20130325 Interior Lighting Summary 12042014 aw
� � 2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and>3 story R2 and R3
- • � • .
2012 Washington State Energy Code Compliance Forms for Commercial,Group R1,and>3 story R2 and R3 Revised June 2013
Project Info ProjectAddress 10099 senaen Drive sE Date 12/2/2014
Yelm, wa, 98597 For Buiiding Department Use
Applicant Name: c�tY Of Yelm, Kevin Ray
ApplicantAddress: ios Yelm Ave W, Yelm, WA, 98597
Applicant Phone: �360) 458-8414
Project Description �❑ New Building ❑ Addition ❑ Alteration ❑� Plans Included
Lighting Compliance Q Lighting Power Density Calculations Q Total Building Performance
Path (If Total Building Performance then only LGT-CHK is required.)
Interior Lighting Q guilding Area Method QQ Space-by-space Method
Compliance Option
Interior Lighting System Interior lights wil) be 120VAC,fluorescent light fixtures. Lights in the
Description maintenance room and electrical room will be controlled by 3-way switches.
Briefly describe lighting
system type and features.
Additions and Change of Space Use (C101.4.3 & C101.4.4)
❑' Addition area or Change of Space Use area complies with all applicable provisions as stand alone project
� Addition area or Change of Space Use area is combined with existing building lighting systems to demonstrate
compliance with ail appiicable provisions
Provide Building Area Method(LTG-INT-BLD)or Space-By-Space Method(LTG-INT-SPACE)Compliance Form. Document maximum
allowed and proposed(including existing if applicable)lighting wattage of Addition or Change of Use scope. Provide applicable
lighting controls per C405.2 and commissioning of lighting controls per C405.13.
Alterations, Renovations and Repairs (C101.4.3.1)
❑ 60%or more of luminaires in space replaced
Provide Building Area Method(LTG-INT-BLD)or Space-By-Space Method(LTG-INT-SPACE)Compliance Form. Document maximum
allowed and proposed(including existing)lighting wattage of project scope
� Less than 60%of luminaires in space replaced
Provide Space-by-space Method(LTG-INT-SPACE)Compliance Form. Document existing total wattage in space and proposed
(including existing)lighting wattage of project scope
� Lamp and/or ballast replacement within existing luminaires only—existing total interior building wattage not increased
� New wiring installed to serve added fixtures and/or fixtures relocated to new circuit
Provide applicable manual lighting controls(C405.2.1),occupancy sensors(C405.2.2.2),daylight zone controls(C405.2.2.3),specific
application controls(C405.2.3),and commissioning of lighting controls per C405.13
� New or moved lighting panel
Provide all applicable lighting controls as noted for New Wiring,automatic time switch controls(C405.2.2.1),and commissioning of
lighting controls per C405.13.
� Space is reconfigured-luminaires unchanged or moved only
Provide all applicable lighting controls as noted for New Wiring and commissioning of lighting controls per C405.13.
❑ No changes are being made to the interior lighting and space use not changed.
Z�l.�G3z S�
...�
r 2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and>3 story R2 and R3
• � � . � .
• • . � �
2012 Washington State Energy Code Compliance Forms for Commercial,Group R1,and>3 story R2 and R3 Revised June 2013
Project Info ProjectAddress 10099 sensen Drive SE Date 12/2/2014
Yelm, wa, 98597 For Building Department Use
Applicant Name: cicy of Yelm, Kevin Ray
Maximum Allowed Lighting Wattage
Location(plan#, Allowed ross n erior a s owe
room#,or ALL) Space Type` Watts er ftz Area in ft2 (watts/ft2 x area)
Treatment Electrical/mechanical 0.95 2320 2204
Building
Atrium** Enter Height:
Ratail Display Allowance from LGT-INT-DISPLAY
* Select Table C405.5.2(2)category from drop down menu. Area Allowed Watts
"For atriums,indicate height.Allowed wattage for first 40 feet is 0.03 W/ft.ht., Total 2 3 2 0 2 2 04
above 40 feet is 0.02 W/ft.ht.
