20150321 Permit Pkg 12242015City of Yelm
Community Development Department
Building Division
Phone: (360) 458 -8407
Fax: (360) 458 -3144
Applicant:
Name: MT RAINIER PROPERTIES (A)
Address: 10814 128TH AVE SE
RAINIER WA 98576
Property Information:
Site Address: Q1AA Rl1RNFTT RD SE A
Assessor Parcel No.: 21713340601 Subdivision:
Contractor Information:
Name: CAPEZIO HOMES
Address: JEFF
2344 SUMIT LAKE SHORE RD NW
OLYMPIA WA 98502
Contractor License No.: CAPEZHL954QH Expires
Project Information:
Project: COMMERCIAL REMODEL
Permit No.: 20150321
Issue Date: 1212412015
(Work must be completed within 180 days)
Phone: 360- 561 -8820
Owner: Mt Rainier Properties
Phone:
7/31/2015
Lot:
Description of Work: 1800 square foot fitness center with two showers. Water usage calculated at 229 gallons per
1000 square feet. Used fitness center at 16910 SR 507 with 2 showers as comparison. Add
sprinkler heads for additional coverage.
Sq. Ft. per floor: First
Second
Third
Garage
Basement
Fees:
Heat Type (Electric, Gas, Other):
Item
Contractor
BUILDING
CAPEZIO HOMES
MECHANICAL
CAPEZIO HOMES
PLUMBING
CAPEZIO HOMES
FIRE ALARM
FIREONE
FIRE SPRINK
KNI FIRE
TOTAL FEES:
Applicant's Affidavit:
I certify that I have read and examined the information contained within the application and know the same
to be true and correct. I also certify that the proposed structure is in conformity with all applicable City of
Yelm regulations including those governing zoning and land subdivision, and in addition, all covenants,
easements and restrictions of record. If applying as a contractor, I further certify that I am currently
registered in the State of Washington.
Signature _ Date
Firm
Fees
$17,039.64
$ 39.00
$ 34.00
$ 63.93
_$ -1fit3 46 $17,337.03
OFFICIAL USE ONLY
# Sets of Prints:
Final Inspection:
Date:
By: _
t1Yqfi 58-12 44 •56 AM
(36U�
45B-32
2015 11'
00211013 1001'
REG #: TERM•
DPER'
RF# 8008 1E
PAID 8y ' PERMITS
33.0000 BUILDI 63.9�GR
RAN 20150321 PROPERTIES
g 44A BURN TT RD SE CR
63.0
FA 63,93 CHECK
TENDERED 63.93-
APPLIED' ��� 0 00
GRANGE:
CITY OF YELM
COMMERCIAL BUILDING PERMIT APPLICATION FORM
Project Address: RtLK- BLAZN4 PXJ SE Parcel #: 01 1O) 2-112.9'9
Zoning;
Current Use:
Proposed Use:
❑ New Construction ❑ Re -Model / Re -Roof / Tenant Improvement
❑ Plumbing C' Mechanical Fire Prevent/Suppress /Alarm -] Other
Project Description /Scope of Work:
Project Value: ql -7 90.00
Building Area (sq. ft) Parking Garage 1st Floor X 2nd Floor 3rd Floor
Building Height —Srtb 2c'�S
Are there any environmentally sensitive areas located on the parcel? If yes, a
completed environmental checklist must accompany permit application.
BUILDING O NE !TENANT NAME: 2 -ie-
ADDRESS 0 1600 �SU6 EMAIL _
CITY yikNSTATE W Pc- ZIP 91511 -) TELEPHONE
ARCHITECT /ENGINEER LICENSE #
ADDRESS EMAIL
CITY STATE ZIP TELEPHONE
GENERAL CONTRACTOR P, L O ft\t S TELEPHONE 3(00 a
ADDRESS 244�k Saw•4•�' r L&t SrKW C_ I N W EMAIL JCf�yo(PCOMCA$+. r r_4
CITY (, W STATE WZIP 01S650'Z FAX
CONTRA`CTOR'S LICENSE # EXP DATE CITY LICENSE #
PLUMBING CONTRACTOR TELEPHONE
ADDRESS EMAIL
CITY STATE ZIP FAX
CONTRACTOR'S LICENSE # EXP DATE CITY LICENSE #
MECHANICAL CONTRACTOR Vr1C (• TELEPHONE _GCXo -0 VJ UJ► 1
ADDRESS EMAIL S1,t 2,,-t MK r1LA.!'h AK --ate'
CITY t\A- STATE ZIP 9900A FAX 25 3— -13 I-7
CONTRA TOR'S LICENSE #V:Xt WT$ t)99 KWXP DATE�6CITY LICENSE # IO 3
Copy of City Mitigation documentation (TFC).
I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the
above described property will be in accordance with the laws, rules and regulations of the State of Washington and the
City of Yelm.
I 1 I zo N
Applicant's Siddaturel Date
Owner/ Contractor/ Owner's Agent/ Contractor's Agent/ Tenant (Please circle one.)
All permits are non - transferable and will expire if work authorized by such permit is not begun
within 180 days of issuance, or if work is suspended or abandoned for a period of 180 days
DEC 0 � 2015 (360) 458 -3835
105 Yelm Ave W 1 (360) 458 -3144 FAX
Yelm, WA 98597 www.ei.yelm.wa.us
T.4 HLE OF CONTENTS
7. SCOPE OF WORK (1 PAGE)
Z. WHEELOCK RSS STROBES
SPEC SHEETS (4 PAGES)
FIRE ONE, INC.
107 WASHIINGTON BLVD.
ALGONA WA, 9BO01
2 06- 575 -0331
FAX - 253 - 735 -4976
SCOPE OF WORK FOR:
WELLSPRING SUITE 1 02
9144 BERNETT RD. .SE
YELM WA, 9BS97
OVERVIEW
THE SCOPE OF THIS PROJECT IS TO INSTALL NOTIFICATION DEVICES
FOR THE PURPOSE OF TENANT IMPROVEMENT. SHOWER ADDITIONS
CONTROL PANEL'
THE CONTROL PANEL IS AN EXISTING SILENT KNIGHT SSOB WITH
AN INTEGRATED DUAL LINE DIGITAL DIALER.
WIRING:
ALL WIRING WILL BE FPLP RATED AND SIZED AS FOLLOWS:
INITIATING CIRCUITS WILL BE AWG 7 6 OR GREATER
INDICATING CIRCUITS WILL BE AWG 74 OR GREATER
INSTALLATION:
INSTALLATION WILL BE PERFORMED IN ACCORDANCE WITH NF-PA
70, NFPA 72 AND APPLICABLE PROVISIONS OF THE WASHINGTON
ADMINISTRATION CODE. TECHNICIANS FROM FIRE ONE, INC., CERTIFIED
BY THE STATE OF WASHINGTON AND UNDER PERMIT BY THE AUTHORITY
HAVING JURISDICTION WILL PERFORM ALL INSTALLATION.
TESTING AND WARRANTY:
A COMPLETE TEST WILL BE PERFORMED IN THE PRESENCE OF THE
OWNER, AND ANY OTHER AUTHORITY HAVING JURISDICTION DEEMED
APPROPRIATE. FOLLOWING AN ACCEPTABLE TEST RESULT, THE OWNER
AND FIRE ONE, INC. WILL SET THE TERMS FOR WARRANTY SERVICE AND
ARRANGE A CONFIDENCE TESTING SCHEDULE. FIRE ONE, INC. WILL
PROVIDE SYSTEMS TRAINING TO THE OWNER TO ENSURE PROPER
OPERATIONS.
4R(_I4ITFrTS dNl) FNI;INFFRS SPECIFICATIONS
General
Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard
1638 (Standard for Visual Signaling Appliances) for Indoor /Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices
for Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using
either exposed conduit or concealed conduit, or semi -flush mounting to a recessed electrical box in walls or ceilings using Wheelock
mounting accessories.
Weatherproof Strobes
Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range
of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings
up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77 °F shall be available. The
strobes shall operate over an extended temperature range of —40 °F to 150 °F ( -40 °C to 66 °C) and be listed for maximum humidity of
95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm
Control Panel (FACP).
Weatherproof Audibles and Audible /Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor /Outdoor
use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code -3 output that can be synchronized.
The horns shall have at least 3 sound level settings. Horn /Strobe combinations shall be able to be synchronized on a single NAC.
Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone
Audible /Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized.
The audibles shall be able to be coded when operated on a separate NAC.
Weatherproof Speakers and Speaker /Strobes
Weatherproof speakers and speaker /strobes shall be listed for Indoor /Outdoor use under UL Standard 1480. All speakers shall provide
field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back
construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET -1010. They shall be
listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series
ET70WP. They shall be available for surface or semi -flush mounting to walls or ceilings and shall be listed to produce up to 93 dBA.
Synchronization Modules
When synchronization of strobes or temporal code -3 audibles is required, the appliances shall be compatible with the Wheelock Series
DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built -in Wheelock Patented Sync Protocol. The
strobes and audibles shall not drift out of synchronization at any time during operation.
Series ASWP audibles and strobes shall be able to be synchronized on a 2 -wire circuit with the ability to silence the audible if required.
The strobes on Series MT multitone audible /strobe appliances shall be able to be synchronized and shall be able to be operated on a
separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC.
Weatherproof Mounting Accessories
Weatherproof mounting options shall include surface mounting or semi -flush mounting to walls or ceilings. Surface mounted appliances
shall mount to Wheelock IOB, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit.
For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock's WP -KIT to provide a
weatherproof seal for the electrical box. Semi -flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP
or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance.
�ri>v�
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
S9004 WP 11/12
r..._- ...--- ._...- - - - - - - - - - - - -- ----- - --- - -- ✓ XWC -r"
Notification
Mounting Accessories
El El
i
WFP WFPA
Gasket Kit
Backboxes, Plates, Gasket Kits
Order Code
WP -KIT
Exposed Conduit
4486
Flush Plates
WPSBB
WPSBB + WP -KIT
WFPA -R
Red
4698
WFPA -W
White
4701
WFP -R
Red
4696
WFP -W
White
4697
Backboxes
ET -1010 Speakers
WBB
IOB -R*
Red
5046
IOB -W*
White
5047
WPSBB -R*
Red
9751
WPSBB -W*
White
3033
WPBB -R*
Red
9014
WPBB -W*
White
4692
WBB -R
Red
2959
WBB -W
White
2960
Wiring Diagrams
It* a
1013 WPSBB WPBB WBB
Mounting Options:
Backboxes, Plates, Gasket Kits
Surface Mount
Flush
Mount
Exposed Conduit
Concealed Conduit
RSSWP Strobes
WPSBB
WPSBB + WP -KIT
WFP
ET70WP Speaker Strobes
106
1013 + WP -KIT
WFP
ASWP Horn Strobes
WPBB
WPBB + WP -KIT
WFPA
AHWP Horns
WBB
-
WFP
ET -1010 Speakers
WBB
-
WFP
MTWP Multitone Horn Strobes
IOB
106 + WP -KIT
WFP
Multitone Horn
1013
1013 + WP -KIT
WFP
WEI, WPSBB and WPBB models include weep holes and plug in the event that
moisture may have entered the appliance
SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE
IN UNISON. RED AND BLACK SHUNT -WIRES ARE SUPPLIED.
FROM TO NEXT
PRECEDING + +
APPLIANCE RED APPLIANCE
O
BLACK
R FACP - OR EOLR
STROBE AUDIBLE
SERIES RSSWP, ASWP, AHWP, MTWP AND MT -12/24
APPLIANCES
FROM
+ + TO NEXT
PRECEDING
NAC
SYNC
_ APPLIANCE
APPLIANCE OR
OUT
+OUT t
OR EOLR
FACP
\
MINUS 1
FACP
SERIES MTWP APPLIANCES SYNCHRONIZED STROBE
OPERATION WITH CODED FACP
MTWP
Strobe
Sync Circuit
NAC #1 Module
or
PS 0 Audible
Power Circuit
FACP Supply
NAC #2
Note: Strobe circuit requires constant voltage.
SERIES RSSWP /ASWP APPLIANCES SYNCHRONIZED W/
DSM MODULE SINGLE CLASS "A" NAC CIRCUIT
DSM
STROBE
+
NAC
SYNC
CIRCUIT
OUT
+OUT t
0 +IN1 ST
\
MINUS 1
FACP
+AUDIBLE
MINUS 2
+IN2 RSS ST
—STROBE
NAC
+OUT2
CIRCUIT
RETURN
Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery.
#Refer to Data Sheet S7000 for Mounting Options
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc. dba Cooper Notification standard terms and conditions.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND /OR OTHERS.
General Notes:
• Strobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range.
• All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table.
