20150309 Approved PlanSCOPE OF WORK:
REPLACE (1) ROOFTOP PACKAGED HVAC
UNIT. NEW UNIT TO BE INSTALLED BACK
IN SAME LOCATION ON FACTORY CURB
ADAPTER.
Packaged Unit With Curb Adapter Attachment Detail
s
HVAC GENERAL NOTES
1) THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACTRODUNG OR EVERY
OFFSET, WE I C1 I MAYBE REQUIRED. HVAC CONTRACTOR TO COORDINATE WITH ALL
OTHER TRADES
2) ALL WORK SHALL CONFORM TO THE HILQL'IRMEN IS OF WASHING ION STATE CODES.
REGULATIONS. ORDINANCES AND THE AUTHORITY HAVING JURISDICTION INCLUDING
BUT NOT LIMITED TO ANY OF THE FOLLOWING: IOC 2012, IMC 2012, UPC 2012 AND THE
WSEC 2012
31 AIR ECONOMIZERS SHALL BE PROVIDED ON ALL NEW SYSTEMS IF APPLICABLE.
ECONOMIZERS SIIAI.I.COMPLY WITII SECTIONS 0403.4.1.1 THROUGH C403.4.1.40FTIIE
WSEC 2012
4) FLEXIBLE DUCT LENGTHS SHALL NOT EXCEED 18' UNLESS PRIOR APPROVAL HAVE
BEEN GIVEN. FLEXIBLE DULL 10 COMPLY WITH 2012 MC SECTIONS 603.6.1, 603.611 i
AND 603.6.4
5) PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH
THECURRENTIBC
6) PIPING AND DUCT PENETRATIONS TIIRU FLOORS AND WALLS SHALL BE SLEEVED
AND /OR FIRE STOPPED 50 ASTO MAINTAIN THE INTEGRITY OF THE SURFACE PER 2012
MC 603.]
2) MAINTAIN 10' MINIMUM CLEARANCES TO ALL OUTSIDE AIR AND ECONOMIZER
INTAKES FROM ANY EXHAUST VENTS
8) DUCTWORK TO MEET THE R -VALUE REQUIRMENTS OF THE 2012 WSEC [403.2.2.1/2
9) ALL DUCTWORK CONSTRUCTED AND SEALED PER 2012 W SEC [403.2.2.1 & C403.2.2.3
10) EQUIPMENT SCHEDULE PROVIDED PER 2012 WSEC C403.2.3. C403.2.3.2, C403.2 13
AND [403.2.12.1
11) THERMOSTATIC CONTROLS INDICATED ON PLANS PER WSEC C403.2A.1
12) THERMOSTATS 10 PROVIDE 5 DEG DEADBAND MINIMUM PER WSEC C403.2.4.2
13) T HERMOS IAT TO PROVIDE AUTOMATIC SETBACK & MANUAL OVERRIDE PER WSEC
C403.7A 3
14) ALL NEW HVAC PIPING TO BE INSULATED PER 2012 WSEC 0403.2.8
15) DUCT SMOKE DETECTORS TO BE INSTALLED IN RETURN AIR SYSTEMS WITH A
DESIGN CAPACITY GREATER IT HAN 2000 CFM IN THE RETURN AIR DUCT OR PLENUM PER
20121MC ELI 2.1
LOCATION MAP
Csi
N
L.L I
Z
J Lf )
J 4t
L LJ
O
dj
V U,
W
Q �
a0 dLU 0.
_ H
V H Q ..
zL.ug
W O W
I
NORTH
VAR
Ple
F.R.O.
10 -1 -15
16453
JFS
I
NORTH
VAR
Single Packaged Convertible
Gas /Electric 14 SEER
4YCC4042A1060A
4YCC4042A1090A
TAG:
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air - conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
December 2014 4YCC4042A -SUB -1 B -EN Ingersoll Rand
SAFETY SECTION
Important— This document contains a wiring
diagram, a parts list, and service information. This is
customer property and is to remain with this unit.
Please return to service information pack upon
completion of work.
HAZARDOUS GASES!
Exposure to fuel substances or by- products of
incomplete fuel combustion is believed by the
state of California to cause cancer, birth defects, or
other reproductive harm.
This warning complies with state of California law,
Proposition 65.
HAZARDOUS VOLTAGE!
Failure to follow this Warning could result in
property damage, severe personal injury, or death.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper
lockout /tagout procedures to ensure the power
cannot be inadvertently energized.
SAFETYAND ELECTRICAL HAZARD!
Failure to follow this Warning could result in
property damage, severe personal injury, or death.
These servicing instructions are for use by
qualified personnel only. To reduce the risk of
electrical shock, do not perform any servicing
other than that contained in these operating
instructions unless you are qualified to do so.
GROUNDING REQUIRED!
Failure to inspect or use proper service tools may
result in equipment damage or personal injury.
Reconnect all grounding devices. All parts of this
product that are capable of conducting electrical
current are grounded. If grounding wires, screws,
straps, clips, nuts, or washers used to complete a
path to ground are removed for service, they must
be returned to their original position and properly
UNIT CONTAINS R-41 OA
REFRIGERANT!
Failure to use proper service tools may result in
equipment damage or personal injury.
