°C).
Humidity range: 10%to 93%(non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125"(5.398 cm)deep.
MDF-300(A) AUTOMATIC ADDRESSING
The MDF-300(A) automatically assigns itself to two address-
able points, starting with the original address. For example, if
the MDF-300(A) is set to address "26", then it will automati-
cally assign itself to addresses"26"and"2T'.
NOTE: "Ones"addresses on the MDF-300(A)are 0,2, 4, 6, or 8
only. Terminals 6 and 7 use the first address,and terminals 8 and
9 use the second address.
QCAUTION:
Avoid duplicating addresses on the system.
Installation
MMF-300(A), MMF-302(A), and MDF-300(A) modules mount
directly to a standard 4" (10.16 cm)square,2.125"(5.398 cm)
deep, electrical box. They may also be mounted to the
SMB500 surtace-mount box. Mounting hardware and installa-
tion instructions are provided with each module. All wiring
must conform to applicable local codes,ordinances,and regu-
lations. These modules are intended for power-limited wiring
only.
The MMF-301(A)module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes,ordinances,and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
• UL: S2424
• ULC: S2424
• FM Approved
• CSFM:7300-0075:0185
• MEA:72-01-E
DF-52121:C•10/O6/2010—Page 3 of 4
DF-52385:D•E-710
� H355(A) Series � �ry�;.«T+�A��C`m�
Intelligent Addressable
�
Thermal Detectors �}/ �t�l�l��(W$�)
+
General � �� �
The Fire•Lite Alarms H355(A) Series thermal detectors are ��M 1�
addressable sensors that use a state-of-the-art thermistor ���,���� ����,���
sensing circuit for fast response.These sensors provide open �� � ��
area protection and are intended for use with Fire•Lite's ����������� ���
°� _�z�.�,. �� �� ���\�\�����_
addressable Fire Alarm Control Panels(FACPs). _ �� �y��
� �,���:
The H355(A) and H355R(A) sensors provide fixed tempera- `"�`� `
ture alarm detection at 135°F (57°C). The H355R(A) sensor � L��
�°
also responds to rate-ot-rise conditions of greater than 15°F
(8.3°C) per minute. The H355HT(A) is a fixed high-tempera- � � ��� ����
ture detector that activates at 190°F (88°C). These thermal �_
detectors provide addressable property protection in a variety �
of applications.
Two LEDs on each sensor light to provide a local,visible sen- H355(A) in B210LP(A) Base m
sor indication. Remote LED annunciator capability is available
using an optional accessory,the RA100Z.
• 94-5V plastic flammability rating.
Features options:
SLC loop: • Remote LED output connection to optional RA100Z remote
LED annunciator.
• Two-wire SLC loop connection. • Flanged surtace mounting kit.
• Unit uses base for wiring.
Addressing: 111St111at1011
• Addressable by device. H355(A) Series plug-in intelligent thermal detectors use a
• Rotary,decimal addressing:01 —159 with MS-9600 series, detachable base to simplify installation, service and mainte-
01 —99 with MS-9200 series. nance. Installation instructions are shipped with each detector.
Architecture: Mount base (all base types)on an electrical backbox which is
• Sleek,low-profile,stylish design. at least 1.5"(3.81 cm)deep. For a chart of compatible junction
• State-of-the-art thermistor technology for fast response. boxes,see DF-60059.
• Integral communications and built-in device-type identifica- NOTE:Because of the inherent supervision provided by the SLC
tion. loop, end-of-line resrstors are not required. Wiring 'T-taps" or
branches are permitted for Style 4(C/ass`B')wiring only.
• Built-in tamper resistant feature.
• Built-in functional test switch activated by external magnet. App�jCat1017S
Operation:
Use thermal detectors for protection of property.
• Factory preset at 135°F (57°C) for the H355(A) and
H355R(A); 190°F(88°C)for the H355HT(A). Construction
• Rate-of-rise triggers at 15°F (8.3°C) per minute for the
H355R(A). These detectors are constructed of off-white fire-resistant
plastic. The H355(A) Series plug-in intelligent thermal detec-
• 360°-field viewing angle of the visual alarm indicators (two tors are designed to commercial standards and offer an attrac-
bicolor LEDs). LEDs blink red in Normal condition and turn tive appearance.
on steady red in Alarm.
• Visible LEDs"blink"every time the unit is addressed. Qperation
Mechanicals: Each H355(A) Series detector uses one of 159 (MS-9600
• Sealed against back pressure. series)or 99 (MS-9200 series) possible addresses on a con-
• SEMS screws for wiring of the separate base. trol panel SLC loop. It responds to regular polls from the con-
• Designed for direct-surface or electrical-box mounting. trol panel and reports its type and the status. If it receives a
Plugs into separate base for ease of installation and main- tesi command from the panel(or a local magnet test),it stimu-
� lates its electronics and reports an alarm. It blinks its LEDs
tenance. when polled and turns the LEDs on when commanded by the
• Separate base allows interchange of photoelectric, ioniza- panel. The H355(A) Series offers features and pertormance
tion and thermal sensors. that represent the latest in thermal detector technology.
Other system features:
• Remote test feature from the panel.
• Walk test with address display.
• Low standby current.
DF-52385:D•5/17/2013—Page t of 2
y " Spefications INTELLIGENT BASES
Size:2.1"(5.3 cm)high;base determines diameter. NOTE:"A"suNix indicates ULC Listed model.
—B210LP(A): 6.1"(15.5 cm)diameter. NOTE:The detector's plug-in base can be changed oN for special
applications. For details about intelligent bases and their mount-
—B501(A):4.1"(10.4 cm)diameter. ing,see DF-60059.
—B200SR(A):6.875"(17.46 cm)diameter. B210LP(A): Plug-in detector base (included); standard U.S.
—B224R6(A):6.2"(15.748 cm)diameter. flanged low-profile mounting base.
Shipping weight:4.8 oz.(137 g). B210LPBP: Bulk pack of B210LP;package contains 10.
Installation temperature: B501(A):Standard European flangeless mounting base.
—H355(A),H355R(A):—4°F to 100°F(-20°C to 38°C). B501 BP:Bulk pack of 6501;package contains 10.
—H355HT(A):—4°F to 150°F(-20°C to 66°C). g200SR(A): Intelligent sounder base capable of producing
Humidity range: 10% to 93°/a relative humidity (noncon- sound output with ANSI Temporal 3 or continuous tone.
densing). Replaces 6501 BH series bases in retrofit applications.
Voitage range: 15 to 32 VDC peak. B224RB(A): Plug-in System Sensor relay base. Screw termi-
Standby current: 300 NA C� 24 VDC (one communication nals:up to 14 AWG(2.0 mmz). Relay type:Form-C.Rating:2.0
every five seconds with LED blink enabled). A C� 30 VDC resistive; 0.3 A C� 110 VDC inductive; 1.0 A �
30 VDC inductive.
LED current:6.5 mA C� 24 VDC.
B224BI(A): Plug-in System Sensor isolator detector base.
Mounting: B210LP(A) flanged base, included. See "Product Maximum 25 devices between isolator bases(see DF-52389).
Line Information: Intelligent Bases"if using a different base.
Fixed-temperature setpoint: 135°F (57°C) for the H355(A) ACCESSORIES
and H355R(A); 190°F(88°C)for the H355HT(A). F110: Retrofit flange to convert B210LP(A) to match the
Rate-of-rise detection:responds to greater than 15°F(8.3°C) g350LP(A) profile, or to convert older high-profile bases to
per minute. low-profile.
F1106P: Bulk pack of F110;package contains 15.
Listings and Approvals F210: Replacement flange for B210LP(A)base.
Listings and approvals below apply to the H355(A) Series RA100Z(A): Remote LED annunciator.3—32 VDC.Mounts to
detectors. In some cases, certain modules may not be listed a U.S. single-gang electrical box. For use with B501(A) and
by certain approval agencies, or listing may be in process. B210LP(A)bases only.
Consult factory for latest listing status. SMB600:Surface mounting kit
• UL Listed:S2517. M02-04-OO:Test magnet.
• ULC Listed(models H355A, H355RA, H355HTA). M02-09-00:Test magnet with telescoping handle.
• CSFM approved:7270-0075:0195.
FM approved. XR2B: Detector removal tool. Allows installation and/or
� removal of detector heads from bases in high ceiling applica-
tions.
Product Line Information XP-4: Extension pole for XR26. Comes in three 5-foot(1.524
NOTE:'A"suffix indicates ULC Listed model. m)sections.
H355:Intelligent thermal sensor;135°F(57°C);B210LP base T55-127-010: Detector removal tool without pole.
included.
H355A: Same as H355 but with ULC Listing; B210LPA base
included.
H355R:Same as H355 with rate-of-rise feature; 6210LP base
included.
H355RA: Same as H355R but with ULC Listing; 6210LPA
base included.