Strobe
Candela Ratings
Order Code
Strobe
Order Code
RSSWP- 2475W -FR
Red
9013
RSSWP- 2475C -FR Red
4338
RSSWP - 2475W -FW
White
3034
RSSWP - 2475C -FW White
4446
RSSWP - 24MCWH -FR
Red
5161
RSSWP - 24MCCH -FR Red
5167
RSSWP - 24MCWH -FW
White
5165
RSSWP - 24MCCH- FWWhite
5187
Audible Strobe
0.150
0.034
Audible Strobe
135
ASWP - 2475W -FR
Red
9012
ASWP - 2475C -FR Red
4251
ASWP - 24MCWH -FR
Red
5137
ASWP - 2475C -FW White
4502
ASWP - 24MCWH -FW
White
5140
ASWP- 24MCCH -FR Red
5149
115
47
0.300
ASWP - 24MCCH -FW White
5157
Multi -tone Strobe
MCCH
177
177
73
MTWP- 2475W -FR
Red
8420
Multi -tone Strobe
24185
MTWP- 2475W -FW
White
3112
MTWP - 2475C -FR Red
4457
MTWP - 24MCWH -FR
Red
5132
MTWP - 2475C -FW White
4478
MTWP - 24MCWH -FW
White
5134
MTWP- 24MCCH -FR Red
5102
MTWP - 24MCCH -FW White
5122
Speaker Strobe
X
X
X
X
ET70WP- 2475W -FR
Red
9077
Speaker Strobe
X
ET70WP- 2475W -FW
White
3179
ET70WP- 2475C -FR Red
4452
ET70WP- 24185W -FR
Red
4885
ET70WP- 2475C -FW White
4454
ET70WP- 24185W -FW
White
4891
ET70WP- 24177C -FR Red
4845
ET70WP- 24135W -FR
Red
4872
ET70WP- 24177C -FW White
4859
ET70WP- 24135W -FW
White
4875
ET70WP- 24115C -FR Red
4550
-
ET70WP -177
X
ET70WP- 24115C -FW White
4732
UL Max. Current
(Audible)
Candela Ratings
Series
UL 1971
UL 1638
.77
UL 1638
@ -40 °F
RSS, ET70WP and
MTWP UL Max Current
Strobe On y)
ASWP
High
Med
Low
2475W
30-
180
115
0.138
0.168
0.155
0.150
2475C
15
180
115
0.138
0.168
0.155
0.150
0.034
135
135
56
0.300
0.355
0.340
0.335
MCWH
185
185
77
0.420
0.480
0.465
0.460
Hi /Lo
115
115
47
0.300
0.355
0.340
0.335
MCCH
177
177
73
0.420
0.480
0.465
0.460
24185
185
185
77
0.420
"Wall mount rating only
24177
177
177
73
0.420
UL Max. Current
(Audible)
MTWP /MT
24 VDC
MT
12 VDC
BA
HI
STD
HI
STD
Horn
0.108
0.044
0.177
0.034
Bell
0.053
0.024
0.095
0.020
March Time
0.104
0.038
0.142
0.034
Code 3 Horn
0.091
0.035
0.142
0.034
Code 3 Tone
0.075
0.035
0.105
0.021
Slow Whoop
0.098
0.037
0.142
0.035
Siren
0.104
0.036
0.152
0.030
Hi /Lo
1 0.057
0.025
0.114
0.026
Audible
AH
Order Code
AH- 24WP -R
Red
7416
AH- 12WP -R
Red
7415
Horn
Low (90) dBA
0.021
MT- 12/24 -R
Red
5023
Speaker
94
ET70WP
ET- 1010 -R
Red
3135
ET- 1010 -W
White
3137
UL Max. Current
AH
24 VDC
12 VDC
High (99) dBA
0.080
0.192
Med (95) dBA
0.043
0.108
Low (90) dBA
0.021
0.058
UL Reverberant dBA @ 10 Feet
Watts
1/8
114
1/2
1
FM I
4
8
ET -1010
77
80
83
86
L87
92
94
ET70WP
78
81
84
87
93
1 95
Model Number
Agency Approvals
Strobe
UL
MEA
CSFMj
FM I
BFP
RSSWP -2475
X
X
X
X
-
RSSWP- 24MCWH
X
X
-
RSSWP- 24MCCH
X
X
-
-
Audible Strobe
ASWP -2475
X
X
X
X
X
ASWP -MCWH
X
X
-
-
ASWP -MCCH
X
X
-
-
Multitone Strobe
MTWP -2475
X
X.
