20170188 Permit Pkg 06012017CITY OF YELM
RESIDENTIAL B,UIILDING PERMIT APPLICATION FORM
Project Address: t)0, K u.AR�AJ 1�Yc r�a5� Parcel #:
Subdivision: Lot #:, Plan #: Zoning:
❑ New Construction _: Re- Model l Re -Roof 1 Addition Home Occupation Sign
❑ Plumbing -k Mechanical r E Mobile 1 Manufactured Home Placement E Other
Project Description/Scope of Work:
Project Value:
Building Area (sq. ft) I" r 2 "d Floor Floor Garage -2 3 car
Covered Patio Covered Porch Patio 4 eck
# Bedro
Are there any environmentally sensitive areas located on the parcel? k�a
If yes, a completed environmental checklist must accompany permit application.
BUILDING OWNER NAME. XZ4tP 2b /u 2-
ADDRESS _ l;A '}-, 5 1 EMAIL
CITY STATE4tl1� - -ZIP ' 55�i 7 TELEPHONE.` - D - '
ARCHITECT /ENGINEER LICENSE #
ADDRESS EMAIL
CITY STATE ZIP TELEP E
GENERAL CONTRACTOR we TELEPHONE
ADDRESS EMAIL
CITY TATE ZIP FAX
CONTRACTO CENSE # EXP DATE Y LICENSE #
PLUMBING CONTRACTOR TELEPHONE
ADDRESS EMAIL
CITY STATE ZIP FAX
CONTRACTOR'S LICENSE # EXP DATE CITY LICENSE #
MECHANICAL CONTRACTOR ELEPHONE Z • 17.0(06_5
ADDR S q701L EMAIL i ? ki&;f Y HAlmhrzns.eblry�
CITY STATE_W_A__ZIP 10 qq( FAX 9 -3�
CONTRACTOR'S LICENSE #KLISM O146218z EXP DATER/ CITY LICENSE # /OV07
1 I - ,,7.1
MICA Copy of mitigation agreement with Yelm Community Schools, if applicable.
hereby certify that the above information is correct and that the construction on, and the occupancy and the use of the
above described property will be in accordance with the laws, rules and regulations of the State of Washington and the
City of Yelm.
Applicant's Signature Date
Owner / Contractor /.Owner's Agent 1 Contractor's Agent (Please circle one.),
/.-7
All permits are non - transferable and will expire if work authorized by such permit is not begun
within 180 days of issuance, or if work is suspended or abandoned for a period of 180 days
105 Yel +n Avenue West (360) 458 -3835
Yelm, WA 98597 (360) 458 -3144 FAX
www.vi.yelm.wa.us
5
KLIEMAK-K. allt
Heating a n d A i r c o n d; l i o n i n g 4703 - 116" Street E, Tacoma, WA 98446 253 -537 - 06551253 -539 -3861 Ear,
Date V5 (t 1 I p
HEAT PUMP SITE PLAN
Address 1Sa2) 5 nyor,�Gwn Vlf-Ll yell ':�,r
Homeowner QDC'-' ,r\P.r _
EWPERMITS1HP Site P10ro 3 -25.16 k�
Job # \9-6%Z
L-3
Rear Property Line
i---- .�_____ ___ _______ ______ _ _i
I I
i I
I I
I I
I I
w !
I !
I I
I I
I i
I [
t I
I i
I I
I I
I — I
I I
1 I
I I
I I
I I
I I
1 I
r
kAl
21
Front Property Line
1
Printed 3/25116
&A iC Z>/\r Eat. ,i`Yi t�e 11
Submittal
�- C-t
P
a� o6 3 (') 0llf 4401 �') V1 6J
Single Packaged Heat Pump
14 SEER Convertible
4WCC4036A1000A
!Vote: "Graphics in this document are for representation only. Actual
model may differ in appearance."