H355HT: Intelligent fixed high-temperature thermal detector;
190°F(88°C);B210LP base included.
H355HTA: Same as H355HT but with ULC Listing; 6210LPA
base included.
Fire•Lite�Alarms is a registered trademark of Honeywell International Inc.
�02013 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
1S0 �oo� This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
- We cannot cover all specific applications or anticipate all requirements.
ENCII�ENINC 8 MANtlFA6N111� All specifications are subject to change without notice.
QUALITII S�STEMS MadeintheU.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2—DF-52385:D•5/17/2013
�.ow�r
Cu,�'��t
aW��
pr � � � �
Commander� Series GEC3/GE53
Selectable Candela Evacuation Signals 12 & 24 VDC
Applications S E R I E S
The Commander3 Series is a low profile strobe and horn/strobe combination that
offers dependable audible and visual alarms and the lowest current available.
The GE3 Series 24VDC offers tamperproof field selectable candela options of 15, �� r°
� � � ���_
�� �, �
30, 60, 75, and 110 candela. The 12VDC offers tamperproof field selectable �- � r� � �
candela options of 15, 30, 60, and 75 candela. <� �°��� �� ��
;�;; �:
The Commander3 Series horn offers a continuous or synchable temporal three in '' °
2400Hz and mechanical tone, a chime and whoop tone. All tones are easy for � ���� ������ �
the professional to change in the field by using switches. °�
The GE3 Series has a minimal operation current and has a minimum flash rate ...m.�.�°°�~°'
of 1 Hz regardless of input voltage.
The Commander3 Series is shipped with the standard 4" metal mounting plate Product Listings
which incorporates the popular Super-Slide�feature that allows the installer to SIGNAI.IN6 =
easily test for supervision.The product also features a locking mechanism which `�`"�
secures the product to the bracket without any screws showing. U` F M ;O=:
The Commander3 also features the Checkmate0- Instant Voltage Verification ��STED APPROVED �"�
feature which allows the installer to check the voltage drop draw and match it to .ANSI/UL 464&ANSINL 1971 Listed
the blueprint. •FM Approved
The GE3 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed for use 'CSFM:7135-0569:122(GEC3-24&GEH-24)
with fire protective systems and are warranted for three years from date of purchase. �125-0569:123(GES3-2a)
7125-0569:129(GES3-12)
7135-0569:130(GEC3-12&GEH-12)
•MEA 285-91-E(GEC3-24&GES3-24)
Standard Features 580-O6-E(GEC3-12&GES3-12)
• Nominal voltage 12VDC and 24VDC
•24VDC units have field selectable candela options of 15, 30, 60, 75 & 110 Product Compliance
• 12VDC units have field selectable candela options of 15, 30, 60 & 75 • NFPA 72
•GEH horn is available in 12VDC or 24VDC • Americans with Disabilities Act(ADA)
•Super-Slide�Bracket- Ease of Supervision Testing • Quality Management S�stem is cert"rfied
•Checkmate�- Instant Voltage Verification to:�SO sooi zoos
• Unit Dimensions:5"high x 4.5"wide x 2.5"deep
•Synchronize strobe and/or horn with Gentex AVSM Control Module � ��
• Prewire entire system, then install signals MEMBER qSSEMBLEDIN
• Lower installation and operating costs T"E°�
• Input terminals 12 to 18 AWG
•Switch selection for high or low dBA
•Switch for chime, whoop, mechanical and 2400Hz tone
•Tamperproof re-entrant grill
• Switch for continuous or temporal 3 (not available on whoop tone)
• Surface mount with the GSB (Gentex Surface Mount Box)
• Silence horn while strobes remain flashing
• Wide voltage range 8-17.5VDC (12VDC units) 16-33VDC or FWR (24VDC units)
• Faceplate available in red or off-white
GEH 12VDC or 24VDC Low Profile Evacuation Horn
e art omma eve erant n nec oic oom
Number Number Voltage 10ft., per ANSINL 464 dBA �10ft.
GEH12-R 904-1239-002 12V C 62-82 100
24- 904-1207-002 24 62-82 100
GES3 12VDC or 24VDC Selectable Candela, Low Profile Evacuation Strobe
Model Part Nominal andela Model Designations:
Number Number Voltage (ANSINL 1971) W=N/all mount
GES3-12WR 904-1235-002 12 VDC 15, 30, 60, 75 R=Red Faceplate W=White Faceplate
3- 2 904- 237-002 2 5, 30, 60, 75
All units are available in plain (no lettering).
GES3-24WW 904-1319-002 24 VDC 15, 30, 60,75, 110 P�sin units are non-retumable.
ALERT bezel available AGENT bezel available
GEC3 12VDC or 24VDC Selectable Candela, Low Profile Evacuation Horn/Strobe
Model Part Nominal Candela Reverberant dBA � In Anechoic Room
Number Number Voltage (ANSI/UL 1971) 10ft.,per ANSI/UL dBA � 10ft.
GEC3-12WR 904-1231-002 12 VDC 15, 30, 60, 75 62-82 100
- 904-1233-002 12 VDC 15, 30, 60, 75 62-82 100
GEC3-24WR 904-1317-002 24 VDC 15, 30, 60, 75, 110 62-82 100
GEC3-24WW 904-1315-002 24 VDC 15, 30, 6U, 75, 110 62-82 100
GE3 Product Strobe Current Ratings(mA)
12VDC(8-17.5 Volts) 24VDC(16-33 Volts) VP 1"�
Candela 12VDC UL Max1 24VDC UL Max1 30�
15cd 106mA 92mA 30mA 42mA
Ocd 131 mA 141 mA 35mA 60mA ��nt �ra
Ocd 186mA 260mA 66mA 97mA Reduction
5cd 237mA 312mA 80mA 116mA
110cd 103mA 157mA
GE3-12 Product Horn Current Ratings GE3-24 Product Hom Current Ratings
irnmum inimum egu ate Mlnlmum dBA Mlnlmum dBA Regulated 24VDC
Hom Mode �10ft.,per �10it.,per Mau.operating� Hom Mode �10ft.,per �10it,per Max.Operating�
UL 464(HIGH) UL 464(LOV1n High Setting(mA) UL 464(HIGH) UL 464(LOVh High Setting(mA)
emp 3 2400Hz 76 69* 29 emp 3 2400Hz 78 71' 28
emp 3 Mechanical 75 68' 26 emp 3 Mechanical 76 70' 25
emp 3 Chime 62' 60' 13 emp 3 Chime 70' 66' 15
Continuous 2400Hz 79 74' 29 Continuous 2400Hz 81 74* 28
Continuous Mechanical 78 72' 26 Continuous Mechanical 80 72' 25
Continuous Chime 63* 61' �3 Continuous Chime 70' 66' 15
hoop 78 71' S5 hoop 82 69' 56
NOTES:
•Operating temperature:32°to 120°F(0°to 49°C). The GE3 Series is not listed for outdoor use.
•The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is
producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
•For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see
installation manual. 12VDC models are DC only.
•Gentex dces not recommend using a coded or pulsing signaling circuit with any of our strobe products(see Technical Bulletin 014).
'Operating the horn in this mode at this voltage will result in no?meeting the minimum UL reverberant sound level required for public mode fire protection service. These
settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone
is always private mode).
� RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units)(8-17VDC for
12VDC units). For strobes the UL max current is usually at the minimum listed voltage(16VDC for 24VDC units)(&VDC for 12VDC units). For audibles the max current is usually at
the maximum listed voltage. For unfiltered FWR ratings,see installation manual.
Mounting Super-Slide� Tone Switch Locations
�_ SWITCH POSITION
TONE 3 4 5
� Mechanical Temporal 3 ON ON ON
Mechanical-Continuous OFF ON ON
400Hz-Temporal 3 ON OFF ON
400Hz-Continuous OFF OFF ON
�� — � Chime-Temporal 3 ON ON OFF
�) � Chime-Continuous OFF ON OFF
hoop ON OFF OFF
� hoop OFF OFF OFF
Note:
GpN7F -Switch Positions 1 and 2 in the OFF position to
—� select isolated horn and strobe power inputs
� -Switch Position 6 ON=HIGH dBA
-Switch Position 6 OFF= LOW dBA
Gentex Super-Slide�Mounting Bracket:Allows the installer to
pre-wire the system,test for system supervision, remove the signal
head until occupancy, switch out Gentex signals without changing
mounting brackets and has locking edge connector for snap-in-place
installation.
Die Cast Metal Mounting Plate:Mounts to single gang, double gang 4"
square boxes or GSB box.
Candela Selection Checkmate�- Instant Voltage Verification
�
Candela seledion slider
switch. Depress center ^ 0
and slide switch to desired f�S S¢
brightness level. U S�
� �I �" �f
E t � ��
8reak off pin and insert into f t5 ' '
hole at the bottom of the �� �" �
so I
seledorto lock candela setting. 75
Signal must be removed from t+a modei
bracket and pin pushed forward M selectron �
� marker
from backside out of hole '
to change candela.