R -410A operating pressure exceeds the limit of R-
22. Proper service equipment is required. Service
using only R -410A Refrigerant and approved POE
compressor oil.
SAFETY HAZARD!
Operating the unit without the access panels
properly installed may result in severe personal
injury or death.
Do not operate the unit without the evaporator fan
access panel or evaporator coil access panel in
place.
Important. Wear appropriate gloves, arm sleeve
protectors and eye protection when
servicing or maintaining this equipment.
Important. Air filters and media wheels or plates shall
meet the test requirements in UL 900.
02014 Trane 4YCC4042A- SUB -1 B -EN
Product Specifications
MODEL
4YCC4042A1060A
4YCC4042A1090A
RATED Volts /PH /Hz
208- 230/1/60
208 - 230/1/60
Performance Cooling
CONSTANTTORQUE
ECM
BTU (a)
40500
40500
Indoor Airflow (CFM)
1450
1450
Power Input (KW)
3.4
3.4
EER /SEER (BTU /Watt-
12.0/14.00
12.0/14.00
Hr.)
208 - 230/1/60
208 - 230/1/60
Sound Power Rating
6
6
[dB(A)] (b)
74.6
74.6
PERFORMANCE
DIRECT/ 1
DIRECT/ 1
HEATINGO
1/34/3345
1/34/3075
Input 13TUH -1st Stage
230/1/60
230/1/60
(Natural Gas) (d)
60000
90000
AFUE
81
81
Temp. Rise — Min /Max
30/60
35/65
( °F)
5) .3
5.3
Orifice Qty /Drill Sz.
2 / #37
3 / #37
(Natural Gas)
7.3
7.3
POWER CONN. — V/
Ph /Hz
208- 230/1/60
208 - 230/1/60
Min. Brch. Cir.
100
100
Ampacity (e)
28.5
28.5
Fuse Size — Max.
H X D X W
H X D X W
(amps)
45
45
Fuse Size — Recmd.
(amps)
45
45
COMPRESSOR
SCROLL
SCROLL
VOLTS /PH /HZ
208- 230/1/60
208- 230/1/60
R.L. Amps — L. R.
Amps
16.7/109.0
16.7/109.0
OUTDOOR COIL—
SPINE -FIN
SPINE -FIN
TYPE
Rows /F.RI
2/24
2 / 24
Face Area (sq. ft.)
15.63
15.63
Tube Size (in.)
3/8
3/8
INDOORCOIL—
MCHE
MCHE
TYPE
Rows /F.RI
2/16
2 / 16
Face Area (sq. ft.)
3.9
3.9
Tube Size Width (in.)
.81
.81
Refrigeration Control
EXPANSION VALVE
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
3/4 FEMALE NPT
OUTDOOR FAN—
SWEPT
SWEPT
TYPE
DIA.(IN.)
28.25
28.25
DRIVE /NO. SPEEDS
DIRECT/ 1
DIRECT/ 1
CFM @ 0.0 in. w.g. M
3400
3400
Motor — HP /R.P.M
1/4/825
1/4/825
4YCC4042A -S1JB -1 B -EN
Volts /Ph /Hz
208 - 230/1/60
208 - 230/1/60
F. L. Amps /L.R Amps
1.51/3.07
1.51/3.07
INDOOR FAN—
TYPE
CONSTANT
TORQUEECM
CONSTANTTORQUE
ECM
Dia. x Width (in.)
10.62 X 10.62
10.62 X 10.62
Drive /No. Speeds
DIRECT/ 3
DIRECT/ 3
CFM @ 0.0 in. w.g. W
SEE FAN PERF
TABLE
SEE FAN PERF
TABLE
Motor— HP /R.P.M.
3/4/1050
3/4/1050
Volts /Ph /Hz
208 - 230/1/60
208 - 230/1/60
F. L. Amps
6
6
COMBUSTION FAN
— TYPE
CENTRIFUGAL
CENTRIFUGAL
Drive /No. Speeds
DIRECT/ 1
DIRECT/ 1
Motor— HP /R.P.M.
1/34/3345
1/34/3075
Volts /Ph /Hz
230/1/60
230/1/60
FLA
.20
.24
FILTER /
FURNISHED
NO
NO
Type Recommended
THROWAWAY
THROWAWAY
Recmd. Face Area (sq.
ft (h)
5) .3
5.3
REFRIGERANT
R -410
R -410
Charge (Ibs.)
7.3
7.3
CHARGING
SPECIFICATIONS
Subcooling
100
100
GAS PIPE SIZE (in.)
1/2
1/2
DIMENSIONS
H X D X W
H X D X W
Crated (in.)
46 X 47 X 62
46 X 47 X 62
WEIGHT
Shipping (lbs.) / Net
(lbs.)
555/452
561/457
(a) Rated in accordance with AHRI Standard 210/240. AHRI standard
rating conditions are: 80 D.B.67 W.B. entering air to indoor coil. 95 D.
B. entering air to outdoor coil.
(b) Sound Power values are not adjusted for AHRI 270 -95 tonal
corrections.
W Ratings shown are for elevations up to 2000 ft. For higher elevations
reduce ratings at a rate of 4% per 1000 ft. elevation.
(d) Convertible to LPG.
W This value is approximate. For more precise value, see Unit
Nameplate,
M Standard Air — Dry Coil — Outdoor.
(a) Based on U.S. Government Standard Tests.
h) Filters must be installed in return air stream. Square footages listed
are based on 300 f.p.m, face velocity. If permanent filters are used
size per manufacturer's recommendation with a clean resistance of
0.05" W.C.
Outline Drawings
12.2e
111 /161
SECTION X-X
TYPICAL 181 SIDES OF SIDEFLM DUCT OPENINGS
L
18.03 18.29
12]/321 123/121
N.
[9 /22 I6]
SECTIOM
TYPICAL 181 SIDES OF OONNFL07 DUCT OPENINGS
Mi
Figure 1. 4YCC4042 -4060
RECOMMENDED SERVICE CLEARANCE MMIIN.
v
e
2vore: I ne view /aoe2ea
"Bottom Side" represents
the base as viewed looking
up from underneath the unit.
4YCC4042A -SUB -1 B -EN
v
2vore: I ne view /aoe2ea
"Bottom Side" represents
the base as viewed looking
up from underneath the unit.
4YCC4042A -SUB -1 B -EN
Figure 2. 4YCC4042 -4060
Outline Drawings
I 372.82
NI [14 - 11 /16]
(OUTSIDE)
�• �`�' T 158 19
-�
12 -9/321
RETURN 322.84
SUPPLY 112-231321
I � 449.02
j� [11-11 /161
79.50 (OUTSIDEI
[3-1/81
449 02 176.07
[17 II /I6] [6-15/161
(OUTS IDEI
BACK DUCT OPENINGS
1402.34
[55 -7/32]
(SURFACE AREA)
BACK SIDE
D
/81
Model
Height mm /in
Approx. Corner Weight - kg / Ibs
Shipping
Weight
kg /Ibs
Total Unit
Weight
kg /Ibs
Center of Gravity mm /in
A
W1
W2
W3
W4
B
C
4YCC4042 (060)
898.53 [35 -3/8]
71.2 [157]
46.6 [103]
34.6 [76]
S3.1 [117]
252.2 [SSS]
202.0 [452]
470.0 [18.5]
731.0 [28.8]
4YCC4042 (090)
898.53 [35 -3/8]
71.8 [158]
47.2 [104]
35.2 [78]
53.6 [118]
254.5 [561]
207.3 [457]
470.0 [18.5]
731.0 [2B.8]
4YCC4048 (070)
1000.13 [39 -3/8]
71.4 [157]
44.6 [98]
33.2 [73]
53.9 [119]
250.3 [552]
202.1 [448]
433.0 [17.0]
743.3 [29.3]
4YCC4048 (090)
1000.13 [39 -3/8]
72.0 [159]
45.0 [99]
33.8 [75]
54.4 [120]
252.6 [557]
205.4 [453]
433.0 [17.0]
743.3 (29.3]
4YCC4060 (090)
1000.13 [39 -3/8]
77.1 [170]
1 45.8 [101]
34.4 [76]
58.3 [128]
263.1 [580]
215.9 [476]
433.0 [17.0]
1 743.3 [29.3]
4YCC4060 (115)
1000.13 [39 -3/8]
78.0 [172]
46.3 [102]
34.9 [77]
59.0 [130]
265.8 [586]
218.6 [482]
414.0 [16.3]
635.0 [25.0]
4YCC4042A -SUB -1 B -EN 5
Outline Drawings
457.20
[181
(INSIDE)
75.41
[2-31/32
Figure 3. 4YCC4042 -4060
24V ENTRY
[151"
