20110166 Permit Pkg 03052015 _
��o� rHFp�' City of Yelm Permit►vo.: 20110166
� � Community Development Department Issue Date: 3/30/2011
p, tri (Work must be completed within 180 days)
Building Division
Phone: (360)458-8407
YEL
""'°"'»"°" Fax: (360)458-3144
Applicant:
Name: YELM DAYCARE CENTER Phone: 360-402-6871
Address: 1401 MARVIN RD NE, STE 307
LACEY WA 98516
Property Information:
site,4ddress: 15210 BERRY VALLEY RD SE Owner: MARIJKE DEUTSCHER
Assessor Parcel No.: 21724131001 Subdivision: Lot:
Contractor Information:
Name: YELM DAYCARE CENTER Phone:
Address: MARIJKE DEUTSCHER
1401 MARVIN RD NE, STE 307
LACEY WA 98516
Contractor License No.: Expires:
Project Information:
Project: SITE PLAN REVIEW
Description of Work: ORIGINAL APPLICATION 20080243, EXPIRED. CONSTRUCTION OF A NEW CH�LD CARE
CENTER THAT WILL BE BETWEEN 8,500 AND 10,000 SF. PHASE I WILL INCLUDE
CONSTRUCTION OF FRONTAGE IMPROVEMENTS ON BERRY VALLEY ROAD AND
INFRASTRUCTURE ON-SITE TO SUPPORT THE CHILD
Sq. Ft. per floor: First Heat Type(Electric, Gas, Other):
Second
Third
Garage
Basement
Fees:
Item Contractor Fees
CIVL CIV YELM DAYCARE CENTER $ 72.50
SITE YELM DAYCARE CENTER $1,262.50
NEW COMMERCIAL BUILDING YELM DAYCARE CENTER—ISSUED 2/19/2015 �� � $90,438.91
TOTAL FEES: $91,773.91
ApplicanYs Affidavit: OFFICIAL USE ONLY
I certify that I have read and examined the information contained within the application and know the same
to be true and correct. I also certify that the proposed structure is in conformity with all applicable City of #Sets of Prints:
Yelm regulations including those governing zoning and land subdivision,and in addition,all covenants,
easements d restriction of re ord. If appl ing a contractor, I further certify that I am currently Final Inspection:
registered i t�pe State of shin
� /� - _ _ �� Date:
Signature , Date
By:
Firm �
'�o� T"�o,��" City of Yelm Permit No.: 20110166
w ,
� � Community Development Department Fee Calculation Worksheet
Building Division
Phone: (360)458-8407
EL
w�"`"'""°" Fax: (360)458-3144
Applicant:
Name: YELM DAYCARE CENTER Phone: 360-402-6871
Address: 1401 MARVIN RD NE, STE 307
LACEY WA 98516
Property Information:
Site Address: TAHOMA BLVD Owner: MARIJKE DEUTSCHER
Assessor Parcel No.: 21724131001 Subdivision: Lot:
Project Information:
Project: SITE PLAN REVIEW
Description of Work: ORIGINAL APPLICATION 20080243, EXPIRED. CONSTRUCTION OF A NEW CHILD CARE
CENTER THAT WILL BE BETWEEN 8,500 AND 10,000 SF. PHASE I WILL INCLUDE
CONSTRUCTION OF FRONTAGE IMPROVEMENTS ON BERRY VALLEY ROAD AND
INFRASTRUCTURE ON-SITE TO SUPPORT THE CHILD
Sq. Ft. per floor: First Heat Type(Electric, Gas, Other):
Second
Third
Garage
Basement
Fees:
Item Units Fees
WATER ERU 2 $12,125.98
SEWER ERU 2 $12,788.00
SEWER INSPECTION FEE 2 $ 290.00
BUILDING PLAN REVIEW 0 $3,645.68
, WATER METER(COMMERCIAL) 0 $ 650.00
STATE BUILDING FEE 1 $ 4.50
TRAFFIC FACILITIES CHARGE 0 $36,680.00
BUILDING PERMIT CONSTRUCTION VALUE 1,208,464 $5,951.85
LONGMIRE ST SIGNAL 35 $4,802.00
93RD REALIGNMENT 35 $11,293.80
COATES EXTENSTION 35 $2,207.10
TOTAL FEES: $90,438.91
PAYMENTS MADE: $- 3,645.68
BALANCE DUE: $86,793.23
I
�
Cit� af Y�lm
(36 ) 458-3244
REC#: 00187524 2/19/2015 12:04 PM
QPER: CO TERM: 001
REF#; 15027
PAID BY:
TRAN: 33.0000 BUILDING PERMITS
20110166 86,793.23CR
YELM pAYCARE CENTER
TAHOMA BLVD
BLD-CQM1 $6,793.23CR
TENDERED: 86,793,23 CHECK
APPLI�D: 86,793.23-
GHANGE: 0.00
�o� t"�o,� City of Yelm Permit No.: 20110166
�
� � Community Development Department Issue Date: 3/30/2077
d � (Work must be completed within 180 days)
Building Division
Phone: (360)458-8407
L
"'�""'"`T°" Fax: (360)458-3144
Applicant:
Name: YELM DAYCARE CENTER Phone: 360-402-6871
Address: 1401 MARVIN RD NE, STE 307
LACEY WA 98516
Property Information:
Site Address: TAHOMA BLVD Owner: MARIJKE DEUTSCHER
Assessor Parcel No.: 21724131001 Subdivision: Lot:
Contractor Information:
Name: YELM DAYCARE CENTER Phone:
Address: MARIJKE DEUTSCHER
1401 MARVIN RD NE, STE 307
LACEY WA 98516
Contractor License No.: Expires: 0/00/0000
Project Information:
Project: SITE PLAN REVIEW
Description of Work: ORIGINAL APPLICATION 20080243, EXPIRED. CONSTRUCTION OF A NEW CHILD CARE
CENTER THAT WILL BE BETWEEN 8,500 AND 10,000 SF. PHASE I WILL INCLUDE
CONSTRUCTION OF FRONTAGE IMPROVEMENTS ON BERRY VALLEY ROAD AND
INFRASTRUCTURE ON-SITE TO SUPPORT THE CHILD
Sq. Ft. per floor: First 9502 Heat Type (Electric, Gas, Other):
Second
Third
Garage
Basement
Fees:
Item Contractor Fees
CIVL CIV YELM DAYCARE CENTER $ 72.50
MECHANICAL YELM DAYCARE CENTER $ 47.50
PLUMBING YELM DAYCARE CENTER—3/05/2015 �� • $ 258.00
SITE YELM DAYCARE CENTER $1,262.50
NEW COMMERCIAL BUILDING YELM DAYCARE CENTER $90,438.91
TOTAL FEES: $92,079.41
ApplicanYs Affidavit: OFFICIAL USE ONLY
I certify that I have read and examined the information contained within the application and know the same
to be true and correct. I also certify that the proposed structure is in conformity with all applicable City of #Sets of Prints:
Yelm regulations including those governing zoning and land subdivision,and in addition, all covenants,
easements and restrictions of r cord. If applying as a contrac r, I further certify that I am currently Final Inspection:
registered i t tate of 1Nas i gton.
,��^ `` Date:
Signature Date J
By:
Firm
Cit o� yelm
(36�) 458-3244 �15 2,38 PM
00188501 3JU51�
REC#� �ERM: 001
OPER� 1�029
REF#:
PAID �'�� PERMITS
��.0�00 BUILD 25a�00CR
�fRAN�0110166 CENTER
VELM aABLVD�
TANOMA 25g,00CR
p� CHECK
258.00
�fENDERED: 258,00-
APPI-IED�
_----0 OQ
uHANGE:
CITY OF YELM
COMMERCIAL BUILDING PERMIT APPLICATION FORM
Project Address: ;��� ��p%���� CS��� d � /��rr�''�11�s�rParcei#: ��/ � L���� � C� f
Zoning; C - / Current Use:���C�r�,f�„� Proposed Use: C���d��,�� � -�c �a-� �
�'New Construction ❑ Re-Model/ Re-Roof/Tenant Improvement
❑ Plumbing ❑ Mechanical ❑ Fire Prevent/Suppress/Alarm ❑ Other
Project Descriptio lScope of Work: [ !rn S f z� c.7���-� a � C�'��v C a�'� 1� �"c K '-r��°` /
�.
Project Value: � ��� C���O
Building Area (sq. ft) Parking Garage 1�` Floor/�2�d Floor 3�d Floor
Building Height �/�
Are there any environmentally sensitive areas located on the parcel? �� If yes, a
completed environmental checklist must accompany permit application.
BUILDF(VG OWNER/TENANT[V E: �rr�' ��c rK x� t✓
ADDRESS �y0/ �)c�✓v,'�� ��/t/f� ��3a�-2s'y EMAIL .r� r�i�✓ y.7/�� eG,.�c'atJ�'i��7`
CITY ��t c� Y STATE�ZIP 9�'s°/,� TELEPHONE 36U �%01-� S7�
AFtCNITEGT/ENGINEEEt � � ,..ra�� LICENSE# .S" -�T-2 4
ADDRESS EMAIL
CITY C;� �y���� STATE�ZIP �'jkj%' TELEPHONE `� D �U/` `/U�.S-'
GENERAL CONTRACI'4R D�l�V �v ��n r� TELEPHON ` O � ° �� 7/
u
ADDRESS /y�/ �11�,-�.%, Ic'� /1/E S� 1'o7-1J's' EMAIL c �1 �n� 5iZ/J�%�'u,7� �a sf�»7`'
CITY�GI� �i STATE G�v/� ZIP�,5�%6 FAX �/G �-/-3 �" L`.Z Z O
CONTRACTOR'S LICENSE#D�.,,�OFVk,D9�"/kf' EXP DATEs/s�CITY LICENSE#
PLUMBtNG CONTRACTOR r'/s'-F� r.'��, .o,�.� / TELEPHONE iC O6 ��Z "�Cl 9�
ADDRESS g/� S� .3,� � '` Sf' EMAIL
CITY f-c��r,-n/ LL'�� STATE �/� ZIP � �JC�3 FAX
CONTRACTOR'S LICENSE# ' ` EXP DATE �sCITY LICENSE#
MECHANICAL CONTERACTOR o1� �� -� �. TELEPHONE ��C� �-S 5'-y7C� �
ADDRESS � �"�� //�t�'�� �� EMAIL
CITY C">%' � ?��� STATE�ZIP�FAX
CONTRAC OR'S LICENSE# /fG�Tj�/l�'llDy'��} EXP DATE " `CITY LICENSE#
Copy of City Mitigation documentation(TFC).
I hereby certify that the above information is correct and that the construction on,and the occupancy and the use of the
above d cribed property will be in accordance with the laws,rules and regulations of the State of Washington and the
City . Ye . � � �
� ` _
� C �� O � s�
Applica t's Sign ure Date
Owner/Contra to I Owner's Agent/Contractor's Agent/Tenant (Please circle one.)
All permits are non-transferable and will expire if work authorized by such permit is not begun
within 180 days of issuance, or if work is suspended or abandoned for a period of 180 days
�'' � � � �' �,"' JA N 0 2 2015 �
�,�� �
��
(360) 458-3835
105 Yelm Ave W (360) 458-3144 FAX
Yelm, WA 98597 www.ci.yelm.wa.us
�''�of THEp,� City of Yelm Permit No.: 20110166
�
� �� Community Development Department Fee Calculation Worksheet
Building Division
Phone: (360)458-8407
LM
b�'»`T°� Fax: (360)458-3144
Applicant:
Name: YELM DAYCARE CENTER Phone: 360-402-6871
Address: 1401 MARVIN RD NE, STE 307
LACEY WA 98516
Property Information:
Site Address: TAHOMA BLVD Owner: MARIJKE DEUTSCHER
Assessor Parcel No.: 21724131001 Subdivision: Lot:
Project Information:
Project: Building Permit
Description of Work: Construct 9436 square foot Childcare and Pre K School
Sq. Ft. per floor: First Heat Type(Electric, Gas, Other):
Second
Third
Garage
Basement
Fees:
Item Units Fees
BUILDING PLAN REVIEW 0 $3,645.68
BUILDING PERMIT CONSTRUCTION VALUE 1,093,915 $5,951.85
TOTAL FEES: $ 9,597.53
PAYMENTS MADE: $ 0.00
BALANCE DUE: $ 9,597.53
Cit� of Y�lm
(36 ) 458-8402
����� R E P R I NT R E C E I PT*****
REC#: U0181825 1/02/2015 11 :37 AM
OPER: CO TERM: 001
REF#; 15011
TRAN: 33.0000 BUILDING PERMITS
20110166 3,645,68CR
YELM DAYCARE CENTER
TAHOMA BLVD
BLD-COM1 3,�45.68CR
�fENDERED: 3,645.68 CHECK
,'�U�'! I�ii; 3,b45.68-
l.a�ti�U 4. .._._.._,_..�....___..�.44
- - — 420 College St SE ' ' ' '
= � Lacey,WA 98503 Account Number Billing Date Due Date
www.ci.lacey.wa.us 105859-956 03/22/2013 04/19/2013
Billing Inquiries:(360)491-5616 or
�pF��j� utilitybilling@ci.lacey.�va.us
� � �
Kee�� ��«ur Family Safei
• Avoid using products labeled PC�15C�(�,
I���ILJJ�JI��L�I�IJ��II��I���II��I�LI�JI������II��LII DANGER, WARNING c�r CAUTION.
MARIJKE DEUTSCHER • Disf�ose of motor oil, fertilizc�rs, cleanin�;
1401 MARVIN RD NE supplies, propane tanks, fluorescent li�;ht
LACEY WA 98516 .�''�` bulbs ancl more frce of charge <�t Hazo
37 House. Visit www.co.thurstan.wa.us/
sol idwasie/hazardous/f�az-h�me.htm,
or call (360} 867-2491, for information.
o- � �
SERVICE ADDRESS: 7503 PACiFIC AVE SE METER# 16608256
SERVICE FROM 02/17/2013 TO 03/18/2013 PREVIOUS READ 84,216 CURRENT READ 85,550
USAGE 1,334 DAYS 29
WR NONRESIDENT BASERATE 14.19
WR WATER CONSUMPTION 2�.43 YOUR WATER USAGE IS CUBIC FEET. 1 CF=7.48 GALLONS.
UTILITY TAX 2•50 YOUR WATER USE FOR THIS BILLING PERIOD WAS
UTILITY TX-FIRE SUPP 2•51 9,978.32 GALLONS.
TOTAL CURRENT CHARGES 46.63
PREVIOUS BALANCE 82•$$
RECEIPT AMOUNT -213.92
ADJUSTMENTS 0.00
AMOUNT DUE THIS STATEMENT 84.41 CR
CREDIT BALANGE DO NOT PAY
i0000
f �ik�`,��,�*Y���V��v 4;7 �. . 4- y 5 k`� �' 8000
4� '3 ,�' - � ' f' %4�¢ �
k �:�� � � ���$t�'� ."������� .�� ; r� �`�u��� '�"`� �,� "m���
�'
,� '�'� _�� ���,� s����"������� ;������, 6000
�' �, �, ��s�
4000
2000
� -1 � �. G Q '� J C, a 0 Q-
�e-�' e?' ��P .� �J Q� Gti � o �w ,e� �� �,P
PLEASE RETURN THIS PORTION WITH YOUR PAYMENT. MAKE CHECK PAYABLE TO CITY OF LACEY.
AMOUNT DUE NONE
ACCOUNT NUMBER: 105859-956
SERVICE LOCATION: 7503 PACIFIC AVE SE
BILLING DATE: 03/22/2013 $ is enclosed as a donation to"Lacey's Utility Assistance Fund"
DUE DATE: 04/19/2013
��i�n�ii�i��n����n�i�i����n���ini�i���������i�i���ini��)
MARIJKE DEUTSCHER City of Lacey
1401 MARVIN RD NE P.O. Box 90025
LACEY WA 98516 Bellevue, WA 98009-9025
�
' ,
1
1
� STRUCTURAL CALCULATIONS
For
Stepping Stones Children's Center
� Lateral and Vertical
Design
June 12, 2013
� Project# 201395
1
1
�1
� By �
PRECISE ENGINEERING 1NC.
� HAROLD HAHNENKRATT, P.E.
� �,
�q�. H.�#��,,�� 1
�3 Ok �t 4 y� .�.
� -�- �� �„ ;� �O�►�
�� v� : �
— ,o - ,�': w .
1 � 3•, i75� �'�
�� �� � � � �`s�`�e�s��a�`���
� ONAL �
� , �, ,
�j� �/�
�
RECJEIVED
� JUN �'4 2013
� �'�;
�
�
� i � � ii � ii
� - ' � I I I I I I I I 1 I � f -
-_- lll- - - - -11- --_-
- - _ �
� ► � � � � � � , � � - _ -
� III I � _ _ -
� I I I I I 1 I � - -
I I � - _
� I I I 1 I I i - -
� � � � � _ - -
� � � � � � � � � �-- - _ _
� - - -_ - - - ------- �
a
�
� � '
�
� ,
� -��
�� � I
� ------- - �
_ �
�
�
� I
�
�
�
�
� �
� ;
; �
e
,� �
� - �-----�---
� Title Biock Line 1 Project Title:
You can changes this area Ef1�If1EE�: Project ID:
using the"Settings"menu item Pro�ect Descr:
and then using the"Printing&
� Title Block"selection.
' Title Block Line 6 ��m�a ia�u�;zo»,ioaor�.r.�
-----_ ___ _ --------- -- --- - -_ - --�.
rMU�tl le Sim �@ B@8111 File=C:1DOCUME-11HAROlD-11MYOOCU-11ENERCA-11KIDSKA-i.EC6 �
p p ENERCALC,INC.1983 2013,Bwld:6.13.52,Ver.6.13.5.2
�,�� s�a�:o� ��.. , ..,; ;< _ .. _
� Description : Roof Framing ___ __ _ ___ _________�____ __
Wood Beam Design : A
Calculations per 2005 NDS,IBC 2009,CBC 2010,ASCE 7-05
� - -- ---_ -- - ----
BEAM Size : 5.5x18, GLB, Fully Unbraced
Using Allowable Stress Design with 20091BC&ASCE7-05 Load Combinations, Major Axis Bending
Wood Species: DF/DF Wood Grade: 24F-V4
Fb-Tension 2,400.0 psi Fc-Prll 1,650.0 psi Fv 265.0 psi Ebend-xx 1,800.0 ksi Density 32.210 pcf
� Fb-Compr 1,850.0 psi Fc-Perp 650.0 psi Ft 1,100.0 psi Eminbend-xx 930.0 ksi
Applied Loads
Unif Load: D=0.0150, S=0.0250 k/ft,8.0 ft to 24.0 ft,Trib=15.0 ft
Point: D=0.90, S=1.50 k@ 8.0 ft
� Unif Load: D=0.0->0.0940, S=0.0->0.1560 k/ft,0.0 to 8.0 ft I
Design Summarv �,
Max fb/Fb Ratio = 0.714: � p o.o,o.osao s o.0,o.�5so����Y���
D(0.2250)S(0.3750)
fb:Actuai: 1,854.85 psi at 11.600 ft in Span#1 j � • • • � �_ � T_� I
� Fb:Allowabie: 2,596.77 psi � , -- �
Load Comb: +D+S+H ,
Max fv/FvRatio= 0.326: 1 � ` �i
24.0 ft, 5.5x18
fv:Actual : 99.37 psi at 22.560 ft in Span#1 ii
Fv:Allowable: 304.75 psi � �
� Load Comb: +D+S+H Max Deflections
Max Reactions (k) D L �r S w E H Downward L+Lr+S 0.613 in Downward Total 0.980 in
Left Support 2.09 3.49 Upward L+Lr+S 0.000 in Upward Total 0.000 in
Right Support 2.78 4.64 Live Load Defl Ratio 470 >240 Total Defl Ratio 293 >240
� Wood Beam Design : A
Calculations per 2005 NDS,IBC 2009,CBC 2010,ASCE 7-05
BEAM Size : 5.5x13.5, GLB, Fully Unbraced
Using Atlowable Stress Design with 20091BC&ASCE7-05 Load Combinations,Major Axis Bending
� Wood Species: DF/DF Wood Grade: 24F-V4
Fb-Tension 2,400.0 psi Fc-Prll 1,650.0 psi Fv 265.0 psi Ebend-xx 1,800.0 ksi Density 32.210 pcf
Fb-Compr 1,850.0 psi Fc-Perp 650.0 psi Ft 1,100.0 psi Eminbend-xx 930.0 ksi
Applied Loads
� Unif Load: D=0.0150, S=0.0250 klft,Trib=6.250 ft
Desiqn SummaN
Max fb/Fb Ratio = 0.484• � � D(0.09375)Si0.1563)
fb :Actual: 1,292.93 psi at 12.000 ft in Span#1 ; '
Fb:Allowabfe: 2,672.56 psi �
� Load Comb: +p+g+H i -- ------
Max fv/FvRatio= 0.180: 1 24.0 ft, 5.5x13S ` I
fv:Actual: 54.95 psi at 22.880 ft in Span#1 I,
Fv:Allowable: 304.75 psi I i
� Load Comb: +D+S+H Max Deflections
Max Reactions (k) D L Lr S w E H Downward L+Lr+S 0.578 in Downward Total 0.924 in
Left Support 1.13 1.88 Upward L+Lr+S 0.000 in Upward Total 0.000 in
Right Support 1.13 1.88 Live Load Defl Ratio 498 >240 Total Defl Ratio 311 >240
Wood Beam Design : C
� Calculations per 2005 NDS,IBC 2009,CBC 2010,ASCE 7-05
BEAM Size : 6x8, Sawn, Fully Unbraced
Using Allowable Stress Design with ASCE 7-05 Load Combinations,Major Axis Bending
Wood Species: Douglas Fir-Larch Wood Grade: No.2
� Fb-Tension 875 psi Fc-Prll 600 psi Fv 170 psi Ebend-xx 1300 ksi Density 32.21 pcf
Fb-Compr 875 psi Fc-Perp 625 psi Ft 425 psi Eminbend-xx 470 ksi
�plied Loads
Unif Load: D=0.0150, S=0.0250 k/ft,Trib=5.0 ft
� Design Summarv ;
D(0 0750)S(0 1250)
Max fb/Fb Ratio = 0.580• � �
fb :Actual: 581.82 psi at 5.000 ft in Span#1 �
Fb:Allowable: 1,003.48 psi � '
�oad Comb: +p+S+N � C�� �
Max fv/FvRatio= 0.164: 1 �=
fv:Actual: 32.00 psi at 9.400 ft in Span#1 �o.o n, sXa �
Fv:Allowable: 195.50 psi I _�
Load Comb: +D+S+H Max Deflections
� Max Reactions (k) D L Lr S W E H Downward L+Lr+S 0.112 in Downward Total 0.180 in
Left Support 0.38 0.63 Upward L+Lr+S 0.000 in Upward Total 0.000 in
Right Support 0.38 0.63 �ive Load Defl Ratio 1066 >240 Total Defl Ratio 666 >240
�
� Titie Block Line 1 Project Title:
You can changes this area En9ineef: Project ID:
using the"Settings"menu item Pro�ect Descr:
and then using the"Printing&
� Titie Block"selection.
Title Block Line 6 u„�r�d�it i��N,��,io ,oar,i
,. —__. _.._,__ _._..._T .._.____ ___----.._.....____�.. _._..________._._�.---.__.__--,-----___--- _.- - --,
' MU�tI le Sim I@ B@ai'Yl file-C:IDOCUME-11HAROLD-11MYDOCU-11ENERCA-tIKIDSKA-1.EC6
p p ENERCALC,INC.1983 2013,Build:6.13.5.2,Ver:6.13.5.2
� —_�a� �--- i��1.,°�— — �. �— � . . -- --- —� ---�- �-- � — .
Wood Beam Design : D
Calcu�ations per 2005 NDS,IBC 2009,CBC 2010,ASCE 7-05
BEAM Size : 6x8, Sawn, Fu�ly Unbraced
Using Allowable Stress Design with ASCE 7-05 Load Combinations, Major Axis Bending
Wood Species: Douglas Fir-Larch Wood Grade: No.2
Fb-Tension 875.0 psi Fc-Prli 600.0 psi Fv 170.0 psi Ebend-xx 1,300.0 ksi Density 32.210 pcf
Fb-Compr 875.0 psi Fc-Perp 625.0 psi Ft 425.0 psi Eminbend-xx 470.0 ksi
Applied Loads
Unif Load: D=0.0150, S=0.0250 k/ft,Trib=5.80 ft
Design Summary � oro.oa�o�s�o.�aso� '
Max fb/Fb Ratio = 0.873• � I .T—�-T-_—= - �-� -_-- � '
� fb :Actual: 674.91 psi at 5.000 ft in Span#1 i - - -- --
Fb:Allowable: 1,003.48 psi '
Load Comb: +D+S+H ,
Max fv/FvRatio= 0.190: 1 I � - '
� fv:Actual: 37.12 psi at 9.400 ft in Span#1 '� io.on, sxa
Fv:Allowable: 195.50 psi
�oad Comb: +D+S+H Max Deflections
Max Reactions (k) D � Lr S W E H Downward L+Lr+S 0.130 in Downward Total 0.209 in
Left Support 0.44 0.73 Upward L+�r+S 0.000 in Upward Total 0.000 in
� Right Support 0.44 0.73 �ive Load Defl Ratio 919 >240 Total Defl Ratio 574 >240
Wood Beam Design : E
Caiculations per 2005 NDS,IBC 2009,CBC 2010,ASCE 7-05
BEAM Size : 6x8, Sawn, Fully Unbraced
� Using Allowable Stress Design with ASCE 7-05 Load Combinations,Major Axis Bending
Wood Species: Dougias Fir-Larch Wood Grade: No.2
Fb-Tension 875 psi Fc-Prll 600 psi Fv 170 psi Ebend-xx 1300 ksi Density 32.21 pcf
Fb-Compr 875 psi Fc-Perp 625 psi Ft 425 psi Eminbend-xx 470 ksi
Applied Loads �
�, Unif Load: D=0.0150, S=0.0250 k/ft,Trib=28.0 ft
Desiqn Summal y , oro azo,s,c�o;
Max fb/Fb Ratio = 0.811 : � `---------._s.—______�--------*--- ------� ,'
� fb:Actual: 814.55 psi at 2.500 ft in Span#1 ', _ __
Fb:Allowable: 1,004.90 psi '_ �
Load Comb: +D+S+H ' � � �
.� � '
Max fv/FvRatio = 0.392: 1 U �
fv:Actual: 76.70 psi at 4.383 ft in Span#1 '! '
Fv:Allowable: 195.50 psi e.oe, sxa :
� Load Comb: +D+S+H Max Deflections
Max Reactions (k) D L Lr S W E H Downward L+Lr+S 0.039 in Downward Total 0.063 in
Left Support 1.05 1.75 Upward L+Lr+S 0.000 in Upward Total 0.000 in
Right Support 1.05 1.75 Live Load Defl Ratio 1524 >240 Total Defl Ratio 952 >240
�
�
,
�
r
r
�
� Title Block Line 1 Project Title:
You can changes this area Engineer: Project ID:
using the"Settings"menu item Project Descr:
and then using the"Printing&
� Title Block"selection.
Title Block Line 6 a��, . �:�urv.oi�,aa�F:;
�-- ---_-----------_--- - - -------._. --- --- - --- ---- - ---
' St@eI COIUf11C1 File=c:IDOCUME-tIHAROID-11MYDOCU-1\ENERCA-11KIDSKA-1.EC6 �
ENERCALC,INC.1983-2013,Build:6.13.5.2,Ver.6.13.52
� � ��' i.,B�d:4' . - . .
Description: Back Covered Play area post
Code References
� Calculations per AISC 360-05, IBC 2009,CBC 2010,ASCE 7-05
Load Combinations Used :ASCE 7-05
General Information
- - - --- ---_ --
� Steel Section Name: HSS6x6x1/8 Overall Column Height 10.0 ft
Analysis Method: Allowable Strength Top&Bottom Fixity Top Free, Bottom Fixed
Steel Stress Grade Brace condition for deflection(buckling)along columns:
� Fy:Steel Yield 46.0 ksi X-X(width)axis:
E:Elastic Bending Modulus 29,000.0 ksi Fully braced against buckling along X-X Axis
Load Combination: ASCE 7-05 Y-Y�depth)axis:
Fu ly braced against buckling along Y-Y Axis
� Applied Loads Service loads entered. Load Factors will be applied for calculations.
Column self weight included:98.504 Ibs'Dead Load Factor
AXIAL LOADS...
Beam B:Axial Load at 10.0 ft,D=1.130,S=1.880 k
� Beam A:Axial Load at 1 D.0 ft,D=2.090,S=3.490 k
BENDING LOADS...
Lat.Point Load at 10.0 ft creating Mx-x,W=0.4440 k
� DESIGN SUMMARY _
Bending 8�Shear Check Results
PASS MaY.Axial+Bending Stress Ratio = 0.4612 :1 Maximum SERVICE Load Reactions..
Load Combination +p+W+H Top along X-X 0.0 k
Location of max.above base 0.0 ft Bottom along X-X 0.0 k
At maximum location values are... Top along Y-Y 0.0 k
Pa:Axial 3.319 k Bottom along Y-Y 0.4440 k
Pn/Omega:Allowabie 74.371 k
� Ma-x:Applied -4.440 k-ft Maximum SERVICE Load Deflections...
Mn-x/Omega:Allowable 10.116 k-ft Along Y-Y 0.5661 in at 10.Oft above base
for load combination:W Only
Ma-y:Applied 0.0 k-ft
Mn-y/Omega:Allowable 10.116 k-ft Along X-X 0.0 in at O.Oft above base
� for load combination:
PASS Maximum Shear Stress Ratio= 0.02049 :1
Load Combination +p+W+H
� Location of max.above base 0.0 ft
At maximum location values are...