The access holes are provided in the back of the terminal
block to allow the voltage to be measured directly without
removing the device.Typically this would be done at the
end of the line to confirm design criteria. Most measure-
ments will be taken using the S+and S-�ocations although
access is provided to other locations. NOTE: Care
should be taken to not short the test probes.
Conventional Wiring Diagrams for Emergency Notification Evacuation Series
UL Listed
UL Listed Control
COIltf01 Panel signal sgnel
Signal Signal s. s+ s- H+ H- s+ s+ s- H+ H-
Panel
S+ S+ S- H+ H- S+ 5+ S- H+ H- SupervisBd
Supervised 0 0 0 0 Signal Circuit
+
Signal Circuit � E"°°°""E
+ \ RESISTOR
\ ENO OF LIN
RESIS70R ,r1
_��_ \ �r ENOOFLJNE
RESISTOR
Wiring Diagram GE3 Series with Gentex Synchronization Module
F.A.C.P.
ENOOFUNE }
RESISTOR FaR TO NEX7 SIGNAL TO NOTIFICATION AURM CIRCUIT
i
Cuss n
�
wwwcorar. - �
----'------'------------'---------------- �
TO NEXT SIGNAL TO NOTIFlCATION ALARM CIRWIT
RE�70VE JU4IPER
FORINDEPENDENT
SYNCHRONIZED STROBE
AUDIBIE SIGNAL + aesisroa�coa pND NORN OPERATION xw ame.,,n. ��am..�.
CIRCUIT WIRINa�or�eiv. ����EJUMPERINPLAC SYNCHRONIZATION
TO ELIMINATE NEED FC1R MODULE LEAVE JUMPER IN PLACE ON
�� � HORN INPUT ON AVSM SIAYE UNITS UNLESS SEPARATE
AN�OPERATE SIGNAL � - CONTROL OVER HORN CKT
oru,s. IN UNISON MODE ��� IS RE�UIRE�.
SVNCHRONIZATION
MODULE s�¢�ei s�enei
S+ 5+ S Ht 1+ 5+ 5+ 5- Ht H-
B B 0 �
VISIBLESIGNAL � � I � I ENOOFLINE
RESISTOR FOR
CIRCNT cuss a
WMMG ONLY
I
1 I 1 1
1 I 1 I �
1 I 1
� r
ENOOFLME ______ i �..t_t__________________________________________________________________________________________�__________J �
RESISTORLOR + � �
CV.55R
�
1 1 i
� i i
WIRINGONLV. - i_____________________________'___.__._____________ __________________._______________�
Note:See Technical Bulletin 015 for proper synchronization module for application.
Note:When synchronizing the GE3 12VDC Series,the AVSM synchronization module MUST be used.
Architect & Engineering Specifications
The audible and/or visible signal shall be Gentex GE3 Series or approved equal and shall be listed by Underwriters Laboratories,Inc.per UL 1971
and/or UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM),the California State Fire Marshal(CSFM)and the
Bureau of Standards and Appeals(NYC).
The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 12VDC or 24VDC as measured in an
anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energizetl with the
use of a single pair of power wires.Atlditionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having
the ability to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm
control panel.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2Hz regardless of power input voltage. The
appliance shall have an operating current of 55mA or less at 24VDC for the 15Cd strobe circuit and 106mA or less at 12VDC for the 15Cd strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with termi-
nals and barriers for inpuUoutput wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.
The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models or a voltage range of
8-17.5 volts for 12VDC models.
The appliance shall be capable of testing supervision without disconnecting wires.Also the appliance shall be capable of mounting to a surface back
box. The unit shall also be able to verify voltage at the unit without removing unit.
24 units per carton
28 pounds per carton
Important Notice:
G E N T E X �ecessmaterials have beeri prepared by Gentex Corporation("Gentex")for intormational purposes only,are 551-0050-04
arily summary,and are no1 purported to serve as legal advice and should not be used as such.
Gentex makes no reFresen[ations and wa�ranties,express or implied,that these malerials are complete and
CO R P O R AT 1 O N acwrate,up-to-date,or in compliance with all relevant local,state and tederel laws,regulations and rules.
The materials do nn�address all legal consitleretians as there is inevilaWe uncerWinry regarding in�erpreta-
Ifun ot laws,ragulations and rules and the applicatian of such laws,regulations and rules to particular fact
Fire Proteetion Produets Group•www.gentex.eom panems Each person's actrvities can diflerently aBect the obligations tha�exisl under applicable laws,regu-
lations or rules.Therelore,�hese materials should be used only tor informational purpwes and should not
10985 C hieago Drive •Zeeland, M iehigan 49464 6e used as a substiNte for seeking professional legal advice.Gentex will not be responsihle for any aciion
or failure to act in reliance upon the in�ormation contained in this malerial.
616.392.7195• 1.800.436.8391 • 616.392.4219 Fax
Genrex Corporation reserves the right m make changes m[he product data sheet at their discre[ion. �'S Printed on Recyded Paper
° DF-52418:E1 •Ai-20
MS-9050UD(E) � ��,��T£;Alc�rt�1�
Fire Alarm Control Panel 1�-••'"�
with DACT ��/ ���e�/V1����
General ,, . ,,
'���� ; ,
The Fire�Lite MS-9050UD(E) is a Fire Alarm Control Panel
(FACP) and Digital Alarm CommunicatorlTransmitter (DACT)
combined into one circuit board. This compact, intelligent
addressable control panel supports up to 50 addressable
devices of any type of detectors and modules. With an exten-
sive list of powerful features,the MS-9050UD programs just like
Fire•Lite's larger products, yet fits into applications previously � ��'
served only by corrventional panels. � ��
The MS-9050UD's integral DACT transmits system status � ,.;�. ��
(alarms,troubles,AC loss,etc.)to a Central Station via the pub- ����
lic switched telephone network. It also allows remote and local
programming of the control panel using the PK-CD Upload/
Download utility. In addition, the control panel may be pro-
grammed or interrogated off-site via the public switched tele-
phone network. Any personal computer with WindowsT" 95 or
greater, and compatible modem with a speed of 14.4 kbps or
faster and Fire•Lite Upload/Download software kit PK-CD, may
serve as a Service Terminal.This allows download of the entire
program or upload of the entire program, history file, walk-test
data,current status and system voltages. • Point trouble identification.
The power supply and all electronics are contained on a single • Waterflow selection per module point.
circuit board supported on a new quick install chassis and . Alarm verification selection per detector point.
housed in a metal cabinet. Available accessories include local . Maintenance alert warns when smoke detector dust accumu-
and remote upload/download software, remote annunciators, lation is excessive.
and reverse polarity/city box transmitter.(4XTMF) One-person audible or silent walk test with walk-test log and
New options include a UL listed printer, PRN-6F and the new • printout.
IPDACT Internet Monitoring module.The FireWatch Series inter- . System alarm verification selection per detector point.
net monitoring modules IPDACT-2 and IPDACT-2UD permit
monitoring of alarm signals over the Internet,saving the monthly ' PAS (Positive Alarm Sequence) and Pre-signal per point
cost of two telephone lines. Although not required, the second- (NFPA 72 compliant).
ary telephone line may be retained providing backup communi- • Up to eight ANN-BUS annunciators
cation over the public switched telephone line. • Remote Acknowledge, Alarm Silence, Reset and Drill via
NOTE:Unless othenvise specified, the term MS-9050UD is used addressable modules or remote annunciator.
in this data sheet to refer to both the MS-9050UD and the MS- • Upload/Download (local or remote) of program and data via
9050UDE FACPs. For MS-9050UDC,refer to DF-60445. integral DACT.
Features SLC COMMUNICATION LOOP
• Single addressable SLC loop which meets NFPA Style 4, 6
• Listed to UL Standard 864,9th edition. and 7 requirements.
• Auto-program (learn mode) reduces installation time. . 50 addressable device capacity(any combination of address-
Reports two devices set to the same address. able detectors and modules).
• On-board DACT. • Compatible with Fire•Lite's addressable devices(refer to SLC
• Two independently programmable Style Z(Class A)or Style Wiring Manua�.
Y(Class B)NAC circuits.
• Selectable strobe synchronization for System Sensor,Whee- NOTIFICATION APPLIANCE CIRCUITS(NACS)
lock,and Gentex devices. • Two independently programmable output circuits. Circuits
• Remote Acknowledge, Silence, Reset and Drill via address- can be configured for the following outputs:
able monitor modules. —Style Y(Class B)
• Two programmable relays and one fixed trouble relay. —Style Z(Class A)
• Built-in Programmer. —Door Holder Service(cannot be used for notitication appiiances)
• Telephone Line ACtive LEDs. —Aux Power Sou1'Ce(cannot be used for notlfication appliances)
• EIA-232 PC interface. • Silence Inhibit and Autosilence timer options.
• Integral 80-character LCD display with backlighting. • Continuous, March Time, Temporal or California code for
• Real-time clock/calendar with automatic daylight savings main circuit board NACs with two-stage capabiliry.
control. • Selectable strobe synchronization per NAC.
• History file with 500 event capacity. • 2.5 A total power for NACs.
• Automatic detector sensitivity testing(NFPA 72 compliant). NOTE:Maximum or total 24VDC system power shared between
• Automatic device type-code verification. all NAC circuits and the ANN-BUS is 2.7A.
DF-52418:E1•1/27/12—Page 1 of 4
_ `
PROGRAMMING AND SOFTWARE
• Autoprogram(learn mode)reduces installation time.
• Custom English labels (per point) may be manually entered
or selected from an internal library file.
• Two programmable Form-C relay outputs.
• 20 software zones.
• Continuous fire protection during online programming at the
front panel.
MS-9o5oUD • Program Check automatically catches common errors not
Fire Alarm linked to any zone or input point.
Control Panei OFFLINE PROGRAMMING: Create the entire program in
.
� ANN-SO your office using a Windows�-based software package(order
� programming kit PK-CD, containing PS-Tools, separately).
- � Upload/download system programming locally.
;��,.,,; '
SD355
Pr��t�r User interface
Photo Oetector Gateway LED INDICATORS
ANN-S/PG
„ • AC Power(green)
• Fire Alarm(red)
• Supervisory(yellow)
AD355 Graphic LED Motlule • Tfouble(yellOw)
Adapt Detector ANN-Ii0
• Alarm Silenced signals(yellow)
KEYPAD
• 16 key alpha-numeric pad
H355M355R/H355HT Relay Motlule • ACknowledge/Step
Heat Detector ANN-RLY PZR • Alafm SilenCed
Strobe • Drill(Manual Evacuate)
• Reset(lamp test)
rr;,
MoF-aoo '�W Product Line Information
Dual Monitor Module
P2R MS-9050UD(E): Combination DACT/Fire Alarm Control Panel
, Strobe with one SLC loop. Includes main circuit board with display,
Power Supply chassis with transformer,backbox with door,plastic bag contain-
,;�,�a„ " FCPS-24FS6 ing screws, cables, key, etc., manual. (For MS-9050UDC, refer
,. FCPS-24FS8 r to DF-60445.)
SD355T
PhotoRhermal �ZR PK-CD: Contains PS-Tools programming software for Win-
Strobe dows0-based PC computer(cable not included).
� DP-51050:Optional dress panel for the MS-9050UD.
�
� Multi-Modules TR-CE:Optional trim ring for semi-flush mounting.
MMF-300 • CRF-300-6 Six-Relay Control Module BB-2F:Optional cabinet for one or two modules.
Monitar Module
• CMF-3oo-6 Six-Circuit Superuised Controi Module gB-6F: Optional cabinet for up to six modules mounted on
• MMF-302-6 Six-Zone Interface Module CHS-6 Chassis.
• MMF-30o-10 Ten-Input Monitor Moduie gg_26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
MMF-3o2 BB-55F:Battery box,houses two 55 AH batteries
2-Wire Detectar
Monitor Module CHS-6: Chassis, mounts up to six multi-modules in a BB-6F
«t cabinet.
�; - CHG-75: Battery charger for lead-acid batteries with a rating of
� � 25 to 75 AH.
�,,,;F,i . Beam Detector CHG-120F: Remote battery charging system for lead-acid bat-
nu�f t,,.e.;�;�� BEAM-335/(S) teries with a rating of 55 to 120 AH. Requires additional BB-55F
for mounting.
� t+������ BAT Series:Batteries,see data sheet DF-52397.
`� PRT/PK-CABLE: Cable printer/personal computer intertace
� ����������� �����{��� cable.
�Q�fi��� �A��� PRN-6F: UL listed compatible event printer. Uses tractor-fed
BG-12LX Addressable paper.
Manual Pull Station
IPDACT, IPDACT2/2UD Internet Monitoring Module: Mounts
in bottom of enclosure with optional mounting kit(PN IPBRKT).
Connects to primary and secondary DACT telephone output
ports for internet communications over customer provided ether-
Page 2 of 4—DF-52418:E1•1/27/12
.
net internet connection. Requires compatible Teldat Visoralarm 4.0"(10.16 cm.)box.Includes plastic cover plate and end-of-line
Central Station Receiver. Can use DHCP or static IP. (See data resistor.Module may be configured for either a Style B(Class B)
sheet df-52424 for more information.) or Style D(Class A)IDC.
IPBRKT:Mounting kit for IPDACT-2/2UD in common enclosure. MDF-300: Dual Monitor Module. Same as MMF-300 except it
IPSPLT:Y-adaptor option allows connection of both panel dialer Provides two Style B(Class B)only IDCs.
outputs to one IPDACT-2/2UD cable input. MMF-301: Miniature version of MMF-300. Excludes LED and
AC-TRMBLK: AC Terminal Block mounts to a metal bracket, in Style D option.Connects with wire pigtails. May mount in device
turn, mounts to the FACP chassis. Use AC-TRMBLK when wire backbox.
nuts are not allowed for AC connections to the transformer. MMF-302A:Similar to MMF-300A.Addressable Monitor Module
OPTIONAL MODULES for one zone of conventional two-wire detectors. Requires reset-
table 24 VDC power. Refer to the Device Compatibility Docu-
4XTMF Reverse Polarity Transmitter Module: Provides a ment for listed compatible devices and quantiry limitation.
supervised output for local energy municipal box transmitter, CMF-300:Addressable Control Module for one Style Y/Z(Class
alarm and trouble. Includes a disable switch and disable trouble g�A) zone of supervised polarized Notification Appliances.
LED. Mounts directly to a 4.0" (10.16 cm.)electrical box. Notification
ANN-SEC: Optional secondary ANN-BUS interface module. Appliance Circuit option requires external 24 VDC to power noti-
Note:Used only with firmware 3.0 or higher. fication appliances.
COMPATIBLE ANNUNCIATORS CRF-300: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
ANN-80(-W): Remote LCD annunciator mimics the information Mounts directly to a 4.0" (10.16 cm.) box, surface mount using
displayed on the FACP LCD display. Recommended wire type is the SMB500.
un-shielded.(Basic model is red;order-W version for white;see BG-12LX: Addressable manual pull station with interface mod-
DF-52417.) ule mounted inside.
ANN-I/O: LED Driver Module provides connections to a user 1300:This module isolates the SLC loop from short circuit condi-
supplied graphic annunciator.(See DF-52430.) tions(required for Style 6 or 7 operation).
ANN-LED: Annunciator Module provides three LEDs for each SMB500: Used to mount all modules except the MMF-301 and
zone: Alarm, Trouble, and Supervisory. Ships with red enclo- M301.
sure. (See DF-60241.)
ANN-RLED: Provides alarm (red) indicators for up to 30 input MMF-300-10:Ten-input monitor module.Mount one or two mod-
zones or addressable points. (See DF-6024i.) ules in a BB-2F cabinet(optional).Mount up to six modules on a
CHS-6 chassis in a BB-6F cabinet.
ANN-RLY: Relay Module provides 10 programmable Form-C MMF-302-6: Six-zone intertace module.Mount one or two mod-
relays. Can be mounted inside the cabinet.(See DF-52431.) ules in a BB-2F cabinet(optional).Mount up to six modules on a
ANN-S/PG: Serial/Parallel Printer Gateway module provides a CHS-6 chassis in a BB-6F cabinet.
connection for a serial or parallel printer. (See DF-52429.) CMF-300-6:Six-circuit supervised control module.Mount one or
ADDRESSABLE DEVICES two modules in a BB-2F cabinet(optional).Mount up to six mod-
All feature a polling LED and rotary switches for addressing. ules on a CHS-6 chassis in a BB-6F cabinet.
CP355:Addressable low-profile ionization smoke detector. CRF-300-6: Six-relay control module (Form-C relays). Mount
one or two modules in a BB-2F cabinet(optional). Mount up to
SD355:Addressable low-profile photoelectric smoke detector. six modules on a CHS-6 chassis in a BB-6F cabinet.
SD355T: Addressable low-profile photoelectric smoke detector NOTE:For more information on Compatible Addressable Devices
with thermal sensor. for use with the MS-9050UD,see the following data sheets(docu-
SD355R: Remote test capable addressable photoelectric ment numbers):AD355(DF52386), BG-12LX(DF52013), CMF
smoke detector for use with DNR(W)duct detector housing. 300-6(DF-52365),CRF-300-6(DF-52374),CMF/CRF Series(DF
52130), CP355(DF-52383), H355 Series (DF-52385), 1300(DF-
H355: Fast-response,low-profile heat detector. 52389), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10
H355R: Fast-response, low-profile heat detector with rate-of- (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-
rise option. 52384).
H355HT: Fast-response, low-profile heat detector that activates qDDRESSABLE DEVICE ACCESSORIES
at 190°F/88°C. End-of-Line Resistor Assembly (R-47K and R-3.9K): The
AD355: Low-profile, intelligent, "AdapY' multi-sensor detector 47k ohm assembly supervises the MMF-300, MDF-300, MMF-
(6350LP base included). 301, and CMF-300 module circuits. The 3.9k ohm assembly
BEAM355:Intelligent beam smoke detector. supervises the MMF-302 module circuit. These resistors are
BEAM355S: Intelligent beam smoke detector with integral sen- included with each module.
sitivity test. Power Supervision Relay: Supervises the power to 4-wire
D355PL: InnovairFlex low-flow non-relay duct-detector housing; smoke detectors and notification appliances.
includes SD355R.
DNR: InnovairFlex low-flow non-relay duct-detector housing. W�ring Requirements
(Order SD355R separately.) While shielded wire is not required, it is recommended that all
DNRW: InnovairFlex low-flow non-relay duct-detector housing, SLC wiring be twisted-pair to minimize the effects of electrical
with NEMA-4 rating. Watertight.(Order SD355R separately.) interference. Refer to the panel manual for wiring details.
MMF-300: Addressable Monitor Module for one zone of nor-
mally-open dry-contact initiating devices. Mounts in standard
DF-52418:E1•1/27/12—Page 3 of 4
SYSTEM SPECIFICATIONS
System Capacity condensing) at 32°C t 2°C (90°F t 3°F). However, the useful
life of the system's standby batteries and the electronic compo-
• Intelligent Signalling Line Circuits.........................................1 nents may be adversely affected by extreme temperature ranges
• Addressable device capacity..............................................50 and humidity. Therefore,it is recommended that this system and
• Programmable software zones...........................................20 its peripherals be installed in an environment with a normal room
• Annunciators.........................................................................8 temperature of 15–27°C/60–SO°F.
Electrical Specifications NFPA Standards
AC Power: MS-9050UD 120 VAC,60 Hz,3.0 A. MS-9050UDE: The MS-9050UD(E) complies with the following NFPA 72 Fire
240 VAC,50 Hz, 1.5 A.Wire size:minimum 14 AWG(2.00 mm2) Alarm Systems requirements:
with 600 V insulation. Nonpower-limited,supervised. —LOCAL (Automatic, Manual, Waterflow and Sprinkler
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger Supervisory).
Capacity: 7-18 AH (MS-9050UD cabinet holds maximum of two —AUXILIARY (Automatic, Manual and Waterflow) (requires
18 AH batteries.) 4XTMF).
Communication Loop: Supervised and power-limited. —REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
Notification Appliance Circuits: Terminal Block provides con- supervisory relays may be connected to UL 864 listed
nections for two NACs, Sryle Y(Class B) or Style Z (Class A). transmitters. For reverse polarity signaling of alarm and
Special Application power. Power-limited, supervised circuitry. trouble,4XTMF is required.)
Maximum signaling current per circuit:2.5 A. End-of-Line Resis- _pROPRIETARY(Automatic,Manual and Waterflow).
tor:4.7k ohm,�/z watt(P/N 71252 UL listed)for Style Y(Class B)
NAC. Refer to the Fire•Lite Device Compatibility Document for —CENTRAL STATION (Automatic, Manual and Waterflow,
listed compatible devices. and Sprinkler Supervised).
Two Programmable Relays and One Fixed Trouble Relay: —OT,PSDN(Other Technologies, Packet-switched Data Net-
Contact rating: 2.0 A@ 30 VDC (resistive), 0.5 A Q 30 VAC Work)
(resistive).Form-C relays, nonpower-limited, nonsupervised.
Agency Listings and Approvals
Cabinet Specifications 7ne listings and approvals below apply to me basic nns-
Door: 19.26"(48.92 cm.)high x 16.82"(42.73 cm.)wide x 0.72" 9050UD(E)control panel. In some cases, certain modules may
(1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" not be listed by certain approval agencies, or listing may be in
(42.29 cm.)wide x 5.25"(13.34 cm.)deep.Trim Ring(TR-CE): Process.Consult factory for latest listing status.
22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide. • UL: S624
• FM approved
Shipping Specifications • CSFM:7165-0075:210
Weight: 26.9 Ibs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) • MEA:442-O6-E
high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. NOTE:See DF60445 for ULC-listed model.
Temperature and Numidity Ranges
This system meets NFPA requirements for operation at 0 —
49°C/32—120°F and at a relative humidity 93%t 2%RH(non-
FireLite�Alarms0 and System Sensor�are registered trademarks of
Honeywell International Inc. Microsoft� and Windows� are registered
trademarks of the Microsoft Corporation.
002012 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
1S0 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate alI requirements.
ENCIPEEAII�8 MANUfAC1�SING All specifications are subject to change without notice.
QUALITI SYSTEMS MadeintheU.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firel�te.com
Page 4 of 4—DF-52418:E1•1/27/12
DF-60430:C2•E-650
D355PL(A)/DNRW InnovairFlex � F�����TE'�ALc�rt"�l�
Intelligent Non-Relay Photoelectric
Duct Smoke Detector by H�r�eyvwrell
_ ,
General %
F,;�.
The Fire•Lite InnovairFlex� D355PL(A) intelligent non-relay
photoelectric duct smoke detector and DNRW watertight non-
relay photoelectric duct smoke detector feature a pivoting �.:,�� �
housing that fits both square and rectangular footprints capa- ���
ble of mounting to a round or rectangular duct. � _u '�� �� �� ��
DNRW duct smoke detector, with its NEMA-4 rating, is listed
as a watertight, UV resistant enclosure providing protection � � �� �
against falling dirt, rain, and windblown dust, splashing and �
�'�I ; �� �� ���ik
hose directed water, allowing operators to use the detector in " 1i����. ����'+�r e��I I�I���IQyVIIfI�I�y� �W�II�I��,II�III� �
the most extreme environments.
� M�I�I U�P�.,,�
These units sense smoke in the most challenging conditions, ��
operating in airtlow speeds of 100 to 4,000 feet per minute(0.5
to 20.32 m/s),temperatures of-4°F to 158°F(-20°C to 70°C),
and a humidity range of 0 to 95 percent(non-condensing.)
An improved cover design isolates the sensor head, which Specifications
allows for ease of maintenance. A cover tamper feature indi- Size: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm)
cates a trouble signal for a removed or improperly installed �/�dth,2.5 in(6.6 cm)Depth.
sensor cover.The Fire•Lite InnovairFlex housing provides a 3/
4-inch conduit knockout and ample space to facilitate easy wir- Size:(Square)7.75 in(19.7 cm)Length;9 in(22.9 cm)Width;
ing and mounting of a relay module. 2.5 in(6.35 cm)Depth.
The Fire•Lite InnovairFlex duct smoke detector can be custom- Weight: 1.6 Ib(0.73 kg).
ized to meet local codes and specifications without additional Operating Temperature Range: -4°F to 158°F (-20°C to
wiring.The new InnovairFlex product line is compatible with all 7p°�).
previous Innovair models,including remote test accessories. Storage Temperature Range: -22°F to 158°F (-30°C to
Features ������
Operating Humidity Range: 0% to 95% relative humidity
• Photoelectric,integrated low-flow technology. (non-condensing).
• Air velocity rating from 100 ft/min to 4,000 ft/min(0.5 m/s to Air Duct Velocity: 100 to 4,000 ft/min(0.5 to 20.32 m/s).
20.32 m/s).
• Versatile mounting options: square or rectangular configu- /\CC@SSOI'1@S
ration.
• Broad ranges for operating temperature (-4°F to 158°F, - Fire•Lite provides system flexibility with a variety of accesso-
20°C to 70°C)and humidity(0%to 95%non-condensing). ries, including two remote test stations and different means of
visible and audible system annunciation. As with our duct
• Patented sampling tube installs from front or back of the smoke detectors,all duct smoke detectors accessories are UL
detector with no tools required. listed.
• Cover tamper signal. D355PLs and DNRWs with a date code of 0013 or higher do
• Increased wiring space with a newly added 3/4" conduit not require external 24VDC for remote test applications when
knockout. used with a remote-test-capable detector.
• Available space within housing to accommodate mounting ACCESSORY CURRENT LOADS AT 24 VDC
of a relay module.
• Easily accessible code wheels on sensor head (sold sepa- Device Standby Alarm
rately).
• Clear cover for convenient visual inspection. RA100Z OmA 12 mA Max
• Remote testing capability. RTS151/
• Requires com line power only. RTS151 KEY OmA 12mA Max
• Accommodates the installation of an addressable relay
module, sold separately, �cRF-aoo�for appiicat�ons requ�r- Agency Listings and Approvals
ing a Form-C relay.
