20160152 Interior Lighting Summary 021920162012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Revised Jan 2014
Project Address 1304 Yelm Ave.
Date 2/19/2016
Lighting Alterations, Renovations & Building Additions
For Building Department Use
0 Less than 60% 0 60% or more 0 Stand alone 0 Addition
Food Prep Service
Area
Notes:
8
a. Lighting fixtures in a building addition may comply as a stand alone project, or they may be
288
combined with the overall existing bldg lighting to demonstrate compliance. Refer to C101.4.3.
2' x 2' Troffer 36 Watt LED
b. For retrofits and building additions, provide Space Types and gross interior areas in the
36
Maximum Allowed Lighting table. If a builidng addition will comply as combined with the overall
Lobby
existing builidng, include all applicable existing Space Types and gross interior areas.
8
c. Document new fixtures and all existing to remain fixtures in the Proposed Lighting table.
336
d. If less than 60% of existing fixtures will be replaced, provide total existing lighting wattage
Pendant Light Small 3 Watt LED
(prior to retrofit) in the space provided in the Maximum Allowed Lighting table.
3
Maximum Allowed Lighting Wattage
Location (plan #,
Pendant Light Large 4 Watt LED
Allowed
Gross Interior
Watts Allowed
room #)
Space Type*
Watts per ft2
Area in ft2
(watts /ft2 x area)
Lobby
Dining area: Family dining area
0.89
702
625
Bathroom
Restroom
0.98
53
52
Food Prep Service
Food preparation
0.99
475
4 7 0
Area
Retail Display Lighting from LTG -INT- DISPLAY
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Watt
843
Atrium ** Enter Height:
Existing Lighting Enter Exist. Watts:
Retail Display Allowance from LTG -INT- DISPLAY
* Select Table C405.5.2(2) category from drop down menu.
** For atriums, indicate height. Allowed wattage for first 40 feet is 0.03 W /ft. ht.,
above 40 feet is 0.02 W /ft. ht.
Proposed Lighting Wattage
Area Allowed Watts
Total 1230 1147
Location (plan #,
room #)
Fixture Description * **
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
Food Prep Service
Area
2' x 2' Troffer 36 Watt LED
8
36
288
Bathroom
2' x 2' Troffer 36 Watt LED
1
36
36
Lobby
Mini High Bay 42 Watt Fluorescent
8
42
336
Lobby
Pendant Light Small 3 Watt LED
9
3
27
Lobby
Pendant Light Large 4 Watt LED
4
4
16
Food Prep Service
Area
Downlight 17 Watt LED
3
17
51
Lobby
Downlight 17 Watt LED
1
17
17
Lobby
Track Light 4'w/2 9 Watt LED Heads
4
18
72
Retail Display Lighting from LTG -INT- DISPLAY
Total Proposed Watts may not exceed Total Allowed Watts for Interior Lighting Total Proposed Watt
843
* ** Include existing to remain lighting fixtures and exempt lighting equipment per notes below.
Notes:
1. Include ALL proposed lighting fixtures.
2. For proposed Fixture Description, indicate fixture type, lamp type (e.g. T -8), number of lamps in the fixture, and ballast type (if included). For
track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
3. For proposed Watts /Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and other criteria
as specified in Section C405.5.1. For line voltage track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50,
or as applicable, the wattage of current limiting devices of the transformer. For low voltage track lighting list the transformer rated wattage.
4. For lighting equipment eligible for exemption per C405.5.1, note exception number and leave Watts /Fixture blank.
5. Document existing to remain fixtures in Proposed Lighting table in the same manner as new fixtures. Identify as existing in fixture description
6. If #NA appears in Retail Display cells, information on L TG-INT-DISPLA Y is incomplete.
(Interior Lighting Power Allowance COMPLIES