TAG:
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air - conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
December 2015 4WCC4036A -SUB -1 E -EN "RlngersofiRand
Product Specifications
MODEL
4WCC4036AI000A
RATED Volts /PH /Hz
208 - 230/1/60
Performance Cooling BTUH (a)
35800
Indoor Alrflow (CFM)
1114
Power Input (KW)
2.8
EER/SEER (BTU/Watt -Hr.) (b)
12.00/ 14.00
Sound Power Rating [dB(A)] W
69.4
PERFORMANCE HEATING
CONSTANTTORQUE ECM
(High Temp.) BTUH
32600
Power Input (KW)
2.7
(Low Temp.) BTUH
21,800
Power Input (KW)
1.75
HSPF (BTUH/Watt-Hr)
8.0
POWER CONN. — WPh /Hz
208- 230/1/60
Min. Brch. Cir. Ampacity (a)
24.4
Fuse Size —Max. (amps)
40
Fuse Size — Recmd. (amps)
40
COMPRESSOR
SCROLL
VOLTS /PH /HZ
208 - 230/1/60
R.L. Amps — L.R. Amps
15.4/77.0
OUTDOOR COIL — TYPE
SPINE FIN
Rows /F. P.I
2/24
Face Area (sq. ft.)
15.49
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
INDOOR COIL — TYPE
PLATE FIN
Rows /F P.I
4115
Face Area (sq. ft.)
3.5
Tube Size (in.)
3/8
Refrigeration Control
EXPANSION VALVE
Drain Conn. Size (In.)
3/4 FEMALE NPT
!'"`1
OUTDOOR FAN — TYPE
SWEPT
DIA. (IN.)
23.4
DRIVE/NO. SPEEDS
DIRECT/3
CFM @ 0.0 In. w.g. (a)
3250
Motor — HP /R.P.M
1/5/855
Volts/Ph /Hz
208-230/ 1/ 60
F.L. Amps /L.R Amps
1.1/2.0
INDOOR FAN — TYPE
CONSTANTTORQUE ECM
Dia. x Width (In.)
10.62 X 10.68
Drive /No. Speeds
DIRECT/ 3
CFM @ 0.0 in. w.g. (f)
SEE FAN PERF TABLE
Motor — HP /R.P.M.
1/2/1050
Volts /Ph /Hz
208- 230/1/60
F.L. Amps
4.1
FILTER / FURNISHED
NO
Type Recommended
THROWAWAY
Recmd. Face Area (sq. ft) (9)
4.0
REFRIGERANT
R-410
Charge (lbs.)
7.2
CHARGING SPECIFICATIONS
Subcooling
11°
DIMENSIONS
H X D X W
Crated (in.)
48 X45 X 52
WEIGHT
Shipping (Ibs.) / Net (lbs.)
439/364
(0) Rated in accordance with AHRI Standard 210/240.
(b) Rated in accordance with D.O.E. test procedure.
60 Sound Power values are not adjusted for AHRI 270 -95 tonal
corrections.
(a) Calculated in accordance with currently prevailing Nat1 Electrical
Code.
W Standard Air — Dry Coil — Outdoor.
M Standard Air — Dry Coil — Indoor
(7) Filters must be Installed in return air stream. Square footages listed
are based on 300 f.p.m. face velocity. If permanent filters are used
size per manufacturer's recommendation with a dean resistance of
0.05' W.C.
4WCC4036A -SUB -1 E -EN
e0o"1
Outline Drawings
25.40
ill
Figure 1. 2 — 3 TON MODELS
MCI
1041
[41•
18.03 18.29
[231321 [231321
14.2
[91161
SECTION Y -Y
TYPICAL (0) SIDES OF DOINFLOW OUCT OPENINH
Note: The view labeled Bottom Side
represents the base as viewed looking
up from underneath the unit.
4WCC4036A -SUB -1 E-EN
Y Y
OUTLET
M
GRAVITY
Outline Drawings
Figure 2. 2 -- 3 TON MODELS
TYPICAL 181 SIDES OF SIDEFLOW DUCT OPLNINGS
145 -1121
(SURFACE AREA!
BACK SIDE
9
181
4WCC4036A -SUB-1 E -EN
Height MMIIN
APPROX. CORNER WEIGHT
SWIGHTG
TOTAL
CENTER OF GRAVITY
Model
KG /LBS
UNIT
MMIIN.
