20160134 EQUIP_SCHED_TEMPLATE 02292016General Mechanical Notes All fhermosfafs used for both heating and cooling shall provide a range or deadband of of least 5 °F. WSEC Section C4032.4.2 Su nset In. All fhermosfafs are fobe seven dgprogrammable ,micro - processor based. Pio�ect, ftlucN Restauwl All heating and cooling systems shall have aufomafic start controls for each HVAC system WSEC Section C4032.4.3.3 Al ductwork shall be consfmcfed and sealed per SMACNA standards. All ductwork shall be braced per IMC 2012. Duct support per Section 603.10. All refrigerant used shall be Puron (R41 Oa). All flues shall be located a minimum of 10' from outdoor airinfakes. All exhaust ferminafions shall be a minimum of 10' horizontally from, or 3' above outdoor intakes. All air - economizers shall have modulating outdoor air and relum airdampers capable of providing 100% outdoor air for cooling. WSEC Section C403.3.1.1.1 All air -economizers shall be fully modulating and capable of partial cooling (integrated operation). WSEC Section C403.4.1.3. All addressable functions of duct smoke defectors, and wiring for shutdown, shall be by others. All roof mounted units shall be secured fo their respective roof curbs. Al exposed edges of infernal duct liner shall be sealed with a mastic coating. Al completion requirements must comply with WSEC Section C4082 To comply with WSEC Section C408.1.32 systems documenfafion, record documents and training will be completed and coordinated with owner. To comply with WSEC Section C408.1.2 preliminary commissioning report will be submitted lo owner after being certified by registered design professional or approved agency. All thermostats fo be mounted such that the fop of the device is 48" above finished floor. All gas piping shall be sized per2012 IFGC. All HVAC systems shall be air balanced and adjusted lo deliver final flow rates within 10% of design rates. Outdoor air supply and exhaust ducts shall shut automatically when the system or spaces served are not in use orduring building warm -up, cooldown, and setback, WSEC Section C4032.4.4 Outdoor air supply and exhaust ducts shall be equipped with motorized dampers according fo WSEC Section C4032.4.4 Equipment shall meet the minimum efficiency requirements of WSEC Section C4032.3 System sizing fo comply with WSEC Section C40322 Damper leakage rates shall comply wfih WSEC Section C402.4.52 Duct Insulation Schedule; All ductwork shall be insulated as follows; DUCT TYPE: LOCATION INSULATION R•TYPE TYPE Supply Retum Not within insulated envelope (exterior of building, on roof, in attic -above insulation, in crawl spaces] R -7 2" wrap or liner Supply Refum% Nof within insulated envelope (in ground) R -5.3 1.5" liner or 1" Spuntand OA Intake Nof within insulated envelope R -0 OA Intake (Rectangular) Within insulated envelope, in mechanical room. R -7 2" liner OA Intake (Round) Within insulated envelope R -7 2" wrap Supply on cooling systems Within insulated envelope, not exposed fo space served. R -3.3 I wrap or liner Supply on cooling systems Within insulated envelope, exposed fo space served. R -0 Supply on heating only systems Within insulated envelope R -0 Return Within insulated envelope R -0 Exhaust Other tan Roccupancy R -0 Exhaust Roccupancy (Residential) R -8 2" wrap or liner Per section 4032 of the 2N2 IMC Pashington State Amendments), we are using ASHRAE Standard 62.12010 as or alternate means of compliance with the 2DV IMC Section 403.2 Washington State Amendments. Description Space Occupancy People OSARat OSAISQFT Vent Repred REFGRNT LBS) ISQFTIRooms) IFmmASHRAEStde.l) CFMIPerson IPer1000SQFT) OSA CFM RTU•1 0 RTU -1 CARRIER 48TCDA01AIA5 2400 Beverage Beverage Redaurant &dining Redaurant &dining YES Service 1,465 moms 1.5 0.18 986 Total 1 1,465 1 1 1 1 986 ASHRAE Standard 611 -VI) VIAQ Per section 403.2 of the 2012 IMC (Washington State Amendmentsl, we are using ASHRAE Standard 629 2010 as or alternate means of compliance with the 20t21MC Section 4032 Washington State Amendments. Description Space Occupancy People OSA Rate OSAISQFT VentRegired REFGRNT LBS) ISQFTIRooms) (From ASHRAE Std 62.11 CFMIPerson (Per 1000 SQFTI OSA CFM RTU•2 0 RTU -1 CARRIER 48TCDA01AIA5 2400 0.15 Beverage 12000 Redaurant &dining YES CIRCUIT #1142 11.0 Service 1,465 moms 1.5 0.18 986 Total 1 1,465 1 1 1 1 986 GAS PACKAGED UNITSCHEDULE Sunset Inc, Project, Marib Restaurant MARK MAKE MODEL CFM ESP IN H2O (AFUE) COOLING CAP Total B1UIH Sens, ECONO JYESINO REFGRNT LBS) EER MCA (Amps MOCP Am Voltage olt• Phase Weight lbs. CO2 YIN Comments RTU -1 CARRIER 48TCDA01AIA5 2400 0.15 82.0% 12000 57600 YES CIRCUIT #1142 11.0 33.0 50 2081230-3 815 Y 14" CURB DN SHOT ECONO SEE NOTE 1 RTU -2 CARRIER 48TCDA01AIA5 2,400 015 82.0% 12,000 1 51,600 YES CIRCUIT #1142 11.0 33.0 50 2081230-3 815 Y 14 "CURB, DN SHOT ECONO, SEENOTE 1 1. Per IMC 606.2 Exception, no duct smo0eteclors are required in ihs installation. Pei IMC sedlon606, Air moving systemssupplyingin excess of2NOCFM shallbeequippedwith adudmounfedduddefceforsmokedefedor. Where dud mounted smoke defedorsare required by the IMC, we propose lo furnish non- addressable fype units. If addressable unls are required for infedacewifh ofhw building systems, these units will elher besupplled by dhers, or the unls provided by Sunset will be modified as required by others to allow such infedace FAN SCHEDULE MARK MAKE MODEL 11YLE FLOW Constant I VFD FLA [Amps) WATTS Voltage olt•Phase) WT EF -1 PANASONIC FV- 30NLF1 I NLINE CONSTANT 1 0.9 94.9 115-1 18 GRILLE SCHEDULE MARK MAKE MODEL Comments A SHOEMAKER 100 MA LAY IN SUPPLY B SHOEMAKER MA HARD LID SUPPY C SHOEMAKER 645T LAY IN RNEXH D SHOEMAKER 645 HRRD LID RNEXH