Loading...
Tech Spec Step Onsite System f, CITY OF YELM TECHNICAL SPECIFICA nONS STEP ONSITE SYSTEM Prepared for CIty crf Yelm POBox 479 Yelm, WA 98597 Prepared by EXF!F.ES 9-/z'9r./ . I Parametnx, Inc POBox 460 Sumner, Waslungton 98390 PMX # 21-1781-04 October 1992 Revised August 1993 ~ TABLE OF CONTENTS Page I SEPTIC TANKS 1 A GENERAL 1 B SEPTIC TANK SIZING 2 C LOADING CRITERIA 5 D FIBERGLASS TANKS 5 E. CONCRETE TANKS 7 F CONSTRUCTION REQUIREMENTS 9 II. PIPE 10 A. BEDDING 10 B JOINTS 11 C FITTINGS 11 D GRADE AND ALIGNMENT 11 E. TRENCH EXCA V A TION AND BACKFILL 11 F DETECT ABLE MARK1NG TAPE 12 G HYDROSTATIC PRESSURE TEST 12 III. VALVES 16 A. BALL VALVES 16 B GATE VALVES 16 C CHECK VALVES 16 D VALVE BOXES 16 IV SERVICE CONNECTIONS 17 A SADDLES 17 B STANDARD SERVICE BOX 17 C TRAFFIC BEARING SERVICE BOXES 17 V SEWER CLEANOUTS 18 A. GRA VITY SERVICE CLEANOUTS 18 VI. PUMP ASSEMBLIES 18 A. EFFLUENT PUMP - 4" SUBMERSIBLE PUMPS 18 B. PUMP VAULT, RISER, AND LID 20 C INTERNAL SPLICE BOX . . 22 D LEVEL CONTROL AND ALARM FLOATS 23 E. HOSE AND VALVE ASSEMBLY 24 F ADDmONAL MATERIAL REQUIREMENTS 24 City of Yelm STEP Onsile Syslem 21-1781-04 Augusl1993 ',- TABLE OF CONTENTS (continued) VII. ELECTRICAL CONNECTIONS VIII. RESTORATION A DESCRIPTION B CRUSHED SURF ACING IX. SIDE SEWERS x. DRAWINGS 1 TypICal Intenm On-Site Connection 2 TypIcal I" ServIce Connection 3. Typical PIpe Trench 4 Remote Post - ResIdential Pump Control Panel InstallatIOn 5 TypIcal Pump Control Ptrnel InstallatIon on Extenor House 6 Typical Pump Control Panel 7 TypIcal ConnectIOn 8 Retammg Wall Undercrossmg 9 TypIcal STEP Tank InstallatIOn 10 1, OOO-Gallon STEP Tank 11 1,500, 3,000, 4,500 Gallon STEP Tank/Pump Tank 12 TypIcal Sewer AutomatIc Air Release Valve 13 Float Sethng Vault DimensIOns for a Simplex Pump Vault 14 Float Sethng Vault DimensIOns for a Duplex Pump Vault 15 Float Setting Vault DimensIOns for a Tnplex Pump Vault 16 Fiberglass Tank Beddmg 17 Concrete Tank Beddmg 18 TypIcal Riser 19 Traffic Beanng Lid 20 TypIcal End of Lme Cleanout 21. TypIcal Sewer Mamlme Gate Valve City of Yelm STEP Onsite System ii Page 24 25 25 26 26 26 21-1781-04 August 1993 CITY OF YELM TECHNICAL SPECIFICATIONS STEP ONSlTE SYSTEM October 1992 Revised August 1993 The CIty of Yelm Techmcal SpecIficatIOns were developed for use wIth on sIte STEP tank mstallatIOns, onsIte wastewater disposal system InstallatIOns that are to be converted to STEP, and STEP collectIOn lme mstallatIOns. These specificaTIons are m addITIon to ArTIcle IV, Rules and RegulatIOns of the Thurston County Board of Health Govermng Disposal of Sewage, mcludmg all publicatIOns referenced m that arTIcle such as the EP A On-SIte Waste Water Treatment and Disposal Systems DeSIgn Manual (EP A-625/1-80-012) The CIty of Yelm Techmcal SpecIficatIOns are subject to change as new regulatIOns come mto effect. 1. SEPTIC TANKS -to A GENERAL SeptIC tanks mstalled after completIOn of the public wastewater system and to be used for onslte wastewater disposal shall be SIze and type as denoted In these specifications and as shown on the standard drawmgs Grease traps shall be SIZed m accordance WIth the EP A DeSIgn Manual (625/1-80-012) and shall be of a configuratIon conSIstent WIth Industry standards Grease traps will be subject to reqUirements of the STEP/septic tanks 1 SeptIC tanks WIth an mvert elevatIon of less than or equal to 4 feet, whIch are not placed m traffic beanng areas shall meet the followmg cntena. All models of tanks will be cerTIfied by a licensed Structural Engmeer that they will meet the loading condItions specIfied herem. The Structural Engmeer certIfymg each model of tank shall submIt drawings mcluding but not limIted to the followmg: a. Plan VIew shOWIng dImenSIOns of tank and the SIze and locaTIon of any opemngs In the tank. b Side section of tank showmg dImenSIOns and thIckness c End section of tank showmg dImenSIOns and thIckness City of Yelm STEP Onsire System 1 21-1781-04 August 1993 2 Septic tanks WIth mverts greater than 4 feet, and/or are subJected to truck 10admg, shall meet the followmg cntena. All models of tanks will be deSIgned by a licensed Structural Engmeer CalculatIOns shall be submItted for reVIew 3 An mspectIon port will be reqUired over the mlet baffle for all septIc tanks. STEP tanks not supplIed WIth a nser on the mlet sIde wIll be provIded WIth a length of 8-mch PVC pIpe ASTM 3034 WIth watertIght cap The PVC pIpe shall be affixed to the tank WIth a two-part epoxy as manufactured by ten, or equal. B SEPTIC TANK SIZING Septic tanks for the City of Yelm WIll be SIZed as lIsted m the followmg table TABLE 1 - SEPTIC TANK SIZING Descriptions Tank Size .. Up to 4 Bedroom Home 5/6 Bedroom Home/Duplex 1,000 gallons 1,500 gallons Any applIcatIOns for mstItutIOn, multi-family dwellIng or, other structures not listed above shall be SIZed as follows The pnmary tank shall be SIzed accordIng to the follOWIng formulas: Q = eShmated flow from Table 2 V = volume of septIc tank, 1,000 gallon mImmum Flow less than 1,500 gpd formula, V = 1,125 gallons + 75Q Flow greater than 1,500 gpd formula, V = 1 5Q The formulas to denve septIc tank volumes and the estimated sewage flows were taken from the Manual of SeptIc - Tank PractIce U S Department of Health, Evaluation and Welfare and Article N Rules and RegulatIons of the Thurston County Board of Health. All 1,000 gallon tanks will be single compartment. All 1,500 gallon tanks and larger will be two compartment tanks dIVIded by a baffle as shown in Drawmg Detail #11 On 1,500, 3,000, and 4,500 gallon tanks, install three each 4-mch diameter holes umformly spaced across WIdth of tank 29 Inches above floor of tank m each baffle. Install three each 4-mch dIameter holes umformly spaced across WIdth of tank 8 Inches below the top lId of the tank In each baffle. City of Yelm STEP Onsite System 2 21-1781-04 August 1993 Type of Establishment 'rA'BLE:Z ~$STINlAl'ED DAILYSEWEk FLOWS. AIrports (per passenger) Apartments - multiple family (per resident) Bathhouses and swimming pools Camps: Campground WIth central comfort statIons With flush toilets, no showers ConstructIon camps (seIDl-permanent) Day Camps (no meals served) Resort camps (rnght and day) WIth liIDlted plumbmg Luxury camps Cottages and small dwelhngs wIth seasonal occupancy Country clubs (per resIdent member) Country clubs (per non-resIdent member present) Dwellmgs: Boardmg houses addItIonal for non-resident boarders Luxury resIdences and estates MultIple family dwellmgs (apartments) RoolDlDg houses Smgle family dwellmgs Factors (gallons per person, per shIft, exclusive of mdustnal wastes) .,. HOspItals (per bed space) Hotels WIth pnvate baths (2 persons per room) Hotels without pnvate baths InStItutIOns other than hospItals (per bed space) Laundnes, self-servIce (gallons per wash, I.e., per customer Mobile home parks (per space) Motels with bath, toilet, and latchen wastes (per bed space) Motels (per bed space) Picmc Parks (toilet wastes only) (per pIcrncker) Picmc parks WIth bathhouses, showers, and flush toilets Restaurants (toilet and latchen wastes per patron) Restaurants (latchen wastes per meal servICed) Restaurants additIOnal for bars and cocktail lounges Schools: Boarding Day, WIthout gyms, cafeterias, or showers Day, WIth gyms, cafetena, and showers Day, with cafeteria, but without gyms, or showers Service statIons (per vehIcle served) SwiIDIDlDg pools and bathhouses Theaters: Movie (per auditorium seat) Dnve-m (per car space) Travel trailer parks without indiVIdual water and sewer hook-ups (per space) Travel trailer parks with mdividual water and sewer hook-ups (per space) Workers: ConstructIOn (at semi-permanent camps) Day, at schools and offices (per shift) City of Yelm STEP Onsite System 3 Gallons Per Person Per Day (Unless Otherwise noted) 5 65 10 35 25 50 15 50 100 50 100 25 50 10 150 65 40 75 35 250+ 60 50 125 50 250 50 40 5 10 10 8 2 100 15 25 20 10 10 5 5 50 100 50 15 21-1781-04 August 1993 On 6,000-gallon tanks, mstal1 three each 6-inch diameter holes umformly spaced across wIdth of tank 40 Inches above floor of tank m each baffle. Install three each 6-mch dIameter holes uniformly spaced across the wIdth of tank 8 mches below the top hd of the tank m each baffle. All tanks Install a 4-mch diameter hole wIthm 1 Inch of crown of baffle for ventmg On-sIte system deSIgners to consult WIth CIty Engmeer pnor to deSIgn of commercIal STEP mstallatIons and tanks 3,000 gallons and larger to venfy tank sIzmg, pump reqUirements, and electncal reqUirements UndereSTImatIng the wastewater flow antiCIpated to be receIved by eIther the STEP tank or pnmary tanks by the property owner based on eSTImated use will result m the property owner IncreasIng the septIc tank holdIng capacIty to meet the above cntena. Refusal to Increase the SIze of the septIc tank to meet the deSIgn cntena will result m dIscontInuance of sewage collectIon servIces C LOADING CRITERIA <to 1 135 lb/cu ft. weIght of backfill. 2 The water table IS at ground level Lateral loadIng IS 85 1b/cu ft., WhICh Includes hydrostaTIC water pressure. 