A
Wi
W2
W3
W4
s
C
KG I LBS
WEIGHT
KG I LBS
4TCG4024
898.53 [35-3/8]
58.3
129
36.8 [81j
26.1
[58]
41.0
[90]
196.1
432
162.4
358
479.8 [18.9]
527.8 [20.8]
61.3
38.7 [85]
275
43.1
204.8
171.1
406.5 [96.0]
594.1 [23.4]
4TCC4030
135
[61]
1951
451
377
4TCC4036
949.33 [37 -318 ]
61.7
136
38.9 [86]
27.7
1611
43.7
[96]
205.7
453
172.0
379
414.3 [16.3]
697.6 [27.5]
4WCC4024
898.53 [35 -318]
52.9
1 i
33.3 [73]
24.1
[53]
38.3
[84]
182.3
402
148.6
328
430 [16.9]
565.3 [22.3]
4WCC4030
949.33 [37 -318]
55.3
122
50.3 [110]
16.6
[37]
39.2
[86]
195.0
430
161.3
355
413.5 [16.3]
581 [22.9]
59.6
37.3 [82]
26.6
41.7
199.0
165.3
430 [17.0]
535 [21.1]
4WCC4036
131
[59j
[92]
439
364
4WCC4036A -SUB-1 E -EN
304.80
[121
(INSIDE)
75.41
[2- 31132]
Outline Drawings
Figure 3. 2 -- 3 TON MODELS
RECO"ENDED SERVICE CLEARANCE WNIIN.
I�0
359. 79
[14-5132]
ENTR
288.42 225!68
[II- 111321 18 -7181
117.73 -J
[4 -5181
85.22
13- 1 11321
[i611V
(INSIDE) B0TT0M DUCT OPENINGS
73.46
6-271321
406.40
[161
(INSIDE)
.89
5181
WEA ENTRY
Ilf� 28.58 [1-1181 DIA. KNOCKOUT
POWER ENTRY
28.58 11 -1181 DIA. KNOCKOUT
34.93 [I -31 81 plA. KNOCKOUT
128.08 50.01 [I- 311321 DIA. KNOCKOUT
15-1/321 SINGLE POINT ENTRY A. RIGHT SIDE 50.01 [1- 31832D]I DIA. KNOCKOUT
62.71 [2-151321 DIA. KNOCKOUT
4WCC4036A -SUB -1 E -EN 5
Indoor Fan Performance (230v)
Table 1. Horizontal Airflow
4WCC4036A1
EXTERNAL STATIC PRESSURE (IN. WG)
MOTORSPEED
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
COOLING
WATTS
145
152
159
167
175
-
-
-
-
-
-
LOW
CFM
1145
1098
1047
982
926
-
-
-
-
-
-
COOLING
WATTS
195
202
210
218
227
236
-
-
-
-
-
MEDIUM
CFM
1268
1226
1177
1125
1072
1019
-
-
-
-
-
COOLING
WATTS
-
-
323
331
342
351
361
372
-
-
-
HIGH
CFM
-
-
1400
1359
1308
1261
1216
1172
-
-
-
Table 2. Down Airflow
4WCC4036A1
EXTERNAL STATIC PRESSURE (IN. WG)
MOTORSPEED
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
COOLING
WATTS
146
153
159
168
176
-
-
-
-
-
-
CFM
1133
1087
1037
972
916
-
-
-
-
-
-
- LOW
COOLING
WATTS
196
203
211
220
228
237
-
-
-
-
-
CFM
1255
1213
1166
1114
1062
1009
-
-
-
-
-
- MED
COOLING
WATTS
-
-
324
333
343
353
363
373
-
-
-
CFM
-
-
1386
1346
1295
1248
1204
1160
-
-
-
- HIGH
4WCC4036A -SU B -1 E-EN
r_3
Full Peri \ter Roof Mounting Curb
Figure 4. 4024 — 4036 Models
BAYC RB050A Full Perimeter Roof Mounting Curb
PPLY
LIR
15
387/8
1 1/
177/8
RETURN 3 5/8
AIR
19 1/2
191/2
23/16
The drawings on this page are prepared by the
manufacturer order to provide detail regarding
job layout only. hese drawings are not intended to
\ be used as a base to construct, build or modify the
` items depicted in t e drawings. The manufacturer
is not responsible fo the unauthorized use of these
> drawings and expre4 disclaims any liability for
p► B damages resulting fro such unauthorized use.