Va:Applied 0.4440 k
Vn I Omega:Allowable 21.671 k
� Load Combination Results
Maximum Axial+Bending Stress Ratios Maximum Shear Ratios
Load Combination Stress Ratio Status Location Stress Ratio Status Location
D Only 0.045 PASS 0.00 ft 0.000 PASS 0.00 ft
� +D+L+H 0.045 PASS 0.00 ft 0.000 PASS 0.00 ft
+D+Lr+H 0.045 PASS 0.00 ft 0.000 PASS 0.00 ft
+D+S+H 0.117 PASS 0.00 ft 0.000 PASS 0.00 ft
� +D+0.750Lr+0.750L+H 0.045 PASS 0.00 ft 0.000 PASS 0.00 ft
+D+0.750L-�.750S+H 0.099 PASS 0.00 ft 0.000 PASS 0.00 ft
+p+W+H 0.461 PASS 0.00 ft 0.020 PASS 0.00 ft
+D+0.70E+H 0.045 PASS 0.00 ft 0.000 PASS 0.00 ft
� +D+0.750Lr+0.750L+0.750W+H 0.351 PASS 0.00 ft 0.015 PASS 0.00 ft
+D+0.750L+0.750S+0.750W+H 0.379 PASS 0.00 ft 0.015 PASS 0.00 ft
+D+0.750Lr+0.750L+0.5250E+H 0.045 PASS 0.00 ft 0.000 PASS 0.00 ft
+D+0.750L+0.750S+0.5250E+H 0.099 PASS 0.00 ft 0.000 PASS 0.00 ft
� +0.60D+W+H 0.452 PASS 0.00 ft 0.020 PASS 0.00 ft
' +0,60D+0.70E+H 0.027 PASS 0.00 ft 0.000 PASS 0.00 ft
,
� Title Block Line 1 Project Title:
You can changes this area En�ineer: Prolect ID:
using the"Settings"menu item Pro�ect Descr:
and then using the"Printing&
� Title Block"selection.
Title_BlockLine6..____---------_ .__-----��__.�_.----- N-���ea �s�uNaoi, caaur.�.
_ _ - --__ ________--- _..------------ --- - - __
I!, St@@I COIUIl1C1 Ftle=c:1DOCUME-11HAROLD-11MYDOCU-11ENERCA-11KIDSKA-1.EC6
ENERCALC,INC.19832013,Build:6.i3.5.2,Ver6.13.5.2
� ��.. t:i d:l' . ..� . - . ��..a . _ -�.a. .
DesCription: Back Covered Play area post
Maximum Reactions-Unfactored Note:�nly non-zero reactions are listed.
� - X-X Axis Reaction - Y-Y Axis Reaction Axial Reaction
Load Combination @ Base @ Top @ Base @ Top @ Base
D Only k k 3.319 k
S Only k k 5.370 k
� W Only k -0.444 k k
D+S k k 8.689 k
D+W k -0.444 k 3.319 k
� Maximum Deflections tor Load Combinations -Unfactored Loads _ _ _ __ - - -
Load Combination Max.X-X Deflection Distance Max.Y-Y Deflection Distance
D Only O.00DO in 0.000 ft 0.000 in 0.000 ft
S Only 0.0000 in 0.000 ft 0.000 in 0.000 ft
� W Only 0.0000 in 0.000 ft 0.566 in 10.000 ft
D+S 0.0000 in 0.000 ft 0.000 in 0.000 ft
D+W 0.0000 in 0.000 ft 0.560 in 9.933 ft
Steel Section Properties : HSS6x6x118
� Depth = 6.000 in I�c = 15.50 in^4 J = 23.900 in^4
S�c 5.15 in^3
Width = 6.000 in R xx = 2.390 in
Wall Thick = 0.125 in Zx = 5.920 in^3
� Area = 2.700 in^2 I yy = 15.500 in^4 C = 8.030 in"3
Weight 9.850 plf S yy 5.150 in^3
R yy = 2.390 in
� Ycg = 0.000 in
�
_ _ _ _
� __ Adeeo�Loads _
I �! ��'�
,�,
� `' � �
� �� ��' r; �I ��a ��
o'I 'I Load F � X o�
�� �� �_� ���
�w �� r{ 11 I ,j
� L :j
I �I
'� � a
jI " = i
! ���
�i � � �� �
� I . . . i: I � ��
L Y '
6.00in �j Loads are total entered value.Arrows do not reflect absolute direction.
� _._ __ __ _ __ _ _ _ _ _ _ _ _ _ ;
�
�
�
� Title Block Line 1 Project Title:
You can changes this area En�ineer: Proiect ID:
using the"Settings"menu item Pro�ect Descr:
and then using the"Printing&
� TitleBlock"selection. _ �:�te�.�3�uh��i� �a�F��^
Tltle._BIOCk Lme 6 .______ ---- .-- -- Fde=c:1DOCUME-11HAROLD-11MYDOCU–t\ENERCA-11KIDSKA-1.EC6
POIE.' FOOtlilg ECl'1�@CICi@Ci 111 SOI) ENERCALC,INC.1983-2013,Buiid,6.13.5.2,Ver:6.13.5.2
� .���� �, ��.e��:�� + .��_,� . � ��,a °:-:;, �*< ,�s_�. . ��� .a-�_
� �
Description: —None--
__Code References___ _____ __
� Calculations per IBC 2009 1807.3, CBC 2010,ASCE 7-05
Load Combinations Used :ASCE 7-05
General Information
� Pole Footing Shape Circular _
Footing Diameter............ 24.0�� '°^"�°
Calculate Min.Depth for Allowable Pressures
Lateral Restraint at Ground Surface
� Allow Passive. . .. .............. 150.0 pcf
Max Passive... ................ 1,500,0 psf
Controlling Values
� Goveming Load Combination: +p+Nl+{i
Lateral Load 0.4440 k
Moment 4.440 k-ft
� Restraint @ Ground Surface
Pressure at Depth Sal Sudace � Surface Lateral Restraint
Actual 718.0 Psf '`" `` `— `� � `— � '-
Allowable 723.19 Psf _ `L..; � � �i �. ?� �.� � !
� Surface Retraint Force __ 3,046.76 Ibs � �, � � �, � � �' � � �
Minimum Required Depth 3.625 ft �" � �' ��..���� '— `— `- i`-
� Footing Base Area 3.142 ft^2 _. _�J
Maximum Soil Pressure 2.766 ksf Footing Diameter=2'-0•
� Applied Loads
Lateral Concentrated Load Lateral Distributed Load Applied Moment Vertical Load
D:Dead Load k k!ft k-ft 3.320 k
� Lr:Roof Live k k/ft k-ft k
L:Live k k/ft k-ft k
S:Snow k k/ft k-ft 5.370 k
W:Wind 0.4440 k k/ft k-ft k
� E:Earthquake k k/ft k-ft k
H:Lateral Earth k k/ft k-ft k
Load distance above TOP of Load above ground surface
ground surface 10.0 ft ft
� BOTTOM of Load above ground surface
ft
Load Combination Results
r
"' Forces@ Ground 5urface Required Pressure at Depth 5oil Increase
Load Combination Loads-(k) Moments-(ft-k) Depth-(ft) Actual-(ps� Ailow-(ps� Factor
�' +D+S+H 0.000 0.000 0.13 0.0 18.8 1.000
+p+W+H 0.444 4.440 3.63 718.0 723.2 1.330
� +D+0.750L+0.750S+0.750W+H 0.333 3.330 3.38 621.2 673.3 1.330
+0.60D+W+H 0.444 4.440 3.63 718.0 723.2 1.330
�
�
'
�
� SCOPE: Provide structural calculations for lateral and vertical design per the 2009
IBC.
�
LOADS AND MATERIALS
� Roof Comp Roofing(2layers) S.Opsf
Pre-engineered Trusses @ 24" oc 2.9psf
� Roof Sheathing 1.Spsf
Insulation 1.2psf
5/8" GWB 2.8psf
� Misc. 1.Spsf
Dead Load = 14.9»17psf
Snow Load = 25psf
� Wall: 2x6 Studs @ 16"oc Dead Load = l Opsf
r
� Floor: Attic Trusses Dead Load = 12psf
Live Load = 40psf
Plus Mechanical
� Wind: 85 MPH Exp. B
r
Seismic: Site Class = D
Design Category = D
Use Group = I
� R = 6.5,2.2
Cd = 4
� �o = 3
Soil: = 1500 PSF, Assumed bearing capacity
� = 38 PCF, Assumed Active Fluid Pressure
350 PCF, Assumed Passive fluid Pressure
= 0.45, Assumed Coefficient of Friction
� = 110 PCF, Assumed Soil Density
� Lumber: 2x > 4x = #2DF
6x > _ #1DF
GLB = 24f-v4 for simple span
� = 24f-v8 for cont. and cantilever.
Concrete: flc = 2500psi
�' Rebar = Grade 60
�
�
� .
_ _.
,
�
�
LATERAL DESIGN
� Wlnd Load111g: Simpiified(ASCE 7-05 Section 6.4)
� ps = �Kn�WP53o
Wind Speed s5 mph
Exposure B
� Roof Pitch 5:12
� _ �
� Kn= �
1 = 1
ps30 = 10 (Roof)
� 12.8 (Wall)
ps= 10.0 (Roo�
� 12.8 (Wall)
� Seismic Design Category - Conterminous 48 States
Latitude = 46.9461, Longitude = -122.62449
MCE MAP VALUES
� Short Period Map Value - Ss = 117.3% g
1.0 sec Period Map Value - S1 = 37.3% g
RESIDENTIAL DESIGN INFORMATION
� Short Period Map Value - Ss = 117.3% g
Soil Factor for Site Class D - Fa = 1.03
Residential Site Value = 2/3 x Fa x Ss = 80.6% g
� Residential Seismic Design Category = D1
� Seismic Loading: Section 12.4,12.8 IaC
Eh=pQh Qh=V p=1.3
� V= CSW
CS=SoS/1.4R
� E=(1.3Sps/1.4R)W
$ps 0.806
� R = 6.5 (Wood Shear Wall)
R = 1.5 (Cantilever Column)
V= 0.115 Wt. (Wood Shear Wall)
V= 0.461 Wt. (Cantilever Column)
� .
'
� o a o o �
O O � �
� �
�
� �
�
O O
� � o
�
�
� �
O -�
� O �
� O
�
�
O
� � �
� ❑
� � O
� �
� �
� � �
o �
� � � �
�
� �---
� �
� 0 �
�
�
� � �
0 0 � �
�
�..
� o 0
�
n !' a o 0 0 �� �
�'� �
�
�
.
�
� One Sto Wind to Diaphra m
rY 9
Wind
� Main Plate Height 10 Roof 10
Walls 12.8
� Diaphragm
� Roof Ht. Gable Ht. Wind Load Length Total Load
1-2 Roof 0 3.5 44.8 8.0 358.4
� 2-3 Roof 7 0.0 134.0 11.0 1474.0
� 3-4 Roof 11 0.0 174.0 35.0 6090.0
4-5 Roof 11 0.0 174.0 53.5 9309.0
5-6 Roof 11 0.0 174.0 54.5 9483.0
�,
� 6-7 Roof 11 3.5 44.8 8.0 358.4
� SUM 27072.8
Roof Ht. Wind Load Length Total Load
A-B Roof 5.5 0.0 71.0 25.0 1775.0
�
B-C Roof 11 0.0 174.0 54.0 9396.0
��
C-D Roof 5.5 0.0 119.0 32.0 3808.0
�
� �'��� ����� SUM 14979.0
���
�� �Q �}.y�- l'�� I�3�1�I�� 1� I � �
� � �
��J'�i t� 1��1-� �►���l�rt �,y1 �'z�`� � �'a- I � Z�^�'`' Z����'�
L . �� c�
� �
� . 1 �.,7 ,
,� �����, h��� �; �i� � I�� ���`� , � ,
`�'� � ��� �'�� � `
� � � �� �� �����
�r� � �,� `►�� � %�� �' �
� �;�, °���� - ,��.�
����
_
�
1
� �
�
� o 0 0 0 0 0 0 0 0
� �� � ti � � � � � � �
� � II II II 11 II II II II II
°� Q. n. a n a a n. a a
� m m m c� cu ca m m co
� U U U U U U U U U
� �� � � � � � � � � �
ca �
d O Z � o-°o a-°o a-°o � w � � o�°o
(� y OJ � � N (O � � � N
�. 11 � I� n � tf� 6� I� V �
� � �t C'7 � � c- '�t � (O ct
� �
C �(O a0 CO O� 6� � � � O
E � M N � � O M V� '�t �
� O � � O CO N � � U'7 CO �
� " N N (D CO � � <-
C O t� � � � O tn � �
� �N Lf� N N ' N N tf) 6j
N M t1') 6) �Ci � � � oJ O �
� Q V M rf
co
� C N � V � �,-� N I� 1� O
� � r co v r� co ri r�
e� N cfl � � c0 6� � o
= V � � � �
>
� � ,�� CO � N 00 � CO N �
N Q � M lf') (O I� 6> � V
� c- <- C� 00 00 N � l!')
�
� � v o o � �n � � o 0
� � � r~i � � v � � a�o 0
s " C`') 1� Ch t7 V M 00 00 �
�
� �
��O O O O O O O � O
C � O �t t0 � V' O O � �
� J `� M � OD � Lf) M M � M
�
� � � � O O � � � O O O
a � � � tn M 'V' � � V N
Q � �'' M � Lf� N � M
� �
C�� O O O O � � O O
� d' V V V N Q�
O n- � M f� !� 1� V � N �-
� V J
C
C `� N
� O O O O O O O O O
� � � O O O O O O O O O
� C @ Q J
�� >
W 0 �p
y fp � N M � tn CO h L.YI U �
'� � � J .� N ri v �n co Q [0 U
� a o U
�
�
�
�
��"" � tf7 N O t� O � � N 00 � �
�, � O O O p O � O � O M O � O O O O O o0 O � O ti O � O O M O
1— � M t� 6� � N °� �p p� � N
�B
� O
� O O O O O O O O O O O O O O O O O O O O O O O O O O O O
�
�
�
�
7 7
� �
.:::.:�:::.;�::.:,�: .:� �::::� .�. ��:-.::: �...::::.::-��::.::::�:.::.>�.�::�:: �: :;.: �.... . ... .. . .::..:::.: .:::�..:. ...:.�:::.. .. . .:.:.: :::. .. . ..::::
� �
N
J
� . . . . . . . . . . .
.... .......... .......... .......... ........ . ....... ..... ......... ...... .... .... ...... .... ... ......... ..
�
�
�.
.. ... ....... .... ... ......... . . . ...... .. .. ..... ......... ..... ..
�
� W
Z
J
�
� � N
� � � N O t� O � � N �O '� �
Q � O O O � O � O � O � O � O O O O O N O � O � O � O O c'7 O
O `— M f� � � N � � � � N
J
� � � �
� � �
� : ::::::.. _. . ::;::..: :.:: ::.: :.........::.: :.:: ._..:: . ::::::.. .. ::;; :.::::: :. .::: ::::..::_ .::.;
� lfl Lf')
�' d" �'
�
tl) tC) ct' �
Q"' O O � d>
j M (h r c-
� ... .:;::... �:��.�::::: �:::.:..:: ....:.:.�::::. .:::.....: �.:. -.:::. �.. �:::::::: �:.::::: �:. �:::.�:.:::�.:.:. ��. :: ::::�::::. :::::::::
� � � � �
� . . . . . . . - . . - . .
� � �
�„ C'') CO CO
i
�
� N M �h � CO Q Cfl U �
�" C
J
�;
�
I �
� TYPICAL SHEAR WALL NOTES
Use 5/8" dia. by 10" Anchor Bolts (AB's) with single plates and 5/8" dia. by 12" AB's with double
� and 3x plates spaced as shown on the drawings. AB's shall have 7"of embedment into footing,shall
be centered in the stud wall, and shall project through the bottom plate of the wall and have a
3x3x1/4 plate washer. At existing foundation use 5/8" diameter Simpson Titen HG bolts with
� minimum of 4" embedment into the existing concrete.
All wall sheathing shall be 1/2" CDX plywood, 5/8" T1-11 siding, or 7/16" OSB with exterior
� exposure glue and span rated"SR 24/0"or better. All free sheathing edges shall be blocked with 2x4
or 2x6 flat blocking except where noted on the drawings or below.
� All nails shall be 8d or l Od common(8d common nails must be 0.13 2 inch diameter, Senco KC27
Nails are equivalent. If l Od common nails are called for the diameter must be 0.148 inches, Senco
� MD231�Tails are equivalent). Nail size and spacing at all sheathing edges shall be as required below
or as in the drawings. Nail spacings shall be 12" o.c. for all field nailing except as noted.
� Hold downs are Simpson"Strong Tie"and shall be installed per the manufacture's recommendation.
Equivalent hold downs by United Steel Products Company"Kant-Sag"that have ICBO approval can
be substituted in place of Simpson hold downs. All floor systems must be blocked solid below
� member that the hold down is attached to. This block should be equal to or larger than the member
the hold down is attached to and be placed as a"squash block".
� All double and triple studs shall glued and nailed together with l Od's at 3" o.c. for each layer.
A114x studs are to be#2 DF and all 6x studs are to be#1 DF when used for hold downs and shear
walls.
� All fasteners in contract with pressure treated lumber shall be zinc coated in accordance with
ASTM B 695,Class 55 minimum. Fasteners exposed to weather must meet the requirements
� of the pressure treating manufacture's minimum. IN ADDITON, the contractor shall
coordinate connector/fastener coating requirements with recommendations from
connector/fastener manufacturer and type of pressure treating chemical and retention being
� used. See Section 2304.9.5 of the 2009 IBC for additional information.
� ALL WALL AND ROOF FRAMING LUMBER SHALL BE DOUG-FIR#2 OR BETTER.
� NOTE.• MST STRAPS attaches to (2) 2x or 4x studs in wall above and below unless noted
otherwise. Nail all holes with 16d sinkers.
� SHEAR WALL SCHED ULE
�-=--a sheathing nailed with l Od's at 6" on center all edges.
�
i
f
,
� HOLD DOWN SCHED ULE
It is the responsibility of the contractor to locate hold down anchor bolt to accommodate all
� structural framing. Anchor bolt to be located nearest the corner or opening at the end of the
shear wall. All foundation vents to be a minimum of 12"off centerline of the anchor bolt on
either side. Holdown stud to be coordinated with shear wall panel edge framing
� requirements. Larger stud size controls
* For holdown anchor bolt embedment greater that foundation depth, thicken footing
� for 2'-0" either side of holdown anchor bolt to a depth that provides for 3" clear
below the bottom of the anchor bolt. Provide(2) additional #4 x 3'-0"pieces of
longitudinal rebar at this location.
�
OHDZI2 attaches to concrete foundation with a Simpson SSTB 16. HDU2 attaches to
� double 2x studs or 4x or 6x stud with (6) Simpson SDS 1/4 X 3 Wood
Screws in wall above.
�
r
r
�c
r
i
�
1
�
1
I
I .
�
� w w w � 3
� n n o �
� o 0 0 o a Q Q Q a
Ur� v � � = c
I � �V\c'J N � � O � V
� � v� � — lf1 M aD
m a — � ° o 0 o H � � ro c�
>� N N
>
N
� L � � O O .-- V
� � _ ^ O O V T
Z � � � rn c� W
�n N c�
j CV � N
O
— � N
(0
U
c o 0 0 0 0
>' 3 v o cD cfl v
m � � > � � N � �
N t
� � �
>@ V � � � � �
� > � � � N � �
,V '—^ — — — 'U � t[7 ln t!J � 7 O O .-- V
�CJ O O (O I�
@ cD o7 O) 7 � O t[7 cD M �' N I� I� (7 N
� — U N c') V c0 v c") V tA N � t-- N N M N
cD V c`� N N V 1n N
� N (0 (6 @ t0 3 N � 7 � U CO N O O O O
� cna �o � �o � i� � � � � Q v v a �
`m �pmo� m � 22 2 2 �
a� o �
L = � ca
�
Q a �
0 o Q � �
m m Q _ �
U U w � o 0 0 0
�tl = � �— � � N .—
�
� O [O I�
> � � � �
N I� c`"J N
N c�"J N
� — L O O O O
� @ O O O O
� _
�
� L � @ � O O O
p > CO CO a0 c7
� � > M N N N
2
N II �� II
� @ t L L
a �,
a� � '�
= = x
� � � r
o � o
p � o
LL LL LL
� � �
N C �
� N (''J
� �
�
�� x � �
W
N
�" @ O
— � r
�' "' Q
� N � O O �
�.,
U � N � ai
i�` 0] N N N� tn O O �
� � O �
� O Q) � � N
L � �
V II II II
� _ _ _ = O O O O O O
� � � � �
ltJ r N O h O
X X X X � � � � O O� O
�� N N M c`') O W f� f� M
� V c`� I� W �
N 16 N N
Q 0 � 0
� � � � � �
\ W` � N
� � � � J
�
� >� N C`') V �A CO
� >
�
�
� www � _
u a n o � � �
O U O V CO�D O = C C C
� � 7 M N � � N �D O
T@ N � 'O 'o 'O O � I� V
� V1 � O O O F- � N <p �C1
ma �
�
� �
� � N cD o
N — � M N
Z � � 1� V
� N � �
O
N �
� U c o 0 0
m a°'i � o co cri v
� O c� c%� �
� ca �
Otn
°. o 0
� � N r �
�•
U w w ..-w .V tn tn uJ � � � � �
Lf� O�
t° 0000 �60 ;° � � a �n � �
� — � co co rn a � c� c �n co � cD �
rn
U t� c� v cn U .-
cD V c�] N N C � N
m n�i m m m m 3 n�i > > > CJ [0 m o O o
3 (� a 'o � 'o �° (4 � = � � Q � V V V
� m m co m m
r = t�
� J (0
�
O O Q � I�
N N a _ �
� U U w � o 0 0
� � ~ E
�
O �J O N
� U � W �
d � n �
>
� � `-
C
— L �
o � V o 0 0
� � o 0 0
2
� L � @ O O O
� F > ln U7 N
�
d II �� II
d � L �
� � � �
_ _
///(((...���^^^ � � � �
� O � 0
p � O
lL ,D � �
N C �
� N M
� �
x � O O
� �
� �
� � O
— M �
T > N
U a
lv N O O �
U � N N � �
� 0 O7 O � O O
CO N N N
� � � N n �
O m r �
r II II II �
U
�: � � � � � Q O O O
� J � r W O
N N t� ch p� I� f� 6)
N !9 @ @ N �
� 0 � �
N N N � N a' Q' Q' Q'
� � ln r tn J
@ Q m V �
�
�
' • • - • � •
2012 Washington State Energy Code Compliance Forms for Commercial Buildings inGuding R2&R3 over 3 stories and all R' Re��sedocc2ois
Pro.ject Info Project Address TAHOMA BLVD sE, YELM WA Date 2/17/2015
For Building Department Use
Compliance forms
do not require a
password to use. q licant Name: rraxi,7xa DEUxscx�x
Instructional and PP
calculating cells are Applicant Address: iaoi Maxvix xD sE #307-256, I,ACEY WA 98516
write-protected.
Applicant Phone: s6o-aoz-ea�i
Project Description �New Building ❑Addition ❑Alteration ❑ Change of Occupancy/Conditioning
Complianee Path Q Prescriptive Q Component Performance Q Total Building Pertormance
Selection required to enable forms.
Occupancy Group ��mmercial 0 Group R-R2& R3 over 3 stories and ali R1
Selectron required to enable forms.
Vertical Fenestration and To#al Vertical Gross Exterior
Sliylight Area Calculation Fenesiration Above Grade %Vertical
(rough opening} divided by Wall Area times 1�equals Fenestration
If complying via the Prescriptive path,
entervaluesforverticalfenestration, 774 .0 — 5238.0
skylights,gross walls and roof on this - X ��� - �.4 •8°
ENV-SUM worksheet. If complying via
the Component Performance path,enter Gross Exierior
these values in the ENV-UA worksheet. Total Skylight divided by Roof Area times 1 QO equals °fo Skyligh#
These values auto-fill from ENV-UA and
are write-protected on ENV-SUM. 0 .0 — 0.0 X �QQ =
Vertical VER7IGAL FENESTRATION AREA COMPLIES
Fenestration Area �enestration Area
Compliance
Skylighf Area
Vertical Fenestration 0 5d°l,ar more of the floor area is within a daylight zone per C402.3.1.1
Alternates Q High Performance Fenestration U-factors and SHGC per C402.3.1.3
Compliance Method
❑Skylight area 3%or grea#er,VT-0.40 or greater
Single Story Spaces ❑Skylight effective aperture 1°!0 or greater,provide calculation
Requiring Skylights ❑space eligible tor exception
Requiies a minimum of 50%of ftoo��a�a to be vrifhin a skytight daylight zone tor spac�frc
space types.Reter to C402.3.2 for requirernents.
❑ Project has semi-heated spaces as defined per C402.1.4
❑Applying wall exception to semi-heated spaces
1. Semi-heated spaces may comply under Prescriptive or Component Performance compliance
Semi-Heated Spaces path.
2. Semi-heated spaces shall be documented separately from other conditioned spaces-provide
separate compliance forms for each conditioned space type.
3.Envelope elements separating semi-heated from other conditioned spaces shall comply with
exterior thermal envelope requirements.
�Walk-in Cooler ❑ Walk-in Freezer
❑ Refrigerated Warehouse Cooler ❑ Refrigerated Warehouse Freezer
Refrigerated Spaces Refrigerated spaces shall comply under the Prescriptive Path only. Compliance documentation for
these areas may be combined with non-refrigerated areas in the ENV-PRESCRIPTIVE form. Refer
to C402.5 and C402.6 for requirements.
Project includes more than one occupancy type and/or level of space conditioning.Multiple
Mixed Oeeupaney and/or compliance forms may be required. Select all that apply to scope of project:
Spaee Conditioning ❑ Commercial � R2&R3 over 3 stories and all R1 � Refrigerated Space
❑ Fully Conditioned ❑ Semi-Heated (� Low Energy`
❑ R2&R3-3 stories or less
"Low energy areas are exempt from al!thermal envelope provisions and compliance forms for
these areas are not required.Refer to C101.5.2 for exemption.
- � • - - � • • � � • A
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all I RevisedOci2073
Minimum Requirements This table summarizes prescriptive compliance requirements for opaque elements and fenestration.Refer
for Prescriptive Compliance to Tables C402.1.2,C402.2 and C402.3 in the 2012 WSEC for important foofnotes thaf apply to
these tab/es. Refer to Section C402 for al/applrcab/e requirements that apply for each envelope element
type and applicable exceptions
"fablc C402.2���s�'� Table C402.1.2�otes 1,2
Prescriptive Path Insulation Minimum R-Valae Assembiy Maximum C(-factor
Occupaocy Group All Other Group R AII Other Group B
Opaque Elemcnts ,
Roofs
Insulation Entirely above Deck R-30 c.i. R-38 c.i. U-0.034 U-0.031
Metal Buildin (with R-3.5 thermal blocks)Nore s R-25+R-I 1 Ls R-25+R-11 Ls U-0.031 U-0.031
Attic and Other R-49 R-49 U-0.021 U-0.021
WaUs,Above-grade
Mass R-9.5 c.i. R-13.3 c.i. U-0.104 Note 6 U-0.078
Metal Building R-13+R-13 c.i. R-13+R-13 c.i. U-0.052 U-0.052
Steel Framed R-13+R-lOc.i. R-19+R-8.5 c.i. U-0.055 U-0.055
Wood Framed and Other R-21 int R-21 int U-0.054 U-0.054
Below Grade Wa[l Noce a Same as above grade Same as above grade
Floors
Mass R-30 c.i. R-30 c.i. U-0.031 U-0.031
Steel Joist R-38+R-10 c.i. R-38+R-]0 c.i. U-0.029 U-0.029
Wood Framed and Other R-30 R-30 U-0.029 U-0.029
Slab-On-Grade F[oors
Unheated R-10 for 24 in.(from top of slab) F-0.54 F-0.54
Heated Noce 5 R-10 perimeter&under entire slab F-0.55 F-0.55
Opaque Doors
Swinging No T2-Ualue for prescriptive compliance.' U-0.37 U-0.37
Roll-u or slidin K-4J� IZ-4.7� Tti'��U-Value for rescriptive coinpliaoce.
Table C403.3-0-30%of wnll area,or Seetron Cd02.3.1.3 Hia/1 Performr�rrce
30%-�0°o per Seciio�a C4(12.3./.1 DLZ Fenestratio�e Option-0-40�o of ivatl area
�euestratio h�r�s i,2
�E As�emblv Vlaximum U-factor
Vertic¢!Fenestration
Nonmetal framing U-0.30 U-0.30 U-0.28 U-0.28
Metal framing(fixed) U-038 U-0.38 U-0.34 U-034
Metal framing(operable) U-0.40 U-0.40 U-036 U-0.36
Entrance doors U-0.60 U-0.60 U-0.60 U-0.60
Skyligl:ts
Skylights U-0.50 [i-0.50 U-0.50 U-0.�0
Fenestration Assembty Maximum SHGC Factor
vertica[Fenestration PF<02:all oricntations-SHGC-0.40 PF<02:all orientations-SHGC-0.3�
02<-PP<Q5:north-SHGC-0.44; 0.2<_PF<0.5:north-SfiGC-0.385;
all other-SHGG0.48 all other-SHGG0.42
PF?0.5:north-SHGC-0.48; PF?0.5:north-SHGC-0.42;
all other-SHGC-0.64 all other-SHGC-0.56
Skylights S HGC-0.3� S HGC-0.35
� Insulation Minimum R-Value
Refrigerated Spaces Insulation Table C402S and C402.6 Assembly Maximum U-factor
Freezers-Walk-irz aad Wareltouse
Roof/Ceiling R-32
Wall R-32
Door R-32 No U-Valtae far prescriptive compliaijce
Door-transparent reach-in triple-pane,heat-reflective treated or ga,
Floor R-28
Coolers-Walk-in and Warel:ouse
Roof/Ceiling R-25
Wall R-25
Door R-25
Door-transparent reach-in double-pane,heat-reflective treated& No U-Valuc f��r prescriptive complia3�ce�
gas fill,or comply with freezer doar req.
Floor No Requirement
• • ' � ' • • • �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 8 R3 over 3 stories and all I Revised Oct 2013
Definitions:
Ls=Liner system--A continuous membrane installed below the purlins and uninterrupted by framing members.Uncompressed,unfaced
insulation rests on top of the membrane between the purlins.Refer to Section A 102.2.5.4.
c.i.=Continuous insulation--Insulation that is continuous across all structural members without thermal bridges other than service
openings and penetrations by metal fasteners with a x-sectional area of less than 0.04%of the opaque surface area of the assembly.
int=Intermediate framing--Includes insulated headers,corners and interior partition wail to exterior wall intersections.Refer to Section
A103.2 for framing definitions.