(INS IDEI
BOTTOM DUCT OPENINGS
i7
359.80 294.02
[14 -5/321 [11 -9/161 178.66 ,
1 1 [7 -1/321
4 96 II I —GAS LINE ENTRY
84.96 FOR 12.70 [1 121 N.P.T.
GAS CONNECTION
98.66
[3 -7/81
POWER ENTRY
27.78 DIA. HOLE
[1 -3/321
127.84 RIGHT SIDE
[5 -1/321
381.00
[151
(INSIDE)
75
9/161
20
iIDE)
09
/81
6 4YCC4042A -SUB -1 B -EN
Indoor Fan Performance
Table 1. Horizontal Airflow
4YCC4042AI060A
EXTERNAL STATIC PRESSURE (IN. WG)
MOTOR SPEED
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
HEAT— LOW
CFM
1104
1042
977
911
841
764
687
598
-
-
-
WATTS
109
116
124
134
142
152
161
171
-
-
-
HEAT— HIGH
CFM
-
1171
1112
1050
990
927
851
779
704
-
-
WATTS
WATTS
-
154
162
172
182
192
203
214
225
-
-
COOLING—LOW
CFM
1358
1393
1348
1296
1253
1204
1157
1096
1057
988
-
WATTS
WATTS
224
233
242
252
262
272
283
295
305
319
-
COOLING — MED
CFM
1521
1490
1448
1391
1362
1338
1315
1307
1254
1148
-
WATTS
306
316
327
337
348
359
369
382
395
407
-
COOLING HIGH
CFM
1659
1637
1604
1594
1529
1491
1467
1425
1385
1345
-
—
WATTS
409
421
432
443
455
467
477
490
503
513
-
4YCC4042A1090A
EXTERNAL STATIC PRESSURE (IN. WG)
HEAT— LOW
CFM
1419
1380
1341
1295
1249
1204
1160
1115
1069
1015
961
WATTS
WATTS
240
250
259
269
279
291
302
312
323
333
348
HEAT— HIGH
CFM
1559
1524
1483
1443
1401
1363
1319
1276
1233
1195
1147
315
WATTS
313
324
335
346
356
367
379
392
403
415
428
COOLING—LOW
CFM
1358
1393
1348
1296
1253
1204
1157
1096
1057
988
-
WATTS
224
233
242
252
262
272
283
295
305
319
-
COOLING MED
CFM
1521
1490
1448
1391
1362
1338
1315
1307
1254
1148
-
—
WATTS
306
316
327
337
348
359
369
382
395
407
-
COOLING HIGH
CFM
1659
1637
1604
1594
1529
1491
1467
1425
1385
1345
-
—
WATTS 1
409 1
421 1
432
443
455
467
477
490
503
513
Table 2. Down Airflow
4YCC4042AI060A
EXTERNAL STATIC PRESSURE (IN. WG)
MOTOR SPEED
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
HEAT— LOW
CFM
1109
1047
982
916
845
767
690
601
-
-
-
WATTS
109
117
125
134
143
153
162
172
-
-
-
HEAT— HIGH
CFM
-
1177
1117
1055
995
931
856
783
707
-
-
WATTS
-
155
163
173
182
193
204
215
226
-
-
COOLING—LOW
CFM
1345
1379
1334
1283
1241
1192
1145
1085
1046
979
-
WATTS
228
238
247
257
267
278
289
301
312
325
-
COOLING MED
CFM
1506
1475
1433
1377
1348
1325
1302
1293
1241
1136
-
—
WATTS
312
322
333
344
354
366
377
389
403
41S
-
COOLING — HIGH
CFM
1642
1621
1588
1578
1514
1476
1453
1411
1371
1331
-
WATTS
417
430
441
452
464
477
487
499
513
523
-
4YCC4042A1090A
EXTERNAL STATIC PRESSURE (IN. WG)
HEAT
CFM
1426
1387
1348
1301
1255
1210
1166
1120
1074
1020
966
—LOW
WATTS
241
251
260
270
281
292
303
314
325
335
349
HEAT— HIGH
CFM
1567
1531
1491
1450
1408
1370
1326
1282
1239
1201
1152
WATTS
315
325
337
347
358
368
381
394
405
417
430
COOLING LOW
CFM
1345
1379
1334
1283
1241
1192
1145
1085
1046
979
-
—
WATTS
228
238
247
257
267
278
289
301
312
325
-
COOLING MED
CFM
1506
1475
1433
1377
1348
1325
1302
1293
1241
1136
—
WATTS
312
322
333
344
354
366
377
389
403
415
COOLING—HIGH
CFM
1642
1621
1588
1578
1514
1476
1453
1411
1371
1331
WATTS
417
430
441
452
464
477
487
499
513
523
-
4YCC4042A -SUB -1 B -E N
Full Perimeter Roof Mounting Curb
1 1/2
Figure 4. 4042 — 4060 Models
BAYCURB051A Full Perimeter Roof Mounting Curb
i
i
D�
CHANNEL END—'
i
i
i
i
8
10 7/8
14
The drawings on this page are prepared by the
manufacturer in order to provide detail regarding
job layout only. These drawings are not intended to
be used as a basis to construct, build or modify the
items depicted in the drawings. The manufacturer
\ is not responsible for the unauthorized use of these
\ drawings and expressly disclaims any liability for
damages resulting from such unauthorized use.
B�
i
C
CHANNEL SIDE
OOiD NAILER
i
i
i
** 42.00 WITH ECONOMIZER WITH 25% FRESH
AIR ACCESSORY
4YCC4042A- SUB -1 B -E N
SERVICE CLEARANCE DIMENSIONS
A
B
C
D
WC * /TC*
42.00
36.00
12.00 **
24.00
DC * /YC*
42.00
36.00
12.00 **
36.00
** 42.00 WITH ECONOMIZER WITH 25% FRESH
AIR ACCESSORY
4YCC4042A- SUB -1 B -E N
Optional Equipment — Filter Rack
Figure 5. BAYFLTR101 Filter Rack (4024 -4036)
BAYFLTR102 (4042 -4060)
(Mounts in Filter /Coil Section)
Figure 6. BAYACCD0R1A Hinged Filter Access Door (4024 -4036)
BAYACCD0132A (4042 -4060)
Replaces Filter /Coil Access Panel
Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for
the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
4YCC4042A- SUB -1 B -E N
Optional Equipment — Economizer
Table 3. BAYECON101,102A Down Discharge Economizer and Rain Hood
(Mounts Over Horizontal Return Air Opening)
Table 4. BAYCON200, 201A Horizontal Economizer and Rain Hood
HVAC Unit
Economizer
Unit Application
Models
Economizer
Economizer
�.�..��..��.�..�.�d�..
