20160134 Permit Pkg Mechanical 02292016City of Yelm
Community Development Department
Building Division
Phone: (360) 458 -8407
Fax: (360) 458 -3144
Applicant:
Name: RICK CHRISTENSEN
Address: 11915 CLEAR LAKE RD
EATONVILLE WA 98328
Property Information:
Site Address: 16605 106TH AVE SE
Assessor Parcel No.. 64303400502
Contractor Information:
Name: RICK CHRISTENSEN
Address:
11915 CLEAR LAKE RD
EATONVILLE WA 98328
Contractor License No.:
Project Information:
Project: COMMERCIAL REMODEL
Description of Work: 3740 RESTAURANT TI
Sq. Ft. per floor: First 3740
Second
Third
Garage
Basement
Fees:
Item
BUILDING
MECHANICAL
PLUMBING
Permit No.: 20160134
Issue Date: 2/19/2016
(Work must be completed within 180 days)
Phone.
Owner: RICK CHRISTENSEN
Subdivision: Lot:
Phone:
t
Expires: 0 /00 /0000
Heat Type (Electric, Gas, Other): HEAT PUMP
Contractor
RICK CHRISTENSEN
SUNSET AIR INC - 2/29/2016
AFFORDABLE PLUMBING
TOTAL FEES:
Applicant's Affidavit:
I certify that I have read and examined the information contained within the application and know the same
to be true and correct. I also certify that the proposed structure is in conformity with all applicable City of
Yelm regulations including those governing zoning and land subdivision, and in addition, all covenants,
easements and resa?, ctions of record. If applying as a contractor, I further certify that I m currently
registered in t e e Washington
Signature ) Date
Firm
Fees
$49,100.40
$ 56.00
$ 132.00
$ 49,288.40
OFFICIAL USE ONLY
# Sets of Prints:
Final Inspection:
Date:
By:
City of selm44
(360i . PM
REC#: 00223883
2/20/2016 1.33
GPER: CO TERM: 001
REF #:
PAID BY
ACCT #: XXXXXXXXXXXXXXXXXXX
AUTH #: 029877
TRAN #: 000000000137
Pi
TRAN: 33.0000 BUILD156 ooCR TS
20160134
CHRISTENSEN, RICK
16605 106TH AVE SE
MECH
CARD
TENDERED: 56.00 CREDIT
56
APPLIED:
:00 -
--''
CHANGE:
p 00
l�
CITY OF YELM
/
COMMERCIAL BUILDING PERMIT APPLICATION FORM
Project Address: 164 6
Zoning; Current Use: Proposed Use:
❑ New Construction Re -Model / Re -Roof / Tenant Improvement
❑ Plumbing Mechanical -! FireLLPrevent/Suppress /Alarm // Other
Project Description/Scope of Work: Z AM / %010 K,.,fb �°'✓�
Project Value:
Building Area (sq. ft) Parking Garage 1" Floor 2nd Floor 3rd Floor
Building Height
Are there any environmentally sensitive areas located on the parcel? If yes, a
completed environmental checklist must accompany permit application.
BUILDING OWNER /TEN,P T NAME: 1 vc ► ►,
ADDRESS L if_ EMAIL a P.C. aiy&V;,�,y e �►�ri��2 �.C.•�
CITY / /./ STATE &IA -ZIP C1f2?_Z TELEPHONE 23-3--
ARCHITECT /ENGINEER LICENSE #
ADDRESS EMAIL
CITY STATE ZIP TELEPHONE
GENERAL CONTRACTOR L TELEPHONE 740 S6 y«j 41
ADDRES 2!O !vD EMAIL KLS L S*��rt� •cevh
CITY STAT ZIP D FAX
CONTRA
S LICENSE #Z uXP DATE 'fGITY LICENSE #
PLUMBING CONTRACTOR TELEPHONE
ADDRESS EMAIL
CITY STATE ZIP FAX
CONTRACTOR'S LICENSE # EXP DATE CITY LICENSE #
MECHANICAL CONTRACTOR G
ADDRESS EMAIL
CITY STATE ZIP FAX
CONTRACTOR'S LICENSE # EXP DATE CITY LICENSE #
Copy of City Mitigation documentation JFC).
I hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the
above described property will be in accordance with the laws, rules and regulations of the State of Washington and the
City of Yelm.
Ap is u� Date
O r / ractor / wner's Age / Contractor's Agent / Tenant (Please circle one.)
All permits are non - transferable and will expire if work authorized by such permit is not begun
within 180 days of issuance, or if work is suspended or abandoned for a period of 180 da
(360) i 35 - -- -:: •
(360) 10-31 14 FAX
www.ci.yelm.wa.us
105 Yelm Ave W
Yelm, WA 98597
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Mechanical Summary MECH-SUM
2012 W ashinaton State Enerov Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Info
Project Address 11915 CLEAR LAKE RD S
Date 2/18/2016
EATONVILLE, WA 98328
For Building Dept. Use
Applicant Name: SUNSET AIR, INC
Applicant Address: 5210 LACEY BLVD SE, LACEY, WA
Applicant Phone: 360 -456 -4956
Project Description
Briefly describe mechanical
system type and features.
21 Includes Plans
INSTALL 2 RTU AND NEW RESTROOM EXHAUST
Drawings must contain notes requiring compliance with commissioning provisions per Section C408
Compliance Option
Simple System 0 Complex System 0 Systems Analysis
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on
the plans. For projects without plans, fill in the required information below.
Coolin g Equipment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Capacit/
Btu /h
OSA CFM
or Econo?