ETURN /
AIR /
PPLY
\ AIR
C
D
, �- � / � i CHANNEL SIDE
CHANNELEND '
` WOOD NAILER
3
' HOLE IN; ROOF
i
'
433/8
35 7/8
42.00 WITH ECONOMIZER WITH 25% FRESH
AIR ACCESSORY
4WCC4036A –SUB -1 E -EN 7
SERVICE CLEARANCE DII ENSIONS
A
B
C
D
WC+ /TC•
42.00
36.00
12.000
4.00
DCo /YC■
42.00
36.00
12.009+
3fi.00
35 7/8
42.00 WITH ECONOMIZER WITH 25% FRESH
AIR ACCESSORY
4WCC4036A –SUB -1 E -EN 7
W"
Supplementary Electric Heater
Table 3. BAYHTRV — Supplementary Electric Heaters
/1041
Table 4. BAYSPEK — Single Power Entry Kit
SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION
ELECTRIC
RATED
HEATER MODEL
MIN CKT AMP
HEATER
NO.
KW /STAGE
BAYHTRV105
MAX. FUSE
CANADA
UNIT
HEATER
VOLT-
PHASE
AMPS
CAPACITY
OF
BAYSPEK63
MCA
OR HACR
ONLY MAX.
MODEL
MODEL
AGE
STAGES
CKT BKR
CKT BKR
KW
STUN
1
2
SIZE
SIZE
4024 -4060
BAYHTRV105
208/240
1
18/21
3.76/5.0
1
3.70/
—
23126
25/30
25/30
178 00/
4024 -4060
BAYHTRV108
208/240
1
29/33
6.0/8.0
27
1
g p/
—
36/41
40/45
40/45
300/
4024 -4060
BAYHTRV110
208/240
1
36142
7.5/10.0
34600/
1
—
45/52
45/60
45/60
10.0
4030 -4060
BAYHTRV115
208/240
1
54/63
11.27/
38500/
2
7.5/
3.761
68/78
70/80
70/80
15.0
51200
10.0
5.0
4048 -4060
BAYHTRV120
208/240
1
72/83
15.01
51200/
2
7.5/
7.5/
90/
90/110
90/110
20.0
68300
10.0
10.0 1
104
4060
BAYHTRV125
208/240
1
90/
18.78/
64100/
2
11.26/
7.5/
113/
125/150
125/150
104
25.0
85300
15.0
10.0
130
Table 4. BAYSPEK — Single Power Entry Kit
SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION
UNIT MODEL
SINGLE POWER
ENTRY KIT
HEATER MODEL
MIN CKT AMP
MAX OVER - CURRENT DEVICE
4WCC4036A
BAYSPEK60
BAYHTRV105
50
60
BAYSPEK62
BAYHTRV108
65
70
BAYHTRV110
76
80
BAYSPEK63
BAY 115
102
110
CP►�L��r7cT�_�'iq :bl � �
Optional Equipment — Filter Rack
Figure 5. BAYFLTR101 Filter Rack (4024-4036)
BAYFLTR201 (4042 -4060)
(Mounts in Filter /Coil Section)
Figure 6. BAYACCD0R1A Hinged Filter Access Door (4024-4036)
BAYACCD0132A (4042 -4060)
Replaces Filter /Coil Access Panel
Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct build or modify the items depicted in the drawings. The manufacturer is not responsible for
the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
4WCC4036A —SUB -1 E -EN
Optional Equipment — Filter Rack
Optional Equipment — Economizer
Table 5. BAYECON101,102A Down Discharge Economizer and Rain Hood
(Mounts Over Horizontal Return Air Opening)
fdft�
HVAC Unit
Economizer .— ..— .._._.. —..