3 The tank will support a mInimum 1000 Ib wheel load. 4 Tanks deSIgnated as traffic beanng tanks shall be deSIgned to WIthstand HS-20 truck loadIng WIth appropnate Impact factors All tanks shall be structurally sound and watertIght and shall be guaranteed m wntmg by the tank manufacturer for a penod of five (5) years from the date of final acceptance. The tank guarantee/warranty shall be furnIshed at the tIme of submIttal. Tank warranty shall not limIt liability to replacement cost of the tanks. D FIBERGLASS TANKS Unless superseded by the specIficatIons, the fiberglass tanks will meet all reqUirements of IAMPO PS 1-87. If requested by the Engmeer, the manufacturer shall supply to the Engmeer, WIthout charge, approved ongmallaboratory report showmg compliance WIth IAMPO PS 1-87 and reqUirements of the suppliers lIcensed Structural Engmeer. City of Yelm STEP Onsire System 4 21-1781-04 August 1993 City of Yelm STEP Onsire System Method of Calculations Fiberglass tanks shall be analyzed usmg fimte element analysIs for buried structures. CalculatIons shall address the follOWIng a. Strength wIth a safety factor of 2 5 b Bucklmg wIth a safety factor of 2 5 c DeflectIOn of 5 percent of the tank dIameter, based on servIce load (includmg long-term deflectIon lag) d. Buoyancy Performance Testing In lIeu of calculatIOns for fiberglass tanks, the supplier may elect for m SItu performance testmg In SItu testmg of each tank model shall mclude use of staIn gauges and deflectIOn gauges The tank will be subJ~ted to external forces equal to tWIce the actual load MaxImum ImtIal deflectIon based on servIce loadIng shall not exceed 2 percent of the tank diameter Performance testIng WIll be evaluated by a licensed Structural EngIneer regIstered In the State of Washmgton. The Engmeer will have the sole responsibilIty to determIne the maximum external loadmg on any of the tank models 1 InspectIons may be made by the EngIneer In the supplier's yard, wIthm the plant, upon delIvery and agam after Installation The wall thIckness shall average at least 1/4 Inch unless superseded by the requrrements of the Structural EngIneer When less than 3/16 Inch m thIckness or any delamInation IS suspected withm any porTIon of the tank, the Engmeer may drill a 1/4-inch diameter hole through the tank wall for inspectIon purposes. If the reqUired mImmum 3/16-Inch tluckness is not found, repair, If feasible, shall be the responsibility of the Contractor. If repair IS Judged not feasible, the tank shall be rejected If twenty percent or more of the tanks are rejected for any of the aforementIoned reasons, each tank under thIS bId will become suspect of substandard qUalIty and subJect to reJ ectIon by the Engmeer. If the requrred minimum 3/16- Inch thIckness IS found, and no delammation IS present, the repair shall be the responsibilIty of the Engmeer. 5 21-1781-04 August 1993 2 The Structural Engmeer shall SpecIfy the mInImUm weIght of each tank model that will be allowed and submIt those weIghts dunng the submIttal process The manufacturer WIll weIgh each tank and place that weIght on the sIde of each tank m a manner that will not be affected by ram or mclement weather 3 Holes reqUired m the tank shall be provIded by the manufacturer Resm shall be properly applied to all cut or ground edges so that no glass fibers are exposed and all vOIds are filled 4 Dual Tite or Ty-Sea1 neoprene gaskets, or equal, shall be used at the mlet to Jom the tank wall and the ABS mlet pIpmg ABS Schedule 40 pIpe and fitTIngs shall be used at the Inlets. 5 Inlet plumbmg shall penetrate 18-mches mto the liqUid from the Inlet flow lIne. 6 Each tank shall be water tested on the proJect SIte after assembly by the manufacturer and WItnessed by the EngIneer Every tank shall be assembled by the manufacturer and water raised to the bnm of the manhole for a mImmum of two (2) hours The tank shall show no leakage from sectIon seams, pm-holes or other ImperfectIOns Any leakage IS cause for rejectIon 7 When leakage occurs, If the tank IS not rejected by the EngIneer, an addItional water test for a mImmum of two (2) hours shall be made on the tank after repairs have been completed, upon request by the Engmeer The manufacturer shall be responsible for makmg all correctIve measures In production or assembly necessary to ensure a completely watertIght tank. 8 After InstallatIOn of tank WIth nser IS completed each tank shall be fIlled WIth water to the top of the nser for a two (2) hour penod as per paragraph 6, to assure that there IS no leakage. Every tank test shall be WItnessed by the Engmeer 9 Each tank will also include a serial number and date of manufacture 10 InstallaTIon shall be m accordance WIth the manufacturer's recommendations, and as shown on the contract plans, no vanatIons E. CONCRETE TANKS City of Yelm STEP Onsile System 1. Concrete tanks will be allowed In SIzes up to 1,500-gallon capacity 2. Walls, bottom and top of remforced-concrete tanks shall be deSIgned across the shortest dImenSIOn usmg one-way slab analYSIS. Stresses m 6 21-1781-04 August 1993 each face of monolithIcal1y-constructed tanks may be determmed by analyzmg the tank cross-sectIon as a continuous fixed frame. 3 The walls and bottom slab shall be poured monolithIcally; alternatively, water stops may be provIded. 4 Reinforcmg steel shall be ASTM A-615 Grade 60, fy=60,000 psi. Details and placement shall be m accordance WIth ACI-315 and ACI-318 5 Concrete shall be ready mIX WIth cement conformIng to ASTM C-150, Type II. It shall have a cement content of not less than SIX (6) sacks per cubIC yard and maxImum aggregate SIze of 3/4 Inch Water/cement ratIO shall be kept low (0 35 + ), and concrete shall achIeve a mImmum compresSIve strength of 4000 psi m 28 days. The Contractor shall submIt a concrete mIX deSIgn to the Engmeer for reVIew and approval. Three (3) concrete sample cylmders shall be taken and tested for each tank manufactured until the manufacturer and EngIneer are satIsfied that the mImmum compressIOn strength IS bemg obtamed To msure complIance, the manufacturer shall then make and test three (3) sample cylInders for a mImmum of 20 percent of the remamIng tanks at the dIscretIon of the EngIneer If the mImmum compressIve strength IS not beIng obtamed, the manufacturer shall be reqUired to make and test sample cylInders for each tank manufactured. CalCIUm chlonde WIll not be allowed In the mIX deSIgn. The cost of testIng cylmders shall be the tank manufacturer's responsibilIty The tank manufacturer may supply a SWISS hammer for compressIve testmg m the field m lIeu of sample cylInders. 6 Tanks shall be protected by applymg a heavy cement-base waterproof coatIng (Thoroseal or equal), on both InSIde and outSIde surfaces, m complIance WIth Council of Amencan BuildIng OffiCIals (CABO) report #NRB-168, 6181 7 Form release used on tank molds shall be Nox-Crete or equal. DIesel or other petroleum products are not acceptable. 8 Tanks shall not be moved from the manufactunng SIte to the Job SIte until the tank has cured for seven (7) days or has reached two-thIrds of the design strength 9 Tanks shall be manufactured and furnIshed WIth access opemngs of the size and configuration to accommodate mdIvIdual packaged pump systems. ModIfication of completed tanks will not be permItted 10 The septIc tank and the top slab shall be sealed WIth a preformed flexible plastIc gasket. The flexible plaSTIC gasket shall be equal to the flexible butyl reSIn sealant conseal CS-102 or CS-202 as manufactured by City of Yelm STEP Onsire System 7 21-1781-04 August 1993 Concrete Sealants, Inc. of New Carlisle, OhIO, and shall conform to federal specIfication SS-S-0021O(21OA) and AASHTO M-198. 11 Tanks shall be furnIshed wIthout concrete access hole lids. In order to demonstrate water tightness, the tanks shall be tested as follows. 12 Inlets to the septic tank WIll be water tight pIpe seal as Ty Seal pIpe seal or equal. Outlets for effluent filters shall be configured as shown on the contract plans. a. Factory Test: All of the tanks supplIed by the precast manufacturer will be hydrostaTIcally tested m the factory The tank shall be tested by fillmg WIth clean water to the soffit and let stand for a mImmum of 24 hours After the 24-hour penod, the water will be replaced to the soffit. The water level shall be checked after 2 hours. Any water loss will not be acceptable. b Field Tests After the tanks have been set In place, but prior to backfilling, each tank shall be tested for a 2-hour penod. Any tank that fails the test as outlIned In 11A shall be repmred and/or replaced until the tank passes smd test. After backfilling, the tank shall be filled WIth water to ground level and tested for exfiltratIon over a two (2) hour penod No tank will be accepted If there IS any leakage over the two (2) hour penod. F CONSTRUCTION REQUIREMENTS City of Yelm STEP Onsire System It shall be the Contractor's responsibility to venfy the locatIOn and the elevatIon of all eXIstIng sewer lines pnor to mstal1mg the mdIvIdual tank. It IS antICIpated that eXIstIng utility lines WIll be encountered dunng mstallatIOn of the STEP tank and appurtenances Pnor to starTIng construction the Contractor will notIfy the proper utility for underground locations and also contact the property owner to determIne locatIOn of foundation drmns, electncal lInes, etc The Contractor shall be responsible to obtaIn all necessary permIts for work on publIc nght-of-way such as street opemng permIt available at CIty hall. All cost for permIts will be the Contractor's responsibility ExcavaTIons for all tanks shall be suffiCIent to leave a mImmum of 6 mches of clear space between their outer surfaces and the earth bank. See tank beddmg Detail DraWIngs 16 and 17. All septic tanks shall be mstalled on a levelIng course of a mImmum of 6 Inches of beddmg.Fiberglass tanks will receIve addItIonal beddIng to the spnng lIne of the tank as denoted. See tank beddmg Detail Drawings 16 and 17. 8 21-1781-04 August 1993 ll. All excess excavated matenal not used for backfill will be removed from the SIte and disposed of at an approved dump SIte Location of the SIte will be submitted to the Engmeer upon request. Upon request by the property owner the contractor may leave the excess matenal on SIte. All tank InstallatIons whIch mvolve mterruptIOn to sewer servIce shall be Installed as follows: 1. The homeowner shall be notified 48 hours In advance that sewer servIce will be mterrupted for a maxImum of 4 hours ImmedIate notice WIll be gIVen before disconnectmg the eXIstIng sewer lIne 2 All excavatIon and backfill of tanks shall conform to standard specIficatIons CompactIOn for non traffic areas shall be 85 percent of maxImum denSIty CompactIOn for traffic areas shall be 95 percent of maxImum denSIty 3 The contractor shall be responsible on a dally baSIS for prOVIdIng Ingress and egress for both pedestnan and vehIcle traffic on all work SItes. The contractor shall clean up hIS work area on a daily baSIS to aVOId mconvemence to the property owner 4 The contractor shall safeguard hIS work on a dally baSIS to prevent possible mJunes. The contractor shall submIt to the CIty hIS method of safeguardIng hIS work pnor to begInmng any constructIon. PIPE All pIpe less than 2 Inches shall meet the followmg reqUirements Schedule 40 PVC pIpe shall be deSIgned for solvent weld JOInts and shall comply wIth ASTM D 1785 All pIpe 2 mches and above shall meet the follOWIng reqUirements PVC 1120 Pipe PVC 1120 pIpe shall have rubber nng gasket JOInts, shall comply wIth ASTM D 1784 and have a working pressure rating of 200 pSI, SDR 21. A. BEDDING City ofYelm STEP Onsite System 1. Bedding shall be crushed or granular matenal passIng 3/8" square SIeve as per Section 9-03.16 of the WSDOT 1991 Standard SpecIfications. 2. Bedding shall be installed as shown on the construction details. 9 21-1781-04 August 1993 B. JOINTS 1 Solvent Weld JOInts Solvent cements and pnmer for JomIng PVC pIpe and fittings shall comply wIth ASTM D 2564 and be as recommended by the pIpe and fittIng manufacturers 2 Rubber Ring Gasket Joints Rubber nng gaskets shall comply wIth ASTM D 1869 and ASTM D 3139 and shall be supplIed by the pIpe or fittIng manufacturer wIth a sufficIent amount of lubncant. The lubncant shall be water soluble, non-toXIc, non- supportIve ofbactenal growth and have no detenoratmg effect on the PVC or gasket. C FITTINGS All fittmgs shall have a mImmum working pressure equal to the pIpe WIth whIch they are connected. 1 Solvent Weld FitTIngs .,. Solvent weld fittIngs for pIpe less than 2 Inches shall be socket type Schedule 40 fitTIngs and shall comply wIth ASTM D 2466 and 2467 2 Rubber Rmg Gasket Fittings Rubber nng gasket fittIngs for pIpe 2 mches and larger shall be PVC 1120 complYIng wIth ASTM F 477, as manufactured by Head Manufactunng Co , Preston, Idaho; Gault Fabncauon Company, Stockton, California, Spears Fabncauon, Stockton, CalIfornia, or approved equal. D GRADE AND ALIGNMENT ServIce lmes shall be placed at a mImmum of 18 Inches of cover wIthIn pnvate property Deeper excavation may be reqUired due to localIzed breaks In grade such as curbs, retamIng walls, and terraced ground Where shown on the Drawmgs, the pIpeline shall be laid to the profile or elevation shown, regardless of depth Mimmum cover of any mamlme wIthm public nght-of-way or easement shall be 30" E. TRENCH EXCAVATION AND BACKF~L Trench WIdths for pIpes from 1 mch to 4 mches In dIameter shall not exceed 14 Inches WIde at the top of the trench Native material from trenches and excavations may be consIdered unsuItable for trench backfill. The City of Yelm shall determIne the SUitabilIty of nauve City of Ydm STEP Onsite System 10 21-1781-04 August 1993 matenal for trench backfill. If the native matenal IS deemed unsUitable by the CIty, "Bank Run Gravel for Trench Backfill" shall be used Bank run gravel shall be equal to SectIon 9-03 19 of the 1991 WSDOT Standard SpecIficatIons. The Contractor has the option of Jackmg or bonng pressure sewer lines under eXIstIng Improvements The Contractor's proposed method of constructIon and matenal type shall be submItted for the City's approval pnor to commencIng work. PIpelIne matenal shall be approved by the manufacturer for JackIng or bonng applIcatIon No Jackmg operatIon shall exceed 40 feet unless authonzed by the City At locations where paved or graveled streets, shoulders, alleys, parlang lots, dnveways, patIos, and SIdewalks will be reconstructed over the trench, the backfill shall be spread In layers not exceedIng 8 Inches In loose thIckness and be compacted by mechanIcal tampers to 95 percent of maxImum denSIty At locatIOns where lawn, landscapmg, and ummproved surfaces WIll be reconstructed over the trench, the backfill shall be spread In layers not exceeding 8 Inches m loose thIckness and be compacted by mechanIcal tampers to 85 percent of maxImum denSIty MaxImum denSIty and optimum..mOlsture content shall be determIned using the modIfied Proctor maxImum dry denSIty procedure (AASHTO T 180 or ASTM D 1557) In place denSIty shall be determmed USIng the WashIngton DenSImeter method or Nuclear Gauge as outlIned m the WSDOT ConstructIon Manual F DETECTABLE MARKING TAPE Fourteen-gage msulated copper tomng WIre shall be placed dIrectly over all non- metallIc pressure sewer lmes and servIce lInes. The Contractor shall bnng the tomng WIre to the surface of the valve box and servIce boxes for purposes of attachmg a utility detectIon deVIce. All connecnon of the tomng Wife for servIce connections shall be stnpped of msulatIon and attached to the copper porTIon of the mam line tomng WIre. The connection pOInt shall be wrapped WIth heat shnnk tape acceptable for dIrect bury m accordance WIth manufacturer's recommendatIons G HYDROSTATIC PRESSURE TEST All sewer mains, service lines, and appurtenances shall be hydrostatically tested m lengths speCIfied. All pumps, gauges, plugs, saddles, corporation stops, mIscellaneous hose and pIpIng, and measunng eqUipment necessary for performing the test shall be furnIshed and operated by the Contractor Gauges and meters used m the test shall be accompanIed WIth certIficatIons of accuracy from a laboratory approved by the Engmeer The sewer pIpelIne shall be backfilled suffiCIently to prevent movement of the pIpe under pressure. All thrust blocks shall be m place and tIme allowed for the concrete to cure before tesnng. Where permanent blocking IS not required, the City of Yelm STEP Onsite System 11 21-1781-04 August 1993 City of Yelm STEP Onsite System Contractor shall furnIsh and mstal1 temporary blockIng and remove It after testIng The sewer lInes shall be filled WIth water and allowed to stand under pressure a sufficIent length of time to allow the escape of air The test shall be accomplIshed by pumpmg the sewer lIne up to the reqUired pressure, stop the pump for 15 mInutes, and then pump the sewer lIne up to the test pressure again. Dunng the test, the section bemg tested shall be observed to detect any vIsible leakage. There shall not be an apprecIable or abrupt loss In pressure dunng the 15-mmute test penod The quantity of water reqUired to restore the pressure shall be accurately determmed by pumpmg through a posIllve dIsplacement water meter WIth a sweep umt hand regIstenng one gallon per revolution The meter shall be approved by the Engmeer. The maxImum allowable leakage for sewer lInes shall be, accordmg to A WW A C600, Section 4 Hydrostatic TestIng, as follows Test ..PIpe Diameter Pressure 3" 4" 6" 8" 150 pSI 28 37 .55 74 125 pSI 25 34 50 67 100 pSI 23 30 45 60 The above table values give the allowable loss In gallons per 1,000 feet of sewer pIpe lIne per hour The allowable loss can be calculated for any condItIon WIth the formula. L = SDx{P 133,200 where. L= S = D= P= Allowable loss for push-on or mechanIcal Jomts (GPH) * The length of the pIpe tested, In feet. The nommal dIameter of the pIpe, In Inches Average test pressure (psi), dunng the test duration * Add 0078 GPH/inch of nomInal valve SIze for metal seated gate valves pumped against. 