Footnote Summary:
Each table in the 2012 WSEC has footnotes applicable to specific information provided in the table.This footnote summary provides only
abbreviated details from these foomotes. Refer to 2012 WSECfor complete footnote information.
1-Assembly descriptions can be found in Chapter 2 and Appendix A.
2-Use of assembly U-factors,Gfactors and F-factors from Appendix A and Chapter 3 are required unless otherwise allowed by the
provisions of this Code.
3-For metal building roofs where using R-value compliance method,a thermal spacer block is required.Otherwise use the U-factor
compliance method.
4-Where heated slabs are below-grade,below-grade walls shall comply with the exterior insulation requirements for heated slabs.
5-Heated slab F-factors shall be determined specifically for heated slabs.Unheated slab F-factors shall not be used.
6-Non-residential CMU walls may be eligible to use Table C402.1.2 U-factor if all provisions stated in applicable foomote are met.Refer
to Footnote D in Table C402.L2 or Footnote C in Table C402.2 for eligibility requirements.
7-Roof,wall or floor assemblies required to have continuous insulation may be eligible for alternate continuous insulation R-values if all
provisions in applicable footnote are met. Refer to Footnote F in Table C402.2 for eligibility requirements.
End of Envelope Requirements Summary
� � � • • � � � � � � �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised Oct 2013
ProjectAddress TAHOMA BLVD sE, YELM WA Date 02/17/2015
Occupancy Group �Commercial Q Group R For Building Department Use
FelleStl'atlOri ATCa as%gross above-grade wall area 14.8$ Max.Target: 30.0�
Sl�ylight Area as%gross roof area Max.Target: 5.0�
Vertical Fenestration Alternates: None Selected on ENV-SUM
Prescriptive compliance of envelope assemb/ies may be accomplished by providing insulation R-values per Table C402.2 or U-factors/F-factors
per Tables C-402.1.2 and C-402.3.A single project may comply via R-values for some envelope assemblies and U-factors/F-factors for others.
Note compliance method taken for each assembly in spaces provided.
U-Factor/F-Factor for Alternative
Building Component R-Value for Prescriptive Compliance Prescriptive Compliance
Alternate CI U-Factor Source
Continuous R-Value (Appendix A,Chapter 3
Cavity Ins. Ins.(CI) (Table C402.2 Assembly table,or approved
Provide page/plan#of assembly detail and ID. R-Value R-Value Footnote F)' U-Factor calculation method)
Y �p,3/A8 Wall Section 49.p 49,p �
a�i I D
�
ID:
� � ID. ' I '
o m ID, ' , �
� � ID
� ID, I ,
L tD: � , �
� ID:
� ID: I
�- ID: ' '
�
a� � ID '
>
� -a I D ', I
a m ID � ', �
m � ID �I
� � ID',3/A8 21.0 I 21.0 I
3 °o ID' '
a �
m �p :
a
� ID: !I
� ��
m ID:
� ID,
N Ip
o� ��', �I
a� °� ,
m� I D'
C� I D: '
N ID:3/A8 10.0 10.0
m ID: ' '
o � ID ' II
0
LL =o I D', i
m ID I
�i ID: j
Perim. Ins. Full Slab CI ' '
R-Value R-Value F-Factor ', F-Factor Source
� �p,3/A8 10.0 � ,� 'i
a� m a� `� ���� �
-a a� �p ���, �
m L �,;,
rn � '
� � ID: ;
° � ID: ; �;�.
a @ �,° �;, I
�a �:
— � ID: . .
� " ' �
= ID, �,,,�:,z� �
,, :
Note 1-Calculations are required.Ratio of cross-sectional area of inetal penetration through otherwise continuous insulation shall be 0.04-0.08%.
Note 2-Thermal spacer blocking and liner system are required for prescriptive R-Value compliance.
Note 3-Intermediate framing is required for prescriptive R-Value compliance in wood-framed wall assemblies.
Note 4-Proposed non-residential building CMU walls meeting Table C402.1.2 Footnote D requirements can enter the target U-value of 0.104.
Note 5-Refer to Table C402.2,Footnote E for prescriptive R-Value requirement for steel floor joist assemblies.
Note 6-Prescriptive slab-on-grade insulation shall extend from top of slab to minimum length per an approved method as defined in C402.2.6.
� � � • • � � • � � �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over: Re��sed oct zois
ProjectAddress TAHOMA BLVD ss, YELM WA Date 02/17/2015
Fenestration Area as%gross above-grade wall area 14.8$ Max.Target: 30.0� For Building Department Use
Skylight At'ea as%gross roof area Max.Target: 5.0�
Notes:1:If vertical fenestration or skylight area exceeds maximum allowed per C402.3.1,then Target
Area Adjustment of all applicable enve%pe elements will be calculated by the compliance form.
Refer to Target Area Adjustment worksheet for this calculation.
2:Provide U-factor for the fenestration assemb/y,which is the combination of frame and glazing
U-Factor/F-Factor for Alternative
Bll1ICIlrig COrilpOrierit R-Value for Prescriptive Compliance Prescriptive Compliance
Alternate CI U-Factor Source
Continuous R-Value (Appendix A,Chapter 3
Cavity Ins. Ins.(CI) (Table C402.2 Assembly table,or approved
Provide page/plan#of assembly detail and ID. R-Value R-Value Footnote F) U-Factor calculation method)
ID:2/a6 �s
rn� r�f ��3 ��*�,;
C O � �K�i . �jTd \t1� �3 :. �.
�o ID ; �� �h ��'����� '
ID ���1, .��� ��'� �-��,,;y' I
n ID�, .. � :,;, ��
� � �,
= o ID
o�
� ID: I'i
Solar Heat Gain Coefficient(SHGC) U-Factor for Prescriptive Compliance
SHGC
Projection Adjustment U-Factor Source
factor(PF) Multiplier(if Assembly Assembly (NFRC,Appandix A,or
(if applicable) applicable) SHGC U-Factor Chapter 3 table)
� ID:A6 I 0.30
� ID: ,� �
o ID: i '
z �p , !
� ID: I
c �
° �X-- I D: �i
'� -
�° ID: !
c � ID: I� '
a�
� a ID: '
m � I� _ ID.
r m
� � ID; �
� �p
c°�, ID,
c
m �p
a�i I D �
� �D
w fn I D: � 2 ;� .�� i i I
r a� X, :� � ��',
o, T ID: �� �':3 I
Y ~ I D � �,
� ¢ ID y �� ���;..
Note 1-SHGC Adjustment Multiplier based on calculated Projection Factor. Refer to Equation C4-2 Projection Factor Calculation and Table
C402.3.3.1 for corresponding SHGC Multiplier.
Refrigerated Spaces, Walk-in & Warehouse
Coolers Notes R-Values for Prescriptive Compliance Prescriptive U-Factor not allowed.
Walls
Ceiling
Doors
Freezers � � ���g� �, � �g�u � � �. F� s �
�. �,� �z3.�� ;',� � nN��,�;W�,�.��,,`�a,,,,x .��k;.
��,,,. ,,,� ,.. , .,,�,,, ,. ,.�,
Walls
Ceiling
Doors
Floor '
���. �...
• • � � � • � • � • � • �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised Oct 2013
ProjectAddress TAHOMA BLVD sE, YELM WA Date 02/17/2015
Occupancy Group � Commercial Q Group R For Building Department Use
Change in occupancy or space conditioning Q
Note-Proposed UA may exceed Target UA by 10%per C101.4.4 and C101.4.5
FerieStPatlOri Al'Ca as%gross above-grade wall area 14.8$ Max.Target: 30.0�
Skylight Area as%gross roof area Max.Target: 5.0�
Vertical Fenestration Alternates: None Selected on ENV-SUM
Notes: 1:If vertical fenestration or skylight area exceeds maximum allowed per C402.3.1,then Target Area Adjustment of all applicable envelope
elements will be calculated by the compliance form. Refer to Target Area Adjustments worksheet for this calculation.
2:U-factors shall come from Appendix A, Chapter C303, or calculated per approved method as specified in C402.1.2.
Building Component Proposed UA Target UA
Provide source of U-factor,page/plan#of assembly detail&ID U-factor x Area(A) =UA(U x A U-factor x Area(A)= UA(U x A)
Y R=49 ID: 0.034 ' 9436 ' 320.8 0.034 9436 320.8
o R= ID: ' Above Deck Insulation U-0.034
R= ID:
� � R= ID: 0.031
� 00 R= ID: Metal Building U-0.031
� R= ID:
� R= ID: , 0.021
= R= ID: Single raft,attic,other U-OA21
� R= ID:
� R=21 ID: 0.055 � 5238 288.1 0.055 5238 288.1
� R= ID: I Steellmetal frame U-0.055
a�
g R= ID: '
o -a R= ID: I o.052
¢ C0 R= ID: Metal Building U-0.052
N � R= ID:
m
� 0 R= ID: � 0.054
� o R= ��� Wood Frame,other U-0.054
n � R= ID:
O
. R= ID: ! o.io4
�
� R= ID: Mass Wall U-0.104
� R= ID: '
�? R= ID: 0.104
m
o� R= ID: I Assumed to be Mass Wall U-0.104
°'� R= ID:
m � ,
C9 R= ID:
� R=10 ID: 0.031
m R= ID: Mass Floor U-0.031
o � R= ID: II
� � R= ID: o.oz9
�
@ R= ID: JoisUFraming U-0.029
LL R= ID:
F-factor' x Perimeter =UA(U x A) F-factor x Perimeter= UA(U x A)
� R=10 ID: 0.540 480 � 259.2 0.540 480 259.2
� L R= ID: I , Slab-On-Grade U-0.54
�' � R= ID:
9 � R= ID: 0.550
� � R= ID: Heated 51ab-On-Grade U-0.55
= R= ID:
*Proposed non-residential CMU walls meeting Table C402.1.2 Area UA Area UA
Footnote D requirements can use the target U-value of 0.104 rather Page 1
than Appendix A values. Show footnote requirements in plans. Subtotal 15154 868 15154 868
Component Performance Compliance (UA) UA COMPLlES
• � • � ' • � • • • � • �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over; Re��sed oct zoia
ProjectAddress TAHOMA BLVD sE, YELM WA Date 02/17/2015
Fenestration Area as%gross above-grade wall area 14.8$ Max.Target: 30.0� For Building Department Use
Skylight At'ea as%gross roof area Max.Target: 5.0$
Notes: 1:If vertical fenestration or skylight area exceeds maximum allowed per C402.3.1, then Target
Area Adjustment of all applicable envelope elements will be calculated by the compliance form.
Refer to Target Area Adjustments worksheet for this calculation.
2:Provide NFRC rated U-factor or default U-factor from Appendix A for the fenestration assembly
thermal performance(combination of frame and glazing).
3:Fenestration that separates conditioned space from a non-conditioned or semi-conditioned
Building Component Proposed UA Target UA
Provide source of U-factor, page/plan#of assembly detail&ID U-factor x Area(A) =UA(U x A U-factor x Area(A)= UA(U x A)
a,�, U=0.37 ID:A6 DOOR SCHEDULE 0.370 231 � 85.5 0.37 231 85.5
�Q U= ID: �i Opaque Swing Doors U-0.37
U= ID:
n.N U= ID: ' ' o.37
� � i,
o Q U= ID: �� Opaque rollup&sliding U-0.37
� U= ID:
m U=0.3 ID:A6 WINDOW SCHEDULE 0.30 , 774 232.2 0.30 774 232.2
� U= ID: ' Non-Metal Frame U-0.30
o U= ID: ,
Z U= ID:
� U= ID: I 0.38
� w U= ID: , Metal Frame, Fixed U-0.38
`� '� U= ID: ',
� a�
c � U= ID:
a�
� a U= ID: 0.40 '
� °_ U= ID: Metai Frame,Operable U-0.40
r
� � U= ID: ,
� U= ID:
� U= ID: , o.60
c
'� U= ID: , '� Metal Entrance Door U-0.60
aci U= ID:
g U= ID:
�, �, U= I D: ' o.5 0
a�
a, T U= ID: ', All types U-0.50
Y ~ U= ID: �
cn Q U= ID: I
Area UA Area UA
Page 2 Subtotal 1005 318 1005 318
To comply: Page 1 Subtotal 15154 868 15154 868
1)Proposed Tofa!UA shall not exceed Target Total UA.
2)Proposed Total Area shall equal Target Total Area. Total 1615 9 118 6 1615 9 118 6
Component Performance Compliance (UA) UA CtJMPLIES
. • � ' ' • . . •
lf vertical fenestration area exceeds maximum allowed per Section C402.3.1,then Target Area Adjustment of all applicable envelope elements is
required. This worksheet automatica//y ca/cu/ates these adjustments and updates target areas in the ENV-UA and ENV-SHGC worksheets. /nformation
shown in this worksheet is for reference only and is write-protected.Submit this Target Area Adjustment form with ENV-UA and ENV-SHGC forms.
VF=Vertical fenestration NW=Net above grade wall(excludes fenestration and doors.)
DR=Opaque doors Gross Exterior Above-Grade Wall Area=VF+NW+DR
AG=Above- rade
Proposed Areas
Vertical Fenestration-> VF= 774.0 ��`� �s,z ;;,'�,�,,,,
Opaque-> NW= 5238.0 DR= 231.0
Gross Exterior Max Vert.Fen.% Maximum Target
AG Wall Area (C402.3.1) Vert.Fen.Area
6243.0 X 30.0� - 100 = 1872.9
i otai verncai Uelta Vertical txcess verucai
Fenestration Maximum Target Fenestration � Fenestration
774.0 — 1872.9 = —1098.9 �;greater =
—1098.9
Multiplier applied to all
Total Vertical Excess Vertical Target Vertical Total Vertical Proposed Vertical
Fenestration Fenestration Fenestration Fenestration Target VF Multipiier Fenestration Areas to
774.0 — = 774.0 — 774.0 = 1.00 calculate Target Vertical
• Fenestration Area
Net AG Wall Area Excess Fenestration Target Net Wall Area Net Wall Target Net Wall Muit. Multiplierapplied to all
5238.0 + = 5238.0 — 5238.0 = 1.00 Proposed Opaque Above-
Grade Wall Areas to
UA Ad j ustments calculate Target Above-
Vertical Fenestration Proposed Area Target VF Mult. Target Area
Non-metal frame 774.0 X 1.00 = 774.0
Metai frame,fixed X =
Metal frame,operable X =
Metal frame,entrance door X — Target areas in shaded
Above-grade Wall Proposed Area Target Net Wall Mult. Target Area boxes are applied to
Steel Frame 5238.0 X 1.00 = 5238,p target areas on ENV-UA
Metal Building =
Wood/Other frame X =
Mass X =
_„ Sum of target above-grade
Sum of Proposed 6012.0 Sum of Target 6012.0 wall and vertical
fenestration areas are
calculated to equal the
sum ofproposed
SHGC x A Adjustments
Non-North Vertical Fenestration Proposed Area Target VF Mult. Target Area
PF<0.2 X =
0.2<_PF<0.5 X =
PF>_0.5 X = SHGC target areas in
North Vertical Fenestration shaded boxes are applied
to target areas on ENV-
PF<0.2 X = SHGC
0.2<_PF<0.5 X =
PF?0.5 X =
• . • ' � � • •
If skylight area exceeds maximum allowed per Section C402.3.1, then Target Area Adjustment of all applicable envelope elements is required. This
worksheet automatically calculates these adjustments and updates target areas in the ENV-UA and ENV-SHGC worksheets. Information shown in this
SKY=Sk li ht NR-Net roof excludes sk li ht Gross Exterior Roof Area=SKY+NR
Proposed Areas
Skylight(Horizontal Fenestration)-> SKY=
Opaque Roof -> NR= 9436.0
Gross Exterior Max Skylight% Maximum Skylight
Roof Area (C402.3.1) Fenestration Area
9436.0 X 5.0� ,— 100 = 471.8
Tot�al Skylight Area Maximum Target Delta Skylight Area 0 Excess Skylight
— 471.8 = —471.8 �;greater =
—471.8
Total Skylight Area Excess Skylight Target Skylight Area Total Skylight Area Target SL Multiplier Multiplier applied to all
-- Proposed Skylight Areas
— — — - to calculate Target
Skylight Area
Net Roof Area Excess Skylight Target Net Roof Area Net Roof Target Net Roof Mult.