X
X
-
MTWP -MCWH
X
-
X
-
-
MTWP -MCCH
X
-
X
-
-
Horns /Audibles
AH -24WP
X
X
X
X
X
AH -12WP
X
X
X
X
X
MT -12/24
X
X
X
X
X
Speaker Strobe
ET70WP -2475
X
-
X
X
-
ET70WP -185
X
-
X
X
-
ET70WP -177
X
-
X
X
-
ET70WP -115
X
-
X
X
-
ET70WP -135
X
-
X
X
-
Notific --don
Weatherproof Appliances - Series AH Audibles, AS Audible Strobes, MT Multitone Sti-Q4- es,
RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories
Description:
Designed for life safety, performance and reliability, Cooper
Notification's Wheelock cost effective weatherpoof notification
appliances include:
Weatherproof Appliances
Series
Strobes
RSSWP
Horn Strobes
ASWP
Horns
AH -24WP, AH -12WP
Multitone Horn Strobes
MTWP
Multitone Horns
MT
Speaker Strobes
ET70WP
Speakers
ET -1010
All strobe models are UL dual listed - meeting both UL1638
and UL1971 requirements. As dual listed appliances, these
weatherproof strobes, horn strobes and speaker strobes are listed
for outdoor applications under UL 1638 as well as under UL 1971,
the Standard for Safety Signaling Devices for Hearing Impaired.
With an extended temperature range of —31 °F to 150 °F ( -35 °C
to 66 °C), Wheelock weatherproof appliances meet or exceed UL
outdoortest requirements for rain, humidity and corrosion resistance
while providing multiple strobe intensity options, including the
highest strobe ratings available for area coverage per NFPA 72
strobe spacing tables (up to 185 candela for wall mounting and 177
candela for ceiling mounting).
To enable weatherproof mounting, Cooper Notification provides
the industry's widest choice of mounting options for surface or
unique semi -flush installation. Models are available for surface
mounting to Wheelock weatherproof backboxes on walls or ceilings.
The optional WP -KIT allows the weatherproof backboxes (IOB,
WPBB or WPSBB) to be mounted to a recessed electrical box
for concealed conduit installation. For semi -flush installation, the
WPA* and WFPA* kits allow a customer to mount the weatherproof
appliances to a recessed electrical box without the need for an
external weatherproof backbox. See the Backboxes, Plates and
Gaskets Table on page three of this document for a summarization
of these mounting options and the required accessories.
iVl EA APPROVED
E5946 151 -92 -E 7125- 0785:131 (ASWP)
55391 7125 - 0785:146 (ET70WP)
S2652 7125- 0785:156 (MTWP)
low
A
-3m]
All models may be synchronized using the Wheelock DSM Sync
Modules, Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sync Protocol. The
horn output of horn strobes can be independently controlled on
2 -wire circuits using the Wheelock patented sync protocol. MTWP
horn strobe models are 4 -wire appliances; the strobes can be
synchronized while the audible can be connected to a coded fire
alarm system or can be set to produce any of eight selectable
tones.
Features:
• Approvals include: UL Standards 1971, 1638, 464 and 1480
California State Fire Marshal (CSFM), New York City
(MEA), Factory Mutual (FM), Chicago (BFP) and ULC . See
agency approvals by model number on page two of this
document
• Compliance with the following requirements: NFPA, UFC,
ANSI 117.1, OSHA Part 29, 1910.165, ADA
• Weatherproof with extended temperature range of —40 °F to
150 °F ( -40 °C to 66 °C)*
• Dual Listed strobe models (UL 1638 and UL 1971)
• Industry's highest strobe candela options
• Synchronize using the Wheelock Sync Modules or panels
with built -in Wheelock Patented Sync Protocol
• Models with field selectable tone, dBA and candela settings
• Wall or ceiling mounting options
• Surface of semi -flush mounting
• IN /OUT wiring termination accepting two #12 -18 AWG wires
at each terminal
The series RSSWP, ASWP, AH -24WP, MTWP- 2475#, and MT -12/24 have UL /
ULC approval down to-40'F The ET -1010 and ET70WP have UL approval down