SEER
or EER
IPLV3
Econmizer
Option or
Exception 6
Heat
Recovery
Y/N
SEE SCHEDULE
Heatin g Equipment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Capacit/
Btu /h
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency°
Heat
Recovery
Y/N
SEE SCHEDULE
Fan E ui ment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
CFM
SP'
HP /BHP
Flow Controls
Location of Service
SEE SCHEDULE
Service Water Heating Equipment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Input
Capacity
Sub -
Category
EF7
Location of Service
N/A
' If available. 2 As tested according to Table C403.2.3(1)A thru C403.2.3(8). 3 If required. 4 COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. 5 Flow control types: variable air volume (VAV), constant volume (CV), or variable speed (VS). 6 Economizer exception number per
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Project Address 11915 CLEAR LAKE RD S Date 2/18/2016
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH -CHK pages.
Applicability
Code Section
Code Provision
Information Required
Location
Building Department
(yes,no,na)
on Plans
Notes
GENERAL PROVISIONS
Equipment Sizing & Performance
Load calculations performed per ASHRAE Std 183 or equivalent per
na
C403.2.1
Load calculations
Chapter 3
na
Equipment and system
Output capacity of heating and cooling equipment and systems do not
n
C403.2.2
sizing
exceed calculated loads note exceptions taken
na
C403.2.5
Minimum ventilation
Ventilation (natural or mechanical) provided per IMC; indicate mechanical
Sched
Y
ventilation is capable of being reduced to minimum requirement per IMC
C403.2.3 &
Provide equipment schedules or complete MECH -SUM tables with type,
C403.2.3.2
Equipment minimum
efficiency
capacity, efficiency, test standard (or other efficiency source) for all
Sched
Y
&
mechanical equipment
C403.2.13
Electric motor efficiency
Provide equipment schedule with hp, rpm, efficiency for all motors; note
Sched
Y
except.
C403.2.10
Fan power limitation
Fan system motor hp or bhp does not exceed limits per Table
na
C403.2.10.1 1
na
C403.2.10.3
fan
Indicate fan motors 1/12 to 1 hp are ECM type or meet minimum efficiency
na
& C403.2.13
Fractional hp motors
re q.
na
C403.2.3
Maximum air cooled chiller
Indicate air - cooled chiller capacity does not exceed air - cooled chiller limit
na
na
capacity
Non - standard water - cooled
Full -load and NPLV values for water - cooled centrifugal chiller adjusted for
na
C403.2.1
chillers
non - standard operational conditions
na
Centrifugal fan cooling
Large capacity cooling towers with centrifugal fan(s) meet efficiency
na
403.2.12.1.
towers
requirements for axial fan open circuit cooling towers
na
C403.2.3
d air furnace and unit
Indicate intermittent ignition or IID, flue /draft damper & jacket loss
Sched
Y
heaters
C403.2.3.3
Packaged electric
List equipment required to be heat pumps on schedule
na
na
heatin /coolin q equipment
Indicate method of humidification (note requirements for systems with
na
C403.2.3.4
Humidification
na
economizer
HVAC System Controls & Criteria
C403.2.4.1
Thermostatic controls
Indicate locations of thermostatic control zones on plans, including
FPI n
Y
perimeter systems
Heat pump supplementary
Indicate staged heating (compression /supplemental) & outdoor lock -out
na
C403.2.4.1.1
heat
temp
na
C403.2.4.2
Setpoint overlap
Indicate 5 °F deadband minimum for systems controlling both heating &
Sched
Y
deadband
cooling
C403.2.4.3
Automatic setback and
Indicate zone t -stat controls with required automatic setback & manual
Sched
Y
shutdown
override
C403.2.4.3.3
Automatic (optimum) start
Indicate system controls that adjust equip start time to match load
Sched
C402.4.5.2
Dampers
Indicate location of OSA, exhaust, relief and return air dampers; include
FPI n
Y
&
AMCA rated leakage and control type motorized or gravity; note
na
C403.2.11
Heating outside a building
Indicate radiant heat system and occupancy controls
na
na
C403.2.4.5
Snow melt systems
Indicate shut -off controls based on outdoor conditions
na
C403.2.4.6
heating
Indicate modulating or staged control
Sched
Y
�Cormbmenin
C403.2.4.7
Group R1 hotel /motel
Indicate method for guest room automatic setback & set -up of 5 °F
na
s stems
minimum
na
403.2.4.8 / E
Group R2 /R3 dwelling unit
Indicate 5 -2 programmable thermostats in primary spaces with minimum
na
systems
of two setback periods; note exceptions taken
na
C403.2.5.1
Demand controlled
Indicate high- occupancy spaces and systems requiring DCV
Sched
C403.2.5.2
Occupancy sensors
Indicate spaces requiring occupancy -based system control and method; or
na
alternate means provided to automatically reduce OSA when partially
na
Enclosed loading
Indicate enclosed loading dock and enclosed parking garage ventilation
na
C403.2.5.3
dock/parking garage
system activation and control method
na
ventilation
na
C403.2.5.4.1
Kitchen exhaust hoods
Indicate kitchen hoods requiring make -up air, indicate make -up air source
na
and conditioning method
Indicate lab exhaust systems requiring heat recovery, method & efficiency;
C403.2.5.4.2
Laboratory exhaust systems
or alternative method taken (VAV, semi - conditioned makeup, or CERM
na
calculation )
na
Energy recovery -
Indicate ventilation systems requiring ER, method & efficiency; note
na
C403.2.6.1
ventilation systems
exceptions
na
na
C403.2.6.2
Energy recovery -
Indicate on -site steam heating systems requiring energy recovery
9 y q g gy ry
na
condensates stems
C403.2.6.3
Energy recovery -
Indicate remote refdg. condensers requiring ER and use of captured
na
condensers stems
energy
na
Mechanical Permit Plans Checklist - Page 2 of
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised .rune 2013
Project Address 11915 CLEAR LAKE RD S Date 2/18/2016
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define pr int area in Excel priorto rintin MECH -CHK pages.