9436.0 = 9436.0 — 9436.0 = 1.00 Multiplierapplied to all
+ • Proposed Opaque Roof
Areas to calculate Target
UA and SHGC x A Adjustments
Skylight Proposed Area Target SL Mult. Target Area
All X =
Roof Proposed Area Target Net Wall Mult. Target Area Target areas in shaded
Insulation Above Deck 9436.0 X 1.00 = 9436.0 boxes are applred to target
areas on ENV-UA
Metal Building X
Attic/All Others X =
Sum of target roof and
Sum of Proposed 9436.0 Sum of Target 9436.0 calcula'�d to equal the
sum of proposed
• • � •
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised Oct 2013
ProjectAddress TAHOMA BLVD sE, YELM WA Date 02/17/2015
Fenestration Area as%gross above-grade wall area 14.8� Max.Target: 30� For Building Department Use
Skylight Area as%gross roof area Max.Target: 5�
Vertical Fenestration Alternates: None Selected on ENV-SUM
Notes: 1-Proposed vertical fenestration and skylrght areas entered in ENV-SHGC must match proposed
fenestration areas in ENV-UA.
2-If Target Area Adjustment is required per ENV-UA, then target areas will be automatically
adjusted in ENV-SHGC.Refer to Target Area Adjustments worksheet for this calculation.
3-Provide NFRC rated SHGC or default from Table C303.1.3(3)for fenestration assembly SHGC.
4-Fenestration that separates conditioned space from a non-conditioned or semi-conditioned
space shall be included in this worksheet.
Skylights Proposed SHGC Target SHGC
Provide source of SHGC, page/plan#of assembly detail&ID SHGC x Area(A) =SHGC x SHGC x Area(A)= SHGC x A
ID: ' 0.35
ID: ' , SHGC 0.35
ID:
ID: I
ID: I
Totals Totais
All Non-North Vertical Fenestration+ Proposed SHGC Target SHGC++
Provide source of SHGC,page/plan#of assembly pF SHGC` x Area(A)=SHGC x A PF SHGC x Area(A)= SHGC x A
detail&ID Category
ID: ', 0 ' PF<0.2 , 0.40
ID: 0 0.2sPF<0.5, 0.48 '
ID: 0 I PF>_0.5 '� 0.64
ID: 0 ++�{projection factor(PF)credrts are
ID: 0 applied to the proposed design, Ta�get
ID: , 0 SHGC will sum fenestration area by PF
ID: o , category.
ID: I 0 i ,
ID: 0 I
ID: 0 �,
+If projection factor credit is applied, then vertical Totals Totals
fenestration must be entered in the correct table according to
orientafion. If credit is not applied then all vertical
fenestration can 6e entered in either table.
"Note:Fenestration that separates conditioned space from a
non-conditioned or semi-conditioned space shall be listed
here with a proposed SHGC equal to the target value.
North Vertical Fenestration+ Proposed SHGC Target SHGC++
Provide source of SHGC,page/plan#of assembly pF SHGC* x Area(A)=SHGC x A PF SHGC x Area(A)= SHGC x A
detail&ID Category
ID: ' 0 , ; I PF<0.2 0.40
ID: II 0 , 0.2<_PF<0.5 0.44 '
ID: � 0 ', PF?0.5 0.48
ID: 0 � ' ++If projection factor(PF)credits are applied
ID: 0 � ' to the proposed design, Target SHGC will
ID: � p sum fenestration area by PF category.
ID: 0
North Total
Area SHGC x A Area SHGC x A
To comply, the Proposed total SHGC x A for all fenestration(vertical Grand Grand
&skylights)shall not exceed the Target total SHGC x A. Total Total
Less proposed vertical fenestration here than ENV-UA: Add 774.0
Component Performance Compliance (SHGC)
Load-Calc Page 1 of 1
���-�� � A.,F'i'�s� I�,,.,..,.
!b*sigo Indoor Cuoling Temp.:�72��°F yelm daycare Desigo indoor I#asrin�Temp.y70 �6
Desigo OutAoor Cooiing Temp.:$2��:°F' aesign Out400r Heating�Cemp.`2� 4 J�'E
Temp.ll4tference Cooiii,g:10°F Area: Tuom�MCChord Air Force B9se,WA Temp.DiRerevice[Ieati�:46°F
ued�. Humidity:�'S0 v; Grams difi'e�ence:-$ E�ront Door Orien[afion;.'— �''
Wh+�l�e Hous� L�ad Calcu�at�r
TD:Coo1:10°F Heet46°F Sq.ft,-t;�pes t and 2 s'hadi�Sq.ft.-ty es 1�nd 2 shadin Sq.ft-types t and 3 � Sq.fi.
Ou�de Wall North� 2:� Windows x 1:j 2� Glass Doors x 1; 2:' � �rs�`(
Outside Wall South 1 35 2.; Windows C v 1;75 2� Glass Doars l v Il; 2�. Doors�
a,��ae w�i:e�w i.64 z.; window5 C v';i.•,100 z ci�s noas t v i; z: noo� 42 ;
Oufside Wall:NF&NW� 2 j� Windows s I t 2-� G1acs Doors x 1�� 2:t Doors�
OWSide Watl:SE&SW I'� 2;��� Windows�l_J 1.; 2; Glass Doors L V 1:: 2.; Doors�
Slry L�ghts i S�i '., � E-W'. : NE-MV'� SFrSW:���—�
Floor-(linear ft.ff slab)1�,t 34 �ii � 8.13EIIIC� Wa115-above grade:i below grade:l �.sq.ft ��
Ce�6ng 1 j 1 l20 2; —_--;� BacemeII Floor-� dtty 28ft�, feet be(ow gra�ade f 2 fi. v,,
Number of Appliances�l �.
NeunberofPeople 32 Fresh aiz recomm�ded:601cfm� i400 �'�.CFM �.
Condiaoued-Sq_ft: ''1120� CuMa Ft:�.10080 Consm,cnon:;avera e v' nuct sys�em:;conditior v;---�--v',;avera e
Total Btds Cooling Sensible Load Late�Load Total Bm's Heating
�;a�cui�te��aj � '_33�9 6404 ��:`�`
3�JW��
Btu breakdown
ensible Latent Heating Structure types
Outside Walls I:Siding or Stucco R21 insulation
walls -43 �-353
Outside Watls 2:
windows 83�5 �579b Windows I:Low E or triple pane no intemal shade
ceilings �1613 �1649 Windows 2:
doors 529 �1159 Glass Doors I:
floors 00 965 Glass Doors 2:
appliances 1200 � - Floors 1:Concrete slab R-10 edge insulation
people �7360 �� Floor 2:
glass doors �0��0� Ceiling 1:Ceili�g under attic space R-30
skylights 0��� Ceiling 2:
basement wa(]s 0��� Doors:Metal
basement floor 0 �� Skylights:
infittration �425 0�3825 BasementWalls:
fresh air 00 0� 0240 Basement Floor:
duct load ��� Win ht.:5'0" Overhang: 1' Top to overhang:1.5'
Totals 3859 6400 3528]
��������
FEB Q 3 Zt�15
http://www.loadcalc.net/load.php 2/1/2015
, a ;J`I�/UL I � �
/�_.i
�'l.fA/K/N �1��' Submittal Data Sheet
absolute comfort
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit#:
Reference: Drawing#:
Performance
Indoor Unit Mode/No: FTXS36LVJU Indoor Unit Type: Wall Mounted
Outdoor Unit Mode/No: RXS36LVJU Condensing Unit Type: SkyAir Heat Pump (FTXS Only)
Rated Cooling Capacity(Btu/hr): 36000 Indoor:80°F DB/67°F WB
Sensib/e Capacity(Btu/hr): 22390 Rated Cooling Outdoor:95°F DB/75°F W B
Max/Min Cooling Capacity(Btu/hr/kW): �tabook/databook Conditions
Cooling/nput Power(kW): 4 Indoor:70°F DB/60°F W B
SEER: 17.9 Rated Heating Outdoor:47°F DB/43°F W B
Rated Heating Capacity(Btu/hr): 38000 Conditions
Max/Min Heating Capacity(Btu/hr/kW): itabook/databook Rated Piping Length(tt) 25
Heating/nput Power(kW): 3.9 Rated Height Separation(tt) 0
Heating COP(Btu/hr/Btu/hr): N/A
HSPF: 8.3
Indoor Unit Details
Power Supply(V/Hz/Ph:) 208-230/60/1 ph Airflow Rate(CFM wet coil) 770/519/473
Power Supply Connections: L1, L2, Ground Moisture Removal(pbh):
Min Crrcuit Amps MCA (A): N/A Gas Pipe Connection (inch): 5/8
Max Overcurrent Amps MFA (A): N/A Liquid Pipe Connection (inch): 3/8
Drmensions (HxWxD): 13-3/8x47-1/4x9-7/16 Condensate Connection (inch):
Panel(HxWxD): N/AxN/AxN/A Sound Pressure Leve!(d8A): 49
Net Weight(Ibs): 38 Sound Power Level(d8A): 37
Weight with Panel(Ibs): N/A Static Pressure Rated/Max(inWg) l
Condensinp Unit Details
Power Supply(U/Hz/Ph): 208-230/60/1 ph Compressor Type: Inverter
Power Supply Connections: L1, L2, Ground Capacity Control Range(%):
Min. Circuit Amps MCA (A): 19.5 Airflow Rate(CFM): 2627
Max. Overcurrent Amps MFA (A): 20 Gas Pipe Connection(inch): 5/8
Max. Starting Current MSC(A): Liquid Pipe Connection (inch): 3/8
Rated Load Amps RLA (A): 20.3 Sound Pressure Level(dBA): 54
Dimensions (HxWxD): 38-15/16x37x12-5/8 Sound Power Level(d8A): 68
Net Weight(Ibs): 179
Svstem Details
Refrigerant Type: R-410A Max. Pipe Length(Vertica/ft): 65.6 ft
Holding Refrigerant Charge (Ibs): 6.17 Cooling Operation Range(9�): 14- 115
Additiona/Charge(oz/ft): 0.0361bs/ft Cooling Range w/Baff/e (�): 0- 115
Pre-charge Piping(Length ft): 32 ft Heating Operation Range(9�): 5-75
Max. Pipe Length(Total ft): 98.4 ft Heating Range w/Baff/e(�): 0 -75
� _ _;?_, ,
��� �' "�
� .< t .
",J W�..J _�� iG r � A-� .Cc M CON'�N-r�cSa�,C.�ES I�3M i�-rAC. ���`!�,� — S�'E'���
� -- _
Daikin AC(Americas),Inc.,1645 Wallace Drive-Suite 110,Carrollton,TX 75006 Page 1 of 4
Daikin AC TRL Generated Submittai Data �www.daikinac.com
(Daikin's products are subject Io conlinuous improvemenls. Daikin reserves the righ�to modity product design,specitica[ions and Iniormation in this data sheet wilhout nolice and withoul incurring any obligations)
�t�A/K/N �1�� Submittal Data Sheet
absolute comfort
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit#:
Reference: Drawing#:
Dimensional Drawina- Indoor Unit FTXS36LVJU
FTXS3Q136LYJU
TNE AAkRK{»�SHOYtS PIPIIJG f31RECTSON ,�i'`� � � � � /� /
4�-iia{tzaomm) ,,, z
, � z
LEFT �RERFt � NtC�iF , �LL g
� � �
� ���
t-i5ltfi(50teus�}M1N ,.r`�"� 1-15it&5Wmn'MID[ V
(SPACE FOR V (Sf'ACE FO�t
MAIPIT�ENANCE} RE(3U&tEQ SPACE �iN�����
FRONT
GRiLtE
-----"`��,.�"����� �REWS �AiR�1.C1N({IMDQOt�
.;�_.��-'^=,.;,:,�----�-,.��.--=' ?_INSIDE}
[)il�f� 1
BOTTOM� LQWERS S�I+lAIRECEtVER � �IidT�LLlGENTEYESENSaR �P���TE!
o�Ewtrtau uva� �me
T�iER f.AhiP
� iNT'Et1.ICsEN1'EYE LAAAP � t�P�ME
�IN�04R UMT ON(O�F SWffGH p�,A7€
�4 ROOM TEMP.TkEAMtSTOR(It+ISS1DE) � '^^
i ��L
FRONT GRH.LE FIXTURES MO[�i.NA#AE PtA't'E fi yy��a��
,� 7EF�INtNAL
Daikin AC(Americas), Inc., 1645 Wallace Drive-Suite 110,Carrollton,TX 75006 Page 2 of 4
Daikin AC TRL Generated Submittal Data www.daikinac.com
(Daikin's pmducts are subjecl lo continuous improvements.Daikin reserves Ihe right to modify produd tlesign,specifications and intormalion in IhiS data sheel vnthout nolice and without incurting any o6ligations)
�QA/x�N �1�� Submittal Data Sheet
absolute camfort
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit#:
Reference: Drawing#:
Dimensional Drawina-Condensinq Unit RXS36LVJU
RKS3Qt3&LVJU, RXS3Q138L1/J'U
MIMif1RlM SPACE EOR A!R PASSAGE
�
WALL HEiGHT tNi pNi 01fi7.67 S1pE-tESS THAN d7-ti4
2t-7�78 g.yig 4�CUTSFORANCHOABOL75%' � �
a m {M72)
.. n %� � o�
� � � � �
� �.=1 --- `' � �
�'m �:.
ti �, �j r� r- � � ,
� m � � x,
a � '�" �"� �-isrss �-,sns
� --- - � ' �
iii�ii�ii riii,!�iii iii�i
`? �DRAIN 011TLffT � uiiiiii��ii�,riiitiiiiiiiiii
� 1.�.ol5lte NOSf FUR CONNEC710N. � m � � . .. <
. �
?-3t8 7-75+18 4-1118 7-1/18 � � .�, i-tTaPiB M
t5ttfi f BRAND NAME LABEL NAME PtATE GAS STt3P VALVE TERIARdA1 STRIP
—1 LtOUID STOP VALYE �DOR AIR
� ! �' Tt�RM13TQR
- \` � 1 �,6AOUNDTERM9dAL
� �
� l
� � � f
i �
_' � ' I
� •/ .
m B � �
� i
m
I
a �
,� I
• . � m ;
—_-__-.-..___ c�v I ..
1
�
3 '
. . m \ °} !GAS PlPE
3-tl18 � 3-5J18 ���C�HEGTIEV(`WR9�lG t-77116 �{�SINGtE UNlfJN)
3�iP2 ANO WIAHIG INLET �lS(N1t4P1PE
{o3fa 31NGLE UNiOM
Daikin AC(Americas), Inc., 1645 Wallace Drive-Suite 110,Carrollton,TX 75006 Page 3 of 4
Daikin AC TRL Generated Submittal Data www.daikinac.com
(Daikin's produds are suqec!to continuous improvement5. Daikin reserves Ihe�ight to modity product desigq specifications and inlormation in this data shee�without notice and without inwrdng any o6ligations)
��'ll�AlK/IV � t� �� Submittal Data Sheet
absolute comfort
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit#:
Reference: Drawing#:
FTXS36LVJU RXS36LVJU
�..�,N
_ , .. >,. �.• ��:����. -�,.��
_�_�
s`�==°__=: ��
�,�ssx...:—_
.���es—�==s
w ..,,, s����s��x��mt
.,.�, ----•-------�
�___�_,_�_.
��;�==o=�' `.
�—os�----l.
��z�_==����.
c,r.�===__.
zc --=— �
��=c=_.7
�._--
x`i.�r:..�r�.y� . ..�:�"ii
��.'.+;,xA%s� �,''.;� ,z;'.. ��` .'i.N,,wr��"'%���r€�r `%tra
FTXS36LVJU RXS36LVJU
Std U.S. Warranty:7yrs Compressor, 5yrs Parts Std U.S. Warranty:7yrs Compressor, 5yrs Parts
Daikin AC(Americas),Inc., 1645 Wallace Drive-Suite 110,Carrollton,TX 75006 Page 4 of 4
Daikin AC TRL Generated Submittal Data www.daikinac.com
(Daikin's pmducts are subject to con[inuous improvements. Daikin ieserves�he righf to modity p�aduc�design,specifications aM informalion In thls data sheel wilhout notice and wilhoul incuning any obligations)
,. ,,
. . . . GMSS92 / GCSS92
SIN6LE-STA6E
Air Conditioning& Heating Mum-S�EED GAS FtlRiiA(E
uP io 929G AFUE
NEAiIN6�NPUT: ���Q�O-�Z�,000 BTU/N
Standard Features
• Heavy-duty aluminized-steel tubular heat exchanger
• Stainless-steel secondary heat exchanger
• Single-stage gas valve
• Durable Silicon Nitride igniter
• Multi-speed blower motor
• Quiet single-speed induced draft blower
• Self-diagnostic control board
• Color-coded low-voltage terminals
'� ° '`" • All models comply with California Low NOx
emissions standards
fabinet features
• Designed for multi-position installation—
GMSS92:upfiow,horizontal left or right
GCSS92:downfiow,horizontal left or right
• Certified for dired vent(2-pipe)or
non-direct vent(1-pipe)
• Easy-to-install top venting with optional
side venting
• Convenient left or right connedion
for gas and eledrical service
• Cabinet air leakage(Q�eak)<_2%
• Heavy-gauge steel cabinet with durable finish
• Foil-faced insulated heat exchanger cabinet
• Airtight solid bottom or side return with
easy-cut tabs for effortless removal in
bottom air-inlet applications
to�tents
Nomenclature...........................................2
Produd Specifications..............................3
Dimensions...............................................5
Airflow Specifications................................7
Wiring Diagram.......................................10
Accessories..............................................11
—._— -- _. i
�nr �e �� .
s , , �i,� 1 • •. —�_=--
_ _ �,
� _ , �� �: 4�,?a.,
' ,�"_•�a . ,_..s
`Complete warranty details available trom your local dealer or at • �
www.goodmanmfg.com.To receive the life[ime Heat Exchanger Limited Warranty � � �� j� G
(good for as long as you own your home),and 10-Year Par[s Limited Warrantg online ��B � �•� ,,C�),,., � c C D � � �1}�,j
regis[ration mus[be rompleted within 60 days of ins[allation.Online regi4rotion iz not �.. � I e.�.�
required in California or Quebec. �,
SS-6MSS92 ' www.goodmanmfg.com _.___-_._--- -----4l-14
PROOOCr Sr�aFiuno�s
SPEtIFiUT10NS-6MSS92
GM5592 GM5592 GM5592 GM5592 GM5592 GM5592 GM5592 GM5592
Q4026NA 06038NA 0803BNA 0804CNA 0805CNA 1004CNA 1005CNA 1205DNA
Heating DaW
High Fire Input' 40,000 60,000 80,000 80,000 80,000 100,000 100,000 120,000
High Fire Output' 36,840 55,260 73,680 73,680 73,680 92,300 92,100 110,520
AFUEZ 92 92 92 92 92 92 92 92
Temperature Rise Range(°f) 30-60 35-65 35-65 35-65 25-55 35-65 35-65 35-65
Vent Diameter� 2"-3" 2"-3" 2"-3" 2"-3" 2"-3" 2"-3" 2"-3" 3"
No.of Burners 2 3 4 4 4 5 5 6
Circulator Blower
AvailableAC@0.5"ESP 1.5-3 1.5-3 1.5-3 3-5 3-5 3-5 3-5 3-5
Size (DxW) 10"x8" 10"x8" 10"x8" 10"x10" 11"x10" 10"x10" 11"x10" 11"xll"
Horsepower @ 1075 RPM % / %, %z '/• '/z % %
Speed 4 4 4 4 4 4 4 4
Fi{ter Size(in')
Permanent 363 491 654 654 818 818 818 981
Disposabie 182 245 327 327 409 409 409 491
Eledrical Data
Min.Circuit Ampacity` 9.6 9.6 9.6 11.7 13.7 11.7 13.7 13.7
Max.Overcurrent Device(amps)5 15 15 15 15 15 15 15 15
Shipping Weight(Ibs) 109 112 115 137 138 139 140 152
' Natural Gas BTU/h �
z DOE AFUE based upon Isolated Combustion System(ICS)
' Installer must supply one or two PVC pipes:one for combust5on air(optional)and one for the flue outlet(required).
Vent pipe must be either 2"or 3"in diameter,depending upon furnace input,number of elbows,length of run
and installation(1 or 2 pipes).The optional Combustion Air Pipe is dependent o�installation/code requirements
and must be 2"or 3"diameter PVC
° Minimum Circuit Ampacity=(1.25 x Grculator Blower Amps)+ID Blower amps.Wire size should be determined
in accordance with National Electrical Codes.Extensive wire runs will require larger wire sizes.
5 Maximum Overcurrerrt Protection Device refers to maximum recommended fuse or circuit breaker size.
May use fuses or HACR-type circuit breakers of the same size as noted.
NoTES
• AII furnaces are manufactured for use on 115 VAC,60 Hz,single-phase electrical supply.
• 6as Service Connection�"FPT
• important:Size fuses and wires properiy and make electrical connections in accordance with the
National Eledrical Code and/or all existing local codes.
• For bottom return:Failure to unfold flanges may reduce airFlow by up to 18�0.This could result in performance
and noise issues.
• For servicing or cleaning,a 24"front ctearence is required.Unit connections(electrial,flue and drain)may necessitate
greater clearances than the minimum clearances listed above.in all cases,accessibility clearance murt take precedence
over clearances from the enclosure where accessibility clearances are greater.
SS-GMSS92 www.goodmanmfg.com 3
' y pRODB[i S�E[IfiUiIONS
6�SS92 �IMENSIONS
AIR AIR
DISCHARGE DISCHARGE
28'/. A
5� DIMB �
Z�, DISCHANGE 6,�
AIRINTAKE �
2°PIPE 2s/° C 1%S Z 19�
Z ENTERDIMPLE VENT/FIUEPIPE
LEFf SIDE FOR AL7ERNATE Z„Pv� AITERNATE
DRAIN TRAP AIR INTAKE PIPE VEM/FLUE �
EXTERIOR HOLES 3"OD HOLE • LA('A710N
. HIGH VOLTAGE ftIGHT SIDE
ELEL7RICAL OUTLET DflAIN TMP
O IXfERIOR HOIES O
STANDARD O MIGH VOLTAGE
GFS SUPPLY ELECTRICAL OU7LET
LOCATION ALTERNATE
GASSUPPIY
�� 34X O ��
. . . 3 :4 . . .
26i4
24iG
23 23
19',S 21X
� 19iG
14 S�DE CUT-0UT
SIDE NT-OUT
9%
934
5 5
134
� LEfT51�EVIEW 1'/e FRONTV�EW � 1� RIGHTSIDEVIEW
LOW VOLTAGE Z% 2'/.
EIECTRICALOUTLEf Z+h D LOW VOLTAGE
1� FOIDEDFIANGES ELECTIiICAL011TlET ZYs
CONOENSATE ORAIN Zz
TRAP IXTERIOR E FOLDED FLANGES
Z3 UNFOLDED FLANGES
CONNELTION 23'h
- (RIGHT OR LEFf SI�E� UNFOLDED FL4NGF5
�PVC
MODE� A B C D E
GMSS920402BNA 17%z 16" 13%' 12'�" 13�8'
GMSS9206036NA 17%z 16" 13%s" 12%" 13%s"
GMS59208036NA 17%z 16" 13%a" 12%a" 13'/s"
GMSS920804CNA Zl" 19%:" 17%8' 16" 17%i'
"-``- GMS5920805CNA 21" 19/:' �
"�"' ' ' 17�." 16" 17'/�"
GMSS921004CNA 21" 19%2' 17�:' 16" 17%"
GMSS921005CNA 21" 19%:" 17�." 16" 17%:"
GMS5921205DNA 24%i' 23" 20%' 19�'s' 20%a"
Ma��u�t�uMC�s�e taMansnet�M�t���s
POSITION SIDES REAR FRONT BOTTOM FLUE TOP
Upflow 0" 0" 3" C 0" 1"
Horizontal 6" 0" 3" C 0" 6"
C=If placed on combustible floor,the floor MUST be wood ONLY.
SS-GMSS92 www.goodmanmfg.com 5
�� PROeucr SrEaFiun�s
AIRFLOW DATA-6MSS92
(CFM&TEMPERATURE RISE VS.EXTERNAL STATIC PRESSURE)
El(TERNAL$TATIC PRESSURE,(INCMES WATER COLUMN)
MOTOR TONS
MODEL SPEED AC' 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CPM R�SE CFM RISE CFM RISE CFM R�SE CFM R�SE CFM CPM CFM
High 3 1,498 N/A 1,446 N/A 1,368 N/A 1,302 N/A 1,227 N/A 1,145 1,059 954
GMSS92 Med 2.5 1,223 N/A 1,182 N/A 1,153 30 1,099 31 1,051 32 982 901 813
04026NA Med-Lo 2 983 35 971 35 945 36 919 37 878 39 813 746 659
Low 1.5 816 42 794 43 758 45 734 46 678 50 637 597 523
High 3 1,494 N/A 1,428 36 1,362 38 1,294 39 1,231 42 1,162 1,076 972
GMS592 Med 2.5 1,203 42 1,178 43 1,147 45 1,101 46 1,045 49 986 927 831
06038NA Med-Lo 2 977 52 965 53 939 54 904 57 866 59 801 763 639
Low 1.5 801 64 786 65 751 N/A 714 N/A 714 N/A 680 635 596
High 3 1,459 47 1,397 49 1,339 51 1,270 54 1,202 57 1,107 1,049 952
GMSS92 Med 2.5 1,191 57 1,166 58 1,137 60 1,086 63 1,033 N/A 973 S89 797
08036NA Med-Lo 2 985 N/A 967 N/A 932 N/A 900 N/A 859 N/A 805 731 620
Low 1.5 808 N/A 785 N/A 758 N/A 726 N/A 679 N/A 629 590 513
High 5 2,115 N/A 2,050 N/A 1,973 35 1,915 36 1,810 38 1,695 1,587 1,467
GMSS92 Med 4 1,802 38 1,739 39 1,725 40 1,665 41 1,61� 42 1,532 1,443 1,320
0804CNA Med-Lo 3.5 1,517 45 1,509 45 1,496 46 1,475 46 1,441 47 1,388 1,304 1,2�5
Low 3 1,213 56 1,225 56 1,216 56 1,194 57 1,179 58 1,135 1,084 1,005
High 5 2,284 30 2,231 31 2,170 31 2,103 32 2,037 33 1,945 1,836 1,750
6MS592 Med 4 1,865 37 1,869 36 1,775 38 1,732 39 1,684 40 1,619 1,548 1,480
OSOSCNA Med-lo 3.5 1,594 43 1,571 43 1,530 45 1,492 46 1,454 47 1,414 1,355 1,293
Low 3 1,411 48 1,366 50 1,325 51 1,296 53 1,251 54 1,200 1,147 1,096
High 5 2,082 41 1,997 43 1,943 44 1,847 46 1,749 49 1,669 1,560 1,443
GMSS92 Med 4 1,823 47 1,782 48 1,711 50 1,659 51 1,574 54 1,513 1,402 1,305
1004CNA Med-Lo 3.5 1,565 54 1,545 55 1,529 56 1,487 57 1,441 59 1,365 1,287 1,196
Low 3 1,261 N/A 1237 N/A 1,242 N/A 1,216 N/A 1,179 N/A 1,145 1,098 1,034
High 5 2,137 40 2,073 41 2,031 42 1,949 44 1,879 45 1,811 1,734 1,625
GMSS92 Med 4 1,793 48 1,754 49 1,704 50 1,648 52 1,590 54 1,534 1,451 1,371
1005CNA Med-Lo 3.5 1,558 55 1,518 56 1,477 58 1,425 60 1,376 62 1,316 1,242 1,170
Low 3 1,370 62 1,325 64 1,288 N/A 1,237 N/A 1,191 N/A 1,134 1,086 1,024
High S 2,256 45 2,192 47 2,133 48 2,054 50 1,986 51 1,907 1,834 1,718
GMSS92 Med 4 1,805 57 1,762 58 1,722 59 1,677 61 1,618 63 1,563 1,507 1,441
1205DNA Med-Lo 3.5 1,565 65 1,513 N/A 1,480 N/A 1,415 N/A 1,392 N/A 1,346 1,269 1,198
low 3 1,368 N/A 1,326 N/A 1,278 N/A 1,Z38 N/A 1,208 N/A 1,165 1,093 1,052
' at 0.5"ESP
NoTFs
• CFM in chart is without filter(s). Filters do not ship with this furnace,but must be provided by the installer.if the furnace requires two return filters,
this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium-speed heating.Installer mus[adjust blower cooling&heating speed as needed.
• For most jobs,about 400 CFM per ton when cooling is desirable.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATIN6 PLATE.
• This chart is for information only. For satisfactory operation,external static pressure should not exceed value shown on the rating plate.
The shaded area indicates renges in excess of maximum static pressure allowed when heating.