A
rain hood
eeeeeeee ee
:. B
C
D
BAYECON101A
4024 -036
Outside air
Du t
E
! Rain Hood
dampers
i \
Return air
%
dampers Required
filter kit, order
Mixed Aire
Mist
separately
Sensor
.
eliminator
Models
A
B
C
BAYECON102A
4042 -060
F
Return
Relief
22"
damper
16 -7/8"
Duct
11- 11/16"
15"
Roofcurb
4042 -4060
26"
22- 21/32"
Table 4. BAYCON200, 201A Horizontal Economizer and Rain Hood
Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for
the unauthorized use of these drawings and expressly disclaims any liability fordamages resulting from such unauthorized use.
4YCC4042A- SUB -1 B -EN
Economizer
A
:. B
C
D
j Gaskets (2)
Du t
E
! Rain Hood
/
i \
%
Mixed Aire
/
Sensor
.
Economizer
Models
A
B
C
D
E
F
BAYECON200AA
4024 -4036
22"
20"
16 -7/8"
15- 11/16"
11- 11/16"
15"
BAYECON201AA
4042 -4060
26"
22- 21/32"
19"
17- 11/16"
14- 11/16"
21 -3/8"
Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for
the unauthorized use of these drawings and expressly disclaims any liability fordamages resulting from such unauthorized use.
4YCC4042A- SUB -1 B -EN
Optional Equipment — Outside Air Damper
Table 5. BAYOSAH001 and 002A
AEI
Manual Fresh
Air Model
Unit
Application
Models
A
B
C
D
FULLY
OPEN
.C�\
BAYOSAH001A
4024 -4036
22- 7/16"
20- 11/16"
12 -3/8"
9- 3/16"
2/3
D
�f ° % /3
BAYDMPR102A
4042-4060
25- 3/16"
20- 11/16"
12 -3/8"
9- 3/16"
FULLY
8 CLOSED
BAYOSAH002A
4042 —4060
25- 3/16"
20- 11/16"
12 -3/8"
9- 3/16"
Table 6. BAYDMPR101 and 102A, 25% Motorized Outside Air Damper
(Mounts Over Horizontal Return Air Opening)
NN��A
Manual Fresh
Air Model
Unit
Application
Models
A
B
C
D
BAYDMPR101A
4024 - 4036
22- 7/16"
20- 11/16"
12 -3/8"
9- 3/16"
C e
E
BAYDMPR102A
4042-4060
25- 3/16"
20- 11/16"
12 -3/8"
9- 3/16"
Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for
the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
4YCC4042A -SUB -1 B -EN
Mechanical Specifications
General
The units shall be horizontal airflow as shipped and
convertible to downflow.
All units shall be factory assembled, piped, internally
wired and fully charged with refrigerant. Units shall be
certified to UL Standard 1995. Units shall be designed
to operate at ambient temperatures as high as 115 °F.
Cooling performance shall be rated in accordance with
AHRI standards. The YC heating /cooling unit design is
certified to ANSI 221.47/CSA 2.3, specifically for
outdoor applications using natural gas or propane. All
units shall be designed for outdoor rooftop or ground
level installation.
Unit Casing
All components shall be mounted in a weather -
resistant steel cabinet with an enamel finish. Access
panels shall be provided for unit controls and indoor
coil and fans. Indoor air section compartment shall be
completely insulated with fireproof, permanent,
odorless fiber material. Knockouts shall be provided for
utility and control connections. Drain connections shall
be provided to accommodate indoor water runoff.
Compressor
The compressor shall be hermetically sealed, high
efficiency scroll compressors. Internal overcurrent and
over temperature protection, internal pressure relief
shall be standard. Other features include centrifugal oil
pump, low vibration and noise.
Refrigeration System
All units shall have refrigerant control. Service pressure
tap ports and a refrigerant line filter shall be standard.
Evaporator Coil (2 -4 Ton Models) All aluminum
micro channel, extruded tubes, mechanically bonded to
aluminum fins, and factory pressure and leak tested at
480 —650 psig. All units have TXV to control refrigerant
flow.
Condenser Coil
The Spine Fin TM condenser coil shall be continuously
wrapped, corrosion resistant all aluminum with
minimum brazed joints. This coil is 3/8" OD seamless
aluminum tubing glued to a continuous aluminum fin.
Coils are lab tested to withstand 2.000 pounds of
pressure per square inch. The outdoor coil provides
low airflow resistance and efficient heat transfer. The
coil is protected on all four sides by louvered panels.
Indoor Air Fan
Constant Torgue, forward - curved, centrifugal wheel in
a Composite Vortica ® Blower housing. Motor shall
have thermal overload protection and permanently
lubricated motor bearings. Motor /blower assembly
isolated from unit with rubber mounts.
Outdoor Fan
One direct - drive, statically and dynamically balanced
propeller fan shall be used in a draw- through vertical
discharge configuration. Permanently lubricated
weather proof motor shall have built -in thermal
overload protection.
System Controls
System controls include condenser fan, evaporator fan
and compressor contactors.