Consult product manual for lists of compatible UL-Listed
devices. In some cases,certain modules may not be listed by
certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
• UL:S1059.
• ULC:S1059
DF-60430:C2•12/18/2012—Page 1 of 2
• CSFM: 3242-1653:0209.
• FM approved.
Product Line Information
D355PL: Intelligent non-relay photoelectric low flow smoke
detector housing. Includes SD355R Detector.
DNRW: Watertight intelligent non-relay photoelectric low flow
duct smoke detector housing.Does not include detector head.
SD355R(A): Remote test capable addressable low-profile
photoelectric smoke detector.
SD355(A):Addressable low-profile photoelectric smoke detec-
tor.
DCOIL: Remote test coil. Required for older DNR(W) duct
detector housing.
DSTi:Metal sampling tube duct width up to 1 ft(0.3m).
DST7.5: Metal sampling tube duct widths up to 1 ft to 2 ft(0.3
to 0.6 m).
DST3: Metal sampling tube duct widths up to 2 ft to 4 ft(0.6 to
1.2 m).
DSTS: Metal sampling tube duct widths up to 4 ft to 8 ft(1.2 to
2.4 m).
DST10:Metal sampling tube duct widths up to 8 ft to 12 ft(2.4
to 3.7 m).
DH4000E-1:Weatherproof enclosure.
ETX: Metal exhaust tube duct,width 1 ft(0.3 m).
M02-04-00:Test magnet.
P48-21-00:End cap for metal sampling tubes.
RA100Z: Remote annunciator alarm LED.
RTS151: Remote test station.
RTS151 KEY:Remote test station with key lock.
Important Note
• DNRW duct detector housings with a date code of 0013 or
higher do not require a DCOIL or auxiliary 24 VDC for
remote test applications when used with a remote test
capable detector.
• DNRW duct detector housings with a date code of 0012 or
earlier require a DCOIL and auxiliary 24 VDC power for
remote test applications.
Fire•Lite�Alarms is a registered trademark of Honeywetl International Inc.
�02012 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
ENCIPEgIIYi 8 MANtlFAC1YRIN6 All specifications are subject to change without notice.
QUALIi1 SYSTEMS MadeintheU.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)62?-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2—DF-60430:C2•12/18/2012
df-60379:A1•E-400
� CRF-3oo(A) � Fine•�iTe�A�arms
Relay Module
by Honeywell
,
General
The CRF-300(A)Addressable Relay Module provides the sys- „�
tem with a dry-contact output for activating a variety of auxil-
iary devices, such as fans, door holders, dampers, control �����1�''���
equipment, etc. Addressability allows the dry contact to be �a � \\ „�, , �\
activated through panel programming,on a select basis. �. ��� � � � �
LiteSpeedT"^ is a communication protocol developed by v�\;, � � �� `-;-
Fire•Lite Engineering that greatly enhances the speed of com- °° � �� '��
munication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the
devices within the group has new information,the panel CPU „
stops the group poll and concentrates on single points. The w, H, _, �.
net effect is response speed greater than five times that of ,
other designs. �
�� �
� �
� �
_: �t
Features " ��� � '
`� E � �fi:� �
• Built-in type identification automatically identifies these 5� '''°�
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire �
SLC loop.
• Integral LED "blinks" green each time a communication is CRF-300(A)
received from the control panel and turns on in steady red
when activated.
• High noise immunity(EMF/RFI).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease. Specifications
• Direct-dial entry of address:01—159 for MS-9600(A)series Normal operating voltage: 15 to 32 VDC.
panels,01 —99 on MS-9200UDLS(A)and MS-9050UD(A). Maximum SLC current draw: 6.5 mA(LED on).
Applications Average operating current: 230 NA direct poll (CLIP mode),
255 NA group poll(LiteSpeed mode)with LED flashing.
The CRF-300(A)may be programmed to operate dry contacts EOL resistance: not used.
for door holders,Air Handling Unit shutdown,etc.,and to reset
four-wire smoke detector power. Temperature range: 32°F to 120°F(0°C to 49°C).
Humidity range: 10%to 93%non-condensing.
Construction Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
• The face plate is made of off-white heat-resistant plastic. ?�25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
• Controls include two rotary switches for direct-dial entry of 2•125"(5.398 mm)deep box.
address settin9. Relay Contact Ratings
• The CRF-300(A)is configured for a single Class B(Style Y)
or Class A(Style Z)Notification Appliance Circuit. Maximum Current
• The CRF-300(A) provides two Form-C dry contacts that Load Description Application Voltage Rating
switch together.
Resistive Non-Coded 30 VDC 3.0 A
Operation Resistive Coded 30 VDC 2.0 A
Each CRF-300(A)uses one of the addresses on a SLC loop. It Resistive Non-Coded 110 VDC 0.9 A
responds to regular polls from the control panel and reports its Resistive Non-Coded 125 VAC 0.9 A
type and status, including the open/normal/short status of its
Notification Appliance Circuit(NAC).The LED blinks with each Inductive(UR=Sms) Coded 30 VDC 0.5 A
poll received.On command,it activates its internal relay. Inductive(UR=2ms) Coded 30 VDC 1.0 A
NOTE:Open/short supervision is suspended with the CRF-300. Inductive(PF=0.35) Non-Coded 125 VAC 0.5 A
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE(not settable)will identify the module to the con-
trol panel,so as to differentiate between a control module and
a relay module.
df-60379:A1•OS/04/09—Page 1 of 2
" ' Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
• UL:S2424
• ULC:S2424
• FM approved
• CSFM:7300-0075:185
• MEA:72-01-E
Product Line Information
CRF-300(A): Intelligent addressable relay module.
:Intelligent addressable relay module, ULC listed model.
SMB500:Optional surface-mount backbox.
NOTE: For installatron instructions, see document 156-1190-005
and refer to the SLC Wiring Manual,document 51309.
LiteSpeedT"'is a trademark and Fire•Lite�Alarms is a registered trademark
of Honeywell International Inc.
�02009 by Honeyweil International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
EN611�EEtINi 8 MANtliACN11Ni All specifications are subject to change without notice.
QUIILITY SYSTEMS MadeintheU.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2—df-60379:A1•08/04/09
Intrusion Systems�Conettix IP C900V2 Dialer Capture Module
Conettix I P G900V2 Dialer
Capture Module
� ��� -
�._ a
.�<�,�� ° ��� ,� �� _ a� � � � �„�-��� ,,�� � � �� `�" :�° �; • Ca tures alarm and event data
� � �_� �;.� g� . �, p
���� �, � �a�� ��°� from dialer-based control panels
`�` � � � � �� ��� ��� � � �� using CONTACT ID, SIA,
v � =.
� �� � • ° m� ��� � � u �� ��� '
�°� ��.�� �_- � � s . ,.,._���
� �� .
� �"" � � � ���. �� � �°-m �" �"� � Modem II, Modem Ile, Modem
q � ��� . , ..� � � ��� la� P
� � � � � . , � � � � ��, II , ulse,and other formats
� �� " q� �� r� ��� • Performs full data transmissions
°" � �� "� ��,�� �� " �:- without changing the data
� � �
� � • 12 VDC to 24 VDC voltage range
,�,� . �,� ,�, - � �H .. : .� sE;r�
��;. �' .
� �;��' '� Re-routes signals using UDP/�P-
� ,�� �� ` , ��s� based data networks
a � �- � �� ' � �
�, �` �L� � � ��• �,, Convenient connection (RJ-45
`�� ��=`°� `'��� � � ' � ���� Jack)to Ethernet networks
� � � � � _ � ,� : �
�" '' '� • Integrated 10/100 Network
� s � � �
�� �.. � _ � � ���
+ � L �. � . � � .. . :. : { \ �_
� � � � � f„ Interface Module (NIM)
s ,,,, , � ��� _ ����� �� �.��:�' � �� � � �� r? • Provides acknowledgement from
�
�
M
� � �,:�:��,�, ,,,°��� � � `�� �� the receiver to the control panel
�- �,�� � . - z � ,
�{ r�Y: ,{,��x�:, c�c�;`.a,#� � �
�+' ` _ � ��
The C900V2 Dialer Capture Module works with most control System Overview
panels using a standard digital dialer format and provides end- When the dialer has a message to report,the C900V2
to-end security.The module links the digital dialer to the simulates dial tone and line voltages,causing the dialer to
Public Switched Telephone Network(PSTN),the digital behave as though it is connected to a monitoring center digital
dialer's telephone interface,and an Ethernet network.With receiver through the PSTN.The C900V2 decodes and converts
the Ethernet link,the C900V2 can: the transmitted dialer message to data for transport over any
• Communicate with the control panel dialer UDP/IP network.