Economizer
Unit Application
Models
Economizer
-
rain hood
A
BAYECON101A
4024 -036
Outside air
dampers
Gaskets (2)
Return air
E
Rain Hood
Jr/
dampers e Required
Mixed Air
�®
_ filter kit, order
Sensor
Mist separately
Models
A
eliminator
C
D
E
BAYECON102A
4042 -060
Relief Return
22"
20"
damper Duct
15- 11/16"
11- 11/16"
Roofcurb
BAYECON201A
4042 -4060
Table 6. BAYCON200, 201A Horizontal Economizer and Rain Hood
Note., The drawings on this page are prepared by the manufacturer in order to provide detall regarding job layout only. These drawings are not
intended to be used as a basis to construct, build ormodify the items depicted in the drawings. The manufacturer Is not responsible for
the unauthorized use ofthese drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
10 4WCC4036A -SUB -1 E -EN
Economizer
-
A
B_
D
C
Gaskets (2)
Duct
E
Rain Hood
Jr/
Mixed Air
�®
Sensor
Economizer
Models
A
B
C
D
E
F
BAYECON200A
4024 -4036
22"
20"
16 -7/8"
15- 11/16"
11- 11/16"
15"
BAYECON201A
4042 -4060
26"
22- 21/32"
19"
17- 11/16"
14- 11/16"
21 -3/8"
Note., The drawings on this page are prepared by the manufacturer in order to provide detall regarding job layout only. These drawings are not
intended to be used as a basis to construct, build ormodify the items depicted in the drawings. The manufacturer Is not responsible for
the unauthorized use ofthese drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
10 4WCC4036A -SUB -1 E -EN
14"1
Optional Equipment — Outside Air Damper
Table 2 BAYOSAH001 and 002A
rAMI�
Optional Equipment — Filter Rack
I�
AEI
Manual Fresh
Air Model
Unit
A P oriels
Models
A
B
C
D
E
BAYOM-
o
BAYOSAH001A
4024 -4036
22 -7/16"
20- 11/16"
12 -3/8"
9 -3116"
D C
11 -1/2"
12 -1/4"
C 9
f
FULLY
E
BAYDM-
PR102A
B CLOSED
18 -3/16"
15 -1/8"
10 -1/4"
11 -1/2"
12 -1/4"
I� -D - ►I
BAYOSAH002A
4042-4060
25 -3/16"
20- 11/16"
12 -3/8"
9 -3/16"
Table 8. BAYDMPR101 and 102A,25% Motorized Outside Air Damper
(Mounts Over Horizontal Return Air Opening)
A
r, �I
Manual
Fresh Air
Model
Unit
Application
Models
A
B
C
D
E
BAYOM-
i
PR101A
4024 — 4036
15- 13/16"
11- 13/16"
10 -1/4"
11 -1/2"
12 -1/4"
C 9
E
BAYDM-
PR102A
4042 — 4060
18 -3/16"
15 -1/8"
10 -1/4"
11 -1/2"
12 -1/4"
I� -D - ►I
Note: The drawings on this page are prepared by the manufacturerin order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufactureris not responsible for
the unauthorized use ofthese drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
4WCC4036A -SUB -1 E -E N
Mechanical Specifications
General
The units shall be horizontal airflow as shipped and
convertible to downflow. All units shall be factory
assembled, piped, internally wired and fully charged
with refrigerant. Units shall be certified to UL Standard
1995. All units shall be factory run tested to check
cooling operation, fan and blower rotation and control
or TXV sequence. Units shall be designed to operate at
ambient temperatures between 115 °F and 55 °F in
cooling as manufactured. Cooling performance shall be
rated in accordance with AHRI standards.
Unit Casing
All components shall be mounted in a weather -
resistant steel cabinet with an enamel finish. Access
panels shall be provided for unit controls and indoor
coil and fans. Indoor air section compartment shall be
completely insulated with fireproof, permanent,
odorless fiber material. Knockouts shall be provided for
utility and control connections. Drain connections shall
be provided to accommodate indoor water runoff.