12 21-1781-04 August 1993 City of Yelm STEP Onsite System PorTIons of the sewer line that are felt to be cntIca1, or suspect, should be left wIth the JOInts exposed dunng the tesTIng procedure to allow VISUal InspectIon. The use of dye In the tesTIng water will aSSIst the location of leaks If ground water IS present In the trench Any VIsible leakage detected shall be corrected by the Contractor regardless of the allowable leakage specIfied above. Should the tested sectIOn fail to meet the pressure test successfully as specIfied, the Contractor shall, at hIS expense, locate and repaIr the defects and then retest the pIpelIne. Prior to callmg out the EngIneer to witness the pressure test, the Contractor shall have all eqUipment set up completely, ready for operatIon and shall have successfully performed the test to assure hImself that the pIpe IS m a satisfactory condItion DefectIve matenals or workmanshIp, dIscovered as a result of a hydrostatIc field test, shall be replaced by the Contractor at hIS expense Whenever It IS necessary to replace defectIve matenal or correct the workmanshIp, the hydrostatIc test shall be rerun at the Contractor's expense untIl a satisfactory test IS obtained The Contractor shall provide "the water necessary to fIn the pipelines for testing purposes. Water may be purchased from the Water Utility. Contractor to coordInate WIth the CIty of Yelm Water UtIlIty The Contractor will be responsible for transportIng the water to the proJect SIte. The Contractor WIll also be responsible for furnIshmg a backflow preventIOn deVIce or other EngIneer approved method to aVOid contamInation of the water supply dunng loadIng, an appropnate water meter and all other appurtenances reqUired. Water meter and appurtenances shall be approved by the EngIneer The Contractor shall demonstrate to the saTIsfactIOn of the EngIneer that the aIr release valves and vacuum release valves are operaTIng correctly SEWER MAIN LINE TESTING Sewer MaIn Lmes shall be tested under a hydrostatic pressure equal to 150 pSI. After the sewer main test has been completed, each maInlIne valve shall be tested by clOSIng valves m turn and relieVIng the pressure beyond. ThIS test of the valves will be acceptable If there IS no Immediate loss of pressure on the gauge when the pressure comes agaInst the valve beIng checked The Contractor shall venfy that the pressure dIfferential across the valve does not exceed the rated working pressure of the valve. 13 21-1781-04 August 1993 ill. A The ball valve (or self-tappmg saddle If used) at the sewer maIn shall be opened dunng testIng of the sewer mam so that the mam IS tested WIth pressure against the servIce line check valves. Pnor to any mam lme testing, all servIce lines wIthm the main line test area shall be Installed, tested, and approved. The Contractor shall test no more than 5,000 Imear feet for the first test to qualIfy crews and matenals SectIons of collectIOn main lIne to be tested shall not exceed 10,000 lInear feet per each IndIVIdual test. Once successful test results have been achIeved, the Contractor may request m wntmg test sectIons greater than 10,000 lInear feet for the EngIneer's approval. The Contractor IS reqUired to keep hIS pIpe testing and servIce lIne testIng concurrent WIth hIS pIpelme laymg operations. SEWER SERVICE LINE TESTING In order to test the servIce lme, the ball valve (or self-tappmg saddle If used) at the sewer main shall be closed and the test pump shall be attached at the end of servIce hne, a mInImUm of one foot beyond the servIce box as shown on the Drawmgs (or at the end of the stubout at locatIOns where no servIce box IS 1- reqUired) ThIS portIOn of the servIce lIne shall be tested under a hydrostatIc pressure of 70 pSI. The test will be deemed successful If the pressure IS constant for a mImmum of 1 mmute. VALVES BALL VAL YES One-mch ball valves shall be PVC ball valves WIth pre-loaded EPDM stem seals accordmg to U S Patent No. 4,665,937 whIch mcreases the hfe of the stem seal, ABS Impact reSIstant handle, precISIon molded mIcro-fInIshed PVC ball, self- adJustmg polyethylene ball seat seals to compensate for wear, and shall comply WIth ASTM D 2846. It shall be deSIgned for use WIth corrOSIve flUids, for low torque manual operatIon, and for a working pressure of 150 pSI. The PVC matenal shall be Type 1 (NSF) The valve shall be Model No. LT-l000-S as manufactured by KBI (King Brothers Industnes), or equal approved by the CIty B GATE VALVES City of Yelm STEP Onsire System Gate valves for sewer systems shall be NRS gate valves, complymg with A WW A C509, WIth grey Iron body (ASTM C 62, Class B), modIfied wedge dISC (ASTM B 62, Class B), replaceable mternally remforced resilIent rubber disc seat nng (ASTM D 2000, 4AA 730) attached to the face of the disc WIth self-lockmg stamless steel screws (SS 304), machmed seating surface, flat machmed gUide surface on valve body, solId gUide lugs on the valve dISC, bronze stem nut cast 14 21-1781-04 August 1993 mtegral1y WIth the valve disc (ASTM B 62), thermoplastIc anti-fnction washer above the thrust collar, O-nng seals above and below the thrust collar, fully unobstructed flow way free of caVItIes or proJectIOns, no pockets In whIch sedIment or debns can be depoSIted, and shall be fully coated on the InSIde of the valve and the valve dISC WIth a corrOSIOn reSIstant epoxy coating It shall have a workmg pressure of 200 pSI from eIther dIrectIon (NO leakage past the seat from eIther dIrection) and a test pressure of 400 pSI (shell test) It shall be capable of contInuous operation In a septic atmosphere and shall be as manufactured by Mueller Company, or equal approved by the EngIneer Buned valves shall have 2-mch square A WW A Standard operatIng nuts. Valve stem extensIOns, If necessary, shall be proVIded by the same supplIer as the gate valves. C CHECK V ALVES Check valves for sewer systems shall be PVC SWIng check valves deSIgned for use WIth corrOSIve flUids and shall have a Buna-N seal on a SWIng gate whIch lIfts to allow for unobstructed flow The PVC matenal shall be Type 1 (NSF). The .,. valve shall have no metallIc parts. It shall have a workmg pressure of 150 pSI and shall reqUire only 1/2 pSI back pressure for complete closure It shall be as manufactured by KBI (King Brothers Industnes), or equal approved by the EngIneer D VALVE BOXES IV. City of Yelm STEP Onsire System The word Sewer shall be cast Into the lId. The top sectIon shall be made of cast Iron conformIng to the followmg speCIfications ASTM A 4876, WWP 401, and CS-88 It shall be slIp type WIth top flange, weIght 40 pounds or more, be 10 inches In length, have an mside diameter suffiCIent to house the bottom sectIon, and have an average matenal tensile strength of 30,000 pSI. It shall be Rich Model 910 heavy duty, or equal approved by the CIty The bottom sectIon of the valve box shall be 6-Inch PVC pIpe (ASTM 3034), whIte In color. The entIre valve box top and bottom shall perform as a umt that has the ability to extend SERVICE CONNECTIONS ThIS work conSIsts of mstallIng the servIce line and appurtenances. The servIce connectIon at the sewer main includes a check valve and ball valve, WIthOut valve boxes, and a saddle or tee at the sewer maIn The locations of servIce lines and appurtenances are approXimately shown on the DraWIngs. The City will stake theIr location at the time of construction If a self-tappIng saddle IS used at the sewer main, the ball valve at the sewer maIn can 15 21-1781-04 AugUSll993 be deleted. Location of servIce line and servIce box for use for Intenm onsIte dISposal until public sewer IS available IS shown on attached draWIngs A. SADDLES Standard saddles shall be band-type saddles deSIgned for use on PVC pIpe The matenal shall be UNS S 30400 staInless steel for the shell, bolts, washers, nuts, and tapped outlet. Gaskets shall be NBR compounded rubber complYIng WIth AS~ D 2ooo-343K515-E34 Saddles shall be Style 304, manufactured by Romac Industnes, Inc., or equal approved by the CIty. Self tappIng saddles shall have a PVC body and be secured In place by four stainless steel bolts and nuts After tappIng, the tappIng mechanIsm shall retain the coupon from the pIpe and serve as a shut-off valve. The tapping mechanIsm shall be operated by a 5/8" alIen head wrench and have a PVC cover to prevent foulmg of the mechanIsm when not In use. The saddle shall have an O-nng seal glued In place by the manufacturer B STANDARD SERVICE BOX .. The Standard ServIce Box shall be made from a structural plastIC, have extensIons as reqUired, and have a bolt down cover It shall be Model No. 1419, as manufactured by Carson Industnes, Inc , or equal approved by the CIty C TRAFFIC BEARING SERVICE BOXES Traffic Beanng ServIce Boxes shall conform to SectIon llI.B - "Valve Boxes for Ball Valves" v. SEWER CLEANOUTS A. GRAVITY SERVICE CLEANOUTS GraVIty sewer clean outs shall be Installed In each SIde sewer All cleanouts shall be set at the elevatIon establIshed by the EngIneer. Valve boxes shall be set flush WIth ground surface. The ground surfaces and other Improvements around the cleanouts shall be restored m accordance with restoratIon specIfications. See typICal SIde sewer connectIon Detail #7 and SubsectIon IX, SIde Sewers VI. PUMP ASSEMBLIES ThIS work shall Include but not be lImIted to prOVIdIng and InstallIng pump assemblIes, effluent filters, nsers, electncal eqUipment and pump control and alarm assemblIes in accordance WIth the plans and these specIficanons The City of Yelm STEP Onsite System 16 21-1781-04 August 1993 pump assemblIes provided shall restnct the dIscharge to low flow over a wIde range of head condItions to assure that solIds remaIn In the STEP tank and not be transmItted Into the pressure lme. Pumps Installed shall be protected by a screen to prevent solIds greater than 1/8 of an Inch entenng the pressure lIne and prevent pluggIng the Intake to the Impeller or the flow restnctIon deVIce A EFFLUENT PUMP - 4" SUBMERSIBLE PUMPS City of Yelm STEP Onsite System Simplex Pumps: Systems for tanks 1,500 gallons or less. 1 General - For DIscharge to a STEP CollectIOn System ProvIde Orenco Model 20 OSI 05 HHF or approved equal. Pumps shall be lIsted by an approved testIng laboratory, e g , UL or CSA or use as an effluent pump Pumps shall be stainless steel and/or thermoplastIc All wetted fasteners shall be 300-senes stainless steel. .,. 