Applicability
Code Section
Code Provision
Information Required
Location
Building Department
(yes,no,na)
on Plans
Notes
GENERAL PROVISIONS, CONTINUED
HVAC System Controls & Criteria, Continued
Variable flow control -
Indicate fan & pump motors requiring VF control & method (VSD or equiv
na
C403.2.12
fans/pumps
controls
na
C403.2.12.1
Variable flow control -
Indicate cooling tower fans requiring variable flow control and method
na
na
coolin towers
C403.2.12.2
Large volume fan systems
Indicate fan systems requiring airflow reduction based on heating and
na
cooling demand; or exception taken
na
C403.2.12.2
Single zone AC systems
Indicate method of cooling demand -based fan control for sys. > 110,000
na
btuh
na
Identify all DDC system input/output control points and indicate capability
na
C403.2.4.10
DDC system capabilities
for trendina and demand response setooint ad iustment
na
Ducting Systems
C403.2.7.1
Duct construction
Indicate all ductwork constructed and sealed per IMC, C402 leakage
Sched
y
&
requirements and IBC vapor retarder requirements
403.2.7.3.1-
Duct pressure
Identify location of low, medium and high pressure ductwork on plans
Sched
y
classifications
C403.2.7.3.3
High pressure duct leakage
Indicate high pressure duct leakage testing requirements on plans; provide
na
test
test results to'urisdiction when completed
na
y
403.2.7.1 /
fuct insulation
Indicate R -value of insulation on ductwork
Sched
Piping Systems
na
C403.2.8
Piping insulation
Indicate R -value of insulation on piping
na
na
C403.2.8.1
Piping insulation exposed to
Indicate method of protection from damage /degredation
na
weather
SIMPLE SYSTEMS
Qualifying Systems
C403.3
Qualifying single zone
Verify unitary or packaged equipment does not exceed capacity limits,
Sched
y
systems
does not have active humidification or simultaneous heating/cooling
na
C403.3
Qualifying 2 -pipe heating
Verify 2 -pipe heating -only system does not exceed capacity limits
na
s stems
na
C403.3.2
Hydronic system controls
Refer to Complex Systems Section C403.4.3
na
Simple System Economizers
C403.3.1
Air economizer required
Indicate cooling systems requiring economizer controls; note in equip
Sched
y
sched.
y
C403.3.1.1.1
Air economizer capacity
Indicate modulating OSA control capability up to 100% OSA, or exception
Sched
C403.3.1.1.3
economizer high limit
Indicate high limit shut -off control method per Table C403.3.1.1.3(2)
Sched
y
controls
C403.1.1.2
Integrated air economizer
Indicate capability for partial air economizer operation for systems with
na
o eration
ca acit > 65,000 btuh
na
na
C403.3.1
Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with
na
x f
COMPLEX SYSTEMS
Complex System Economizers
na
C403.4.1
Air economizer required
Indicate cooling systems requiring economizer controls; note in equip
na
sched.
C403.4.1.4
Economizer heating system
Verify control method of HVAC systems with economizers does not
na
impact
increase building heating energy usage during normal operation
na
C403.4.1.3
Integrated economizer
Indicate capability for partial economizer operation for air or water econo
na
operation
systems
na
Moved
Water economizer capacity
Indicate water econo capable of 100% cooling capacity at 50 °F db /45 °F
na
wb OSA
na
C403.4.1.2
Water economizer
Indicate precooling coils and heat exchangers do not exceed pressure
na
maximum pressure drop
drop limit
na
na
C403.3.1
Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with
na
exceotion(s)
Lrner
SUBMITTAL
Protect
Mariuchi Restaurant
Date
Friday, February 12, 2016
Table Of Contents
Project: - -Untitled12 02/12/201(
Prepared By: 12:19PN
6.0 Tons .......................................................................................................................................... ............................... 3
UnitReport ................................................................................................................................................................. ..............................4
CertifiedDrawing ....................................................................................................................................................... ............................... 5
PerformanceSummary .............................................................................................................................................. ............................... 8
UnitFeature Sheet .................................................................................................................................................. ............................... 12
SpecSheet .............................................................................................................................................................. ............................... 13
Packaged Rooftop Builder 1.39y Page 2 of 13
6.0 Tons
Project: — Untitled12 02/12/201(
Prepared By 12.19PM
6.0 Tons
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Spec Sheet
Packaged Rooftop Builder 1.39y Page 3 of 13
Unit Report For 6.0 Tons
Project: — Untitled12 02/12/201E
Prepared By: 12:19PN/
Unit Parameters Dimensions (ft. in.) & Weight (lb.) * **
Unit Model: ........................ 48TCDA07A2A5 -OAOAO Unit Length: ......................................... 6' 2.375"
Unit Size: ................................................ 07 (6 Tons) Unit Width: .................................................. 3' 8..
Volts-Phase-Hertz: ..................................... 208-3-60 Unit Height: ......................................... 3' 5.375"
Heating Type: ..................................................... Gas Total Operating Weight:...................... 712 lb
Duct Cfg :............ Vertical Supply/ Vertical Return
Low Heat Weights and Dimensions are approximate. Weight
Round Tube Plate Fin Coils does not include unit packaging. Approximate
dimensions are provided primarily for shipping purposes.
For exact dimensions and weights, refer to appropriate
product data catalog.
Lines and Filters
Description
Gas Line Size: .....................................................
1/2
Condensate Drain Line Size: ..............................
3/4
Return Air Filter Type: ...........................
Throwaway
Return Air Filter Quantity: .......................................
4
Return Air Filter Size: ..............................
16 x 16 x 2
Unit Configuration
Medium Static Option (Belt Drive)
AI /Cu - AI /Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1 -Year parts(std.)
5 -Year compressor parts(std.)
10 -Year heat exchanger - Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500 -089 for explanation of policies and ordering methods.