• The above chart is for U.S.furnaces installed at 0-2000 feet.At higher altitudes,a properly derated unit will have approximately the same
temperature rise at a particular CFM,while ESP at the CFM wili be Iower.
SS-GMS592 www.goodmanmfg.com �
• � •
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised Jan 2014
Project Info Project Address 1 -Stepping Stone Childrens Center Date 5/21/2013
Compliance Tahoma Blvd SE For Building Department Use
forms do not
require a 3-Yelm,WA
usesword to Applicant Name: Marijka Duetscher
Instructional and Applicant Address: 1404 Marvin Rd SE#307-254,Lacey WA 98516
calculating ce//s
are write- Applicant Phone: 360-402-6871
Project Description Q New Building ❑ Addition ❑ Alteration ❑ Plans Included
a Lighting Power Density Ca�culations � Total Building Performance
Lighting Compliance Path
(If Total 8uilding Performance then only LGT-CHK is required.J
Lighting Power Allowance
�Building Area Method (�s Space-By-Space Method
Method Selection required to
enable LPA forms
Interior Lighting System
Description
Briefly describe lighting
system rype and features.
Additions and Change of Space Use (C101.4.3 & C101.4.4)
� Addition area or Change of Space Use area compiies with all applicable provisions as stand alone project
� Addition area is combined with existing building lighting systems to demonstrate compliance with all applicable
provisions per C101.4.3
Provide Building Area Method(LTG-INT-BLD)or Space-By-Space Method(LTG-INT-SPACE)Compliance Form.Document maximum
allowed and proposed(including existing rf applicable)lighting wattage of Addition or Change of Use space.Provide applicable lighting
controls per C405.2 and commissioning of lighting controls per C405.13.
Alterations,Renovations and Repairs (C101.4.3.1)
❑ 60%or more of luminaires in space replaced
Provide Building Area Method(LTG-INT-BLD)or Space-By-Space Method(LTG-INT-SPACE)Compliance Form.Document maximum
allowed wattage withrn the lightrng retrofit space in Maximum Allowed Wattage table and proposed(including existing)lighting wattage in
Proposed Wattage tab/e.Retrofit and non-retrofit spaces shall be documented separately using multiple forms.
� Less than 60%of luminaires in space replaced
Provide a separate Space-By-Space Method(LTG-INT-SPACE)Compliance Form for this retrofrt area.Document existing total wattage
within the lighting retrofit space in cell provided in the Maximum Allowed Wattage table. Document proposed(including existing)lighting
wattage in the Proposed Wattage table.
� Lamp and/or ballast replacement within existing luminaires only—existing totai interior building wattage not increased
� New wiring installed to serve added fixtures and/or fixtures relocated to new circuit
Provide applicable manual lighting controls(C405.2.1),occupancy sensors(C405.2.2.2),daylight zone controls(C405.2.2.3),specific
application controls(C405.2.3),and commissioning of lighting controls per C405.13
� New or moved lighting panel
Provide all applicable lighting controls as noted for New Wirrng,automatic time switch controls(C405.2.2.1),and commissioning of lighting
controls per C405.13.
� Space is reconfigured-luminaires unchanged or moved only
Provide afl applicable lighting controls as noted for New Wiring and commissioning of lighting controls per C405.13.
[� No changes are being made to the interior lighting and space use not changed.
• � i � . � • . � �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and ail R1 Revised Jan 2014
Project Address 1 -Stepping Stone Childrens Center Date 5/21/2013
Lighting Alterations,Renovations & Building Additions For Buiiding Department Use
�Less than 60% � 60%or more � Stand alone �Addition
Notes:
a. Lighting fixtures in a building addition may comply as a stand a/one project, or they may be
combined with the overall existing bldg lighting to demonstrate compliance.Refer to C101.4.3.
b. Fqr retrofits and building additions,provide Space Types and gross interior areas in the
Maximum Allowed Lighting table. If a builidng addition will comply as combined with the overall
existing builidng,include all applicable existing Space Types and gross interior areas.
c.Document new fixtures and all exrsting to remain frxtures in the Proposed Lighting table.
d. Ifless than 60%of existing fixtures will be replaced,provide total existing lighting wattage
(prior to retrofit)in the space provided in the Maximum Allowed Lighting table.
Maximum Allowed Lighting Wattage
Location(plan#, owe ross n er�or a s owe
room#) Space Type" Watts per ft2 Area in ft2 (watts/ftZ x area)
classrooms Classroom/lecture/training 1.24 8000 9920
Haliways Corridorltransition 0.66 750 495
Bathrooms Restroom 0.98 669 656
Mech.Closet Electricallmechanical 0.95 100 95
Storage Storage 0.63 860 542
Office Office-Enclosed 1.11 660 733
Stairs Stairway 0.69 104 72
At�ium'e` Enter Height:
Existing�ighting Enter Exist.Watts:
Retait Display Attowance firorn I.TG-INT-DISRLAY
" Select Table C405.5.2(2)category from drop down menu. Area Allowed Watts
"" For atriums,indicate height.Allowed wattage for first 40 feet is 0.03 W/ft.ht., Total 11143 12512
above 40 feet is 0.02 W/ft.ht.
Proposed Lighting Wattage
Location (plan#, Number of Watts/ Watts
room#) Fixture Description"' Fixtures Fixture Proposed
Classrooms 2x4 Flourecent Light 4 Lamp T8 68 118 8024
Bathrooms 2x4 Flourecent Light 3 Lamp T8 8 89 712
Haliways 2x4 Flourecent Light 3 Lamp T8 10 89 890
Mech Closet 4'Flourecent Strip 2 Lamp T8 3 59 177
Storage 2x4 Flourecent Light 2 Lamp T8 6 89 534
Storage 60W Keyless 6 60 360
Stairs 2x4 3 Lamp Flourecent 3 Lamp T8 2 59 118
Refiait display�ightirtg fram�TG-lNt-DISPLAY
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Watt 10815
'"`Include existing to remain lighfing fixtures and exempt lighting equipment per notes below.
Notes:
1. Include ALL proposed lighting fixtures.
2. For proposed Fixture Description,indicate fixture type,lamp type(e.g. T-8), number of lamps in the fixture,and ballast type(if included).For
track lighting,list the length of the track(rn feet)in addition to the fixture,lamp,and bal/ast information.
3. For proposed Watts/Fixture,use manufacturer's listed maximum input wattage of the fixture(not simply the lamp wattage)and other criteria
as specified rn Section C405.5.1.For line voltage track lighting,list the greater of actual luminaire wattage or length of track multiplied by 50,
or as applicable, the wattage of current limrtrng devices of the transformer. For!ow voltage track lighting list the transformer rated wattage.
4. For lighting equipment eligible for exemption per C405.5.1, note exception number and leave Watts/Fixture blank.
5. Document existing to remain fixtures in Proposed Lighting table in the same manner as new fixtures.Identify as existing in fixture description.
6. !f#NA appears in Retail Display ce/ls,informatron on LTG-INT-DISPLAY is incomplete.
Interior Lighting Power Allowance CflMPLIES
� � • . • � • . • • . � � '
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised Jan 2014
Pro.ject Info Project Address 1 -Stepping Stone Chiidrens Center Date 5/21/2013
Tahoma Blvd SE For Building Department Use
3-Yelm,WA
Applicant Name: Marijka Duetscher
Maximum Allowed Display Lighting Wattage
Location(plan#, owe ross n erior a ts owe
room#) Retail Display Area Type` Watts per ftZ" Area in ftz (watts/ft2 x area)
` Only retail sales areas that meet the requirements defined in Tab/e C405.5.2(2) Area Area Watts
footnote A may be enfered here. Select retail sales areas form drop down menu. Total�
"*Wattages per Table C405.5.2(2)footnote A.
++Display light allowance per footnote A calculation. Display Lighting Base Allowance
++Total Display Allowance
Proposed Display Lighting Wattage
Only separately controlled display fixtures independent of general area lighting per Table C405.5.2(2)footnote A may be entered here.
Location(plan#, Number of Watts/ Watts
Display Area� room#) Fixture Description Fixtures Fixture Proposed
'Select retail sales display area from drop down menu.
Total Proposed Watts�—�
Proposed Display Retail 1 Retail 2 Retail 3 Retaii 4
Lighting Totals
Notes:
1. For proposed Display Fixture Description,indicate fixture type,lamp type(e.g. T-8), number oflamps in the fixture,and ballast type(if
included). For track lighting,list the length of the track(in feet)in addition to the fixture,lamp, and ballast information.
2. For proposed Watts/Fixture,use manufacturer's listed maximum input wattage of the fixture(not simply the lamp wattage)and other
criteria as specified in Section C405.5.1. For Irne voltage track lighting, list the greater of actual luminaire wattage or length of track
multiplied by 50, or as applicable,the wattage of current limiting devices or of the transformer. For low voltage track lighting list the
transformer rated wattage.
3. List all display fixtures.
• • • i � • � • � � �
2012 Washington State Energy Code Compliance Forms for Commercial Buiidings including R2&R3 over 3 stories and all R1 Revised Jan 2014
Project Address 1 -Stepping Stone Childrens Center Date 5/21/2013
Lighting Alterations,Renovations & Building Additions For Building Department Use
�i Less than 60% �60%or more 0 Stand alone d Addition
Notes:
a.Lighting fixtures in a building addition may comply as a stand alone project, or they may be
combined with the overall exrsting bldg lighting to demonstrate compliance. Refer fo C101.4.3.
b.For retrofits and building additions,provide Building Area types and gross interior areas in the
Maximum Allowed Lighting table. If a builidng addition will comply as combined with the overall
existing builidng,include all applicable existing Building Area types and gross interior areas.
c.Document new fixfures and all existing to remain fixtures in the Proposed Lighting table.
d. !fless than 60%of existing fixtures will be replaced, use LTG-INT-SPACE form.
Spac�-��r-S}�ace methad selected. Use LTG-INT-SP�CE form.
Location(plan#, owe ross n erior a s owe
Building Area' room#,or ALL) Area Description Watts per ftZ Area in ft2 (watts/ft2 x area)
Schoolluniversity Classrooms 1stFloorClassrooms 0.99 9768 9670
Office Upstairs Office Office/Admin 0.90 660 594
� Select Table C405.5.2(1)Building Area from drop down menu. Total 10428
Space-E3y-Space method selected. Use IjTG-I:VT-SPAC'E form.
Location(plan#, Number of Watts/ Watts
Building Area' room#) Fixture Description"' Fixtures Fixture Proposed
School/university Classrooms 2x4 Flourescent 102 93 9486
Office Upstairs Admin 3 lamp 60 waats 3 180 540
" Se/ect Table C405.5.2(1)Building Area from drop down menu.
�*Include existing to remain lighting and exempt lighting equipment per notes below.
Compliance by Building Area
Total Allowed Total Proposed interior Lighting Power
Building Area Warnings Watts Watts Allowance
Schooiluniversity 9670 9486 COMPLIES
Office 594 540 COMPLIES
Total 102 64 1002 6
Notes:
1. Proposed Wattage for each Building Area type shall not exceed the Allowed Wattage for that Building Area type. Trading wattage between
Building Area types is not allowed under the Building Area Method compliance path.
2. Proposed fixtures must be listed in the building area in which they occur. Include ALL proposed lighting fixtures.
3. For proposed Fixture Description,indicate fixture type,famp type(e.g. T-8), number of lamps in the fixture,and ballast type(if included).For
track lighting, list the length of the track(in feet)in addition to the fixture,lamp, and ballast information.
4. For proposed Watts/Fixture,use manufacturer's/isted maximum input wattage of the fixture(not simp/y the lamp wattage)and other criteria
as specified in Section C405.5.1. For line voltage track fightrng,Irst the greater of actual luminaire wattage or length of track multiplied by 50,
or as applicable,the wattage of current limiting devices or of the transformer. For low vo/tage track/ighting Iist the transformer rated wattage.
5. For lighting equipment eligible for exemption per C405.5.1,note exception number and leave Watts/Fixture blank.
6.Document existing to remain fixtures in Proposed Lighting table in the same manner as new fixtures. Identify as existing in fixture description.
• � �
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised Jan 2014
Pro.ject Info Project Address: 1 -Stepping Stone Childrens Center Date 5/21/2013
Tahoma Blvd SE For Building Department Use
3-Yelm,WA
Applicant Name: Marijka Duetscher
Applicant Addr: 1404 Marvin Rd SE#307-254,Lacey WA 98516
Applicant Phone: 360-402-6871
Project Description � New Building ❑ Addition ['j Alteration ❑ Plans Included
Li�htin� Zone
As specifred by jurisdiction. Zone selection 0 Zone 1 (� Zone 2 � Zone 3 Q Zone 4
required to enable LTG-EXT form
Compliance Option � Lighting Power Density Calculations Q Total Building Performance
Building Grounds ❑Efficacy>60 Iumens/W � Controlled by motion sensor
Applies to luminaires>100 Watts
❑ Exemption(list)
Exterior Lighting Alterations ❑ No changes are being made to the existing exterior lighting
� New wiring installed to serve added fixtures and/or fixtures relocated to new circuit
Provide applicable exterior lighting controls per C405.2.4 and commissioning per
Tradable Maximum Allowed Lighting Wattage Base s�te Auowa�ce: �50
owe a s Area(ft),perimeter owe a s
Tradable Surfaces Surface Description per ft2 or per If (Ifl or#of items x ftZ(or x Ifl
rtain Entry Door Front Doors 30W/LF door 12 360
width
Other Entry Door Other poors ZOW/LF door 18 360
width
Entry Canopies Entry Canopies 0.4 W/£t2 1609 644
Uncovered Parking and parking 0.10 W/£t2 36520 3652
drives
roun s a ways walkways 0.16 W/£t2 4500 720
wide
Total Allowed Tradable Watts: 5736
Tradable Proposed Lightiilg Wattage (Use mfgr listed maximum input wattage for luminaire.)
Number of Watts! Watts
Tradable Surface Fi�ure Description Fixtures Fixture Proposed
r�in Entry Door cFL Downlight C 18 108
Entry Canopies CFL Downlight 12 18 216
Other Entry Door CFL Downlight 12 18 216
uncovered Parking and � pole Light 9 460 4140
drives
roun s a ways
Wall Light Halagen 50W Decorative 12 75 9��
wide
Total proposed tradable watts may not exceed the sum of total allowed tradable Total Proposed Tradable Watts: 5580
watts plus the base site a/lowance. Any base site allowance not needed to make
tradable watts comply can be applied to individual non-tradable categories.
Non-Tradable Maximum Allowed Lighting Wattage Base Site Allowance Remaining: 750 �
Allowed Watts Area(ft2),perimeter Allowed Watts
Non-Tradable Surfaces SurFace Description per ftz or per If (Ifl or#of items x ftz(or x Ifl
Non-Tradable Proposed Lighting Wattage
Number of Watts/ Watts '
Non-Tradable Surface Fixture Description Fixtures Fixture Proposed
Non-tradable proposed watts may not exceed allowed watts for any individual Total excess Non-Tradable watts: o
suRace unless the total excess waKS tor all non-tradable surtaces are less tnan me
remaining site allowance. Site Allowance Balance: �50
Exterior Lighting C4MPLIES WtTH S1TE ALL.�WANCE
, ,