2 Motors Motors shall be permanent splIt phase-type operatIng at 3450 RPM. Motors shall be 1/2 HP, 115 volt, SIngle phase, 60 Hz. Motors shall be thermally-protected WIth an automatIc-reset feature. 3 Operating CondItIons The effluent pump shall be of the submersible turbIne type capable of delIvenng 5 gpm against a TDH of 105 feet, and WIth a shut-off head of not less than 160 feet. Pumps will be provIded WIth an onfice mstal1ed In the dIscharge pIpIng to restnct flow to a maxImum of 9 gpm over any head condItion. The supplIer shall provIde a head curve shOWIng performance of the pump WIth the onfice installed. 4 Bypass A 1/8" bypass orifice shall be drilled In the dIscharge head of the pump to allow for coolIng pump motor dunng penods of no discharge. 5 General - For Intenm DIscharge to DraInfie1d or Pressure-Dram field Pump operatIng condItions shall be selected by the deSIgner of the onsIte system as approved by the Thurston County Health Department. The 17 21-1781-04 August 1993 City of Yelm STEP Onsire Sysrem pump must be capable of provIding 80 feet of total dynamIc head and .beIng throttled In the future to less than 10 gpm by Installanon of a flow control onfice. If It IS ImpraCtIcal or unfeasible to use a pump for both onsIte and STEP applIcation, the pump used for on sIte will be removed and reqUirements for SectIon VLA(l) will apply All costs aSSOCIated WIth InterchangIng pumps or mstallatIon of a flow control onfice will be the responsibility of the property owner Duplex Pump Systems and Triplex Pump Systems for 3,000 Gallon Tanks or Larger. 1 General - For DIscharge to a STEP CollectIon System PrOVIde Orenco Model 20 OSI 05 HHF or approved equal Pumps shall be lIsted by an approved testIng laboratory, e.g., UL or CSA for use as an effluent pump Pumps shall be stainless steel and/or thermoplasTIc All wetted fasteners shall be 300-senes stainless steel .. 2 Motors Motors shall be permanent splIt phase-type operatmg at 3450 RPM. Motors shall be 1/2 HP, 115 volt, smgle phase, 60 Hz. Pumps will be proVIded WIth an onfice Installed on the dIscharge pIpmg to restrict flow to a maxImum of 30 gpm over any head condItIon. The supplIer shall proVIde a head curve showmg performance of the pump WIth the onfice Installed Motors shall be thermally-protected with an automatIc-reset feature 3 Operating CondItIons The effluent pump shall be of the submersible turbIne type capable of delIvenng 20 gpm agalnst a TDH of 105 feet, and WIth a shut-off head of not less than 160 feet. 4 Bypass A 1/8" bypass onfice shall be drilled In the dIscharge head of the pump to allow for coolIng pump motor dunng penods of no dIscharge. 18 21-1781-04 August 1993 5 General - For Intenm DIscharge to Dramfield or Pressure-Dram field Pump operating conditions shall be selected by the desIgner of the onsite system as approved by the Thurston County Health Department. The pump must be capable of provIdmg 80 feet of total dynamIc head and beIng throttled In the future to less than 20 gpm by InstallatIon of a flow control onfice. If it is ImpraCtIcal or unfeasible to use a pump for both on sIte and STEP applicatIon, the pump used for on sIte will be removed and reqUirements for SectIon VI.A(l) will apply. All costs assocIated WIth InterchangIng pumps or mstallatIon of a flow control onfice WIll be the responsibIlity of the property owner B PUMP VAULT, RISER, AND LID City of Yelm STEP Onsite System 1 General PrOVIde a pump vault whIch will be of suffiCIent SIze and structural Integnty to house and support the pumpmg eqUipment necessary for transportatIon of effluent. The pump vault WIll have a screen to prevent solIds larger than 1/8" from entenng the pIpeline and to protect the pump and flow restnctIon deVIce from pluggIng The vault may be mternal or external. The Internal vault WIll be removable for access Into the septIC tank for septage pumpIng. The external vault may be dIrect bury and will not be requITed to be removable. All nsers and connections to the septIc tank WIth nsers shall be water tIght. On-SIte system deSIgner to consult WIth CIty EngIneer pnor to deSIgn of external vault InstallatIOn. 2 Internal Vault SImplex pump assemblIes shall reqUire a 15 Inch dIameter screened vault with a single flow Inducer as manufactured by Orenco Systems, Inc , Model Number SV 1554 Fi. The mternal screened vault IS protected by patent rights. Vaults for duplex 4" submersible pump assemblies shall be a 15" dIameter x 54" deep vault WIth two flow Inducers Model Number SV 1554 FiFi as manufactured by Orenco Systems, Inc., or equal. 3. External Vault In lieu of internal screen vaults for SImplex pump assemblIes, the Contractor can provide an external basin which performs the same 19 21-1781-04 August 1993 City of Yelm STEP Onsire System functIons. The external vault shall be 24-mch diameter and shall be water tIght. The vault shall be constructed of PVC, fiberglass, concrete or polyethylene. All connections such as vent lmes, electncal WIre or condUit, and dIscharge lines shall be attached m such a manner as to proVIde a waterTIght seal, USIng appropnately SIZed Buna-N or Neoprene Grommets and cord gnps External vaults wluch contain a 4-mch submersible pump shall be eqUipped WIth a flow Inducer The vault shall be eqUipped WIth a screen WIth a mesh haVIng 1/8-Inch openmgs The screen shall conSIst of a matenal whIch IS reSIstant to a septIc enVIronment. Only T-316 stainless steel 16 gauge as manufactured by McNichols Co or equal as approved by the EngIneer, or polyethylene WIth a weIght of 140 Ib/1ooo ff or SImilar strength PVC will be allowed The screen will have a mImmum surface area of 12 square feet. External vaults will be vented to the m1et plumbIng to meet L&I reqUirements Extenor vaults shall be equal to model number PB24 (length as reqUired) as manufactured by Orenco Systems, Inc Effluent screens shall be equal to model ES 1560 Fi for a 4-mch submersible pump as manufactured by Orenco Systems, Inc (There are no known equal to these Items) .. 4 Risers Risers shall be reqUired for access to mternal vaults and access Into the septic tanks for septage pumpIng All nsers shall be constructed of PVC, fiberglass, or polyethylene and shall be constructed water tIght. Risers shall be a mImmum of 24 inches In dIameter and shall be of suffiCIent dIameter to allow removal of mternal vaults WIthout removIng splice boxes, etc All nsers shall be a mImmum of 25 Inches In length and shall vary dependIng on the depth of bury on the vanous tanks The nsers shall be attached to the tanks such that a watertight seal IS proVIded Epoxy reqUired to adhere the PVC or fiberglass nsers to fiberglass or concrete tanks shall be a two part epoxy as supplIed by the manufacturer of the nser. When applIcable, Neoprene grommets shall be mstalled by the manufacturer for discharge pIpIng, vent pIpmg and/or the e1ectncal condUit to assure a waterTIght seal. Neoprene grommets will not be allowed on nsers not requInng dIscharge pIpmg, etc Risers shall be Model RR24 (length as reqUired) for SImplex systems and RR30 (length as reqUired) for duplex systems as manufactured by Orenco Systems, Inc., or approved equal. 20 21-1781-04 August 1993 5 Lids a. Standard LId: The standard lid shall be a flat fiberglass lid, green In color, WIth a non skid aggregate fimsh. The lid shall be the diameter reqUired to fit the reqUired nser and shall be supplIed wIth a mmimum of two stainless steel bolts and the lid shall have a gasket. Allen wrench will not be reqUired as a part of the pump packages but 2 wrenches will be Included In the spare parts. Lids shall be as manufactured by Orenco Systems, Inc , Model Number Fl-24G or Fl-30G or approved equal. b Traffic Beanng LId The traffic beanng lId shall be a cast Iron frame and cover whIch will fit over a standard lid The cover shall have the word "SEWER" cast Into It and both frame and cover shall meet reqUirements of SectIon 9-05 15(1) C INTERNAL SPLICE BOX City of Yelm STEP Onsite System Each resIdentIal nser requInng electncal connectIOns shall have a PVC splIce box located In the mtenor of the nser All splice boxes shall be Installed wIthIn 1 '0" of the nser lId for access purposes The splice box shall be complete wIth cord gnps and dual wall heat shnnk wIth butt connectors SplIce boxes shall be UL lIsted for the applIcatIon The number of cord gnps and WIre nuts shall be eqUivalent to the number of floats and electncal leads wIthm the pump vaults. The splIce box and accessones shall meet all requrrements of labor and mdustnes and shall be UL listed for wet locatIOns. For all Class I, DIVIsIOn I mstallatIons, nsers reqUInng electncal connectIOns shall have two separate splIce boxes All splIce boxes shall be UL listed for the applIcation. All splIce boxes shall be mstalled wIthm 1 '0" of the nser lid for access purposes One splice box shall be for the pump wrre and one splIce box shall be for the low voltage WIre for the float system. The splIce boxes for the pump leads shall meet all reqUirements of the Department of Labor and Industnes for a Class I, Division I, Type D gas application. The splice box for the low voltage float leads on an IntrinsIcally safe relay shall be a non-metallIc PVC splIce box. The PVC splIce box shall be complete WIth cord gnps and dual wall heat shnnk butt connectors. The number of cord gnps and WIre nuts withIn the PVC splIce box shall be eqUivalent to the number of floats The pump WIre splice box for sImplex assemblIes shall be SIngle gang, qUick dIsconnect, alumInum receptacle and malleable Iron mountIng box-Model B-Model EFS 175- 2023 and the splIce box for duplex assemblIes shall be two gang, qUick dIsconnect, alumInum receptacle and malleable Iron mounting box-Model B- Model EFS275-2023 as manufactured by Appleton Electnc Company or equal as approved by the EngIneer. Mounting box shall be mounted to nser With stainless 21 21-1781-04 August 1993 steel bolts An explosIon proof EY fitting shall be provIded dIrectly outsIde of the mounting box for the pump WIre connectIon. The pump WIres shall be fitted WIth a waterTIght plug Model B Model ECP-2023 as manufactured by Appleton Electnc Company or equal as approved by the Engmeer D LEVEL CONTROL AND ALARM FLOATS City of Yelm STEP Onsire System Level control floats shall be mercury floats UL or CSA listed for use In effluent on an adJustable or preset PVC stem whIch attaches dIrectly to the pump vault. Floats shall conSIst of hIgh level alarm, on, off, and redundant off Level control floats shall be Model MF-ABR for SImplex pump assemblies and Model MF-2ACRA for duplex pump assemblies and Model MF-3ACRA for tnplex pump applicatIons as manufactured by Orenco System, Inc. or equal as approved by the City 1 Pump control and alarm panels for SImplex pump assemblIes shall be Model S 1 RO ETMCT as manufactured by Orenco Systems, Inc. or equal as approved by the CIty Pump control panels for SImplex commercIal and IntnnsIcally safe applIcatIOns shall be Model S 1 1R (ROF) ETMCT as manufactured by ORENCO or equal. 2 Pump control and alarm panels for duplex pump assemblies shall be Model DAX1 1R (ROF) ETMCT as manufactured by Orenco Systems, Inc. or equal as approved by the CIty Duplex pump assemblies for commercIal and IntnnsIcal1y safe applIcation shall be Model DAX1 1R (ROF) ETMCT as manufactured by Orenco or equal as approved by the CIty 3 Pump control and alarm panels for tnplex pump assemblIes shall be Model TAl 1R RO ETM CT as manufactured by Orenco Systems, Inc , or equal. 4. All pump control panels shall have NEMA 4x fiberglass enclosures, an audio and VISUal alarm, an elapsed tIme meter, event counter, stainless steel latch and mternal 120-volt, 20-amp CIrCUIt breaker 5 All alarm and control panels, panel boards, and alternate power transfer SWItches shall be supplIed WIth a padlock and key set. All padlocks on the proJect will be keyed alike WIth a common key The padlock will be Model Number 8BD MAR (KA) as manufactured by Masterlock or equal. 22 21-1781-04 August 1993 E. HOSE AND VALVE ASSEMBLY 1 Hose and valve assembly for a 4" submersible shall Include I" dIameter 100 pSI PVC hose WIth PVC umon and ball valve and anti-sIphon valve Model Number HVl00BAS as manufactured by Orenco Systems, Inc , or approved equal. F ADDITIONAL MATERIAL REQUIREMENTS All eqUipment IncludIng but not limIted to pump vault, nser, standard lid, bondIng epoxy, splIce box, dIscharge pIpIng, control float assembly, pump(s), pump control and alarm panels, etc shall be supplied by one smgle supplier or manufacturer as a packaged umt. The supplier or manufacturer shall upon request by the CIty, submIt InformatIon on availability of replacement parts, maintenance records of operatIng pump assemblIes. The package as supplied by the manufacturer or supplIer WIll have a standard guarantee against matenal defect for a period of not less than 1 year The date of guarantee shall begIn on the date eqUipment IS delivered on a partIcular SIte and may be a SIngle guarantee IncorporatIng all the components or IndIVIdual guarantees on the vanous components. The manufacturer or supplIer WIll be responsible to handle replacement or repair of defectIve parts Vll. ELECTRICAL CONNECTIONS All electncal eqUipment and materials shall be Installed In conformance to reqUirements of the latest edItion of the National Electncal Code as enforced by the State of Washmgton Labor and Industnes Electrical SectIon. The contractor shall be reqUired to acqUire all necessary permIts and coordmate dIrectly WIth the appropnate authonty on the necessary InSpectIOn SplIce boxes shall be mstalled In the septic tank nser In accordance WIth the InstructIon from the supplIer or manufacturer. The control panel shall be Installed eIther on a remote 8" x 4" post as shown on the contract plans or on the permanent structure. The panel locatIon shall be determmed by the City or the Owner The panel shall be affixed by stainless steel wood screws to eIther the structure or the post. The wood screws shall be of suffiCIent SIze and length to securely fasten the panel. Power and control WIre from the splice box In the riser to the pump control shall be UL approved for direct bury WIth a mimmum of 12 gauge for each control or power wire. The contractor shall submit type and size of cable for reVIew and approval by the City and Labor & Industnes. Cable attached to the extenor of the bui1dmg shall be contained in approved electncal condUit. City of Yelm STEP Onsire System 23 21-1781-04 AugUSll993 Power and control wire for commercIal or IntnnsIcally safe applicatIons shall be contained In two IMC or rigid metal condUits for separatIon of low and high voltage 1mes between the control panel and pump vault and shall meet the reqUirements of Labor and Industnes. All extenor electncal WIre shall be contained WIthIn PVC condUit, unless dIrect btined. Extenor condUit and WIre will only by allowed on the extenor of the house dIrectly above or below the control panel and will be Installed plumb and vertIcal. Underground electncal cable shall have a mImmum of 24 Inches of earth cover. All above ground cable shall be contained In PVC condUit. Electncal. All materials used for control and electncal connectIons shall meet requirements of labor and mdustnes and the U mform Electncal Code. The PumpIng Assemblies shall comply WIth the latest State of Washmgton's Department of Labor and Industnes Electncal InspectIOn SectIon PolIcy VllI. RESTORATION .. A. DESCRIPTION ThIS work shall conSIst of vanous types of surface restoratIOn If reqUired by the owner for pnvate property and as required by the CIty of Yelm for all work on publIc nght-of-way, all surfaces and surface Improvements effected by the Contractors operatIons shall be restored to condItions equal to or better than pre- constructIon condItIons. The City shall be the sole Judge as to the equalIty of matenals and work when companng post-construction condITIons to pre- construction condItIons. Cement concrete SIdewalk and dnveway repair shall conform to the Standard Specifications except that the fimsh, dImenSIOns, and Jomts shall be the same as the ongmal work. Cement concrete dnveways shall be defIned so as to Include cement concrete alleys and parking lots. Curb repaIr shall conform to the Standard SpecIficatIons, except that the fimsh, dimenSIons, and Joint shall be the same as the ongInal work. B. CRUSHED SURFACING Shoulders, dnveways and other graveled or crushed surfaced areas whIch are dIsturbed by the Contractors operations shall be resurfaced with 2 Inches of crushed surfacIng. All work and matenal shall conform to the requIrements of the Standard Speclficaoons. City of Yelm STEP Onsire System 24 21-1781-04 August 1993 IX. SIDE SEWERS Mimmum slope for any 4" or 3" gravIty sIde sewer lines shall be no less than 2 percent or 1/4 Inch of nse to 1 foot of run. Slopes less than 2 percent will only be allowed If approved by the CIty or Owner. InstallatIon of gravIty clean-outs shall meet the reqUirements of the City of Yelm, the umform plumbIng code or, In the case of Intenm onsite Installation, Thurston County Health Department. At a mImmum, a graVIty clean-out will be reqUired two feet from the foundatIon of the structure. Grade stakes will not be prOVIded by the City for SIde sewers. It shall be the contractor's responsibility to determme the dIfferential In elevatIon between the Invert to the STEP tank and the Invert at the building SIde sewer. Based on that mformatIon the contractor shall determIne the percent of fall between the STEP tank and the connectIon poInt at the SIde sewer x. DRA WINGS The supplIer of the pump system shall proVIde detailed draWIngs to the septIC tank manufacturers that mdIcate requJred opemngs, locatIon of mserts, etc , to msure a compatible septic tank-pump assembly package The supplIer shall also prOVIde the tank manufacturer WIth all necessary mserts or fittIngs so they can be cast In the walls pnor to testIng of the tanks City of Yelm STEP Onsire Sysrem 25 21-1781-04 August 1993 jv{ ~(( <JCUl+ STATE OF WASHINCTON o EP,I\RTIV1E'IT OF LA.BOR AND !1'10USTRIES 80S Plum St Sf . PO Box ~.u60 . Olvmpla WA 98S0~~60 DEPA.P..