Ordering Information
Part Number
Description
Quantity
48TCDA07A2A5 -OAOAO
Rooftop Unit
2
Base Unit
Medium Static Option Belt Drive)
None
None
Accessories
ECD- SRT12SA -D2EH
Ultra LOW LEAK - Vertical EconoMi$er X with solid -state W7220
controller
2
Packaged Rooftop Builder 1.39y Page 4 of 13
cci
Qi
o n
C) m
N
11111 � m
rp
Igo
L
4m
O
Milo,
LZ
moo,
.6n!
12
7
0
LO
J.
N
0
v
0
0
a)
IL
ze;
n
SV9
11111 � m
rp
Igo
L
4m
O
Milo,
LZ
moo,
.6n!
12
7
0
LO
J.
N
0
v
0
0
a)
IL
N
O
k—
O
cfl
L
L
L
V
oa
N �2
N N
0
N
N
C >
2 -p
N
U �
m n
o a�
a`a`
0
W �
ggs
°a
a=
-
DVS V
IIW
e_ O -
_ w �
c'J 3
o O
O
v V
o
H
a
Di
o
o
o
--
10
MU
_ _ O
M
0
(9
N
0)
m
a-
M
r
L
M:3
W
Q
0
0
0
ca
Y
U
ca
U)
c
0
F-
CD
0
CD
O
0
16
0
QL
ZT
70
In
E E,
F E
3t A
E E u
E — E E E E
oo
E E :E E E
I I I I
0
r-
a)
n
Cl?
>1
0')
E E,
F E
3t A
E E u
E — E E E E
oo
E E :E E E
I I I I
0
r-
a)
n
Cl?
>1
0')
Performance Summary For 6.0 Tons
Project: --Untitled 12 02/12/201(
Prepared By:
12:19PIy
Part NumberA8TCDA07A2A5 -0A0A0
ARIEER :............................................................................................
............................... ..........................11.00
IEER:...................................................................................................
............................... ...........................11.2
F
Base Unit Dimensions
............................... ........................... 77.9
F
UnitLength: .............................................................................................................................................
74.4
in
UnitWidth: ..............................................................................................................................................
44.0
in
UnitHeight: .............................................................................................................................................
41.4
in
Operating Weight
............................... ........................... 54.0
F
BaseUnit Weight: ....................................................................................................................................
652
lb
Medium Static Option (Belt Drive): .............................................................................................................
10
lb
Accessories
59.61
MBH
Ultra LOW LEAK -Vertical EconoMi$er X with solid -state
W7220 controller: ....................................... 50
lb
TotalOperating Weight: ...........................................................................................................................
712
lb
Unit
UnitVoltage-Phase-Hertz: ...............................................................................................................
208-3-60
AirDischarge: ....................................................................................................................................
Vertical
FanDrive Type: ........................................................................................................
............................... Belt
ActualAirflow: ........................................................................................................................................
2400
CFM
SiteAltitude: .............................................................................................................................................
200
ft
Cooling Performance
CondenserEntering Air DB :.....................................................................................
............................... 87.0
F
EvaporatorEntering Air DB :..........................................................
............................... ........................... 77.9
F
EvaporatorEntering Air WB :........................................................
............................... ........................... 64.5
F
EnteringAir Enthalpy: ...........................................................................................................................
29.65
BTU /Ib
EvaporatorLeaving Air DB :...........................................................
............................... ........................... 54.8
F
EvaporatorLeaving Air WB :.........................................................
............................... ........................... 54.0
F
Evaporator Leaving Air Enthalpy: ..........................................................................................................
22.63
BTU/Ib
GrossCooling Capacity: .......................................................................................................................
75.23
MBH
GrossSensible Capacity: ......................................................................................................................
59.61
MBH
CompressorPower Input: .......................................................................................................................
4.71
kW
CoilBypass Factor: ...............................................................................................................................
0.095
FanRPM: ...............................................................................................................................................
Mixed Air
OutdoorAir Airflow: ..................................................................................................................................
420
CFM
OutdoorAir DB :........................................................................................................ ...............................
87.0
F
OutdoorAir WB :............................................................................ ............................... ...........................
67.0
F
OutdoorAir Htg. Temp.: ..........................................................................................................................
18.0
F
ReturnAir DB :............................................................................... ............................... ...........................
76.0
F
ReturnAir WB :.............................................................................. ............................... ...........................
64.0
F
ReturnAir Htg. Temp .:.................................................................. ............................... ...........................70.0
F
Heating Performance
HeatingAirflow: ...................................................................................................................................... 2400
CFM
EnteringAir Temp: ..................................................................................................................................
60.9
F
LeavingAir Temp: ...................................................................................................................................
83.8
F
GasHeating Input Capacity: ...................................................................................................................
72.0
MBH
Gas Heating Output Capacity: ................................................................................................................
59.0
MBH
TemperatureRise: ..................................................................................................................................
22.9
F
Supply Fan
ExternalStatic Pressure: .........................................................................................................................
0.70
in wg
Options / Accessories Static Pressure
Economizer: ......................................................................................................................................
0.17
in wg
Total Application Static (ESP + Unit Opts/ Acc.) :...................................................... ...............................
0.87
in wg
FanRPM: ...............................................................................................................................................
1492
Packaged Rooftop Builder 1.39y Page 8 of 13
Performance Summary For 6.0 Tons
Project: -Untitled12 02/12/201(
Prepared By: 12:19PN
FanPower: ..............................................................................................................................................
2.07 BHP
NOTE: ............................................................................................
Selected IFM RPM Range: 1173 - 1518
Electrical Data
90.2
VoltageRange: ...............................................................................................................................
187- 253
Compressor#1 RLA :.....................................................................................................
.............................19
Compressor#1 LRA :.....................................................................
............................... ............................123
IndoorFan Motor Type: ..........................................................................................................................
MED
IndoorFan Motor FLA :...............................................................................................
............................... 8.4
CombustionFan Motor FLA (ea): ............................................................................................................
048
PowerSupply MCA: ...................................................................................................................................
34
PowerSupply MOCP (Fuse or HACR) :.......................................................................
............................... 50
DisconnectSize FLA :..................................................................................................
............................... 33
DisconnectSize LRA :...................................................................
............................... ............................199
Electrical Convenience Outlet: ..............................................................................................................
None
Outdoor Fan [Qty / FLA (ea)]: ..............................................................................................................
1 / 1.5
Electrical Data (Units produced on or after 02/09/2015 )
66.3
Compressor#1 RLA :.....................................................................
............................... ...........................19.6
Compressor#1 LRA :.....................................................................
............................... ............................136
PowerSupply MCA: ...................................................................................................................................
35
PowerSupply MOCP (Fuse or HACR) :.......................................................................
............................... 50
DisconnectSize FLA :..................................................................................................
............................... 34
DisconnectSize LRA :...............................................................................................
............................... 212
Electrical Data (Unit produced on or after May 18, 2015)
PowerSupply MCA: ...................................................................................................................................
35
PowerSupply MOCP (Fuse or HACR) :.......................................................................
............................... 50
DisconnectSize FLA :..................................................................................................
............................... 34
DisconnectSize LRA :...............................................................................................
............................... 212
May 18th and beyond units can be identified by serial number 2115XXXXXXXXX and higher
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E -12 Watts
Advanced Acoustics
Page 9 of 13
Discharge
Inlet
Outdoor
63 Hz
90.2
88.8
88.8
125 Hz
85.9
82.9
81.8
250 Hz
80.5
71.2
76.9
500 Hz
76.0
67.2
74.4
1000 Hz
72.3
66.4
73.3
2000 Hz
66.8
61.0
69.8
4000 Hz
68.6
57.0
66.3
8000 Hz
64.8
50.5
62.7
A- Weighted
79.1
72.5
78.0
Advanced Acoustics
Page 9 of 13
Performance Summary For 6.0 Tons
Project: - Untitled12 02/12/201E
Prepared By: 12:19PIy
Advanced Accoustics Parameters
63
1. Unit height above ground: ..................................
30.0 ft
2. Horizontal distance from unit to receiver: ...........
50.0 ft
3. Receiver height above ground: ............................
5.7 ft
4. Height of obstruction: ...........................................
0.0 ft
5. Horizontal distance from obstruction to receiver:
.0.0 ft
6. Horizontal distance from unit to obstruction:
........ 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz
63
125
250
500
1k
2k
4k
8k
Overall
A
88.8
81.8
76.9
74.4
73.3
69.8
66.3
62.7
90.1 Lw
B
62.6
65.7
68.3
71.2
73.3
71.0
67.3
61.6
78.2 LwA
C
56.4
49.4
44.5
42.0
40.9
37.4
33.9
30.3
57.7 L
D
30.2
33.3
35.9
38.8
40.9
38.6
34.9
29.2
45.8 L A
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A- Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A- Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user
is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation.
This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to
the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate
sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical
Engineer or a person with sound prediction expertise should be consulted.
Packaged Rooftop Builder 1.39y Page 10 of 13
Performance Summary For 6.0 Tons
Project: —Untitled12 02/12/201E
Prepared By
12:19Pfy
3
c
a�
5D
m
U
Fan Curve
Airflow (CFM - thousands)
RPM = 1492 BHP = 2.07 Maximum RPM = 2100 Maximum BHP = 3.70
Note: Please contact application engineering for selections outside the shaded region.
SC - System Curve RP - Rated Point
Packaged Rooftop Builder 1.39y Page 11 of 13
Unit Feature Sheet for 6.0 Tons
Project: —Untitled 12 02/12/201E
Prepared By: 12:19PN/
r"Al
%W
AleatberMaiker' — 48TC
PACKAGED ROOFTOP GAS HEATINGIELECTRIC COOLING UNITS
3,4,51.6,75, RZ, 10. 125, 15 TONS
O;donal Louvered Hail Guard Shovm
WEATHERMAKER SERIES
WeatherMaker (48TC) units are one-pieceg&s heating, electric
cooling units that are pre-wired and charged with Puron
(R-410) refrigerant. They are factory tested in both heating
and cooling modes, and rated in accordance with AHRI
Standards 210'24D (04-06 sizes) and 3401360 (07-16 sizes).
WeatherMaker units are designed in accordance with UL
Standard 1995, and listed by the Underwriters' Laboratories.
Approved and certified by:
C us
&
— -_ --- 1r
au b
Certified to ISO 9001
STANDARD FEATURES INCLUDE:
• Purcin {R -410A) +4rC reftigers r t
• ASHRAESO-1 energycompliant
• Scroll compressors with iriternefilne breakand overload proteecimn
• Single -stage coaling capsorlycoriballon 04-12niodels
• 7wo-stage�ofngc oactycantmionOB-1,5 models
• SEERs upto 13.0, EER's up to 111 and 1EERs up to 11.8
• A�nt,,W- system
• Exclus I `vI nun-oorroshm composite ociridensate pan in accordance with
ASHRAE Standard 62, sloping design, side orcentudiain
• Standard cooling uperstion up to 1151F(46'r_)and dovvri to 4WF (4'C;)
- down to 25* F (4' C) with winter startkit.
• Pie-owitted exieriorpane69rid pnirrier-coated intemrpanetstested to
500 hours sat'spray protection
• Ful�y insulated cabinet
• Exclusive ](3C sm d-state ountralforon-bosid diagnostioswifli LED
error code designation burnercontrullogio and enerpysaving indoor
tan rnotar delay
• LowNOx modes; thatnteet CaRfornia Air Quality Managernent
• induced draritgas neatcorribustion design
• Redundant gas valves with up to two stagesofhestmg
• :Law pressure and high pressare ",itmh protected.
MAINTENANCE FEATURES:
• Access panel with easy grad handles
• Innuvalve easy starring, nostripsorews on unit access panels-
Direct Drive ECM an 3 Tatum 5 tan (-5 voltage only,) rniodets; and beftdrve
simplified control box anangernent
• Extoluswe LED
error code designation, b urnercontroliogicand energy saving indoor
fan rnolordelsy.
INSTALLATION FEATURES:
• 7hm-tne-bar-ompowe,entryca;,abilty
• Single pointgasarid elaatrio connections
• FuR perirrwterbaseralt with bu4knrigq:ingadsptersandfcrksiot5
• FeWcanverublefrumverticaltio hDraCTIbl: airliDWfITT"tirrounting.
(15 size rnodets require field iinstailled supply duct cove').
STANDARD WARRANTY:
• 10-yearheSt exchanger- I option
• 5J.8100-ripTeSSnT
parts an Novabon CondenseTcclIS—Where avaiiab6e
• tisnyootionslupgmdesaiscavadobie
OPTIONS INCLUDE BUT ARE NOT LIMITED TO:
• PrerniiiirLink- and R7-J Open Muft,Protpcu1DDC Control.
• Supply and Return.kiiSrnoke Detectors, high staliornowis
• Lauvenedcondenserocilgaards
• Economizer, daconnectand convenience nutlet opims
• Stainless Steel heat exonangeroption
• Carrosw resltant ii coating,
Hurnld4AZer2 adavbve deriumldftation system aysilaoiee on BE
modelswth RIFF condenseicivils- Wtof Blaster) contro4emduded
• Hinged socess panels
"S,310z0p am M11KZ71% 12p, za;za "w rxirm im
Packaged Rooftop Builder 1.39y Page 12 of 13
Spec Sheet for 6.0 Tons
Project: - Untitled12 02/12/201
Prepared By: 12:19P
Packaged Rooftop Builder 1.39y Page 13 of 13
Specification Data Panasonic
Panasonic Ventilation Fan 7y/�isper�i�e
YENT /LAT /ON fAN
Description
Ventilating fan shall be Low Noise remote mount type rated for continuous nun.
Fan shall be Energy Star rated and certified by the Home Ventilating Institute 1�1/- SONLFi (340 c im/
(HVI). Evaluated by Underwriters Laboratories and conform to both UL and cUL
safety standards.
Motor /Blower:
• Four -pole totally enclosed condenser motor rated for continuous run.
• Power Rating shall be 120 volts and 60 hz.
• Fan shall be UL listed for tub /shower enclosure when used with
a GFCI branch circuit wiring.
• Motor equipped with thennal -cutoff fuse.
Housing:
• Galvanized steel body for long -life.
• Insulated housing to prevent condensation and noise.
• Tapered duct adapter for easy connection.
Easy Installation:
• 5 positions installation.
• Joist, truss and suspension brackets included.
Warranty:
• The factory warranty shall be a minimum of 3 years
limited warranty on parts.
Typical Specifications
Ventilating fan shall be remote mount, Energy Star rated, with no less than
340 CFM as certified by the Home Ventilating Institute (I-M at 0.2" static
pressure in inches crater gauge and no more than 1.7 sone as rated by
manufacturer at 0.2" static pressure. Power consumption shall be no greater
than 100 watts, Energy Star rated and Energy Efficiency rating shall be no less
than 3.5 cfm /watt. The motor shall be totally enclosed, four pole condenser type
engineered to run continuously. Power rating shall be 120v /60Hz. Housing
shall be insulated to reduce condensation. Duct diameter shall be no less than
6 ". Fan shall be UL and cUL listed for tub /shower enclosure when used with
GFCI branch circuit wiring. Brackets shall be provided for joist, truss or
suspension installations.
1.2
Lu 1.1
a 1.0
3 0.9
W 0.8
H oa
W 0.6
V 0.5
Z 0.4
�j 0.3
H 0.2
0.1
0.0
Fan Curve FV- 30NLF1
50 100 150 200 250 300 350 400
AIR FLOW (CFM)
Specifications:
Fan Model
RPM
Rated
Volts
I Max
Watt*
Max
I Amps
CFM`
Max
SP-
Duct
Di..
Weight
Ibs
Sones
CFMMIatt
"SP
.2 "SP .4 "SP
.6 "SP .8 "SP 1.0 "SP
1.2 "SP
FV- 30NLF1
1247
120
98.2
.086
392
340 302
258 106 53
1.13
6"
24
1.7
3.5
Note:
Sones were measured at factory test facility in a sound -proof room at suction side from a distance of 1.5 meters.
For Complete Installation Instructions Visit www.panasonic.com/building c crE
U� D
Model
Quantity
Comments
Project.
Location:
Architect:
Engineer.
Contractor:
Submitted by.
Date:
Panasonic Building Dept. I Three Panasonic Way 4A -1 I Secaucus, NJ 07094 1 866- 292 -7292 1 www.panasonic.com /building
Commercial Submittal Sheet
NOfAMralk SD34 Series
M A N u F A C T u R I N G Spiral Pipe Diffuser Double Deflection
B
1 1/4
SD34
A
*
NOMINAL +1 7/8
B
SD34
ye
Model: SD34
Description: Spiral Pipe Diffuser Double Deflection
Standard Features:
• Transition box style spiral mount double deflection diffuser
• Extruded aluminum diffuser frame with signature line marks
• Front blades run parallel to shortest dimension
• Back blades run parallel to longest dimension
• Nylon bushings for easy adjustment of blades and allows for 4 -Way airflow
• Curved saddle fits spiral radius
• Neoprene open cell gasket for airtight fit
• Soft White
INAL Options:
'/8
❑ Galvanized (SD34 -GALV)
❑ Linear bar face diffuser (SD -LSW)
❑ Perforated face diffuser (SD -P)
❑ Recessed screwdriver operated Opposed Blade Damper (SD34 -0, SD34 - GALV -0,
SD- LSW -O)
❑ Half- length screwdriver Operated Scoop Extractor (SD34 -SC, SD34 - GALV -SC,
SD- LSW -SC)
❑ Full- length screwdriver Operated Scoop Extractor (SD34 -FS, SD34 - GALV -FS,
SD- LSW -FS)
Finishes:
Diffuser
Standard Colors
Designer Colors
❑ Soft White
❑ Almond ❑ Camaro Silver ❑ Navajo White
8"
❑ Black Velvet ❑ Coffee Tan ❑ Vanilla
12"
❑ Bronze
Product Notes:
18"
Spiral pipe diameter must be 4" larger than the width of the register.