Decode and deliver signals to a D6600 Communications �ter the D6600 Communications Receiver/Gateway receives
• Receiver/Gateway a message or event,it sends an acknowledgement message to
Relay a confirmation message back to the control panel the C900V2.The C900V2 returns an appropriate response to
� the dialer,maintaining end-to-end acknowledgment.
dialer
Whether a control panel dials through a telephone line or The C900V2 operates in Intercept Mode,connecting the
dialer to the network under normal circumstances. If the
through the C900V2 Dialer Capture Module,the data remains C900V2 loses contact with the D6600 Communications
the same.The C900V2 empowers digital dialer control panels Receiver/Gateway,the unit goes into Fallback Mode,
to work over an IP network such as a Local Area Network connecting the dialer to the PSTN telephone line.
(LAN),a Wide Area Network(WAN),or the Internet.
Secu rity you ca n rely on. ■■�O���
�
2�Conettix IP C900V2 Dialer Capture Module
Functions
�� l_?.i Communication Formats
' ;;; �� ADT-SIA Seriee FSK and DTMF
a _,
; �.% BFSK SIA V.21,110/300 baud
� �,, ;, �„�,; (2300Hz ACK Tone or 1400Hz
% ��°�� ACK Tone)
� 3 �` �: ��:� � �z�i
�2 __ r�se�crs.�
v ° r� � �"–�-��: DTMF SIA Bell 103,110/300 baud
r — � ■ (Contact ID,High Speed and 4/2
2.1 ,A
� a ! ` Express)
� �� o ; -
,,_: �~
�'±.J � FBI Superfast DTMF Robofon
C5�
(1400 Hz ACK Tone or 2300 Hz
� " ACK Tone)
i '� Pulse 3/1,3/1 Checksum,4/2 Telim
(1400 Hz ACK Tone or 2300 Hz
� ACK Tone)
� �d� �9 i Radionics Modem II,Radionics
L _ __....r,. _. ,
� �� �� Modem Ile,and Modem Illa�
er�:
�
. ������ x ` 11�.
Inputs
Input Description
1. Control Panel 1 Used as an end-of-line(EOL)supervised loop.Capable of
2. Dialer Connection detecting open,short,and normal states.Terminate this input
with a 10 kU EOL resistor.
2.1 Dialer Output to RJ-31 x Jack and PSTN
2 Used for intercept inhibit to force the C900V2 into Fallback
3. C900V2 Dialer Capture Module
mode for at least two minutes.
4. Ethemet or LAN Connection
3 Used for intercept override,allowing you to switch between
5. LAN,WAN,or the Internet intercept and fallback modes.
6. Connection To Ethernet Network Interface Card(NIC)
7. Host PC with D6200 Programming Software Outputs
S. D6680 Ethernet Network Adapter
Output Description
9. Com 1 (Optional)
1 Provides local annunciation if the power to the C900V2 is lost
10. Com 4
or the CPU fails.
11. D6600 Communications Receiver/Gateway 2 Provides local annunciation if the connection to the
monitoring center is lost.
3 Provides local annunciation whenever the C900V2 is in
intercept mode.
4 Controllable from the monitoring center and the D6200
Programming Software(default is open).
Conettix IP C900V2 Dialer Capture Module�3
' • �
Intercept and Fallback Modes
• Intercept Mode:The C900V2 connects the dialer to the Alarm Outputs: Normally-open NO dry contacts
network.Intercept mode remains on as long as the Interface: IEEE 802.3
C900V2 remains in continuous contact with the D6600 „_, „
� ��.a. .., A.:_ ' � '�',�li��' ��
Communications Receiver/Gateway. " °���
Control Panel: RJ-45 Modular Jack
• Fallback Mode:The C900V2 connects the dialer to the
Telco: RJ-45 Moduiar Jack
telephone line,removing itself from the telephone LAN/WAN: RJ-45 Modular Jack
citcuit.Fallback mode occurs if the C900V2 loses Ethernet Cable: Unshielded twisted pair 100 m(328 ft)
contact with the D6600 Communications Receiver/ For 10BASE-T,use Category 3 or
Gateway,loses power,or stops operating correctly. better.For�ooeASE T,use Category
LED Indicators 5 or better.
The C900V2 has two dual-colored LEDs that indicate the
module's status(the SYSTEM LED and the DIALER LED). k �''�'"` "' "' `'�° "'" ' '�"���s` ` "`'`
Temperature(Operating): 0°C to+49°C(+32°F to+120°F)
Modular Jacks
The C900V2 module has three modular jacks. ��,� '% ,- ' �. ;
„�,///no .. ''�., , .. ;; ?//�,Fi',`3„x.�-�:.. " ...
�;,.,_ . . ,,,, ,,. ,,,,, .
• Panel Jack:Connects to a dialer through a modular Module Status LEDs: 2 dual-colored
telephone cord (D162). ,
• TELCO Jack:Connects to a PSTN line through a �'-" : �`��`y�����.��-.:... �`�r��"%--- '''
modular telephone cord (D162). Dimensions: �7.s cm x tt.4 cm
(7 in.x 4.5 in.)
• Ethernet Jack:Connects to the Ethernet data network
through an Ethernet cable.For lOBASE-T,the cable ': ��� ' '`
= ,,;�,��._... ,,,. ,,,° r�
must be Category 3 or better.For 100BASE-T,the cable Current(Maximum): 280 mA
must be Category 5 or better. Voltage Range: 12 VDC to 24 VDC nominal
Polling and Supervision /��
�
C900V2 polling helps the D6600 Communications Receiver/ '
_ ....... ;. ,Fr H.,
Output To LAN or WAN: UDP/IP packets
Gateway to perform supervision.
.
Certifications and Approvals ConettixYlP C900V2$Dialer Capture Module C900V2
UL Standards UL864,UL Commercial Fire Alarm D162 Modular Telephone Cord D162
Signaling AE1 Standard Enclosure(Gray) AE1
UL1610,Central Station Burglary,Line AE4 Large Enciosure(Red) AE4
Security("Grade AA")
Approvais CE
FCC,Part 15 Radiated/Conducted
Emissions
IC
A-Tick
�
..�.
DF-52013:D•E-100
BG-12�x (� ��•�iTe�A�arms
Addressable Manual Pull Station
by Haneywell
_ , _
General
The Fire•Lite BG-12LX is a state-of-the-art, dual-action (i.e.,
_ _.... _ ___
requires two motions to activate the station) pull station that r`
includes an addressable intertace (mounted inside) for
Fire•Lite's addressable fire alarm control panels (FACPs) ���,,,,
Because the BG-12LX is addressable, the control panel can
display the exact location of the activated manual station.This
leads fire personnel quickly to the location of the alarm. �
Features �
� �,,.
• Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches in down position and the word"ACTIVATED"
appears to clearly indicate the station has been operated.
• Captive screw terminals wire-ready for easy connection to � r ,,�� „
SLC loop(accepts up to 12 AWG/3.25 mm2 wire).
• Can be surtace mounted (with SB-10 or SB-I/O) or semi-
flush mounted. Semi-flush mount to a standard single- � ° °�
gang,double-gang,or 4"(10.16 cm)square electrical box. �
• Smooth dual-action design. °'
a
• Meets ADAAG controls and operating mechanisms guide- LL
lines (Section 4.1.3[13]); meets ADA requirement for 5 Ib.
maximum activation force.
• Highly visible. usually needed for semi-flush mounting with 4" (10.16 cm)or
• Attractive shape and textured finish. double-gang boxes(not with single-gang boxes).
• Key reset. �peration
• Includes Braille text on station handle.
• Optional trim ring(BG12TR). Pushing in,then pulling down on the handle causes it to latch
in the down/activated position. Once latched,the word"ACTI-
• Meets UL 38, Standard for Manually Actuated Signaling VATED" (in bright yellow) appears at the top of the handle,
Boxes. while a portion of the handle protrudes from the bottom of the
station. To reset the station,simply unlock the station with the
Construction key and pull the door open.This action resets the handle;clos-
Shell, door, and handle are molded of durable polycarbonate ing the door automatically resets the syritch.
material with a textured finish. Each manual statiun, on command from the control panel,
sends data to the panel representing the state of the manual
Specifications switch.Two rotary decimal switches allow address settings
(1 —159 with Br�akaway Tab removed for MS-9600 Series,1 —
• Shipping Weight:9.6 oz.(272.15 g) 99 and MS-9200UDLS, 1 —50 for MS-9050UD).
• Normal operating voltage:24 VDC.