~T OF LABOR AND INDuSTRIES ST,Ec=.RI~;L INSPECTION SE~ION POLICY 85-<J7R2 EZ=e~ive ~ovember 1, 1985 Revised January 30, 1992 RESIDENTLU SEWAGE w""ET w-;;!,T. PUMP I EJEC':'ORS The elec~=ical c~nnec~ion of sewage pumps, effluent pumps or ~inde~ pumps L"l on-site, sinale f2.:!!lilv resident:ial sewacre svstems shall c::molv ~,.;it:..:l all general co~ditions and one of t..'1e foll~wing installation :me~cds: .. Metllod .~; ';y~ere di=ec,"= ven-c.:.lation to at::l.os-cnere is crovided at t:..:le cumD location t~ preve...'11: ac::::nnulation -Of i11e'tilane gas, the location shall be unclassified, and all general conditions :must be met. Meooe. B: Where e.i=ec~ ven1:ilation to at::l.cspnere is not provided at pump location to preven-c aC~..JJllula-cion of methane gas, location is classified as Class 1 Divis.:.on 2 ~'1d installat:.:.on must: be of one of t..'1e follcwing types: the the the 1. Equipment: suitable for Class r Division r or II location, or; 2. Guarant:,eed submergence of pumping unit is prov~ded by means of redundant off ~~it=~, or; 3. Pumping equipment is located in a separate, dry well location. Ganeral Installation Reauir~ents 1. Equipment that in nOr::lal operation may cause an arc or spark shall not be installed in ttle SUJIlO - All elec~ical eauiDment must be listed and labeled by an -approved test:ing autiJ.or:.ty for the application. 2. Float concol switc~es shall be her:netically sealed to prevent entrance of gases or vapors_ , J. Junction boxes, i~ enclosed in septic a~osphere shall be of the nonmet:a.l.lic type, have integral threaded hubs, be mechanically attached to the vessel wall and t.'1e lid gasketed to prevent entrance of gases or vapors. 4. Where- conduit is used bet"'..reen the septic or pumping vessel and t.'le cont=ol panel or power source, rigid nonmetallic, rigid steel or intermediate me~al conduit shall be used. An approved conduit sea.l-off mus~ be placed be~..reen the vessel and the control panel with access.provided for inspection. " ,,_, i POLICY 85-1J7R2 SZC:JND P _~GZ RESID~L~ SEWAGE WET WELL PUM~/Z=E~ORS 5. A ~o~~= disco~_~ec~ ~us~ be provided ahead of the cont=oller to comply with the National Elec~=ical Code Article 430 Pa~ H. If the pump motor is not visible f=om the cont=oller, ~~e disconnecting means ahead of the cont=oller mUs~ be capable of being locked open or ano~~er disconnect must be installed wi~~in sight from and no~. more ~~an 50 fee~ from ~~e pump mo~or. .. 6. fNhere there is any evidence or aDDarent Dossibilitv of ~~e in~=oduction of flammable liquids ~nto ~~e septic system, 'C..>:.e loca~icn shall be classified Class 1. Division 1. and wi=ed appropriately. r;J~Ad~ Rotand LeVasseur Chief Elec~ical Ins~ect=r 2-3.2 .HOUSE PUMP CONTROL PANEL INTERIM DISCHARGE TO DISTRIBUTION SYSTEM IN ACCORDANCE W/7H HEAL 7H DEPARTMENT STEP TANK .. o SERVICE BOX I '.. FUTURE CONNECTION I to $7tP MAINl,JN~ I I =-==-=-..=. ==.== ====-l.=-====-=-====='~S::M:N~N~= ==- = STREET .... f1.E: nll1~ JOIIl 21-1751-04 ORA WING #1 TYPICAL INTERIM ON-SITE CONNECTION CITY OF YELM TECHNICAL SPECIFlCA nON STEP ,. '_" ... ... ... _ nn'.... n..~' ~_ __.....;.~_..-...., ' . .'TI:"_,"-~S~. ''TI:''1I ~--_' '_"~ ._. ",_, '~':,L:;;::',!,_'.: ~~~;,,::~ _._. '___-:~-.--.~ '~,,~':..:.:__. _ :fJii.. -'_~-1c...m _~ ?"~;:-1'~~~~:"_-:'~~?':-7~~~9--~~_':-~~~~t;,,,,'_:;~E~.,~,o:..,"':[;:;.~-:':':'.":"~'.::s.:=~~~l'"":..___ SERVICE BOX - CARSON INDUSTRIES MODEL NO 1419B WITH BOLTED HINGED COVER OR EQUAL WITH COVER MARKING TO READ "SEWER" (USE IN NON- TRAFFIC AREAS) TO BE FIELD LOCA TED BY ENGINEER r 14 GA. INSULA TEO COPPER TONING WIRE CONNECT TONING WIRE FOR SERVICE TO MAINLINE TONING WIRE AND WRAP CONNECTION WITH HEA T SHRINK TAPE :~~::5.>((- CONNECT TO EXISTING PVC SERVICE LINE ::::: ~ CONNECT TO EXISTING 14 GAUGE TONING WIRE WITH BUTT ( CONNECTORS AND . HEAT SHRINK TAPE~ __TO STEP TANK" :--"'1 . (l) "l 12" MIN 1" OR 2" SCHEDULE 40 PVC SWP 2" xl" REDUCER AS REQUIRED 1" P VC SL x SL BALL VAL VE 1" PVC NIPPLE, SL x SL 1" x MAIN OIA. PVC REDUCING TEE SL x SL x TH OR PIPE SADDLE FILE: f78104<l4 JOB: 21-1781-04 ORA WING #2 TYPICAL 1" SERVICE CONNECTION ~~~~~~~. CITY OF YELM TECHNICAL SPECIFICA TlON STEP -SITE-SYSTEM, __ RESTORA nON SURFACE SEE RESTORA TION SEE RESTORA nON TABLE TABLE ABOVE FINISH 8" (TYP ) -. ~ / /1/ /1/ 0::: :z: \1/-\1/- Vl ~ ::J l.U ,,~/I ,,~/I ~z l.U ~l.U BACKFILL SEE :::J- Vl :::Jo ~-J Vll.U ~$ ~ RESTORA nON TABLE -0::: ~a -0::: /1/ /1/ ~o 0:::- ~l.U \1/-\1/-\ MAINTAIN SIDE ~f-- <:l::Vl ~Vl SLOPE AS STEEP 0 >>-- : l.U Lu G-J f-- Cl:J0::: ,,/ II ,,/ II AS POSSIBLE "'J-J :> -:::J 0 '<( Vl -"" -"" SEWER LINE u 0::: Vl 1 <:.:l Lu 0::: ~l PIPE eEDolNG FDR CL FLEXIBLE PIPE (SEE SPECIFlCA nON 9-03.16) I ;:- ____ PfP_ 0.0 t PIPE tJO W W=12" PF?ESSURE 24" GRA VITY RESTORA TION TABLE 1 SURFACE THICKNESS BACKFILL! COMMENTS/ TYPE COMPACT/ON RE:OMNTS. OTHER REQUIREMENTS CRUSHED 4" CRUSHED SURFACE SELECT BACKFILL FINISH GRADE SHALL BE SURFACE TOP COURSE COMPACT TO 95% SMOOTH & CONS/STANT WI71-I EXIST7NG J" MIN GRADE B A. C. FINISH ROADWA Y TO kC. PAVEMENT PA VING OVER 4" CRUSHED SELECT BACKFILL CONFORM TO ALL EXIS77NG OVER GRA VEL BASE SURFACE TOP COURSE COMPACT TO 95% GRADES AND CURBS SLOPES SHALL MA TCH CONCRETE SURFACE MA TCH EXIS77NG SELECT BACKFILL MA TCH EXIS77NG FINISH (DRIVEWA Y /SIOEWALK) CONCRETE 71-IICKNESS COMPACT TO 95% TEXTURE, AND GRADE. HYOROSEED/ PLANTINGS NA T7VE BACKFILL FINISH GRADE SHALL BE LA WN /LANDSCAPE OVER 4" MIN. TYPE A SMOOTH & CONSISTANT TOP SOIL COMPACT TO 85% WITH EX/S77NG GRADE NA 77VE BACKFILL MOUND BACKPlLL UNIMPROVED SUFACE N/A COMPACT TO 85% 2" ABOVE EXIS77NG GRADE & SMOOTH csac = CRUSHED SURF ACE BASE COURSE CSTC = CRUSHED SURFACE TOP COURSE SEE SPECIFICA T70NS FOR CONDITIONS ON COMPACT70N. fiLE: F781040~ JOS: 21-17S1-04 ORA WING #3 TYPICAL PIPE TRENCH FORM CONDUITS TO 4.x8" POST SEE TfPICAL PUMP CONTROL PANEL DETAIL @ o j A TTACH CONDUIT TO POST WITH STAINLESS STEEL roo HOLE STRAPS PUMP CONTROL PANEL PVC CONDUIT 4"x8" PRESSURE TREA TED POST h h (() "'t CONCRETE i 1 J. ..,. .v ".p" . v.' . :::: ,..- C'\l::::E ,.,. . V' '.r;: . to r<J . v.' TO NEW ELECTRICAL PANEL DIRECT BURY CABLE '." TO STEP TANK . .. DIRECT BURY CABLE .~.. , v' .., ~ .. 1 2 11 1 2 It DIA. f1..E: f7 81lJo402 JOB: 2\-1781-04 ORA WING #4 REMOTE POST - RESIDENTIAL PUMP CONTROL PANEL INSTALLA TION CITY OF YELM TECHNICAL SPECIFICA nON STEP -=-'-:"u_:':_~i;';";'.~;:;-.__~. ~._ ____..________... .;.~U___ ___ _ "'_. _.__~_.... _. N.=..srJ'E. ._S"tS_TEM:.~~' -:..-~~.~. e~~~~~:t;;~~:::::~~~~;:~~~~~,~~;~~~~::- .... -~-~~~-~.~~~->~-.-~. ~.~~-~~~~.~ J/~_'__N___~ I I t-J ~~~~ CONTROL IT , ! ! ~ ~ I ~ ~ ~ i ~ ~ , , ~ ~ , , , "'/-:::1;.;;>> , , ~ CONDUIT TO rH~ I STEP TANK INN - '11" _H_ '-1 1_ JL j"-FOOTlNG/STEM TO STEP TANK __l=- ';;;!J-- -. WAU r- >- (f) co eJ <( 0 lJJ L Lo..j~ :r: :<: ~ ~ ~aJ GjO::: ::J:: ~ lJJ Lo..j~ Cl 3/4" PVC CONDUI T CONTRACTOR TO ~HOUSE WALL SHIM, ETC. TO ,- ACCOUNT FOR I I PUMP CONTROL PANEL, DIFFERENT TYPES ' i, SEE DETAIL@3 OF SIDING . .,. (CONTRACTOR TO I FORM BOTH CONDUITS 1 AS SHOWN FOR BOTH i CONDUITS) , 1 i --'--1;,.( i ~ <( .,..~ L--=r.=-ST AINLESS STEEL mo W! HOLE S1RAPS AS ! REQUIRED TO SECURE ~ TO ELECTRICAL d,~~ ~ CONDUIT TO WALL PANEL -,..J_'-1 I l ",L_:~~:~~~,_ G~~~ND r L~\ ~I~ L___,,jk]'" '::::.. - :::J 1. - TO STEP TANK 12" 3/4" LB ELECTRICAL LINE FROM UNDER HOUSE f1.E: c: \CAll\1781~ \,F7111 040Il .all 71-17lJ1-04 ORA WING #5 TYPICAL PUMP CONTROL PANEL /NSTALLA TlON ON EX/STING HOUSE CITY OF YELM TECHNICAL SPECIFlCA TlON STEP _.w____--,,':;:'-__:___ .;:.., ;.!~~~q;~I~~ :;:":~";:~~-=>:~.':'~';:;'~'J.-~~ ;:;.c- y-"i.i: ~. '~';'.;."~'_'~'-!':__"'-:~~' TABLE FOR FEEDER WIRE RUN WIRE SIZE MAXIMUM DISTANCE #12 A WG COPPER 150 FEET #10 A WG COPPER 250 FEET #8 A WG COPPER J50 FEET (SEE SPECIFICA nONS FOR ADDmONAL INFORMA nON). 5n CENTERED ON PANEL DECAL - SEE SPEC/FICA TlONS ~ ..... C\l . l") TO SILENCE ALARM'" PUSH UGHT FOR SERVICE: CALL 458-B.m CJ7Y OF YELM BOLD 18PT LEITER1NG PADLOCK WITH COMMON KEY ALARM UGHT AND SILENCE BUITON FROM POWER SOURCE InC, 8-#12 TO STEP TANK - SIMPLEX 1V4nC. 1J-#12 TO STEP TANK - DUPLEX 1V2"C, 17-#12 TO STEP TANK - TRIPLEX ~ PANEL SIZE MAY VARY DEPENDING ON MANUFACURER FLE: nll1 0401 .JOIl: %1-17111-Q.4 ORA WING #6 TYPICAL PUMP CONTROL PANEL I "t~~~_~~i~~;f1t~~~~~~~~~~!~~~~~~~f!~~~~~~~~~~~~~ CITY OF YELM TECHNICAL SPECIFICA nON STEP VI' ~,~,i{\ ':I'P' Jl))j~ i,fM. "uti' i,,'l"l.' fILl" !II~\ , 'i'\ ,~'"I: >k~~ :lti\lf ,:l~ ';:i;1 i~ !~Jt' !;'ijfif' :il~i~ ,,'/'ill:. i:'f. '; ~ ' : :IIi, i: A,j , ;(1, \1: .pf '; r!.~ " 11\ 'I ~~: I ;, '~ft " .J~, : :~iiC ,! ;)v "I'~ , ifl ,:1., . ~1t.. Ij~ (: 'i i,i' \ ~ :'ih: :',1\ I !.J, ,; ;~ l; lilt' ii'll'lt ;1 ,~ "ij: :: (W " ,I~ 11/1\1 ,!J ;'~: : 'k'~'~ ;,~lg, j1~':~ :"l.h IJ'~',i':t",. , r '~ :)f~~ :)':f " 'j.. :~t "I.~I' ~n~1 ..'~"".' " ?' !,'~ iY"i;f I~~h~ d.}"';' ;;/1: I.,~ \ 4t~~. :!,~(i,;: ;lilll!:" l'lIt '~~,:~' '\~~ l}iJ.l'.:' : igfl,; , '~~l~ :~~~~.: EDGE OF HOUSE FROM HOUSE - TYPICAL IN PROTECTED AREAS / NON-PROTECTED AREAS (LAWNS. ErC) . REQUIRE SER'V1CE BOXES (CARSON OR RICH) ~! / WA TER TIGHT CAP 2'-0" TAIL ABOVE GROUND ~~<<-<<<~~'~~~~%%~ ',Y,<"Y <:., Y~~~\((,~<,'(.(~: ~~ % '<<'(/;:.