SD34 Series Dimension Chart
Diffuser
Pipe Diameter
Width
Dimension•
8"
10"
12"
14"
16"
18"
20"
22"
24"
26"
28"
30"
32" 1
34" 1
36"
38"
40"
42"
44"
46"
48"
A
5
47/8
47/8
43/4
43/4 145/8
41/2
41/2 141/2
41/2
4%
41/2
41/2
41/2
41/2
41/2
43/8
43/8
43/8
43/8
43/8
4
B
71/873/8
7 1/2
75/8
73/4
77/8
77/8
77/8
77/8
77/8
77/8
77/8
77/8
77/8
77/8
77/8
8
8
8
8
8
A
n/a
5
5
47/8
43/4
43/4
45/8
45/8
41/2
41/2
4112
41/2
41/2
41/2
41/2
41/2
41/2
43/8
43/8
43/8
43/8
6
B
n/a
9
91/4
91/2
95/8
93/4
97/8
97/8
97/8
97/8
97/8
97/8
97/8
97/8
97/8
97/8
97/8
10
10
10
10
A
n/a
n/a
51/8
5
47/8
43/4
43/4
45/8
45/8
45/8
.41/2
41/2
41/2
.41/2
.41/2
41/2
41/2
41/2
43/8
43/8
43/8
8
B
n/a
n/a
10 7/8
11 1/4
113/8
11 5/8
11 3/4
11 7/8
11 7/8
11 7/8
11 7/8
11 7/8
11 7/8
11 7/8111
7/8
11 7/8
11 7/8.11
7/8
12
12
12
A
n/a
n/a
n/a
5
5
47/8
47/8
4314
43/4
45/8
45/8
45/8
41/2
41/2
41/2
41/2
41/2
4 1/2
41/2
43/8
43/8
10
B
n/a
n/a
n/a
13
131/4
133/8
131/2
135/8
135/8
137/8
137/8
137/8
137/8
137/8
137/8
137/8
137/8
137/8
137/8
14
14
A
n/a
n/a
n/a
n/a
51/8
5
147/8
47/8
47/8
43/4
45/8
45/8
45/8
45/8
41/2
41/2
41/2141/2
4 1/2
41/2
41/2
12
B
n/a
n/a
n/a
n/a
147/8
15 1/8
15 3/8
151/2
151/2
155/8
15 7/8115
/8115
7/8
157/8
157/8
157/8
15 7/8115
7/8
157/8
15 7/8
15 7/8
'A/B dimensions defined in product drawings are dependent on size of spiral pipe product is designed for.
Additional Information:
Project / Location: Submittal Notes
Engineer:
Architect:
Contractor:
Last Revised: 3/18/2015
T
N N 6 L6 m A A �j A
Q oD m o m co
N C14 N N N N 04 N M M m
Q, O m V w cq ol
LO LO M
to 2
O M v m c*,)
Cq N N N IN M
M m m m cl) m It
Lo
11 Lo ol M m
m m M
N
�-o
cy N N N N N N N N m
Lo
0 N 0 'q C? W
It N
N N N N N N. C-4
Lq w ID r- '0 m w Oo m m 'o o 'o o OM N
�
q o
(D �2 N '�R F4 N N N NO �2 R" 'A 04 mm N N cL4
IQ a) w
lo
04
o c, m
N o N M 1 N
LO V v v v v v N v v N v m v m v m v
of co 12 �
�
O c,
pp " , , m o o o .
V N
04 N Ql N C14 M CN t N m N co
V v v v v N V N V N V N v m v m v- v
in un Lq ol
cl co o Lr) o w 0 c
v v v v v N v v
m u, 11) m D N o CN Cv4 v
v w v Nv Nv w N
v
L) c
G z o
O. C) C) 2 u z 2 u
cl
ol
C14 N M = ID (o O r oo M
ELD - - - —M......
0
x X x x
O
A
............. . ...........
General Mechanical Notes
All thermostats used for both heating and cooling shall provide a range or deadband of at least 5 °F. WSEC Section C403.2.4.2
All thermostats are to be seven day programmable, micro - processor based.
Sunset Inc.
Project: Mariuchi Restaurant
All heating and cooling systems shall have automatic start controls for each HVAC system WSEC Section C403.2.4.3.3
All ductwork shall be constructed and sealed per SMACNA standards.
All ductwork shall be braced per IMC 2012. Duct support per Section 603.10.
All refrigerant used shall be Puron (R- 410a).
All flues shall be located a minimum of 10' from outdoor air intakes.
All exhaust terminations shall be a minimum of 10' horizontally from, or 3' above outdoor intakes.
All air - economizers shall have modulating outdoor air and return air dampers capable of providing 100% outdoor air for cooling. WSEC Section C403.3.1.1.1
All air - economizers shall be fully modulating and capable of partial cooling (integrated operation). WSEC Section C403.4.1.3.
All addressable functions of duct smoke detectors, and wiring for shutdown, shall be by others.
All roof mounted units shall be secured to their respective roof curbs.
All exposed edges of internal duct liner shall be sealed with a mastic coating.
