20140275 LTG-CHK 03242016Lighting, Motor, and Transformer Permit Documents
2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised Jan 2014
Project Address 311 CULLENS RD NW YELM, WA. 98597 Date 3/24/2016
The following information is necessary to check a permit application for compliance with the lighting, motor, and transformerrequirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
Building Department
(yes,no,na)
Code Section
I Component
Compliance information required in permit documents
Documents
Notes
LIGHTING CONTROLS (Section C405.2)
Indicate on plans the manual control type & locations served;
E33
Yes
0405.2.1.1
Manual interior
Indicate of plans the 50% lighting load reduction method
C405.2.1.2
lighting controls
provided or identify exception taken
EXCEPTION 2
Indicate lighting system automatic shutoff capability - identify
E33
lighting zone areas served on plans;
zes
04052.2.1
Automatic time
switch controls and
Indicate locations of override switches on plans and the areas
E33
override switching
served, include area sq. ft.;
Indicate locations where automatic shutoff is provided by other
E33
methods (occupancy sensor, daylight controls, etc)
Yes
C405.2.2.2
Occupancy sensors
Indicate on plans the locations served by occupancy sensors
E33
Daylight zones -
Indicate vertical fenestration primary and secondary daylight
E33
Yes
0405.2.2.3
Vertical fenestration
zone areas on plans, include sq. ft;
and skylights
NA
Indicate skylight daylight zone areas on plans, include sq. ft.
Yes
Daylight zone
Indicate on plans the locations served by daylight zone controls;
E33
0405.2.2.3.2
controls
Indicate in plans the lighting load reduction (dimming) method -
stepped or continuous dimming
E33
Specific application
Indicate on plans the locations served by specific application
NA
C405.2.3
lighting controls -
lighting controls
General
Indicate lighting control method for display and accent lighting,
and display rase lighting;
NA
0405.2.3 -
Display and accent
Indicate these fixtures are controlled independently from both
Items 1&2
lighting
general area lighting and other lighting applications within the
same space
0405.2.3 -
Hotel /motel guest
Provide a lighting control device at each guest room entry for all
NA
Item 3
rooms
permanently installed fixtures in guest room;
Indicated whether lighting control is manual or automatic
C405.2.3 -
Supplemental task
Provide automatic shut -off vacancy controls for supplemental
Item 4
lighting
task lighting, including under -shelf or under-cabinet lighting
Identify eligible non - visual applications and method of lighting
0405.2.3 -
Lighting for non-
control;
NA
Item 5
visual applications
Indicate these fixtures are controlled independently from troth
general area lighting and other lighting applications within the
same space
Indicate lighting control method for lighting equipment for sale
0405.2.3 -
Lighting equipment
or demonstration;
Indicate these fixtures are controlled independently from both
NA
Item 6
for sale or
demonstration
general area lighting and other lighting applications within the
same space
If egress lighting power density is greater than 0.05W /ft2,
0405.2.3 -
Means of egress
indicate method of automatic shut -off during unoccupied
NA
Item?
lighting
i
periods,
- --
Identify on plans the egress fixtures that function as both normal
and emergency means of egress illumination
0405.10
Cooler and freezer
Provide vacancy device or timer to turn off fixtures within 15
NA
0405.11
lighting
minutes of unoccupancy for cooler and freezer lighting fixtures
with lamp efficacy less than 40 lumens per watt
Yes
C405.2.4
Exterior lighting
Indicate on exterior lighting plans the automatic lighting control
controls
method and locations served
E33
Exterior building
Provide motion sensor controls for building grounds fixtures
NA
0405.6.1
grounds lighting
rated at greater than 100 watts with lamp efficacy less than 60
controls
lumens, or identify exception taken
Identify applicable commissioning documentation requirements
per Section C408 or eligibility for exception;
NA
C408.3
Lighting system
Provide written procedures for functional testing of all automatic
functional testing
controls and describe the expected system response,
Identify in construction documents the party responsible for
functional testing of automatic lighting controls
INTERIOR LIGHTING POWER & EFFICACY Sections C405.5, C405.10, C405.11
Lighting, Motor, and Transformer Permit Documents Checklist LTG-CHK"
11 2012 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised Jan 2014
Project Address 311 CULLENS RD NW YELM, WA. 98597 Date 3/24/2016
The following information is necessary to check a permit application for compliance with the lighting, motor, and transformerrequirements in the
Washington State Energy Code, Commercial Provisions.
Applicability
Location in
Building Department
(yes,no,na)
Code Section
Component
Compliance information required in permit documents
Documents
Notes
Provide fixture schedule with fixture types, lamps, ballasts, and
E61
rated watts per fixture;
C405.5.1
Identify spaces eligible for lighting power exemption on plans
C405.5.1.1
Total connected
and in compliance fortes;
NA
Yes
interior lighting power
Identify lighting equipment eligible for exemption in fixture
C405.5.1.3
C405.5.1.4
schedule and in compliance forms;
KA
Indicate that exempt lighting equipment is in addition to general
NA
area lighting and is controlled independently
Provide exit sign types and rated watts per fixture in fixture
NA
C405.4
Exit signs
schedule (maximum 5 watts per fixture)
For lighting in walk -in coolers and freezers, and refrigerated
NA
0405.10
Cooler and freezer
warehouse coolers and freezers, provide rated lamp efficacy (in
C405.11
lighting
lumens per watt) in fixture schedule
Lighting Power Calculation - Indicate compliance path taken
Complete required compliance forms — proposed wattage per
NA
C405.5.2
Building Area Method
building area does not exceed maximum allowed wattage per
building area. Identify locations of building areas on plans
Complete required compliance forms — total proposed wattage
Space -By -Space
does not exceed maximum allowed wattage. Identify locations
Yes
C405.5.2
Method
of space types on plans, including retail display areas as
E33
applicable
EXTERIOR LIGHTING POWER 8r EFFICACY Section C405.6
Provide fixture schedule with fixture types, lamps, ballasts, and
rated watts per fixture;
E61
Yes
0405.62
Total connected
exterior lighting
Identify exterior applications eligible for lighting power
NA
exemption on plans and in compliance forms;
power
Indicate that exempt exterior lighting is controlled independently
NA
from non - exempt exterior lighting
Table
Exterior lighting zone
Indicate building exterior lighting zone as defined by the AHJ
FORMS
0405.62(1)
Exterior building
For building grounds fixtures rated at greater than 100 watts,
NA
0405.6.1
provide rated lamp efficacy (in lumens per watt) in fixture
grounds lighting
schedule
Complete required compliance forth — proposed wattage for
Yes
C405.6.2
Exterior lighting
exterior lighting plus base site allowed does not exceed
FORMS
power calculations
maximum allowed
MOTORS & TRANSFORMERS (Sections C405.8, C405.9)
NA
C405.8
Electric Motors
For motors not part of an HVAC system, provide electric motor
schedule on electrical plans with hp, rpm, and rated efficiency
NA
0405.9
Transformers
Provide distribution transformer schedule on electrical plans
with transformer size and efficiency
If "no" is selected for any question, provide explanation: