20140275 05-26-2016-east-haven-villa-16s040-compression-test-concrete-report-c44207-draft N-laterials Testing & Consulting, Inc.
Ck-K*ni"l F'*mrerinp 1S{'1mwL4ing•Spt%cinl In%prctinn■tilmerWh Te5*nc 0 Fnrirnnme'nlal C-rnollkg
A'Akr rs -d L%%a m n m Ainm MY �
East Haven Villa - 16SO40 - Compression Test: Concrete: Report#C44207 - DRAFT
CLIENT Harrington Construction&Dev.,Inc. DATE 05/26/2016
PROJECT LOCATION 311 Cullens Road SE PERMIT#
Yehn WA
Inspection Information:
Inspection Date: 05/26/2016 Time Onsite: 11:30 AM Weather Conditions: Partly Cloudy,50s*F
Inspection Performed: Compression Test:Concrete
Field Data (ASTM C-31):
Location of Placement: Main building perimeter stemwalls.
Sample Location: NE corner of stem walls.
Contractor:Nnington const. Subcontractor: a Supplier/Plant:Miles/206B
Qty Placed,Cu.Yd.: 100 of 20 Slump,Inches(ASTM C-143)or W/C Rati Concrete Tempr F(ASTM C-1064): 67
Delivery Ticket#: 23129 Job Spec.S ump: 4 _1 Ambient Temp,°F: g8
Truck#: M097 Air Content,%(ATSM C-231): Min Temp,°F:❑
Batch Time: 11:27 am Job Spec.Air: n/ Max Temp,°F:❑
Sample Time: 12:15
Mix#and Proportions: 12300F/10 CY
Cement,lbs.:13745 Coarse Agg,lbs.: /8 000 Admixture,oz./cwt: B of 997.240 oz
Flyash,lbs.: 935 "Coarse Agg,lbs.: ea. W Admixture,oz./cwt:
Water,gals.: 21.6 Coarse Agg,lbs.: Admixture,oz./cwt:
Fine Agg,lbs.: 14960 Coarse Agg,Ibs Admixture,oz./cwt:
Gallons of water were rior to
Sample Type & pres est suits:
Received 05/27/201 t 1 of 1 Type of Compression Test: Concrete(ASTM C-39)
Lab Tests:
Test Sample Sample Comp. Break ASTM ASTM
New Log# Age Date of Test L d Area(Sq. Strength Tested By
(Days) ( bs.) Dim.(In.) In.) (PSI) Type C-617 C-1231
2438 17 06/02/2016 39,894 F 4.00 12.57 3,170 Frank Pooler 0 ❑
2439 28 06/23/2016 ���� �0 ❑ ❑
2440 28 06/23/2016 ���� �0 ❑ ❑
2441 28 06/23/2016 ���� �0 ❑ ❑
2442 0 ❑ ❑
REQD ® 3000
Remarks:
Concrete was placed by boom pump truck see report#F73963 for more details.
+�+�+*�r�+rR•�lr4rr...a..ra1.1„rne,M.�.rr,.,olo.r,aK.,.w rrrt.y,,.,rr•a.rl•er.,..r.a,.ln�.rr�r.r w.rrrrrerr�rdrr..�.l,.ur„t,lr�r.r•..f.�n.-a.�..,w.�-
mn frmmnpvdk-4a pq oY ^ila %im r 0 7401 • 1113 MnnrlLll iuelq l C54IM11 nF.be. All rlObo rnarrrN.
Corp-►rile ■ 777 Cbr1slor Drive * 0arlington, W A 08233 • Pbose 364.753-1990 * Fax 362.736.19R@
SV4 Region * 21 IS Black Lako Hlud- S.W.• Olympia, WA 9$512 * phone 3401344777 * FAX 340,334.9779
NW Reolp■ * SOS 1?1jp00L SUCCL, Suite 5 * 6ell1mghom, WA 98225 v Phone 3160.647.606L ' F¢r 11
Yisil our wehsile: www.mLC inc.acl
East Haven Villa-16SO40,0512612016,#C44207,Page I of 2
N-laterials Testing & Consulting, Inc.
Geoletirniril FACkowiriz&CunmAing•Speciel Inlpe[11an*Mlrlerieli Te5*ng 0 Fnrirnnmenlal Coewi ft
y/ Anor ".Sirrm lfV4!
REPORTED BY:Tom Sylvanie REVIEWED BY:,eAN
m�frmmnpvdrilla pqr Is ^ila %im r 0 ]401 • 111] Nn4rlLll iuelq l C541MINIMF.be. All rI010 rnarrrN.
Corp-►rile ■ 777 Ckr1slor Drive + 0arlington, W A 08233 • Phew 360-7.13-1990 * Fax 362.736.19R@
SV4 Region * 2115 Black Laud Hlud- S.W.• Olympia, WA 9$512 * phone 340.534.4777 * Fax 340,334.9774
NW Reolp■ * BIDS Di1POOL SUCCL, Suite 5 * 6e111rQhom, WA 98225 * Phone 3160.647.606L ' F¢r $dd.6i7.$111
Visit Dur wehsiw www.mic inc.acl
East Haven Villa-16SO40,0512612016,#C44207,Page 2 of 2