All completion requirements must comply with WSEC Section C408.2
To comply with WSEC Section C408.1.3.2 systems documentation, record documents and training will be completed and coordinated with owner.
To comply with WSEC Section C408.1.2 preliminary commissioning report will be submitted to owner after being certified by registered design professional or approved agency.
All thermostats to be mounted such that the top of the device is 48" above finished floor.
All gas piping shall be sized per 2012 IFGC.
All HVAC systems shall be air balanced and adjusted to deliver final flow rates within 10% of design rates.
Outdoor air supply and exhaust ducts shall shut automatically when the system or spaces served are not in use or during building warm -up, cooldown, and setback. WSEC Section C403.2.4.4
Outdoor air supply and exhaust ducts shall be equipped with motorized dampers according to WSEC Section C403.2.4.4
Equipment shall meet the minimum efficiency requirements of WSEC Section C403.2.3
System sizing to comply with WSEC Section C403.2.2
Damper leakage rates shall comply with WSEC Section C402.4.5.2
Duct Insulation Schedule: All ductwork shall be insulated as follows:
DUCT TYPE:
LOCATION
INSULATION R -TYPE
TYPE
Supply /Return
Not within insulated envelope (exterior of building, on roof, in attic -above insulation, in crawl spaces)
R -7
2" wrap or liner
Supply /Return /OA
Not within insulated envelope (in ground)
R -5.3
1.5" liner or 1" Spunstrand
OA Intake
Not within insulated envelope
R -0
-
OA Intake (Rectangular)
Within insulated envelope, in mechanical room.
R -7
2" liner
OA Intake (Round)
Within insulated envelope
R -7
2" wrap
Supply on cooling systems
Within insulated envelope, not exposed to space served.
R -3.3
1" wrap or liner
Supply on cooling systems
Within insulated envelope, exposed to space served.
R -0
-
Supply on heating only systems
Within insulated envelope
R -0
-
Return
Within insulated envelope
R -0
-
Exhaust
Other than R occupancy
R -0
-
Exhaust
R occupancy (Residential)
R -8
2" wrap or liner
Per section 403.2 of the 2012 IMC (Washington State Amendments), we are using ASHRAE Standard 62.1 2010 as
an alternate means of compliance with the 2012 IMC Section 403.2 Washington State Amendments.
Description
Space
Occupancy
People OSA Rate
OSA /SQFT
Vent Reqired
REFGRNT
(LBS)
(SQFT /Rooms)
(From ASHRAE Std 621)
CFM /Person
(Per 1000 SOFT)
OSACFM
RTU -1
Food"
RTU -1
CARRIER
48TCDA07A1A5
2,400
0.75
Beverage
1
57,600
YES
CIRCUIT #1 14 -2
11.0
Service
1,465
Restaurant & dining rooms
7.5
0.18
986
Total
1,465
48TCDA07A1A5
2,400
0.75
986
ASHRAE Standard 62.1 -2010
VIAQ
Per section 403.2 of the 2012 IMC (Washington State Amendments), we are using ASHRAE Standard 62.1 2010 as
an alternate means of compliance with the 2012 IMC Section 403.2 Washington State Amendments.
Description
Space
Occupancy
People OSA Rate
1(Per1000SQFT)1
OSA /SQFT
Vent Regired
REFGRNT
(LBS)
(SQFT /Rooms)
(From ASHRAE Std 62.1)
CFM /Person
Voltage
(Volt - Phase)
OSA CFM
RTU -2
00
RTU -1
CARRIER
48TCDA07A1A5
2,400
0.75
Beverage
1
57,600
YES
CIRCUIT #1 14 -2
11.0
Service
1,465
Restaurant & dining rooms
7.5
0.18
986
Total
1,465
48TCDA07A1A5
2,400
0.75
986
GAS PACKAGED UNIT SCHEDULE
Sunset Inc.
Project: Mariuchi Restaurant
MARK
MAKE
MODEL
CFM
ESP
(IN H20)
(AFUE)
COOLING CAP
Total (BTU /H) Sens.
ECONO
(YES /NO)
REFGRNT
(LBS)
EER
MCA
(Amps)
MOCP
(Amps)
Voltage
(Volt - Phase)
Weight
(lbs.)
CO2
Y/N
Comments
RTU -1
CARRIER
48TCDA07A1A5
2,400
0.75
82.0%
72,000
57,600
YES
CIRCUIT #1 14 -2
11.0
310
50
208/230 -3
875
Y
14" CURB, DN SHOT ECONO, SEE NOTE 1
RTU -2
CARRIER
48TCDA07A1A5
2,400
0.75
82.0%
72,000
57,600
YES
CIRCUIT #1 14 -2
11.0
33.0
50
208/230 -3
875
Y
14" CURB, DN SHOT ECONO, SEE NOTE 1
1. Per IMC 606.2 Exception, no duct smoke detectors are required in this installation.
Per IMC section 606, Air moving systems supplying in excess of 2000 CFM shall be equipped with a duct mounted duct detector smoke detector.
Where duct mounted smoke detectors are required by the IMC, we propose to furnish non - addressable type units.
If addressable units are required for interface with other building systems, these units will either be supplied by others,
or the units provided by Sunset will be modified as required by others to allow such interface
FAN SCHEDULE
MARK
MAKE
MODEL
STYLE
FLOW
(Constant I VFD)
FLA
(Amps)
WATTS
Voltage
(Volt - Phase)
WT
EF -1
PANASONIC
FV- 30NLF1
INLINE
CONSTANT
0.9
94.9
115 -1
18
GRILLE SCHEDULE
MARK
MAKE
MODEL
Comments
A
SHOEMAKER
700 MA
LAY IN SUPPLY
B
SHOEMAKER
MA
HARD LID SUPPY
C
SHOEMAKER
645T
LAY IN RA/EXH
D
SHOEMAKER
645
HARD LID RA/EX