Compressor
The compressor shall be hermetically sealed, high
efficiency scroll compressors. Internal overcurrent and
over temperature protection, internal pressure relief
shall be standard. Other features include centrifugal oil
pump, low vibration and noise.
Refrigeration System
All units shall have refrigerant control. Service pressure
tap ports and a refrigerant line filter shall be standard.
Evaporator Coil Internally enhanced 3/8" OD seamless
copper tubing mechanically bonded to aluminum fins,
factory pressure and leak tested at 480 — 650 psig. All
units have TXV to control refrigerant flow.
Condenser Coil
The Spine Fin TM condenser coil shall be continuously
wrapped, corrosion resistant all aluminum with
minimum brazed joints. This coil is 3/8" OD seamless
aluminum tubing glued to a continuous aluminum fin.
Coils are lab tested to withstand 2.000 pounds of
pressure per square inch. The outdoor coil provides
low airflow resistance and efficient heat transfer. The
coil is protected on all four sides by louvered panels.
Indoor Air Fan
Constant Torgue, forward- curved, centrifugal wheel in
a Composite Vortica ® Blower housing. Motor shall
r�_7
have thermal overload protection and permanently
lubricated motor bearings. Motor/blower assembly
isolated from unit with rubber mounts.
Outdoor Fan
One direct- drive, statically and dynamically balanced
propeller fan shall be used in a draw - through vertical
discharge configuration. Permanently lubricated
weather proof motor shall have built -in thermal
overload protection.
System Controls
System controls include condenser fan, evaporator fan
and compressor contactors.
Accessories Roof Curb
The roof curb shall be designed to mate with the unit
and provide support and complete weathertight
installation when properly installed. Adhesive back
polyurethane sealing strips shall be provided to ensure
an airtight seal between supply and return openings of
the curb and unit. The roof curb design allows field
fabricated ductwork to be connected directly to the
curb. Curb ships knocked down for field assembly, and
includes factory installed wood nailer strips.
Electric Heaters
Each heater assembly shall include power supply
fusing if over 48 amps, automatic resetting limit
switches and heat limiters for thermal protection.
Heaters shall be provided with polarized plugs for quick
connection to unit low voltage wiring. Electric heat
modules shall be UL listed.
Single Source Power Entry
This accessory when used with electric heat accessory
shall allow single source power connection to unit and
heater combination. Single source power entry kits
shall have specific matching heater(s). Kit shall include
high voltage terminal blocks, fuse blocks and fuses, cut -
to-length interconnecting wiring, and junction box (if
required) to provide power sources with fuse
protection as required for both the unit and accessory
heater. Kit components shall install within the heater
cabinet in the heater access section. Single source
branch power circuit shall be protected and wired in
accordance with local codes.
12 4WCC4036A -SUB -1 E -EN
Fully Modulating Economizer
This accessory shall be field installed and be composed
of the following items: 0 -100 % fresh air damper,
damper drive motor, fixed dry bulb enthalpy control,
and low voltage pigtails for electrical connections.
Solid state enthalpy or differential enthalpy control is
optional. Economizer operations shall be controlled by
the preset position of the enthalpy control. A
barometric relief damper shall be standard with the
economizer and provide a pressure operated damper
that shall be gravity closing and prohibit entrance of
outside air on equipment "off" cycle. Economizer
requires BAYRLAY004A relay kit to interface the
economizer to the heat pump.
Manual Outside Air Dampers
Rain hood and screen shall be field installed. Suitable
for up to 25% outside air.
Mechanical Specifications
Start Kit
Extra compressor starting capacity for single phase
equipment.
Control Options
Standard Indoor Thermostats
Two stage heating /cooling or one stage heating /cooling
thermostats shall be available in either manual or
automatic changeover.
Programmable Electronic Night Setting Thermostat
Programmable electronic thermostat shall provide
heating setback and cooling setup with 7—day
programming capability. 1 H/1 C or 21-1/2C models
available.
c ETA us
Intertek
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
m2014 Trane
4WCC4036A- SUB -1E-EN 11 Dec 2015 ingel�011 Rand