>;>;:;;>'< <'>>~;;':>%,~ STANDPIPE ~ PVC C.O TEST TEE FERN CO COUPLING OR APPROVED EQUAL · A T COMPLETION OF SIDE SEWER TEST, INSTALL WA TER TIGHT CAP AS PER ORA WING /- EXISTING GROUND / - 14 GA. COPPER TONING WIRE WRAP ONCE AROUND CLEANOUT NEW 4" PVC SEWER LINE (TYP) (3034) 2% SLOPE TO TANK~ - WA TER TIGHT / / CAP * /- PVC TEST TEE / }fRNCO COUPLING OR APPROVED EQUAL "-- TOP OF STEP TANK INLET BAFFLE nrr:n81lH07 JOll: 21-1781-0. ORA WING #7 TYPICAL CONNECTION CITY OF YELM TECHNICAL SPEC/FICA nON STEP ON-SITE SYSTEM 7""'-"'" GROUND LEVEL 1 ~ '~-~r---'~~~~'--~-~---~---~l l,r-RETAINlNG WALL MAY BE :?: i i CONSTRUCTED OF CONCRETE, ~ Ii; RQ.CK. R/R 77ES, Ecr ~ I I ~ 1 GROUND LEVEL r I I~ -180 M1N 45' ELBOW i___~_~~::;;~--=f 1 NOTE: * NO EXTRA PAYMENT WILL BE ALLOWED FOR EXTRA EXCA VA nON fLE: f7810408 .JOB: 2l-17!11-Q4 ORA WING #8 RETAINING WALL UNOERCROSSING err( OF YELM TECHNICAL SPEC/ReA 770N STEP ON-S/TE: SYSTEM '{WA~; ~~I%t)p~~~~~T :i::GG sERVICE '\ 20" MIN RISER HEIGHT fll'ICAL WlTH ALL NoN_TRAFFIC BEARING TANKS ~ BOX wrn..j CORD GRIPS \ ELECTRICAN~CSnPoLNICSE SHALL BE WRAPPED WITH ' ALL CON " HAL.L "- ~ \ HEAT SHRINK rAPE ~ ' \ sLoPE GROUND AWAY F1<OM RISER\ ~ \ 6" FROM TOP OF RIsER ro Ii. ~ OF'ELECTRIC~-~- ~ '\ ~DUIT SE"': " , ELECTRICAL CONDUIT TO poweR SOURCE 14 GAUGE- INSULA TED \ TONING WIRE \ STANOARD \ ~\~ INLET TEE ~ LfA vt: SUfFICIENT / ~\. WIRE TO ALLOW FORI - pUMP REMOVAL~ ~ALARM m----ON 3.~Off 3.~REDUNDANT OFF ~UQUID LEvE!.> -\ ~ j ~\ l"") -.t" F1BERGLASS UD WITH sTEEL BOLTS AND NEOPRENE GASKET 1" DIA.PVC HOSE AND VAL vE ASSEMBLY ORIENT BALL VALVf.. AS SHOwN 24" DIA. RIBBED pVC RISER WlTH NEOPRENE r GROMMETS ; -18" FROIA roP RiSER TO Ii. EFfLUENT DiSCHARGE ~tll TONING v.lRE _ 'llf<AP ONCE AROUND RIsER \; \ \ l~~ . EffLUENT DISCHARGE 2_PART EPOXY IN 1/2" GROOVf.. FORMED IN THE TOP Of THE TANK ~ 1" pvC FLOAT ASSEMBLY 1_1/4" DIA. INLET HOLES AROUND PERIMETER Of VAULT / 4" DIA. pvC FLOW INDUCER ~ pVC VAULT pOL YETHYLfNE SCREEN ~ SUBMERSIBLE ~FLUENT ORENCO TURBINE 8 GPM 20 OSl 05 HHf puMP WITH S 0 poweR CABLE AND 1/S" By_PASS ORifiCE IN THE DISCHARGE HEAD DRAIN pORT WITH / NEOPRENE FLAP CHECK ~ EX AND CLASS 1 DIVISION 1 THE MA rEl'IAL FOR DUPLEX. ;::,:LCo;,TRACToR sHALl MEET THE INSTALLA noNS WILL VARY noN REOUIREMENTS SHOWl'l IN THE INTENT OF THE INST ALLA TYPICAL sTEP INST ALLA nON. QRA WING jfJ TYPICAL SIMPL~ANK INSTAllATION ~ '/&\Qi;09 JOll' 2\- fl1S1-04 -,.:.,.,..::-......, CITY of '(ELM TEeHNICAL SPECIFlCA nON sTEP ON-SITE SYSTEM ;_.::';....,,-..--~~ - , __ __---------.----r ~ --'-__-------,..----" rr=-- \ _------- _, '-_AINISHED GRADE z WATER riCH T CAP ------.-=1--< S; \...-6" 6"ifJ CO INSPECTION pORT, CENTER OVER INLET TEE -'- __I ~S\ - ~ \C) C'-l ~ \ \ \ \ \ \ 200 GAL \ \ \ \ \ C' C' C' \ 800 GAL n '<t \ \ \ \ \ \ \ \ L-__..J o \C) 14 GAUGE TONING WiRE TO GRAViTY SIDE SEWER CONNECTION 6" MIN BEDDING ~ T LEvELS SEE DRAWINGS 1 FOR THE APPRO#P15R!A(ST~li~~: DUPLEX' AND TRIPLEX) #~3, #14 AND IV" AS THEY APPLY ~ 1000 GALLON ST(P TANK f\\.E. n810...'1 ,109: 1.1_,781-04 CITY OF YfLM TECHNICAL SPECIFICA nON sTEP ON-SiTE SYSTEM (14 GAUGE TONING WIRE TO SERVICE BOX -,\ \...- ... MA Y BE RAiSED TO SURfACE: WITH CONCURRANCE OF ?- FINISHED GRADE: rr=====\'--- PROpcRTY owNER I' .-- .-"---'-- t:. ~.J..-""""''''''''-'''-'- ._.._...-.-.--..-.-......... 6" 'i 21." pVC RISER .---=-1,- Z WITH WA noR nGHT;=- \ \ ':i L10- c, N' 14 GAUGE: TONING \ > WIRE: TO S5 CO~---~ i'-\ V-1 -r- \ \ \ \ -,-,-,\ \ '- ...... '- a ..... o N \ c \ \ BAFFLE. sEE \ SPEClflCA TIONS (NOTE 1) \ L_-.J ~\ v-2 o 1<') \ 0' 6" MIN BEDOING VARIES pUMP VAVL T RISER 2 P ART EPOXY IN 1/2" GROOVE FORMED IN THE TOP OF THE TANK pUMP ASSEMBLY, SEE SPECIFlC/iTIONS .---- 1500 3000 4500 60" '\ 72" 72" 0-1 (4 43" \ 55" 55" 0-2 4 62" 0-3 4) 50" 62" V-1 400 GAL 600 GAL \ ,/-2 1100 GAL 2400 GAL tiQJ~ 1 . DELETE BAFFLE FoR A 3000 GALL ON TANK UTILIZED AS A TRIPLEX pUMP VAULT 2. ,,'STALL poWER TRANSFER SWITCH , E"GINEER WILL REV1EW TOLERANCES IN EXCESS OF ~ DIMENSIONS SHOWN 4 j1-IE TRIPLEto~~:frE V ~~gR~[~~~EJ A Ji1 c"t~i :,~S ~~gAii:OANO ONE PUMP THE SECOND VAULT CONiAINS iV/O PUMPS. ~ 1500, 3000, 4500 GALLON STEP TANK / pUMP TANK fiE< 'na,(l~'O JOll> 2\" \ 76\ _04 CITY OF YELM TECHNICAL SPECIFICA noN slfP ON-SITE sYSTEM -1------- 1" AIR RELEASE VALVE OR 2" COMBINA nON AIR RELEASE VALVE &: VACUUM VALVE FINISH GRADE SHALL BE WITHIN 1 "::I:1/4n OF" TOP OF" LIP BACKSLOPE SHALL BE J(HOR.) TO 1(VER.) OR FLA ITER. 21"rtJ RIBBED PVC RISER W / BOL T ON PIBERGLASS LID BY ORENCO OR EQUAL CARBON PIL TER ~ ""- EXISTING GROUND ~ 2n RIGID INSULA nON . a r<) 1" PVC UNION SLOPE U 1" SCHEDULE 40 PV- 1" PVC ELL. SLx7H 1" SCHEDULE 80 PVC (SCH 80) IPT NIPPLE SELF TAPPING PVC SADDLE ROMAC MODEL J04 OR EQUAL PRESSURE SEWER MAIN POL 'fPROPYLENE STRAINER MINIMUM OF" 8" OF" PEA GRA VEL BACKF"ILL F"OR DRAIN ~ PLACE IN A NON- TRAFFIC AREA, UNO JOINTS SHALL BE SOL VENT WELDED. ENGINEER SHALL P/ELD LOCA TE PINAL LOCA TlON. FLE: F711104:22 olQll; Zl-l7a1-G4 ORA WING # 72 TYPICAL SEWER AU TOMA TIC AIR RELEASE VAL VE CITY OF" YELM TECHNiCAL SPECIPICA nON STEP ON-SITE SYSTEM .-.......................-]........ .............1 FINISHED GRADE I t......................-. :2: ~ 24"rzj RISER Ll} ~ ALARM HIGH LEVEL T 1 2" . ON 1-1/." OF!:' .) 1'2 I 1" REDUNDANT OFF 3V2 I J r--. ~ Ll} 00 C) \0 I') C"\I ~ 75" ~ 6" MIN BEDDING J fiLE: f7810+C1. J08: 21-1781-04 DRAWING #13 F10A T SETTING VAUL T DIMENSIONS FOR A SIMPLEX PUMP VAUL T CITY OF YE:LM TECHNICAL SPECIFICA nON STEP ON-SITE SYSTEM F'/NISHfD GRADE J......i It................ . <: ~ 30"0 RISER ~] i'. ,-. ALARM HIGH LEVEL T 4" ON 2- -" '! ON 1 i ~" OFF' 4" LOW LEVEL ALARM 2" REDUNDANT OF'F' "'" L{) :'1-1 C'\j 00 o co "l "l ~ 15" J , 6" MfN BfDDING~ fiLE: F7B10~15 JOB, 11-17Bl-04 ORA WING #14 FLOA T SETTING VAUL T DIMENSIONS FOR A DUPLEX PUMP VAULT CI TY OF' YELM TECHNICAL SPECIFICA nON STEP ON-SITE SYSTEM FINISHfD GRADE}.......I II..... .30"iZ! RISER ~ a ALARM HIGH LEVEL I " C'\J ON.3 4 ON 2-1- J" \1 ON 1-~ f--- - 6" OFF I 4" a LOW LEVEL ALARM -L 2" (Q RfDUNDANT OFF .... -000 "l C"\J l 15" J <: ~ l!) C'\J ----r oi-1 C"\J C"\J ~ 6" MIN BfDDING~ NOTE. THE TRIPLEX PUMP VAULT REOUIRES TWO VAULTS AND TWO COMPLETE RISERS. ONE VAULT CONTAINS FLOA TS AND ONE PUMP THE SECOND VAUL T CONTAINS TWO PUMPS. FILE: F7810+1:3 J08: 21-1781-04 ORA WING #15 FLOA T SETTING VAUL T DIMENSIONS FOR A TRIPLEX PUMP VAUL T CITY OF YELM TECHNICAL SPECIFICA nON STEP ON-SITE SYSTEM SEE RESTORA TlON ~ DETAILS NA TIllE OR SELECT~' BACKFILL AS DIRECTED BY ENGINEER ", ,- ' CJ '- ....,.- , ~ .~; , + .~.~~>:~>>;~~.~">:-;~~' '/>0;~~'/.~/:Y).,;:0 J ~/..<< - '/\."~ /" ,;: .,. "" _,..l'r' TOP OF TANK PRIOR TO i INSTALLA nON OF RISER I I I It.:<.:> SPRINGLlNE OF TANK ~ Ii 3; ;...Q -Q ~,~ -J I i <c! I I \_: \~~ ..- , ;,.., - - ? ~ :..... \ \ '- CRUSHED OR GRANULAR MA TERIAL PASSING .}8n SQUARE SIEVE (SECTION 9-0.3_16 WSDOT 1991 STANDARD SPEC/FICA TlONS) R~ fllll04n JOB: 21-1781-04 ORA WING #16 FIBERGLASS TANK BEDDING CI TY OF YELM TECHNICAL SPECIFICA nON STEP ON-SITE SYSTEM SEE RESTORA nON ~ DETAILS ~ " NA nVE OR SELECT BACKFILL AS DIRECTED BY ENGINEER " _ ..:"';~_, 1/ ~\~-Y>~0:~~>~;' ~~'!-0'\S~>~'!-;,~,,/, ~ 1'<:;' Y ..>:::. /", ,( / J ;/;; , '" f5,. ">>> ">';,~'>~j:::;j,.\ '<<<(~~~~ <:: 6R MIN. ~..f- -,I' ;': ,,- \ !:"'~~ {... -!. u..0 0< ~a a ~l.U :J(!) ~. ~,/' ,.' .~- ". ... " , " .1-:- ~ ~j .~ ;.. : HQIE:.. INST ALL TANKS AS PER DETAIL OR MANUFACTURER'S RECOMMENDA nON 'MiICHEVER IS MORE STRINGENT \ \ '- CRUSHED OR GRANULAR MA TERIAL PASSING ~R SQUARE SIEVE (SECnON 9-03.16 WSDOT 1991 STANDARD SPECIFlCA nONS) FlLk: Hlll0411l JOB: 21-1781-04 ORA WING #17 CONCRETE TANK BEDDING CITY OF YELM TECHNICAL SPEClFfCA nON STEP ON~SlTE SYSTEM ~ CONTRACTOR TO EPOXY TWO 1" / PVC PIPE PIECES 1" LONG TO /' / FIBERGLASS LID FOR LIFTING UD , ''"'~~W'~P'' ".,->>.W .:;, " . 1 '. ...:, <ot ' - . ....-,. 6" MANHOLE RING AND COVER. '" CONCRETE COLLAR 1" 14 GA. COPPER TONING WIRE 2'-0" TAIL ABOVE GROUND . 21- RISER REQUIRES 24" RING &: COVER 24" RISER REQUIRES 30" RING &: COVER 30" RISER REQUIRES 36- RING &: COVER RISER WITH FiBERGLASS LID ORENCO SYSTEMS, INC., OR EQUAL. . ~ f71l1041a olQIl: 'Zl-17111-04 .. .... -...---".. ~ . ORA WING #19 TRAFFIC BEARING LID CITY OF YELM TECHNICAL SPECIFlCA nON STEP ON-SITE SYSTEM ~ TYP RICH NO. 910 VALVE BOX, OR EQUAL WITH COVER MARKING TO READ HSEWfRH (TYP ) 8" 2'-0" ;..~..~~::. ~~?~?:...~.~:~.: :~.'~.~:'.'~.'~v ~6V ~.'V ~.v ~.'V ~.'V ~.v ~ ~ _ ~ ~ _ ~ ~ _ ~ _.~ _.p' _.~ _ p ~ ~ #4 @ 7H D.C. EACH WAY TOP 6H PVC PIPE ASTM D - .30.34 (WHITE) THRUST BLOCK SEE @ 2H~-90' BEND 2H(Il GA TE VALVE SEE@ TONING WIRE CONNECT TO MAINUNE USE EXPANSION FITTINGS AS REQUIRED 2"(6 SCH 80 PVC PIPE FROM VALVE W/SOLVENT WELD JOIN TS tiQIE;... THE 2H VAL VE MA Y BE BELL x BELL A T mE CONTRACTORS OPTION . '" FLE: n81O+tll JOlI: 21-1781-04 DRAWING #20 TYPICAL END OF LINE CLEANOUT CI TY OF YELM TECHNICAL SPECIFICA nON STEP ON-SITE SYSTEM r. . VAL VE BOX, RICl-f NO 910 OR EQUAL WI COVER MARKING TO READ "SEWER" ~t CONCRETE SLAB 2' x 2' CENTERED ON VALVE wi 4-#4'S EACH WA Y TOP 6" PVC PIPE ASTM 0-3034 (WHITE) TONING WIRE, BRING TO SURF"ACE IN VALVE BOX PVC SEWER MAIN \ 00 NOT COVER BOLTS wi CONG.C?ETE GATE VALVE, MJ x MJ 2 - #4 BARS n EMBEDDED -.J L 4" MIN e" MIH.--1 I-- ~t T CONCRETE SUPPORT BLOCK POR VAL VES 4" AND LARGER NOTE: 2" & J" VAL VE5 MA Y BE BELL x BELL AT Tl-fE CONTRACTORS OPTION FILE: F7 810+21 JOB: 21-1781-04 ORA WfNG #21 TYPfCAL SEWER MAIN LINE GA TE VAL VE CITY OF" YELM TECHNICAL SPECIFICA TlON STEP ON-SITE: SYSTEM ~