Accessories Roof Curb
The roof curb shall be designed to mate with the unit
and provide support and complete weathertight
installation when properly installed. Adhesive back
polyurethane sealing strips shall be provided to ensure
an airtight seal between supply and return openings of
the curb and unit. The roof curb design allows field
fabricated ductworkto be connected directly to the
curb. Curb ships knocked down for field assembly, and
includes factory installed wood nailer strips.
Heating System
Gas -Fired Heating Section
Models shall provide completely assembled, wired and
piped gas fired heating systems within unit. Design
certified by UL, specifically for outdoor application.
Threaded gas connection on the unit.
Electric Ignition System
Main burner is lit each time thermostat calls for heat.
Flame sensor proves flame and keeps the main burner
on. Should a loss of flame occur, the main valve closes
and the spark recurs within 0.8 seconds. When
thermostat is satisfied, main burner is extinquished.
Forced Combustion Blower
Insures flame stability under varying wind conditions.
Gives higher combustion efficiency and location
flexibility.
Heat Exchanger
Stainless steel tubes. Free floating design.
Burners
Stainless steel. Multi -port inshot.
12 4YCC4042A -SUB -1 B -EN
Single Source Power Entry
This accessory when used with electric heat accessory
shall allow single source power connection to unit and
heater combination. Single source power entry kits
shall have specific matching heater(s). Kit shall include
high voltage terminal blocks, fuse blocks and fuses, cut -
to- length interconnecting wiring, and junction box (if
required) to provide power sources with fuse
protection as required for both the unit and accessory
heater. Kit components shall install within the heater
cabinet in the heater access section. Single source
branch power circuit shall be protected and wired in
accordance with local codes.
Fully Modulating Economizer
This accessory shall be field installed and be composed
of the following items: 0 -100 % fresh air damper,
damper drive motor, fixed dry bulb enthalpy control,
and low voltage pigtails for electrical connections.
Solid state enthalpy or differential enthalpy control is
optional. Economizer operations shall be controlled by
the preset position of the enthalpy control. A
barometric relief damper shall be standard with the
economizer and provide a pressure operated damper
Mechanical Specifications
that shall be gravity closing and prohibit entrance of
outside air on equipment "off" cycle. Economizer
requires BAYRLAY004A relay kit to interface the
economizerto the heat pump.
Manual Outside Air Dampers
Rain hood and screen shall be field installed. Suitable
for up to 25% outside air.
Start Kit
Extra compressor starting capacity for single phase
equipment.
Control Options
Standard Indoor Thermostats
Two stage heating /cooling or one stage heating /cooling
thermostats shall be available in either manual or
automatic changeover.
Programmable Electronic Night Setting Thermostat
Programmable electronic thermostat shall provide
heating setback and cooling setup with 7 —day
programming capability. 1H /1C or 2H /2C models
available.
c ETA us
-s�a
Intertek
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
02014 Trane
4YCC4042A- SUB -18 -EN 01 Dec 2014 "H Ingersoll Rand
Supersedes 4YCC4042A- SUB -IA -EN (November 2014) (
%IIPCS
Structural Solutions
Seattle 811 First Avenue, Suite 620 • Seattle, WA 98104 • tel: 206.292.5076
Tacoma 1250 Pacific Avenue, Suite 701 • Tacoma, WA 98402 • tel: 253.383.2797
www.pcs-structural com
STRUCTURAL CALCULATIONS
FOR
COUNTRY PLAZA ROOF TOP SUPPORT
715 EAST YELM AVENUE, 5U ITE 5
YELM, Y4A5H INGTON
PREPARED BY
PC5 STRUCTURAL 50LUT/ON5
Iv
�! 42292
4 1OJZj Ir
ON I
OCTOBER 20 2015
16 -022
C
CL
4-
O
O
L
0
0
3
in
3
o
O
O
N
0
LF
P-
C
O_
Q�
60
It
w
a
Q
0
Q
m
Z m u
J +
w N
U O pp
w z Ln
�N3
af ww
z
r-4
w �
'a o
F-
z
L,.;
N O
Ln
w
(V
Full Perimeter Roof Mounting Curb
1 1/2
0
Figure 4. 4042 — 4060 Models
BAYCURB051A Full Perimeter Roof Mounting Curb
� A
CHANNEL END I \,
I
i
387/8
8
10718
14
The drawings on this page are prepared by the
manufacturer in order to provide detail regarding
job layout only. These drawings are not intended to
be used as a basis to construct, build or modify the
items depicted in the drawings. The manufacturer
\ is not responsible for the unauthorized use of these
\ drawings and expressly disclaims any liability for
damages resulting from such unauthorized use.
B \
AIR
SUPPLY
AIR 1
I
r
i
HOLE IN ROOF
I
53 1/8
�CI
— CHANNEL SIDE
WOOD NAILER
I
** 42.00 WITH ECONOMIZER WITH 25% FRESH
AIR ACCESSORY
4YCC4042A- SUB -1 B -EN
SERVICE CLEARANCE DIMENSIONS
A
B
C
WC */TC*
42.00
36.00
12.00 **
_D
24.00
DC * /YC*
42.00
36.00
12.00 **
36.00
** 42.00 WITH ECONOMIZER WITH 25% FRESH
AIR ACCESSORY
4YCC4042A- SUB -1 B -EN
Product Specifications
MODEL
4YCC4042A1060A
4YCC4042A1090A
RATED Volts /PH /Hz
208- 230/1/60
208- 230/1/60
Performance Cooling
40500
40500
BTU (a)
10.62 X 10.62
10.62 X 10.62
Indoor Airflow (CFM)
1450
1450
Power Input (KW)
3.4
3.4
EER /SEER (BTU /Watt-
12.0/14.00
12.0/14.00
Hr.)
208 - 230/1/60
208 - 230/1/60
Sound Power Rating
74.6
74.6
[dB(A)] (b)
CENTRIFUGAL
CENTRIFUGAL
PERFORMANCE
DIRECT/ 1
DIRECT/ 1
HEATING(c)
1/34/3345
1/34/3075
Input BTUH -1st Stage
60000
90000
(Natural Gas) (a)
.20
.24
AFUE
81
81
Temp. Rise — Min /Max
30/60
35/65
( °F)
5.3
5.3
Orifice Qty/Drill Sz.
2 / #37
3 / #37
(Natural Gas)
7.3
7.3
POWER CONN. — V
208- 230/1/60
208- 230/1/60
Phi
10°
100
Min. Brch. Cir.
1/2
Ampacity ( e)
28.5
28.5
Fuse Size — Max.
45
45
(amps)
Fuse Size — Recmd.
45
45
(amps)
COMPRESSOR
SCROLL
SCROLL
VOLTS /PH /HZ
208 - 230/1/60
208 - 23011/60
R.L. Amps — L.R.
16.7/109.0
16.7/109.0
Am s
0U DOOR COIL —
TYPE
SPINE -FIN
SPINE -FIN
Rows /F.P.I
2/24
2 / 24
Face Area (sq. ft.)
15.63
15.63
Tube Size (in.)
3/B
3/8
INDOOR —
MCHE
MCHE
TVPE
Rows /F.P.I
2/16
2 / 16
Face Area (sq. ft.)
3.9
3.9
Tube Size Width (in.)
.81
.81
Refrigeration Control
EXPANSION VALVE
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
3/4 FEMALE NPT
OUTDOOR VAN —
SWEPT
SWEPT
DIA.(IN.)
28.25
28.25
DRIVE /ND. SPEEDS
DIRECT/ 1
DIRECT/ 1
CFM @ 0.0 in. w.g. M
3400
3400
Motor— HP /R.P.M
1/4/825
1/4/825
4YCC4042A -SUB -1 B -EN
Volts /Ph /Hz
208- 230/1/60
208 - 230/1/60
F.L. Amps /L.R Amps
1.51/3.07
1.51/3.07
INDOOR FAN —
TYPE
CONSTANT
TOR UEECM
CONSTANTTORQUE
ECM
Dia. x Width (in.)
10.62 X 10.62
10.62 X 10.62
Drive /No. Speeds
DIRECT/ 3
DIRECT/ 3
CFM @ 0.0 in. w.g. (9)
5 E AN P RF
TABLE
SEE FAN PERF
TABLE
Motor— HP /R.P.M.
3/4/1050
3/4/1050
Volts /Ph /Hz
208 - 230/1/60
208 - 230/1/60
F.L. Amps
6
6
COMBUSTION FAN
— TYPE
CENTRIFUGAL
CENTRIFUGAL
Drive /No. Speeds
DIRECT/ 1
DIRECT/ 1
Motor— HP /R.P.M.
1/34/3345
1/34/3075
Volts /Ph /Hz
230/1/60
230/1/60
FLA
.20
.24
FILTER /
FURNISHED
NO
NO
Type Recommended
THROWAWAY
THROWAWAY
Recmd. Face Area (sq.
ft (h)
5.3
5.3
REFRIGERANT
R -410
R -410
Charge (lbs.)
7.3
7.3
CHARGING
SPECIFICATIONS
Subcooling
10°
100
GAS PIPE SIZE (in.)
1/2
1/2
DIMENSIONS
H X D X W
H X D X W
Crated (in.)
46 X 47 X 62
46 X 47 X 62
WEIGHT
Shipping (lbs.) J Net
(lbs.)
555/452
561 / 457
(a% Rated in accordance with AHRI Standard 210 /240.7AHRLsFeni
rating conditions are: 80 D.B.67 W.B. entering air to indoor coil. 95 D.
B. entering airto outdoor coil.
(b) Sound Power values are not adjusted for AHRI 270 -9S tonal
corrections.
(0 Ratings shown are for elevations up to 2000 ft. For higher elevations
reduce ratings at a rate of 4°/ per 1000 ft. elevation.
(a) Convertible to LPG.
�) This value is approximate. For more precise value, see Unit
Nameplate.
R) Standard Air — Dry Coil — Outdoor.
(9) Based on U.S. Government Standard Tests.
(h% Filters must be installed in return air stream. Square footages listed
are based on 300 f.p.m, face velocity. If permanent filters are used
size per manufacturer's recommendation with a clean resistance of
0.05" W.C.
RI
Figure 2. 4YCC4042 -4060
Outline Drawings
7f--,T--a I (OU 82
An' [14- 1TSI1116)
[OUDE)
��►� 58. 19
[2.9/32]
RETURN 322 84
SUPPLY 112- 23/32]
449.02
(11.11/167
19 50 (OUTSIDE!