Proposed Lighting Wattage
Location(plan#, Fixture Description Number of Watts/ Watts
room#,or ALL) (Include exempt equipment per Note 3) Fixtures Fixture Proposed
Treatment T-8 (2) - 32W lamps, energy saving ballast 34 64 2176
Building
Treatment (1) - Emergency Light, 5.4W 5 5 27
Building
Retail Display Lighting from LGT-INT-DTSPLAY ;�,�,.
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Watts 2 2 03
Notes:
1.For proposed Fixture Description,indicate fixture type,lamp type(e.g. T-8), number of lamps in the fixture,and ballast type(if
included). For track lighting,list the length of the track(in feet)in addition to the fixture,lamp,and ballast information.
2. For proposed Watts/Fixture,use manufacturer's listed maximum input wattage of the fixture(not simply the lamp wattage)and
other criteria as specified in Section C405.5.1. For line voltage track lighting,list the greater of actual luminaire wattage or length of
track multiplied by 50,or as applicable,the wattage of current limiting devices or of the transformer. For low voltage track lighting list
the transformer rated wattage.
3.List all fixtures. For lighting equipment eligible for exemption per C405.5.1,note exception number and leave Watts/Fixture blank.
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and >3 story R2 and R3
• � �
2012 Washington State Energy Code Compliance Forms for Commercial,Group R1,and>3 story R2 and R3 Revised June 2013
Project Info Proj Addres ioo99 Jensen Drive sE Date 12/2/2014
Yelm, wA, 98597 For Building Department Use
Name: citY Of Yelm, Kevin Ray
Appl. Name ios Yelm Ave w, Yelm, wA, 98597
Appl. Phone (seo> 958-B919
Project Description � New ❑ Addition ❑ Alteration � Plans Included
Lighting Zone O Zone 1 Zone 2 O Zone 3 Q Zone 4
(as specified by Jurisdiction)
Compliance Option � Lighting Power Density Calculations � Total Building Performance
Building Grounds �Efficacy>60 lumens/W ❑ Controlled by motion sensor
(luminaires> 100 Watts)
❑ Exemption(list)
Alteration Exceptions ❑ No changes are being made to the exterior lighting
(check appropriate box-sec. C101.4.3.1) � New wiring installed to serve added fixtures and/or fixtures relocated to new circuit
Provide applicable exterior lighting controls(C405.2.4)and commissioning of lighting controls
per C405.13
Tradable Maximum Allowed Lighting Wattage Base Site Allowance: 750
owe a s Area(ft),perimeter owe a s
Tradable Surfaces Description per ft2 or per If (If)or#of items x ftZ(or x If)
Main Entry 0 W/LF of door widt 7 195
Other Entries 0 W/LF of door widt 17 340
Uncovered Parking and drives 0.10 W/ft2 16500 1650
Total Allowed Tradable Watts: 2185
TTaCiable PTOpOSeCl Liglltirig Wattage (use mfgr listed maximum input wattage for luminaire.)
Number of Watts/ Watts
Surface Fixture Description Fixtures Fixture Proposed
Entry Canopies LED, (1) - B4W Flourescent Outdoor Light 5 84 Q2�
Uncovere Par ing an LED, (1) - 134W Pole Mounted Light 5 134 67�
rives
Uncovere Par ing an LED, (1) - 45W Pole Mounted Light 1 45 45
drives
Total proposed tradable watts may not exceed the sum of total allowed tradable watts plus Total Proposed Tradable Watts: 1135
the base site allowance. Any base site allowance not needed to make tradable watts comply
can be applied to individual non-tradable categories.
Non-Tradable Maximum Allowed Lighting Wattage Base Site Allowance Remaining: 750
Allowed Watts Area(ft2), perimeter Allowed Watts
Non-Tradable Surfaces Description per ft2 or per If (If)or#of items x ft2(or x If)
Non-Tradable Proposed Lighting Wattage
Number of Watts/ Watts
Surface Fixture Description Fixtures Fixture Proposed
Non-tradable proposed watts may not exceed allowed watts for any individual Total excess Non-Tradable watts: �
surface unless the total excess watts for all non-tradable surfaces are/ess than the p
remaining site allowance. Site Allowance Balance:
