Loading...
20160114 SEISMIC CALCS 06292016Tol -Brace Seismic Calculations Emerald Fire Project Address: Yelm 9 Unit _ 11021 Cramer Rd KIP N COWERS-Line &TQLCQ Gig Harbor WA 98329 1315 Yelm AVE W 253- 857 -2056 Yelm WA EMERAFL980MR Job #216052 Calculations based on 2013 NFPA Pamphlet #13 Brace Information Tolco Brace Components 35'0" (10.67 m) Tolco Component Pig. Number Adjusted Load Maximum Spacing T.0" (2.13 m) FigAL Clamp 1425 Ibs (646 kg) Maximum Brace Length - 1" Sch.40 Fig.909 No- Thread Swivel 1425 Ibs (646 kg) Bracing Material -. - - 45° Min. "Calculation Based on CONCENTRIC Loading Angle from Vertical 'Please Note: These calculations are for Tolco components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Assembly Detail L1R Value 200 - - TOLCO FIG. 909 Max Horizontal Load 1310 lb5 (594 kg) NO- THREAD SWIVEL SWAY 0 BRACE ATTACHMENT ( 0.5824 Force Factor Cp) _. — STEEL. PIPE LATERAL BRACE TOLCO FIG. 4L p Fastener Information Fastener Orientation NFPA Type E PIPE CLAMP FOR — SWAY BRACING Maximum Load 360 Ibs (163 kg) Diameter 1 /2in. (13 mm) Length 3 -1 /2in. (89 mm) Type Dual Lag Bolts - Fig -906 Orientation of Brace Longitudinal Size and Type of Pipe Total Length Total Calculated Load 4" Sch.10 Steel Pipe (101.6 mm) 35ft (1 D.7 m) 240 lbs (109 kg) Percentage added for Fittings and Sprinklers 15% 36 Ibs (16.33 kg) Total Adjusted Load of all pipe within Zone of Influence 276 Ibs (125 kg) {Tot -Brace Version 71 Tol -Brace Seismic Calculations Yelm 9 Unit 1315 Yelm AVE W Brace Identification Brace Type (Per NFPA #13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 216052 COOPPEER 8-Line I &TQLCQ Worst Case Longitudinal NFPA Type E 4" Sch.10 Steel Pipe 35' 0" (10.67 m) Longitudinal 1" Sch.40 7'0" (2.13 m) 200 45° 112 x 3 -1/2 (13 x 89 mm) Dual Lag Bolts Perpendicular to Beam - TOLCI 3- 1 /2in_ (89 mm) girmmary of Pine within Zone of Influence G- Factor Used 0.5824 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 276 Ibs (125 kg) Material Capacity 1310 ibs (594 kg) Fastener Capacity 360 Ibs (163 kg) FigAL. Clamp 1425 lbs (646 kg) Fig.909 No- Thread Swivel 1425 Ibs (646 kg) Structural Member Doubled Truss Calculations prepared by Michael Hallengren *The description of the Structual Member is for informational purposes only. Tol -Brace software calculates the brace assembly only, not the structure it is attached to. Calculated with Tol -Brace 7 visit us at WwWAUCO.com Tol -Brace Seismic Calculations Emerald Fire Project Address: Yelm 9 Unit 11021 Cramer Rd KP N C00111111 B -Line @TDLCO Gig Harbor WA 98329 1315 Yelm AVE W 253-957-2056 Yelm WA EMERAFL980MR Job # 216052 Calculations based on 2013 NFPA Pamphlet#13 Brace Information Tolco Brace Components 14'0" (4.27 m) Tolco Component Fig. Number Adjusted Load Maximum Spacing 59 Ibs (26.76 kg) Maximum Brace Length TO" (2.13 m) Fig4LA (Let) Clamp 707 Ibs (321 kg) 1" Sch.40 Fig.909 No- Thread Swivel 1425 1 b (646 kg) Bracing Material - _ - _- - 45° Min. *Calculation Based on CONCENTRIC Loading Angle from Vertical - *Please Note: These calculations are for Tolco components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Assembly Detail UR Value 200 Max Horizontal Load 1310 Ibs (594 kg) Force Factor(Cp) 0.5824 _ gB{{��NEETo�corroca4 MO- THBEA4 VMVECSWAY - BRA" ATTACNYEl1T Fastener Information BRACE "IF. Fastener Orientation NFPA Type E w, Bd1NE I TQLG0 FOR 4LA Maximum Load 600 Ibs (272 k9) TN, F„, BRACE ATFACkMENT Diameter 1/2in..(13 mm) Length Minimum 4x Wood Member Type Dual Through -Bolts - Fig.906 Orientation of Brace Lateral Size and Type of Pipe Total Length Total Calculated Load 4" Sch.10 Steel Pipe (101.6 mm) 14ft (4.3 m) 96 Ibs (44 kg) 2" Sch.10 Steel Pipe (50.8 mm) 120ft (36.6 m) 295 lbs (134 kg) Percentage added for Fittings and Sprinklers 5 °/n 59 Ibs (26.76 kg) Total Adjusted Load of all pipe within Zone of Influence 450 Ibs (204 kg) {Tol -Brace Version 71 Tol -Brace Seismic Calculations Yelm 9 Unit 1315 Yelm AVE W Brace Identification Brace Type (Per NFPA #13) Braced Pipe Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job #216052 caa� B -Une d)TOLCO Worst Case Lateral NFPA Type E 4" Sch.10 Steel Pipe 14'0" (4.27 m) Lateral 1" Sch.40 7'0" (2.13 m) 200 45° 1/2 (13 mm) Dual Through -Bolts Perpendicular to Beam - TOLCO Fig 9( Minimum 4x Wood Member Summary of Pipe within Zone of Influence 4" Sch.10 Steel pipe (101.6 mm) 1 14ft (4.3 m) 2" Sch.10 Steel Pipe (50.8 mm) 1120ft (36.6 m) G- Factor Used 0.5824 Allowance for Heads and Fittings 15% Conclusions Total Adjusted load of Pipe in Zone of Influence 450 Ibs (204 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 600 Ibs (272 kg) Fig.4LA (Lat) Clamp 707 Ibs (321 kg) Fig.909 No- Thread Swivel 1425 Ibs (646 kg) Structural Member Doubled Truss Calculations prepared by Michael Ha1engren 'The description of the Struoual Member is for informational purposes only. Tol -Brace software calculates the brace assembly only, not the structure it is attached to. Calculated with Tol -8race 7 visit u5 at ww.tolco.com