(3 1181
449.02 7 116.01
[11-II /161 [6- 15/161
(OUTSIDE)
BACK DUCT OPENINGS
530.60
(20 -1181
X x
1402.34
[55 -1/32]
(SURFACE AREA)
BACK SIDE
Model
Height mm /in
Approx. Comer Weight - kg / Ibs
Shipping
Weight
kg /Ibs
Total Unit
Weight
kg /Ibs
Center of Gravity mm /in
A
W1
W2
W3
W4
8
C
4YCC4042 (060)
898.53 [35 -3/8]
71.2 (157]
46.6 [103]
34.6 [76]
53 -1 [117]
252.2 [5551
202.0 [452J
470.0 [18.5]
731.0 [28.81
4YCC4042 (090)
898.53 [35 -3/8]
71.8 [1581
47.2 [104J
35.2 [78]
53.6 [118)
754.5 [561]
207.3 [457]
470.0 [18.51
731.0 (28.8]
4YCC4048 (070)
1000.13[39 -3/81
71.4 [157]
44.6 [981
33.2[73]
53.9 [1191
1 250.3 [552)
202.1[4481
433.0 '17,01
7433 [29.31
4YCC4048 (090)
1000.13 [39 -3/8]
72.0 (1591
45.0 [99]
33.8 [75]
54.4 [1201
252.6 [557]
1 205.4 (453]
433.0 [17.01
743.3 (29.3]
4YCC4060 (090)
1000.13 [39 -3/81
77.1 [1701
45,8 [101]
34.4 [76]
58.3 [128]
263.1 [580]
215.9 [476)
433.0 [77.0,'
743.3 [29.3]
4YCC4060 (115)
1000.13 [39 -3/81
78.0 fl 721
463 [102J
1
34.9 [771
59.0 [130]
265.8 [586]
)18,6[482)
1 41.4.0 [16.3]
635.0 [25.0]
4YCC4042A- SUB -1 B -E N 5
I ADAPTER CURB FORE I
Z /4TC */WC */YC *3042 -060A
ADAPTER CURB
38 7/8" ��
INSTRUCTIONS:
1. REMOVE OLD A/C UNIT.
2. APPLY 1/4" x 1 114" GASKETING.
3. INSTALL & SECURE ADAPTER CURB
ON EXISTING CURB AS
REQUIRED BY LOCAL BUILDING CODE.
4. APPLY 1/4" x 1 1/4" GASKETING
ON ADAPTER CURB.
5. INSTALL& SECURE NEWA/C UNIT
ON ADAPTER CURB AS REQUIRED
BY LOCAL BUILDING CODE.
2,,
EXISTING TRANE UNIT
YCC036FH & YCC042FM
YCCG48FM
STANDARD FEATURES:
• HEAVY GA. GALV. STEEL CONSTRUCTION
• FULLY INSULATED WITH 1" - 1.5 LB.
DENSITY INSULATION
• 1/4!'x 1 1/4" GASKETING
• SHIPPED FULLY ASSEMBLED
• SUPPLYAND RETURN DUCT
CHAMBERS INCLUDED
I PRODUCT SUBMITTAL QUOTE #
Signature required prior to production.
TC61ACTC45
Manufacturers Equip
Sign Here' ' Approved
Date
PCS Structural Solutions
Job Number= 16 -022
Date = 2- Oct -15
Name = LAH
I
Project = Country Plaza - Roof Top Unit Replacement -
Yelm, Washington
Design Criteria = ASCE 7 -10, IBC 2012
Unit Weight, Wp = 811 Ib""
Existing Unit Weight = unkftaw R -4cl �b
Roof Dead = Actual
Roof Live = 25 psf
IC ("i r �, L—)v'� :%etc:. it
100 tJO + (V 1O
Lateral Analysis: The new unit does not have a significant impact to the building's capacity to resist wind or
seismic forces
Check Seismic Forces (Ultimate):
ASCE 7 Eq 13.3 -1
Fp = 0.4 *SDS *(lp /Rp) *ap *WP *[1 +2 *z /h] =
374 1
ASCE 7 Eq 13.3 -2
Fp max
= 1.6 *SDS *lp *WP =
1298 lb
ASCE 7 Eq 13.3 -3
Fp in
= 0.3 *SD5 *IP *Wp =
243 lb
SDS =
1
0 -'i`;7
ASCE 7 Table 13.6 -1
a =
2.5
jhl j
ASCE 7, Sec. 13.1.3
Ip =
1
ASCE 7, Table 13.6 -1
RP =
6.5
height of attachment
z =
25.0 ft
total of height of bid'g
h =
25.0 ft
i
AWMIh. AdMIIk Project: Job No: V
FUSSubject: Sheet Name:
Structural Solutions Originating Office: ❑ Seattle ❑ Tacoma Date: —
4-v
� - 2.:>A;_4 �
IA
2ja 7
'7
Seattle 811 First Avenue, Suite 620 • Seattle, WA 98104 - tel: 206,292.5076 www.pcs-structural.com
Tacoma i 1250 Pacific Avenue, Suite 701 -Tacoma, WA 98402 • tel: 253.383.2797