• nnax�mum s�c iooP voitaye:2a.o voc. Architectural/Engineering
• Maximum SLC standby current:375 uA. Specifications
• Maximum SLC alarm current:5 mA. Manual Fire Alarm Stations shall be non-coded, with a key-
• Temperature Range:32°F to 120°F(0°C to 49°C) operated reset lock in order that they may be tested, and so
• Relative Humidity: 10%to 93%(noncondensing) designed that after actual Emergency Operation, they cannot
be restored to normal except by use of a key.An operated sta-
• For use indoors in a dry location tion shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
Installation red-r.olored polycarbonate material with clearly visible operat-
The BG-12LX will mount semi-flush into a single-gang,double- ing instructions provided on the cover. The word FIRE shall
gang,or standard 4"(10.16 cm)square electrical outlet box,or appear ori the front of the stations in white letters, 1.00 inches
will surface mount to the model SB-10 or SB-I/O surtace back- �2.54 cm) or larger. Stations shall be suitable for surface
box. If the BG-12LX is being semi-flush mounted, then the mounting on matching backbox SB-10 or SB-I/O;or semi-flush
optional trim ring (BG12TR) may be used. The BG12TR i� mountiny on a standard single-gang, double-gang, or
4"(1 r).16 cm) square electrical box, and shall be installed
DF-52013:D•4/13/2012—Page 1 of 2
,
within the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the con-
trol panel SLC loops. The manual station shall, on command
from the control panel,send data to the panel representing the
state of the manual switch. Manual stations shall provide
address setting by use of rotary decimal switches.
Product Line Information
BG-12LX: Dual-action addressable pull station. Includes key
locking feature. (Listed for Canadian and non-Canadian appli-
cations.)
SB-10:Surtace backbox;metal.
SB-I/O:Surtace backbox;plastic.
BG12TR:Optional trim ring.
17003: Keys,set of two.
Agency Listings and Approvals
In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in pro-
cess.Consult factory for latest listing status.
• UL/ULC Listed: S711 (listed for Canadian and non-Cana-
dian applications).
• MEA:67-02-E.
• CSFM:7150-0075:0184.
• FM Approved.
Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
6,632,108.
FireLiteO AlarmsO is a registered trademark of Honeyweli International Inc.
002012 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
I�O 9001 This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
91CII�91Ni 8 MIWIFACTINIY6 All specifications are subject to change without notice.
QUALITY S�STEMS
Made in the U.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2—DF-52013:D•4/13/2012
df-52417:c•B-90
ANN-8o � Fire•�iTe�A�arms
so-Character LCD by Honeywell
Serial Annunciator
General
The ANN-80 annunciator is a compact, backlit, 80-character
LCD fire annunciator that mimics the Fire Alarm Control Panel
(FACP) display. It provides system status indicators for AC
Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi-
tions.The ANN-80 and the FACP communicate over a two-wire
serial interface employing the ANN-BUS communication format. �
Connected devices are powered, via two additional wires, by
either the host FACP or a remote UL-listed,filtered power supply.
ANN-80 is red;for white,order ANN-80-W. ��'�
���� ; r �
The ANN-80 displays English-language text of system point �.
information including device type, zone, independent point �°��'� �'��� � ��
. �
alarm, trouble or supervisory status, as well as any custom � �„
alpha labels programmed into the control panel. It includes can- �
trol switches for remote control of critical system functions. (A ���`
�.�� ��
keyswitch prevents unauthorized operation of the control � ,
switches.) � � �
� � � �� �
Up to eight ANN-80s may be connected to the ANN-BUS of d - °'
each FACP. No programming is required,which saves time dur- "
ing system commissioning.
Features
• �isted to UL Standard 864,9th Edition.
• Backlit 80-character LCD display(20 characters x 4 lines). ' Supervisory
• Mimics all display information from the host panel. • Alarm Silenced
• Control switches for System Acknowledge, Signal Silence,
Drill,and Reset. Specifications
• Control switches can be independently enabled or disabled • Operating voltage range: 18 VDC to 28 VDC.
at the FACP. • Current consumption C�3 24 VDC nominal(filtered and non-
• Keyswitch enables/disables control switches and mechani- resettable):40 mA maximum.
cally locks annunciator enclosure • Ambient temperature:32°F to 120°F(0°C to 49°C).
• Keyswitch can be enabled or disabled at the FACF • Relative humidity:93%t 2%RH(noncondensing)at 32°C
• Enclosure supervised for tamper. t 2°C(90°F t 3°F)
• System status LEDs for AC Power, Alarm, Trouble, Supervi- • 5.375" (13.65 cm.) high x 6.875" (17.46 cm.) wide x 1.375"
sory,and Alarm Silence. (3.49 cm.)deep.
• Local sounder can be enabled or disabled at the FACP. • For use indoors in a dry location.
• ANN-80 connects to the ANN-BUS terminal on the FACP and • All connections are power-limited and supervised.
requires minimal panel programming.
• Displays device type identifiers, individual poini alarm, trou- Agency Listings and Approvals
ble,supervisory,zone,and custom alpha labels.
The listings and approvals below apply to the ANN-80. In some
• Time-and date display field. cases, certain modules may not be listed by certain approval
• Surface mount directly to wall or to single, double, or 4" agencies,or listing may be in process. Consult factory for latest
square electrical box. listing status.
• Semi-flush mount to single, double, or 4" square electrical . UL:S2424
box.Use ANN-SB80KIT for angled view mounting. . FM approved
• Can be remotely located up to 6,000 feet(1,800 m)from the
panel. • CSFM:7120-0075:211
• Backlight turns off during AC loss to conserve battery power • MEA:442-06-E
but will turn back on if an alarm condition occurs.
• May be powered by 24 VDC from the host FACP or by remote The ANN-61,15
power supply(requires 24 VDC). pOWERING THE DEVICES ON THE ANN-BUS FROM
• Up to eight ANN-80s can be connected on the ANN-BUS.
AUXILIARY POWER SUPPLY
Controls and Indicators The ANN-BUS can be powered by an auxiliary power supply
when the maximum number of ANN-BUS devices exceeds the
• AC Power ANN-BUS power requirements. See the FACP manual for more
• Alarm information.
• Trouble
df-52417:c•05/22/09—Page 1 of 2
ANN-BUS DEVICE ADDRESSING After calculating the total worst case current draw, the following
Each ANN-BUS device requires a unique address(ID Number) table specifies the maximum distance the modules can be
in order to communicate with the FACP.A maximum of S devices �ocated from the FACP on a single wire run.The table ensures
can be connected to the FACP ANN-BUS communication circuit. 6.0 volts of line drop maximum. In general,the wire length is lim-
See the FACP manual for more information. ited by resistance, but for heavier wire gauges, capacitance is
the limiting factor.
WIRE REQUIREMENTS:COMMUNICATIONS CIRCUIT These cases are marked in the chart with an asterisk(`). Maxi-
The ANN-80 connects to the FACP ANN-BUS communications mum length can never be more than 6,000 feet (1,800 m),
circuit. To determine the type of wire and the maximum wiring regardless of gauge used. See table below.
distance that can be used with FACP ANN-BUS accessory mod- w�RE REQUIREMENTS:POWER CIRCUIT
ules, it is necessary to calculate the total worst case current
draw for all modules on a single 4-conductor bus.The total worst • 14 to 18 AWG(0.75-2.08 mm2)wire for 24 VDC power cir-
case current draw is calculated by adding the individual worst cuit is acceptable.Power wire distance limitation is set by 1.2
case currents for each module. volt maximum line drop form source to end of circuit.
NOTE: For total worst case current draw on a single ANN-BUS • All connections are power-limited and supervised.
refer to appropriate FACP manual. • A maximum of eight ANN-80 modules may be connected to
this circuit.
Communication Pair Wiring Distance: FACP to Last ANN-BUS Module
Total Worst Case yy Gauge 78 Gauge 16 Gauge 74 Gauge
Current Draw(amps)
0.100 1,852 ft. 4,688 ft. *6,000 ft. '6,000 ft.
0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.
0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.
0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.
0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.
0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft.
0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft.
0.800 231 ft. 586 ft. 933 ft. 1,476 ft.
0.900 206 ft. 521 ft. 829 ft. 1,312 ft.
1.000(max.) 185 ft. 469 ft. 746 ft. 1,181 ft.
WIRING CONFIGURATION ORDERING OPTIONS:
The following figure illustrates the wiring between the FACP and ANN-80:Red 80 character LCD Annunciator.
ANN-BUS devices. ANN-80-W:White,80 character LCD Annunciator.
ANN-BUS and power ANN-SB80KIT-R: Red surtace mount backbox with angled
wiring are supervised wedge.
and power-limited. ANN-S680KIT W: White surface mount backbox with angled
� B A , _ wedge.
re,
4 3 2 1
ANN-BUS Device
r_ . n s O
MS-9050UD T63
1 2 3 4 5 6 7 8
FACP Wiring to ANN-BUS Device
FireLite�Alarms is a registered trademark of Honeywell International Inc.
002009 by Honeywell International Inc.All rights reserved.Unauthorized use
of this document is strictly prohibited.
'�O �oo� This document is not intended to be used for instaflation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
EN616EEIINi 8 MANtlFACNiINi All specifications are subject to change without notice.
QUIILITY SYSiEMS MadeintheU.S.A.
For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105.
www.firelite.com
Page 2 of 2—df-52417:c•05/22/09